You are on page 1of 92

REF. No.

SS-SSA-DT-A-468
COVER SHEET REVISION 1 PAGE AMOUNT 91

PROJECT 4.9985 MWp SOLAR FARM PROJECT for WVO


OWNER SERMSANG SOLAR CO., LTD
CONTRACTOR SHARP SOLAR SOLUTION ASIA CO., LTD.
PROJECT DOC NO. SS-SSA-TC-E-004

TITLE CABLE SIZING AND VOLTAGE DROP CALCULATION

THIS DOCUMENT IS A CABLE SIZING AND VOLTAGE DROP CALCULATION

REVISION HISTORY
REV. DATE REVISION DETAILS PREPARED CHECKED REVIEWED APPROVED

SIWARUT SIWARUT LAKSAMEE YOSHIMI


1 OCT 17, 2018 FOR FINAL SUWANLAPAPORN SUWANLAPAPORN TIPPAYAWAT NAOKI

SIWARUT SIWARUT LAKSAMEE YOSHIMI


C JULY 6, 2018 FOR APPROVAL SUWANLAPAPORN SUWANLAPAPORN TIPPAYAWAT NAOKI

SIWARUT SIWARUT LAKSAMEE YOSHIMI


B JUNE 13, 2018 FOR APPROVAL SUWANLAPAPORN SUWANLAPAPORN TIPPAYAWAT NAOKI

SIWARUT SIWARUT LAKSAMEE YOSHIMI


A MAY 31, 2018 FOR APPROVAL SUWANLAPAPORN SUWANLAPAPORN TIPPAYAWAT NAOKI

ISSUE PURPOSE DISTRIBUTION ISSUED BY;

FOR REVIEW DATE OCT 17, 2018

FOR APPROVAL

SIWARUT
FOR INFORMATION PREPARED
SUWANLAPAPORN
SIWARUT
FOR CONSTRUCTION CHECKED
SUWANLAPAPORN
LAKSAMEE
AS BUILT REVIEWED
TIPPAYAWAT
YOSHIMI
FOR FINAL APPROVED
NAOKI
TABLE OF CONTENTS

1. INTRODUCTION ...........................................................................................................................2 
GENERAL BACKGROUND ................................................................................................2 
SYSTEM DESCRIPTION ....................................................................................................2 
PURPOSE OF THE REPORT ............................................................................................2 

2. CABLE CROSS SECTION CALCULATION ................................................................................3 


GENERAL ...........................................................................................................................3 
BASIC CONSIDERATION ..................................................................................................3 
2.2.1  Network electrical characteristics ........................................................................3 
2.2.2  Cable characteristics ...........................................................................................3 
a) Cable rated voltages Uo/ U (Um): .........................................................................3 
CURRENT CARRYING CAPACITY UNDER NORMAL CONDITIONS .............................4 
2.3.1  Design data..........................................................................................................4 
2.3.2  Current carrying capacity .....................................................................................4 
MINIMUM PERMISSIBLE CROSS SECTIONS .................................................................4 
VOLTAGE DROP LIMITS: ..................................................................................................7 

3. CABLE SELECTION ....................................................................................................................9 


CABLE SELECTION BASED ON CURRENT RATING ......................................................9 
CABLE SELECTION AND COORDINATION WITH OVERCURRENT PROTECTION ...11 

4. POWER LOSS CALCULATION .................................................................................................13 


POWER LOSS CALCULATION ........................................................................................13 

ANNEXURE I: CURRENT CARRYING CAPACITY CALCULATION..................................................14 

ANNEXURE II: VOLTAGE DROP AND POWER LOSSES CALCULATION ......................................41 

ATTACHMENT I: CABLE SPECIFICATION ........................................................................................78 

ATTACHMENT II: IEC 60287 SUMMARIZE TABLE ...........................................................................81 


Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

1. INTRODUCTION

GENERAL BACKGROUND

5MWp PV solar power plant is placed in Ratchaburi Province, Thailand. The PV power plants are
developing by Sermsang Solar Co., Ltd

The Project will use fixed solar flat panel, each with Poly silicon technology rated 325 Wp Sharp
manufacture and convert radiant energy from the sun into DC power. The DC power is then combined
from all the panels in a given area, and then converted to AC power via the inverters which are each
rated at 1000 kW (SMA Sunny Central 1000CP XT). The supply of electricity from the inverters to the
grid will be done through high efficiency step-up transformer and 22kV switchgear then connect to 22kV
PEA grid.

