You are on page 1of 8

Multilin™

F35
FEEDER PROTECTION SYSTEM

Cost-effective protection and control


for single/multiple distribution feeders
KEY BENEFITS
• Cost effective and flexible protection and control device for • CyberSentry™ Provides High-end cyber security aligned to
distribution feeder applications industry standards and services (NERC-CIP, AAA, Radius, RBAC,
• Improved system stability at reduced cost - Control schemes Syslog)
using hi-speed communications • Robust network security enabling Critical Infrastructure
• Phasor Measurement Unit (synchrophasor) according to IEEE Protection through user command logging, and dual permission
C37.118 (2011) and IEC61850-90-5 support access control
• Three independent Fiber or Copper Eth ports for Simultaneous/ • High-end fault and disturbance recording, including internal
dedicated network connections with advanced 1 micro second relay operating signals thus eliminating the need for redundant
Time-synchronization via LAN with IEEE 1588 support recording devices
• Reduced relay to relay wiring and associated installation costs • Accurate built-in metering functions - Eliminates auxiliary
through high-speed inter-relay communications metering devices and reduces cost
• Embedded IEC61850 Protocol with no external communications • Complete IEC 61850 Process Bus solution providing resource
hardware required optimization and minimizing total P&C life cycle costs

APPLICATIONS
• Primary protection and control for multiple distribution feeders • Busblocking/ interlocking schemes
• Distribution load shedding schemes based on voltage and • Throw over schemes (bus transfer scheme applications)
frequency elements • Distributed Generation (DG) interconnect protection, including
active and passive anti-islanding
FEATURES
Protection and Control IEC 61850 Process Bus Interface
• Instantaneous and time phase overcurrent protection • Robust communications with up to 8 HardFiber Bricks
• Thermal overload, Instantaneous and time ground/neutral/ • Redundant architecture for dependability and security
negative sequence overcurrent protection, Wattmetric Ground
Fault Directional Monitoring and Metering
• Neutral and auxiliary overvoltage • Metering - current, voltage, power, energy, frequency
• Phase and auxiliary undervoltage • Advanced recording capabilities deliver a 1024 event recorder,
configurable and extended waveform capture and data logger
• Under frequency
• Setting Security Audit Trail for tracking changes to F35
• Four shot autoreclose for up six breakers and Broken conductor configuration
elements
• Built-in selector switch EnerVista™ Software
• Graphical Logic Designer and Logic Monitor to simplify designing
Communications and testing procedures - Enervista UR Engineer
• Networking interfaces – Up to three Ethernet ports 100Mb Fiber • Service and Update notification toolset that also ensures device
or copper, RS485, RS232, RS422, G.703, IEEE C37.94 documents and software are up-to-date - Enervista LaunchPad
• Multiple Protocols - IEC61850, DNP 3.0 and Modbus serial/TCP, • EnerVista™ Integrator providing easy integration of data in the
IEEE1588, IEC60870-5-104, Ethernet Global Data (EGD) F35 into new or existing monitoring and control systems
• Direct I/O – secure, high-speed exchange of data between URs
for Direct Transfer Trip applications
• Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber
optic ports and 2 copper ports

g imagination at work
F35 Feeder Protection System

Protection and Control F35 - Protection, Metering, Monitoring and Control


The F35 Feeder Protection System provides
feeder protection, control, monitoring and
metering in an integrated, economical, and
compact package. As part of the Universal
Relay (UR) Family, the F35 provides cost-
effective solutions and features high
performance protection, expandable
Distribution Feeder Protection

