1606-XLE80E
24V,3.3A Single Phase Input
POWER SUPPLY
¾ Ultra-small size
¾ Extra-low inrush current
¾ Active power factor correction
¾ Wide range AC/DC input
¾ Superior efficiency and temperature rating
¾ DC-OK
1. GENERAL DESCRIPTION
The 1606 XLE power suppliesare cost optimized power supplies without compromising quality, reliability and performance. The 1606-XLE80E is part of
the XLE power supply family.
The 1606-XLE includes all the essential basic functions. The most important features are the small size, the high efficiency and the wide temperature
range.The wide-range-input makes worldwide installation and usage very simple.
www.ra.rockwell.com
Rockwell Automation
1606-XLE80E 24V, 3.3A; Single Phase Input
INTENDED USE
Those responsible for the application and use of the products must satisfy themselves that all necessary steps have been taken to assure that each
application and use meets all performance and safety requirements, including and applicable laws, regulation , codes, and standards.
50Hz vs. 60Hz As long as not otherwise stated, AC 380V and AC 400V parameters are valid at 50Hz and AC 480V
parameters are valid at 60Hz mains frequency.
PELV Protective Extra Low Voltage
SELV Safety Extra Low Voltage
www.ra.rockwell.com
Rockwell Automation
1606-XLE80E-2 24V, 3.3A; Single Phase Input
5. AC-INPUT
AC input nom. AC 100-240V Wide-range- input, see Fig. 5-1
AC input range 90-264Vac 100-120V range, continuous operation
85-90Vac Short term or with output derating
264-300Vac < 0.5s
Input frequency nom. 50 – 60Hz ±6%
Fig. 5-1 Input voltage range Fig. 5-2 Turn-on behavior, definitions
Rated
POUT input range max. Intput
500ms Voltage
Shut -dow n
Turn-on
Output - 5%
Overshoot
Voltage
VIN Start-up Rise
delay Time
58 75 90 264 300Vac
Fig. 5-3 Input current vs. output load Fig. 5-4 Power factor vs. output load
Power
1.8A Input 0.65 Factor, typ.
Current, typ. (a)
1.5 (a) 0.60 (b)
Fig. 6-1 Wiring for DC input Fig. 6-2 Output current versus input voltage, max.
Output
Battery Current
Power Supply
3.5A
+ AC
internal
3.0
L
fused 2.5
+ 2.0
N Load 1.5
-
Fuse
PE 1.0
0.5
- DC DC Input Voltage
0
88 110 375Vdc
Input Current
Input: 230Vac
Output: 24V, 3.3A
Ambient: 25°C
Input Voltage
Upper curve: Input current 20A / DIV
Medium curve: Input voltage 500V / DIV
Lower curve: Output voltage 20V / DIV
Output Voltage Time scale: 40ms / DIV
8. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 38ms 60ms 244ms 1.65A, 24V, see Fig. 8-1
typ. 19ms 29ms 120ms 3.3A, 24V, see Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage Fig. 8-2 Shut-down behavior, definitions
225ms Hold-up
Time Zero Transition
200
24V, 1.65A, min. Intput
175
24V, 1.65A, typ. Voltage
150
125
100
75 - 5%
Output
50 24V, 3.3A, min.
Voltage
24V, 3.3A, typ.
25 Hold-up Time
Input Voltage
0
85 120 155 190 230Vac
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.
Fig. 10-1 Efficiency vs. output current at 24V, typ. Fig. 10-2 Losses vs. output current at 24V, typ.
Fig. 10-3 Efficiency vs. input voltage, 24V, 3.3A, typ. Fig. 10-4 Losses vs. input voltage, 24V, 3.3A, typ.
Efficiency Power Losses
91% 18W
90 15
89 12
88 9
87 6
86 3
Input Voltage Input Voltage
85 0
85 120 155 190 225 260Vac 85 120 155 190 225 260Vac
Output
Voltage
Regulator VOUT
L Input +
Input Fuse Rectifier Power Output +
N & & Converter Filter
Input Filter NTC Inrush -
Limiter
-
Output
Over- DC
Voltage ok
Protection
12. RELIABILITY
These units are extremely reliable and use only the highest quality materials. The number of critical components such as electrolytic capacitors has
been reduced.
AC 100V AC 120V AC 230V
Lifetime expectancy min. 57 000h 64 000h 77 000h 40°C, 24V, 3.3A
min. t.b.d. t.b.d. t.b.d. 40°C, 24V, 1.65A
min. 160 000h >15 years >15 years 25°C, 24V, 3.3A
MTBF SN 29500, IEC 61709 t.b.d. t.b.d. t.b.d. 40°C, 24V, 3.3A
t.b.d. t.b.d. t.b.d. 25°C, 24V, 3.3A
MTBF MIL HDBK 217F t.b.d. t.b.d. t.b.d. 40°C, 24V, 3.3A, Ground Benign GB40
t.b.d. t.b.d. t.b.d. 25°C, 24V, 3.3A, Ground Benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the lifetime expectancy of the built-in
electrolytic capacitors.
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The
prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the
statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Input Terminals
Screw terminals
N … Neutral input
L … Line (hot) input
... PE (Protective Earth) input
15. EMC
The CE mark is in conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EWG.