SYSTEM DESCRIPTION

Plant Single Line Diagrams are the basis for electrical generation and distribution system.
 DWG No. SS-SSA-E-1001 22kV Single Line, Relaying and Metering Diagram
 DWG No. SS-SSA-E-1002 DC Single Line Diagram
 DWG No. SS-SSA-E-1003 AC LV Single Line Diagram

PURPOSE OF THE REPORT

This report specifies permissible cross-sections of power cables for serving the MV and LV systems as
normal operating conditions and under short-circuit conditions.
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

2. CABLE CROSS SECTION CALCULATION

GENERAL

The calculations in this report are performed in accordance with;

 IEC 60228 Conductors of insulated cables


 IEC 60364-5-52 Electrical installations of buildings Part 5 : Selection and erection of electrical
equipment- wiring systems
 IEC 60502 Power cables with extruded insulation and their accessories for rated voltages
from 1 kV up to 30 kV
 IEC 60287 Electric cables – Calculation of the current rating

For sizing of power cables, the following conditions are considered;

 Current carrying capacity under normal conditions.


 Short-circuit conditions.
 Voltage Drop during normal operation.
 Cable Power Losses

The following installations are to be considered;

 In air; on ladder, trays or racks in buildings or cable trenches.


 Underground in duct.

BASIC CONSIDERATION

2.2.1 Network electrical characteristics

a) Rated Voltage:
• 22kV AC, 3 Phase, 3 wires
• 400V AC, 3 Phase, 3 wires
• 1,000V DC, 2 wires
b) Frequency 50Hz

2.2.2 Cable characteristics

a) Cable rated voltages Uo/ U (Um):

• 25 kV XLPE, Aluminum, Spaced Aerial Cable for 22 kV AC system


• 12/20 (24) kV XLPE, Copper, for 22 kV AC system
• 1.8/3 (3.6) kV XLPE, Copper, for 400V/230V AC system
• 0.6/1 (1.2) kV XLPE, Copper, for 400V/230V AC system
• 0.6/1 (1.2) kV XLPE, Copper, for DC system
• 0.9/1.8 kV Solar cable, Copper, for PV String, DC system

Where,
Uo: the rated power frequency voltage between conductor and earth or metallic
screen for which the cable is designed
U: the rated power frequency voltage between conductors for which the cable is
designed
U m: the maximum value of the "highest system voltage'' for which the equipment
may be used
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

b) Cable type:

Power cables will be of cross-linked polyethylene (XLPE) and its maximum conductor
temperature is limited to 90°C/250°C under normal operation and short-circuits conditions.

25 kV XLPE, Aluminium, Spaced Aerial Cable for 22 kV AC system

Type : Single conductor up to 185 sq.mm.


Voltage : 25 kV suitable for use in nominal 22 kV system, non-
effectively grounded.
Conductor : Compact Aluminium
Insulation : Cross-linked polyethylene (XLPE) as per TIS 2341-
2555
Temperature : 90 deg. C at continuous load conditions and 250deg.C
under short circuit condition.
Insulation screen : Extruded semi-conducting compound
Armor : Unarmoured
Outer sheath : Cross-linked polyethylene (XLPE)

12/20(24) kV, 22kV AC power cable

Type : Single conductor up to 185 sq.mm.


Voltage : 12/20 (24) kV suitable for use in nominal 22 kV
system, non-effectively grounded.
Conductor : Stranded annealed copper.
Insulation : Cross-linked polyethylene (XLPE) as per IEC 60502
Temperature : 90 deg. C at continuous load conditions and 250deg.C
under short circuit condition.
Insulation screen : Extruded semi-conducting compound with copper
tape shield
Armor : Unarmoured
Outer sheath : PVC Outer sheathed (extruded)

1.8/3(3.6) kV, 400V/230V AC

Type : Single conductor up to 300 sq.mm.