I/O options, integrated monitoring and


metering, high-speed communications, and
extensive programming and configuration
capabilities. The F35 can be configured to
protect up to six feeders or protect up to five
feeders when bus voltage measurement
is required. It also provides fast and
deterministic execution of programmable
logic necessary for substation automation
The F35 is the single point for protection, control, metering, and monitoring in one integrated device
applications. Graphical programming tools that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
(ViewPoint Engineer), supported by a library Monitoring as shown.
of logic components, make the F35 simple
to use and configure. with a sensitive ground current input, which
• Instantaneous or linear reset time
The F35 has a wide range of protection provides ground fault protection on high
characteristic to coordinate with
elements that have many years of proven impedance grounded systems. This can be
upstream transformer damage curves
field experience. Protection and control especially important when using a residual
and downstream reclosers and fuses.
features includes: CT connection to detect ground faults.
• Voltage restraint to increase sensitivity
Overcurrent Protection The majority of distribution systems are Wattmetric Ground Fault Protection
The F35 has built-in standard IEEE, IEC, IAC either solidly grounded or through a A sensitive wattmetric zero-sequence
and FlexCurves overcurrent characteristics low impedance. Fast fault clearance is directional function can be used on isolated
(TOC), most commonly used for primary required due to the ground fault impact. or resonant (Petersen coil) grounded, low-
and back up protection in various protective Following functions are incorporated in resistance grounded and solidly grounded
zones. The F35 has Thermal overload and F35 to provide ground protection: systems to detect ground faults.
phase IOC elements with level detectors This function determines the presence and
for each phase. Each TOC element has the • Neutral IOC and TOC direction of ground faults by measuring
following programmable characteristics: the value and direction of zero-sequence
• Ground IOC and TOC
power. This flexible element responds to
• Pickup current level for trip, alarm, or • Negative Sequence IOC and TOC
power derived from zero-sequence voltage
control and current in a direction specified by the
Sensitive Ground Input
• Choice of 17 curve shapes (including element characteristic angle. Power can
FlexCurves) and curve multipliers The F35 CT/VT modules may be ordered

ANSI Device Numbers & Functions


Functional Block Diagram Device
Number Function
DEVICE
27P
NUMBER FUNCTION
Phase Undervoltage
52 2 3 4 5 27P 27X PhaseAuxiliary Undervoltage
Undervoltage
27X 32N Wattmettric
Auxiliary Zero Squence Directional
Undervoltage
50G 49
(up to 12) Ground Instantaneous
Thermal OverloadOvercurrent
50N 50G
(up to 12) Neutral Instantaneous Overcurrent
Ground Instantaneous Overcurrent
50P (up to 12) Phase Instantaneous Overcurrent
79(6) 51G 50N
(up to 6) GroundNeutral Instantaneous Overcurrent
Time Overcurrent
Monitoring Same Functions as Breaker 1
CLOSE TRIP 51N 50P
(up to 6) Phase Instantaneous
Neutral Time Overcurrent Overcurrent
51P (up
50_2to 6) PhaseNegative
Time Overcurrent
Sequence Instantaneous
52 AC Circuit Breaker
Overcurrent
59N 51G Neutral Overvoltage
Ground Time Overcurrent
50P 51P 50_2 51_2 49 50N 51N 59X Auxiliary Overvoltage
For Breaker 1 51N Neutral Time Overcurrent
2 1 2 2 2 1 79 (up to 6) Autoreclose
51P
81 (up to 6) Phase Time Overcurrent
Underfrequency
32N
27X 27P 81U 59N 59X 51_2 Negative Sequence Time Overcurrent
4
2 6 52 AC Circuit Breaker
50G 51G METERING 59N Neutral Overvoltage
2 1 59X Auxiliary Overvoltage
Transducer
79(6) Automatic Recloser
FlexElement
TM
Inputs
81 Underfrequency
F35 Multiple Feeder Protection System

310 GEDigitalEnergy.com
F35 Feeder Protection System

Comprehensive Protection & Control IEC 61850 fiber optic communications.


The HardFiber System is designed to
integrate seamlessly with the existing
CB1 CB2 Universal Relay applications, including
F35 protection functions, FlexLogic, metering
and communications.

The Multilin HardFiber System offers the


following benefits:

