1606-XLE120E-2
24V,5A Two Phase Input
POWER SUPPLY
¾ Ultra-small size
¾ Extra-low inrush current
¾ Superior efficiency and temperature rating
¾ DC-OK
1. GENERAL DESCRIPTION
The 1606-XLE supplies are cost optimized power supplies without compromising quality, reliability and performance. The 1606-XLE120E-2 is
part of the 1606-XLE power supply family. The most outstanding features of 1606-XLE120E-2 are the high efficiency, electronic inrush current
limitation, active input transient filter and wide operational temperature range, the small size and other technological design concepts.
The 1606-XLE includes all the essential basic functions. The devices have a power reserve of 20% included, which may even be used
continuously at temperatures up to +45°C. The 1606-XLE120E-2 utilizes only 2 legs of a 3-phase system which saves wiring and installation
costs. Furthermore, this allows a smaller unit without compromising the size of the terminals. Due to the low power consumption, an
unbalancing of the individual phases is not expected.
www.ra.rockwell.com
Page 1
Rockwell Automation
1606-XLE120E-2 24V, 5A; Two Phase Input
INDEX
Page Page
1. General Description................................................................1 20. Approvals ..............................................................................13
2. Specification Quick reference.................................................1 21. Fulfilled Standards ................................................................13
3. Agency Approvals...................................................................1 22. Used Substances..................................................................13
4. Related Products ....................................................................1 23. Physical Dimensions and Weight .........................................14
Intended Use...................................................................................2 24. Installation Requirements .....................................................14
5. AC-Input..................................................................................3 25. Accessories...........................................................................15
6. DC-Input .................................................................................4 26. Application Notes ..................................................................16
7. Input Inrush Current................................................................4 26.1. Peak Current Capability ...........................................16
8. Output.....................................................................................5 26.2. Back-feeding Loads..................................................16
9. Hold-up Time ..........................................................................6 26.3. Charging of Batteries................................................17
10. Efficiency and Power Losses..................................................6 26.4. Output Circuit Breakers ............................................17
11. Functional Diagram ................................................................7 26.5. Inductive and Capacitive Loads ...............................17
12. Product Face Label ................................................................8 26.6. External Input Protection ..........................................18
13. Terminals and Wiring..............................................................9 26.7. Parallel Use to Increase Output Power ....................18
14. Reliability ................................................................................9 26.8. Parallel Use for Redundancy....................................18
15. EMC......................................................................................10 26.9. Daisy Chaining of Outputs........................................19
16. Environment .........................................................................11 26.10. Series Operation ......................................................19
17. Protection Features ..............................................................12 26.11. Use in a Tightly Sealed Enclosure ...........................19
18. Safety Features ....................................................................12 26.12. Mounting Orientations ..............................................20
19. Dielectric Strength ................................................................12
INTENDED USE
Those responsible for the application and use of the products must satisfy themselves that all necessary steps have been taken to assure that each
application and use meets all performance and safety requirements, including and applicable laws, regulation , codes, and standards.
www.ra.rockwell.com
Page 2
Rockwell Automation
1606-XLE120E-2 24V, 5A; Two Phase Input
5. AC-INPUT
AC input nom. AC 380-480V
AC input range 323-576Vac continuous operation,
no damage between 0 and 323Vac
576-700Vac for max. 1 second, occasional (not periodical)
Allowed Voltage Phase to Earth 500Vac IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 270Vac load independent, see Fig. 5-1
Shut-down voltage typ. 185Vac at 24V, 0A, see Fig. 5-1
typ. 220Vac at 24V, 2.5A
typ. 230Vac at 24V, 5A
AC 400V AC 480V
Input current typ. 0.75A 0.68A at 24V, 5A, see Fig. 5-3
Power factor * typ. 0.45 0.43 at 24V, 5A, see Fig. 5-1
Start-up delay typ. 75ms 75ms see Fig. 5-2
Rise time typ. 35ms 36ms 0mF, 24V, 5A, see Fig. 5-2
typ. 64ms 68ms 5mF, 24V, 5A, see Fig. 5-2
Turn-on overshoot max. 200mV 200mV see Fig. 5-2
* The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
Fig. 5-1 Input voltage range Fig. 5-2 Turn-on behavior, definitions
Turn-on
Output - 5%
Overshoot
Voltage
VIN
Start-up Rise
delay Time
185V 260V 323V 576V 700Vac
Fig. 5-3 Input current vs. output load at 24V Fig. 5-4 Power factor vs. output load
Input Current, typ. Power Factor, typ.
0.8A ac 0.50
0V
0.7 40 ac
0V 400Vac
0.6 48 0.45
0.5 480Vac
0.4 0.40
0.3
0.2 0.35
0.1
Output Current Output Current
0 0.30
0 1 2 3 4 5 6A 0 1 2 3 4 5 6A
6. DC-INPUT
DC input nom. DC 600V
DC input range 450-780Vdc continuous operation
Allowed Voltage Line to Earth max. 820Vdc IEC 62103
DC input current typ. 0.3A / 0.17A 450Vdc / 780Vdc, 24V, 5A
Turn-on voltage typ. 370Vdc steady state value
Shut-down voltage typ. 260Vdc steady state value
AC 400V AC 480V
Inrush current max. 10Apeak 10Apeak -25°C to +70°C
typ. 4Apeak 4Apeak -25°C to +70°C
Inrush energy max. 0.5A2s 0.5A2s -25°C to +70°C
2>
2
20ms / DIV
Fig. 9-1 Hold-up time vs. input voltage Fig. 9-2 Shut-down behavior, definitions
Hold-up Time at 24Vdc
80ms p.
