GENERATOR 1-5 VOLTAGE REGULATOR UPGRADE

TROGIR MAY. 21ST 2013.

INSTALATION:

DURING THE OFFSHORE TEST PERIOD IN CROATIA (NEAR ŠOLTA), DECS-200 VOLTAGE
REGULATOR SYSTEM WERE FITTED TO GENERATOR CONTROL BAYS. ON THE GENERATOR
CONTROL PANEL FRONT DOOR IS MOUNTED NEW ALUMINIUM PLATE WITH DECS-200
REGULATOR AND ASSOCIATED SWITCHES AND SIGNAL LAPMS. THE NEW INSTALED
SWITCHES AND RELAYS ARE INTEGRATED IN EXISTING SYSTEM. FOR THE DECS-200
MEASURING AND POWER SUPPLY THERE ARE SENSING AND POWER TRANSFORMER
INSTALLED IN BACKSIDE OF GENERATOR PANEL. ALSO FOR GENERATOR AND ELECTRICAL
GRID PROTECTION ARE OVERVOLTAGE AND UNDERVOLTAGE RELAYS PROVIDED. THE
MEASURNIG CURRENT TRANSFORMER IS INSTALLED IN THE BACK SIDE OF GENERATOR
PANEL ON BUS BAR “B”.

ADJUSTING & TESTING:

REGULATOR ADJUSTING IS DONE IN THE BESTCOMS PC SOFTWARE BY SETING THE


GENERATOR MAIN RATED DATA AND REQUIERD PROTECTION LIMITS. THE PID REGULATOR
IS ACORDING TO GENERATOR OPEN CIRCUIT TIME CONSTANT TUNED. WHITH AL RIGHT
AND REQUIERD PARAMETERS THE REGULATOR IS SWITCHED TO AUTOMATIC MODE. OV
AND UV PROTECTION ARE TESTED AND WORKING PROPERLY.

ALL 5 GENERATORS ARE TESTED TO WORK IN PARALEL (IN VARIOUS COMBINATIONS) WITH
INDUCTIVE LOAD (MUD PUMPS AND DRAWWORK). REGULATOR RESPONSES,
RESPECTIVELY GENERATOR VOLTAGES, ARE SATISFACTORY AND PROVIDE MORE
QUALITY TO PLATFORM ELECTRIC GRID.

LIST OF BUILT IN EQUIPMENT:

BASLER AVR DECS-200 VOLTAGE REGULATOR 5 EA.

POWER TRANSFORMER 600/140V, 60 Hz, 2000 VA 5 EA.

SENSING TRANSFORMER 600/120V, 60Hz, 100VA 5 EA,

OV & UV RELAYS 10 EA

ALUMINIUM FRONT PLATE WITH SWITCHES 5 EA.

ATTACHMENT:

PROJECT & DRAWING NUMBER: RECONSTRUCTION OF FIELD EXCITER 0138-1/13

DECS-200 PARAMETER LIST

MARKO HARAMUSTEK CROSCO EL. DEPT.