Distribution Feeder Protection


• Communicates using open standard
TCB1
IEC 61850 messaging
CB3 CB4 CB5 CB6
• Drastically reduces P&C design,
installation and testing labor by
eliminating individual copper
Cost-effective single box auto-transfer scheme solution terminations
• Integrates with existing F35’s by
replacing traditional CT/VT inputs with
be selected as active, reactive, or apparent. • Backup motor protection to prevent IEC 61850 Process Bus module
Therefore, the element may be used to sense automatic restart. • Does not introduce new Cyber Security
either forward or reverse ground faults concerns
Autorecloser
Under/Over Voltage Protection
Up to 6 programmable breaker Visit the HardFiber System product page
The F35 includes the following voltage
autoreclosers for a variety of reclosing on the GE Digital Energy web site for more
elements:
practices are provided. These elements details.
are intended for use with distribution lines
• Up to 6 phase undervoltage elements in tripping schemes for single breaker
• Up to 3 auxiliary undervoltage/ applications. Up to four selectable reclosers Advanced Automation
overvoltage elements “shots” are possible prior to locking out. The F35 incorporates advanced automation
• Up to 3 neutral overvoltage elements Any of the six autoreclose elements can features including powerful FlexLogic™
be dynamically blocked or unblocked by programmable logic, communication, and
other F35 elements or user logic, providing SCADA capabilities that far surpass what
The following are some of the key
coordination with other Protection setting is found in the average line relay. The F35
applications where voltage elements can
groups. integrates seamlessly with other UR relays
be used:
for complete system protection, including
the unit and auxiliary transformers, and
• Source transfer schemes IEC 61850 Process Bus Balance of Plant protection.
• Load shedding schemes The IEC 61850 Process Bus module is
• Back up capacitor bank protection and designed to interface with the Multilin FlexLogic™
control HardFiber System, allowing bi-directional FlexLogic™ is the powerful UR-platform
programming logic engine that provides
the ability of creating customized
Fiber LAN, single
or redundant, for protection and control schemes thereby
Source
added security
minimizing the need, and the associated
CB1
costs, of auxiliary components and wiring.
Using FlexLogic™, the F35 can be
programmed to provide required tripping
Fault 1
logic along with custom scheme logic for line
CB2
phase comparison (including interlocking
with external synchronizers), transfer
tripping schemes for remote breakers and
CB3
dynamic setting group changes.

Fault 2

Reverse zone interlocking protection - By using the IEC61850 GOOSE or hi-speed Direct I/O capability blocking
signals can be transferred upstream, allowing minimal coordination delays. Fast clearance can be provided for
Fault 1 and still maintain coordination for Fault 2.

GEDigitalEnergy.com 311
F35 Feeder Protection System

Scalable Hardware • Data Logger, disturbance recording – Role Based Access Control (RBAC)
The F35 is available with a multitude 16 channels up to 1 sample / cycle / Efficiently administrate users and roles
of I/O configurations to suit the most channel within UR devices. The new and advance
demanding application needs. The • Fault Reports access functions allow users to configure
expandable modular design allows for - Powerful summary report of pre-fault up to five roles for up to eight configurable
easy configuration and future upgrades. and fault values users with independent passwords.
• Multiple CT/VT configurations allow for The standard “Remote Authentication
implementation of many differential The very high sampling rates and large Dial In User Service” (Radius) is used for
Distribution Feeder Protection

