Quick Comparison Between the DECS-200 and DECS-200N Sep-05

PRODUCT DIFFERENCES
Description DECS-200 DECS-200N Benefit
Continuous Output 32, 63 and 125Vdc up to 63 and 125Vdc up to 20Adc Higher output capability to support wider
Ratings 15Adc range of generators.
10 Second Forcing 30Adc 40Adc Higher forcing capability to support
Capability applications that require high initial
response.
Power Stage IGBT Accept 1 or 3 phase 6 SCR Bridge, 1 or 3 phase Capable of being powered from a variety
power 50 to 500Hz power depending on of different sources.
excitation requirements at 50
to 160Hz or 161 to 420Hz
option.
Power input 60, 120 and 240Vac 1 or 3 120Vac 3 phase or 240Vac 1 Capable of being powered from a variety
phase for 32, 63 and 125Vdc phase for 63Vdc of different sources.
applications respectively. applications. 240Vac 3
phase for 125Vdc
applications.
Control Power 24/48Vdc or 125Vdc/120Vac 24/48Vdc/24Vac or Allows DECS-200N to be powered by
125/120Vac two different Control Power Sources.
Note: Isolation transformer required
when dual sources are used.
Programmable Output 3 Programmable Output 5 Programmable Output Increases flexibility
Contacts Contacts Contacts. Relay 4 and 5
Make Rating 30A for 0.2sec
Field Flash N/A Dropout Level and Maximum DECS-200N controls when to apply and
Flashing Time remove flashing. Also provides over-
flash protection.
Selection to Disable Disables Voltage Matching Disable Voltage Matching The selection to only allow Voltage
Voltage Matching via when either 52JK or 52LM when either 52JK or 52LM Matching to be disabled via 52JK allows
breaker Contact Input contact input opens contact input opens (Default) the generator to be parallel to other
OR just 52JK (Optional) machines isolated from the grid and still
allow Bus Voltage Matching to the utility
to occur.
Crowbar Protection N/A Built in. The internal crowbar circuit protects
against field overvoltage and also is
used to discharge energy in the exciter
field during shutdown.
Terminal Connections Compression Type Screw terminals for Screw Terminals incorporated to
Operating Power Input, accommodate higher bridge current and
Current Transformer Input able to accept ring-tongue lugs on CT
and Bridge output. Tension circuits.
clamp terminals for all other
connections.
Dimensions H x W x D 12.0 x 8.08 x 7.32 inches 12.0 x 8.75 x 7.94 inches DECS-200N package is slightly larger
(304.8 x 205.2 x 185.9 mm) (304.8 x 222.3 x 201.7 mm) than the DECS-200, while offering a
significant space saving advantage over
similar negative forcing excitation
systems.
Agency UL, CSA, CE and DNV cURus recognition per UL Combined Agency Recognition
Standard 508 and CSA
Standard C22.2 No. 14 and
CE compliant
Accessory External Fly back Diode Not needed. Simplifies Dual DECS-200N Applications
Assembly for Redundant
DECS-200s