Voltage : 1.8/3(3.6) kV suitable for use in nominal 400/230V AC systems
Conductor : Stranded annealed copper.
Insulation : Cross-linked polyethylene (XLPE) as per IEC 60502-1
Temperature : 90 deg. C at continuous load conditions and 250 deg. C under
short circuit condition
Armor : Unarmoured
Outer sheath : PVC Outer sheathed (extruded)

0.6/1(1.2) kV, 400V/230V AC

Type : Single conductor up to 300 sq.mm.


Voltage : 0.6/1(1.2) kV suitable for use in nominal 400/230V AC systems
Conductor : Stranded annealed copper.
Insulation : Cross-linked polyethylene (XLPE) as per IEC 60502
Temperature : 90 deg. C at continuous load conditions and 250 deg. C under
short circuit condition
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

Armor : Unarmoured
Outer sheath : PVC Outer sheathed (extruded)

0.6/1(1.2) kV, 1,000V DC

Type : Single conductor up to 300 sq.mm.


Voltage : 0.6/1(1.2) kV suitable for use in nominal 1,000 V DC systems
Conductor : Stranded annealed copper.
Insulation : Cross-linked polyethylene (XLPE) as per IEC 60502
Temperature : 90 deg. C at continuous load conditions and 250 deg. C under
short circuit condition
Armor : Unarmoured
Outer sheath : PVC Outer sheathed (extruded)

0.9/1.8 kV, 1,000V DC, PV Cable

Type : Single conductor up to 4 sq.mm.


Voltage : 0.9/1.5 kV suitable for use in nominal 1,000 V DC systems
Conductor : Fine wire annealed copper.
Insulation : Cross-linked copolymer with Waterproof as per TUV
Temperature : 90 deg. C at continuous load conditions and 120 deg. C under
short circuit condition
Armor : Unarmoured
Outer sheath : Cross-linked copolymer with UV resistant

CURRENT CARRYING CAPACITY UNDER NORMAL CONDITIONS

2.3.1 Design data

1) Ambient design temperature in air: 40 deg. C


2) PV solar cable where are installed under PV module will be considered 60 deg. C
3) Ambient design temperature in ground: 30 deg. C with refer to TIS, and PEA standards
4) Soil thermal resistivity 1.2 K m/W with refer to PEA standard, 0.9 meter laying depth for
MV cable and 0.6 meter laying depth for LV cable.
5) Conductor temperature under normal and short-circuit conditions: 90/250 deg. C

2.3.2 Current carrying capacity

The current carrying capacity has design complying with IEC 60287 has to be reduced due to
the ambient temperatures and accumulation of cables. This adaptation formulae given are
essentially literal and designedly leave open the selection of certain important parameters. These
may be divided into three groups:
 parameters related to construction of a cable (for example, thermal resistivity of
insulating material) for which representative values have been selected based on
published work;
 parameters related to the surrounding conditions, which may vary widely, the selection
of which depends on the country in which the cables are used or are to be used;
 parameters which result from an agreement between manufacturer and user and which
involve a margin for security of service (for example, maximum conductor temperature).

MINIMUM PERMISSIBLE CROSS SECTIONS

The mathematical formula is as follows according to IEC 60364-5-54.


Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

Where,
t = duration in seconds
S = cross-sectional area in square millimeters
I = effective short-circuit in A expressed as r.m.s. value
k = the factor k is determined from the below formula

ln 1

Where,
Qc = volumetric heat capacity of conductor material [J/°C mm3]
B = reciprocal of temperature coefficient of resistivity at 0°C for the conductor [°C]
Q20 = electrical resistivity of conductor material at 20 °C [Ω mm]
θi = initial temperature of conductor [°C]
θf = final temperature of conductor [°C]

. .
For copper: ln 1 = 143
. .

.
For Aluminium: ln 1 = 94
.

From above the minimum cross-sections shall be;

For MV cables:
1) For TR. feeders was selected copper conductor (25 kA for 0.2 Sec, relay setting by
instantaneous tripping)

S min = √ /
= √25000 0.2 /143
= 78.18 sq.mm.
Select ing = 95 sq.mm.