schemes, including concurrent split- amount of storage space available for authentication.
phase and differential protection data recording in the F35 can eliminate
Event Recorder (Syslog for SEM)
• Up to 80 digital inputs and up to 56 the need for installing costly standalone
digital outputs are available recording equipment. Capture all cyber security related events
within a SOE element (login, logout, invalid
• Types of digital outputs include trip-
Advanced Device Health password attempts, remote/local access,
rated Form-A and Solid State Relay
Diagnostics user in session, settings change, FW
(SSR) mechanically latching, and
The F35 performs comprehensive device update, etc), and then serve and classify
Form-C outputs
health diagnostic tests during startup data by security level using standard
• Form-A and SSR outputs available with Syslog data format . This will enable
and continuously at runtime to test
optional circuit continuity monitoring integration with established SEM (Security
its own major functions and critical
and current detection to verify proper Event Management) systems.
hardware. These diagnostic tests monitor
operation of the connected primary
for conditions that could impact security
equipment
and availability of protection, and present
• Mechanically latching outputs device status via SCADA communications
Communications
can be used to develop secure and front panel display. Providing The F35 provides advanced commun-
interlocking applications and replace continuous monitoring and early detection ications technologies for remote data and
electromechanical lockout relays of possible issues helps improve system engineering access, making it the easiest
• RTDs and DCmA inputs are available to uptime. and most flexible feeder protection relay
monitor equipment parameters such as to use and integrate into new and existing
temperature & pressure • Comprehensive device health infrastructures. Direct support for fiber
diagnostic performed during startup optic Ethernet provides high-bandwidth
communications allowing for low-latency
• Monitors the CT/VT input circuitry to
Monitoring and Metering validate the integrity of all signals
controls and high-speed file transfers of
relay fault and event record information.
The F35 includes high accuracy metering • Input, outputs, trip circuits and analog The available three independent Ethernet
and recording for all AC signals. Voltage, channels are continuously monitored ports, redundant Ethernet option and
current, and power metering are built into for accuracy and performance the embedded managed Ethernet switch
the relay as a standard feature. Current
provide the means of creating fault
and voltage parameters are available as
tolerant communication architectures in
total RMS magnitude, and as fundamental Cyber Security – an easy, cost-effective manner without
frequency magnitude and angle.
CyberSentry™ UR the need for intermediary communication
Fault and Disturbance Recording CyberSentry™ UR enabled UR devices hardware.
deliver full cyber security features that help The F35 supports the most popular
The advanced disturbance and event
customers to comply with NERC CIP and industry standard protocols enabling easy,
recording features within the F35 can
NIST IR 7628 cyber security requirements. direct integration into DCS and SCADA
significantly reduce the time needed for
This software option delivers the following systems.
postmortem analysis of power system
events and creation of regulatory reports. core features:
Recording functions include: • IEC61850
AAA Server Support (Radius/LDAP)
• DNP3.0
• Sequence of Event (SOE) Enables integration with centrally
• Ethernet Global Data (EGD)
- 1024 time stamped events managed authentication and accounting
of all user activities and uses modern • IEC6870-5-104
- Events up to 45s in length
industry best practices and standards that • IEEE 1588 for time synchronization
• Oscillography,
meet and exceed NERC CIP requirements • Modbus RTU, Modbus TCP/IP
- 64 digital & up to 40 Analog channels for authentication and password
management.

312 GEDigitalEnergy.com
F35 Feeder Protection System

Interoperability with Embedded the connection method, Direct I/O provides the local displays without uploading new
IEC61850 continuous real-time channel monitoring firmware.
Use the F35 with integrated IEC61850 to that supplies diagnostics information on
channel health.
lower costs associated with substation
Direct I/O provides superior relay-to- EnerVistaTM Software
protection, control and automation. GE
Energy’s leadership in IEC61850 comes relay communications that can be used The EnerVista™ Suite is an industry-leading
from thousands of installed devices and in advanced interlocking, generation set of software programs that simplifies
follows on seven years of development rejection and other special protection every aspect of using the F35 relay. The
schemes. EnerVista™ suite provides all the tools to

Distribution Feeder Protection


experience with UCA 2.0.
monitor the status of feeders, maintain the
• Communication with up to 16 UR relays relay, and integrate information measured
• Replace expensive copper wiring
in single or redundant rings rather than by the F35 into DCS or SCADA monitoring
between devices with direct transfer of
simplistic point-to-point configurations systems. Convenient COMTRADE and
data using GOOSE messaging
• Connect to standard DS0 channel Sequence of Events viewers are an integral
• Configure GE Systems based on part of the UR Setup software included with
IEC61850 and also monitor and banks through standard RS422, G.703
or IEEE C37.94 interfaces or via direct every UR relay, to carry out postmortem
troubleshoot them in real-time with event analysis to ensure proper protection
EnerVista™ Viewpoint Engineer fiber optic connections
system operation.
• Multicast C37.118 Synchrophasor data • Built-in continuous loop and channel
between PMU and PDC devices using monitoring provides real-time EnerVista™ Launchpad
IEC61850-90-5 in EnerVista™ Viewpoint diagnostics of your communication
EnerVista™ Launchpad is a powerful
Monitoring channels – no external or handheld
software package that provides users with
tester required
all of the setup and support tools needed
Direct I/O Messaging for configuring and maintaining Multilin
Multi-Language
Direct I/O allows for sharing of high-speed products. The setup software within
digital information between multiple UR The F35 supports English, French, Russian, Launchpad allows configuring devices
relays via direct back-to-back connections Chinese and Turkish Languages on the in real-time by communicating using
or multiplexed through a standard DS0 front panel, EnerVista™ setup software, serial, Ethernet, or modem connections, or
multiplexer channel bank. Regardless of and product manual. Easily switch between offline by creating setting files to be sent to
English and an additional language on devices at a later time.