Switching frequency
50kHz to 450kHz Input voltage and load dependent
16. ENVIRONMENT
Operational temperature -25°C to +70°C (-13°F to 158°F) Resistive load,
Reduce output power according Fig. 16-1
Output de-rating 1.8W/°C 60-70°C (140°F to 158°F)
Storage temperature -40 to +85°C (-40°F to 185°F) Storage and transportation
Humidity 5 to 95% r.H. IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g IEC 60068-2-6
2 hours / axis
Shock 30g 6ms, 20g 11ms IEC 60068-2-27
3 bumps / direction, 18 bumps in total
Altitude 0 to 6000m (0 to 20 000ft) Reduce output power or ambient temperature above
2000m sea level.
Output de-rating (for altitude) 5W/1000m or 5°C/1000m above 2000m (6500ft), see Fig. 16-2
Over-voltage category III EN 50178, IEC 62103 altitudes < 2000m
II Altitudes from 2000m to 6000m
Degree of pollution 2 EN 50178, IEC 62103 not conductive
Fig. 16-1 Output current vs. ambient temp., Fig. 16-2 Output current vs. altitude, 24V
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit
shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when
unnoticed earth faults occur.
IECEE
IEC 60950-1 CB Scheme,
Information Technology Equipment
CB SCHEME
UL 508 18WM LISTED E198865
LISTED Industrial Control Equipment
IND. CONT. EQ.
NEC Class 2 According to NEC (National Electrical Code) Article 725-41 (4).
Listed as Limited Power Source (LPS) in the UL 60950-1 UL report.
UL 60950-1 RECOGNIZED E137006 recognized for the use in U.S.A. (UL 60950-1) and Canada
(C22.2 No. 60950)
Information Technology Equipment, Level 3
CSA CSA approval for Canada
pending R
CAN/CSA C22.2 No 107-1; CAN/ CSA 60950-1-03; UL60950-1
C US
182790
Hazardous voltage inside device. Risk of electric shock, severe burns, or death.
• Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth connection and not one of
the screws on the housing.
• Turn power off before working on the power supply. Protect against inadvertent re-powering.
• Make sure the wiring is correct by following all local and national codes.
• Do not open, modify or repair the unit.
• Use caution to prevent any foreign objects from entering into the housing.
• Do not use in wet locations or in areas where moisture or condensation can be expected.
Mounting Orientation:
Output terminal must be located on top and input terminal on the bottom. For other orientations see section 26.12
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent
device is a heat source, 15mm clearance is recommended.
Service parts:
The unit does not contain any serviceable parts. The tripping of an internal fuse is caused by an internal defect.
25. ACCESSORY
1606-XLB Wall mounting bracket
This bracket is used to mount XLE units onto a flat surface without utilizing a DIN-Rail. The two aluminum brackets and the black plastic slider of the
unit have to be detached, so that the two steel brackets can be mounted.
(Picture shows a different power supply)
Fig. 25-1 1606-XLB Wall Mounting Bracket Fig. 25-2 Assembled Wall Mounting Bracket
Output Output
Voltage 24V Voltage 24V
6.6A 16.5A
12.5V
7V
Output Output
Current Current
0A 0A
10ms/DIV 1ms/DIV
Peak load 6.6A (resistive) for 50ms Peak load 16.5A (resistive) for 5ms
Output voltage dips from 24V to 12.5V. Output voltage dips from 24V to 7V.
Test 1: Short circuit with S1 on the power supply end of the cable (loop impedance approx. 20mOhm)
Fig. 26-3 Branch protectors, test circuit 1
Parameters:
Circuit
Breaker
Input voltage: 230Vac, load current: 0A
Power
Supply I
AC + + The following circuit breaker tripped during the test:
S1 Load
A- or Z- Characteristic:: equal or smaller 6A
B- Characteristic: no tripping ≥ 6A
DC - - no breaker available < 6A
C- Characteristic: equal or smaller 1A
Test 2: Short circuit with S1 on the load end (additional impedance included; represents longer load wire length).
Fig. 26-4 Branch protectors, test circuit 2 Parameters:
Input voltage: 230Vac, load current: 0A
Circuit
Power Breaker The following circuit breaker tripped during the test:
Supply I
R A- or Z- Characteristic:: ≤ 4A and R= 220mOhm
AC + + B- Characteristic: no tripping ≥ 6A
S1 Load no breaker available < 6A
C- Characteristic: ≤ 1A and R= 390mOhm
DC - -
Example:
Which wire gauge must be used to trip a C-Characteristic circuit breaker with a rating of 1A? The load wire length is 25m.
Answer: A 1A C-Characteristic circuit breaker requires a loop impedance of less than 390mOhm (test results). The wire length table shows that up to
32.6m wire with a cross section of 1.5mm2 are below 390mOhm. A wire not smaller than 1.5mm2 shall be used.
internal
fuse
L b) Use a fuse or a circuit breaker to protect the N input. The N input is
internally not protected and is in this case connected to a hot wire.
+10%
Fuse
L3 N
Appropriate fuses or circuit breakers are specified in section 26.9 “External Input
240V
PE
Protection”.
L2 DC
10 20 30 40 50 60°C
A1
INPUT
2
1
Ambient Temperature
0
10 20 30 40 50 60°C
Supply
Power
INPUT
A1
2
1
Ambient Temperature
0
10 20 30 40 50 60°C