Zero Transition
ty .
A, in Input
2.5 A,
m
Voltage
60 2 .5
,t yp .
5A
40 m in.
5A , - 5%
Output
20 Voltage
Input Voltage Hold-up Time
0
320 360 400 440 480Vac
PFC
L1 Input Fuses
Inductor
+
L2 Input Filter Inrush Power
Converter
Output +
Limiter Filter
Input
Rectifier Transient -
Filter
-
Output VOUT
Temper- Output Output Voltage
ature Power Over- Regulator
Shut- Manager Voltage DC-ok
down Protection LED
• Output Terminals
Screw terminals, dual terminals per pole
+ Positive output
- Negative (return) output
• Input Terminals
Screw terminals
L1, L2 Phase input
PE (Protective Earth) input
14. RELIABILITY
AC 400V AC 480V
Lifetime expectancy * 92 000h 92 000h at 24V, 5A and 40°C
186 000h 175 000h at 24V, 2.5A and 40°C
260 000h 260 000h at 24V, 5A and 25°C
MTBF ** SN 29500, IEC 61709 1 173 000h 1 155 000h at 24V, 5A and 40°C
2 105 000h 2 075 000h at 24V, 5A and 25°C
MTBF ** MIL HDBK 217F 454 000h 446 000h at 24V, 5A and 40°C; Ground Benign GB40
607 000h 593 000h at 24V, 5A and 25°C; Ground Benign GB25
* The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of
the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s
manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
** MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is
the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Switching frequency Variable between 45kHz and 170kHz depending on load and input voltage
Fig. 16-1 Output current vs. ambient temp. Fig. 16-2 Output current vs. altitude at 24V
Allowable Output Allowable Output
Current at 24V short Current at 24V short t erm
t erm
6A 6A
cont inuous B C
5 5
A
4 4
3 3
2 2
A... Tamb < 60°C
1 1 B... Tamb < 50°C
Ambient Temperature C... Tamb < 40°C Altitude
0 0
-25 0 20 40 60 70°C 0 2000 4000 6000m
Hazardous voltage inside device. Risk of electric shock, severe burns, or death.
• Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth connection and not one of
the screws on the housing.
• Turn power off before working on the power supply. Protect against inadvertent re-powering.
• Make sure the wiring is correct by following all local and national codes.
• Do not open, modify or repair the unit.
• Use caution to prevent any foreign objects from entering into the housing.
• Do not use in wet locations or in areas where moisture or condensation can be expected.
Mounting Orientation:
Output terminal must be located on top and input terminal on the bottom. For other orientations see section 26.12
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent
device is a heat source, 15mm clearance is recommended.
Service parts:
The unit does not contain any serviceable parts. The tripping of an internal fuse is caused by an internal defect.
Fig. 26-1 Peak load 10A for 50ms, typ. Fig. 26-2 Peak load 25A for 5ms, typ.
Output
24V Voltage 24V Output
Voltage
18.5V
Output
Current 25A
10A
Output
Current 7V
0A 0A
10ms/DIV 1ms/DIV
Peak load 10A (resistive load) for 50ms Peak load 25A (resistive load) for 5ms
Output voltage dips from 24V to 18.5V. Output voltage dips from 24V to 7V.
Fig. 26-3 Test circuit Maximal wire length for a magnetic (fast) tripping *:
0.75mm² 1.0mm² 1.5mm² 2.5mm²
Power Supply MCB Load C-2A 17m 19m 29m 39m
AC + + C-3A 11m 14m 22m 33m
C-4A 3m 4m 6m 14m
Wire length
S1 C-6A 1m 1m 2m 3m
DC - - C-8A - - - -
S1... Fault simulation switch B-6A 6m 9m 13m 17m
B-10A - - - 1m
* Don’t forget to consider two times the distance to the load (or cable length) when calculating the total wire length (+ and – wire).
Unit A
26.7. PARALLEL USE TO INCREASE OUTPUT POWER AC
+
1606-XLE120E-2 power supplies can be paralleled to increase the output power.
This power supply has no feature included which balances the load current -
DC
between the power supplies. Usually the power supply with the higher adjusted +
output voltage draws current until it goes into current limitation. This means no Unit B
Load
harm to this power supply as long as the ambient temperature stays below 45°C. AC
The 1606-XLE120E-2 can also be paralleled with power supplies from the XLS + -
family. The output voltages of all power supplies shall be adjusted to the same -
value (±100mV). A fuse or diode on the output of each unit is only required if more DC
than three units are connected in parallel. If a fuse (or circuit breaker) is used,
choose one with approximately 150% of the rated output current of one power supply. Keep an installation clearance of
15mm (left / right) between two power supplies and avoid installing the power supplies on top of each other. Do not use
power supplies in parallel in mounting orientations other than the standard mounting orientation (input terminals on the
bottom and output terminals on top of the unit) or in any other condition where a derating of the output current is required
(e.g. altitude, above 60°C, …). Pay attention that leakage current, EMI, inrush current, harmonics will increase when using
multiple power supplies.
Input Input
Distribution
Input Input Terminals
(Horizontal cw) A2
Supply
Pow er
4
INPUT
A1
3
2
1
Ambient Temperature
0
10 20 30 40 50 60°C
(Horizontal ccw) 4 A2
Supply
Pow er
INPUT
3 A1
2
1
Ambient Temperature
0
10 20 30 40 50 60°C