Power System Troubleshooting


The F35 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Analyze feeder faults using both analog and digital power system quantities
that are measured and recorded up to a rate of 64 samples per cycle.

Record the operation of the internal F35 elements and external connected
devices with 1ms time-stamped accuracy to identify the Sequence of
Operation of station devices during feeder faults and disturbances.

GEDigitalEnergy.com 313
F35 Feeder Protection System

Included in Launchpad is a document • Plug-&-Play Device Monitoring Viewpoint Maintenance


archiving and management system Viewpoint Maintenance provides tools that
• System Single-Line Monitoring & Control
that ensures critical documentation is will create reports on the operating status
• Annunciator Alarm Screens
up-to-date and available when needed. of the relay, simplify the steps to download
Documents made available include: • Trending Reports
fault and event data, and reduce the work
• Automatic Event Retrieval required for cyber-security compliance
• Manuals • Automatic Waveform Retrieval audits. Tools available in Viewpoint
• Application Notes Maintenance include:
Distribution Feeder Protection

• Guideform Specifications Viewpoint UR Engineer


Viewpoint UR Engineer is a set of powerful • Settings Security Audit Report
• Brochures
tools that will allow you to configure and • Device Health Report
• Wiring Diagrams
test GE relays at a system level in an • Single Click Fault Data Retrieval
• FAQ’s easy-to-use graphical drag-and-drop
• Service Bulletins environment . Viewpoint UR Engineer EnerVista™ Integrator
provides the following configuration and
EnerVista™ Integrator is a toolkit that allows
Viewpoint Monitoring commissioning utilities:
seamless integration of Multilin devices
Viewpoint Monitoring is a simple-to-use into new or existing automation systems.
and full-featured monitoring and data • Graphical Logic Designer Included in EnerVista™ Integrator is:
recording software package for small
• Graphical System Designer
systems. Viewpoint Monitoring provides a
• Graphical Logic Monitor • OPC/DDE Server
complete HMI package with the following
• Graphical System Monitor • Multilin Drivers
functionality:
• Automatic Event Retrieval
• Automatic Waveform Retrieval

User Interface
The F35 front panel provides extensive local HMI capabilities. The local display is used for monitoring, status messaging,
fault diagnosis, and device configuration. User configurable messages that combine text with live data, can be displayed
when user-defined conditions are met.

48 Configurable LED Indicators

Multi-Language
Display
•  English
•  Russian
•  French
•  Chinese
•  Turkish

User Programmable Pushbuttons

314 GEDigitalEnergy.com
F35 Feeder Protection System

Typical Wiring

A B C F1a I P1a TC 1

6G
IA5
P1 P1b
V
F1b IA P1c
I P2a
F1c IA1 P2 P2b
V
F2a IB5
P2c
I P3a
F2b IB P3 P3b TC 2
V
1 F2c IB1 I
P3c
P4a
P4 P4b
F3a IC5 V
P4c
F3b IC P5a

Distribution Feeder Protection


P5c
F3c IC1 P6a
P6c
F4a IG5
P5b
F4b IG P7a
F4c P7c
IG1
P8a
F5a IA5 P8c
P7b
F5b IA
SURGE P8b
F5c IA1
Digital Energy
F6a IB5
Multilin
F6b IB

2 F6c IB1 F35


F7a IC5

F7b IC
I H1a

6G
H1 H1b
V
F7c IC1 H1c
I H2a
F8a IG5 H2 H2b
V
F8b IG H2c
I H3a
F8c IG1 H3 H3b
V
H3c
M1a IA5 I H4a
M1b H4 H4b
IA V
H4c
M1c IA1 H5a
H5c UR COMPUTER
M2a IB5 H6a 1 1 8
H6c
M2b IB TXD 2 2 3 RXD
H5b
3 M2c IB1 H7a
RXD 3
4
3
4
2 TXD
20
H7c SGND 5 5 7 SGND
M3a IC5
H8a 6 6 6
M3b IC H8c 7 7 4
H7b 8 8 5
M3c IC1 9 9 22
SURGE H8b
M4a IG5

M4b IG CONNECTOR CONNECTOR

M4c IG1 RS-232

M5a IA5 DB-9


(front)
M5b IA
I W1a
6G

M5c IA1
W1 W1b
V
M6a IB5 W1c
I W2a
M6b IB W2 W2b
V
4 M6c IB1 I
W2c
W3a
M7a IC5 W3 W3b
V
W3c
M7b IC I W4a
W4 W4b
M7c IC1 V
W4c
W5a
M8a IG5
W5c
M8b IG W6a
W6c
M8c IG1 W5b
U1a IA5 W7a
W7c
U1b IA
W8a
U1c IA1 W8c
W7b
U2a IB5 SURGE W8b
U2b IB
B1b
5 CRITICAL
1

U2c IB1 B1a


FAILURE
B2b
U3a IC5 DC
B3a
OUTPUT B3b
U3b IC
HI B5b
IC1 CONTROL
U3c LO B6b
POWER
B6a
U4a IG5
SURGE B8a
U4b IG FILTER B8b

U4c IG1
NORMAL
Tx1 10BaseFL * Optic
Fibre
Rx1
U5a VA
COM Tx2 10BaseFL
ALTERNATE
U5c VA 1 Rx2

10BaseT Shielded
U6a VB
Remote
U6c VB D1a Device
RS485
D2a
U7a VC com D3a
D4b
U7c VC IRIG-B D4a
CONNECTION

Input
U8a VX BNC Co-axial

U8c VX IRIG-B
Output BNC Co-axial

832767A5.CDR

Minimum
X W V U T S R P N M L K J H G F D B
6 8 6 8 6 8 9 1

Inputs/ CT/VT Inputs/ CT Inputs/ CT CPU Power


outputs outputs outputs Supply
U5a VA
PROVIDED
U5c VA

U6a VB

U6c VB

U7a VC

U7c VC F35-H00-HCH-F8H-H6G-M8H-P6G-U8F-W6G

GEDigitalEnergy.com 315
F35 Feeder Protection System

Ordering
F35 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W * For Full Sized Horizontal Mount
Base Unit F35 Base Unit
CPU E RS485 + RS485 (IEC61850 option not available)
G RS485 + Multi-mode ST 10BaseF
H RS485 + Mutli-mode ST Redundant 10BaseF
J RS485 + Multi-mode ST 100BaseFX
K RS485 + Multi-mode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three Multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two Multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
Distribution Feeder Protection

V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher


Software Options 00 No Software Options
(see note 1 below) 03 IEC61850
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
D0 IEEE 1588 + CyberSentry UR. Req UR FW 7.xx or higher
Mount / Coating H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
F Vertical Front Panel with English display
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
Power Supply H 125 / 250 V AC/DC
(see note 2 below) H RH 125/250 V AC/DC with redundant 125/250 V AC/DC power supply
L 24 - 48 V (DC only)
CT/VT DSP 8F 8F 8F Standard 4CT/4VT
8G 8G 8G Sensitive Ground 4CT/4VT
8H 8H 8H Standard 8CT
8J 8J 8J Sensitive Ground 8CT
8L 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5C 5C 5C 5C 5C 8 RTD Inputs
5D 5D 5D 5D 5D 4 RTD Inputs, 4 dcmA Outputs
5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel

Ordering Note: 1 . To view all the options available for F35, please visit GE’s On-Line Store at http://store.gedigitalenergy.com/viewprod.asp?model=F35
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type. Maximum 2 per chassis

Accessories for the F35 Visit GEMultilin.com/F35 to:


  •  UR Applications I Learning CD TRCD-URA1-C-S-1   •  View Guideform specifications
  •  Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-F1   •  Download the instruction manual
  •  Viewpoint Engineer VPE-1   •  Review applications notes and support documents
  •  Viewpoint Maintenance VPM-1   •  Buy a F35 online
  •  Viewpoint Monitoring IEC61850 VP-1-61850   •  View the UR Family brochure

121203-v4
316 GEDigitalEnergy.com

You might also like