2) For Incomer feeders and outgoing power feeders was selected copper conductor (25kA
for 0.4 Sec, relay setting by instantaneous tripping)

S min = √ /
= √25000 0.4 /143
= 110.5 sq.mm.
Select ing = 120 sq.mm.
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

3) For Incomer feeders and outgoing power feeders was selected aluminium conductor (25
kA for 0.4 Sec, relay setting by instantaneous tripping)

S min = √ /
= √25000 0.4 /94
= 168.2 sq.mm.
Select ing = 185 sq.mm.

For LV cables:
1) For incomer breaker feeders and outgoing power feeders was selected copper conductor
(29.69kA for 1 sec) The LV short circuit current will be considered at 6% voltage impedance
of 1250kVA step-up transformer.

Isc = VA transformer/ 1.732 x 405V x (%Z/100)

Isc = 1250x1000 / 1.732 x 405V x 0.06

Isc = 29.69

S min = √ /
= √29690 1 /143
= 207.62 sq.mm
Selecting = 240 sq.mm.

Hence selected cable size of incoming and outgoing are as follows:

Short circuit Cross-section Selecting minimum


Feeder
withstand capacity minimum (sq.mm.) cable size (sq.mm.)
MV feeder
25 kA , 0.4 sec 168.2 185
(Aluminium)
MV feeder (Copper)
25 kA , 0.4 sec 110.5 120
SWG
MV feeder (Copper)
25 kA , 0.2 sec 78.18 95
TR.
LV Feeder 29.67 kA , 1 sec 207.62 4x240 per phase

PEA have setting instantaneous overcurrent relay at max. fault 0.05 sec. The cables of power plant
enable to withstanding for 25kA 0.2 sec which will be satisfy.

VOLTAGE DROP LIMITS:

Voltage Drop during normal condition:

a) For three phase system

% √3 cos sin

Where,
%Vd = % Voltage drop (V)
V = System voltage (V)
I = Full load current (A)
R = AC resistance of cable (ohms/km)
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

X = Reactance of Cable (ohms/km)


Cos θ = Power factor during running condition
L = Length of cable (km)

b) For DC system
100
% 2
Where,
R = DC resistance of cable (ohms/km)

The accumulating voltage drop of DC cables and AC cables shall not be over 3%.
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

3. CABLE SELECTION

CABLE SELECTION BASED ON CURRENT RATING

The current rating for cables installation which are calculated using the data given from above
section and according to Annexure III, Single line diagram. The minimum cross section area for
the all selected cables shall be complied with section 2.3 above. The results are summarized on
following Table 3-1 below;

No. Feeder Name Selected Operating Installation Rate Result


Cable current, I (A) method installed (IT > I)
(sq.mm.) cable, IT (A)
1 22kV Distribution Line 3 x 1C-185 164.02 Overhead 410 Pass
to Switchgear (SWG) (SAC) with PEA
and Transformer (TR) standard
2 Switchgear to Riser 3 x 1C-120 164.02 Direct burial 299 Pass
Pole HDPE 110
mm conduit
install Trefoil
3 22kV TR Riser Pole to 3 x 1C-95 41 Direct burial 264 Pass
Step up Transformer HDPE 110
(TR) mm conduit
install Trefoil
4 TR to Inverter (INV) 3 x (4 x 1804.22 In Ladder 2,189 Pass
1C-240) 600 mm
install Trefoil
5 INV to String combiner 2 x 1C-95 237.7 Direct burial 292 Pass
box (SCB) HDPE 63
mm conduit
Flat Touch
6 SCB to PV-string 2 x 1C-4 10.8 Free air 32 Pass
along with
mounting
structure
Table 3-1: Selected cable cross section.

The result of voltage drop calculation given formula from above section are summarize in
following Table 3-2 below;
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

No. Operating Voltage


Feeder Name voltage (V) drop, Vd (V) Vd (%)
1 22kV PEA Connection to 22,000 1.889 0.009
Outgoing Riser Pole
2 Riser Pole Outgoing to 22,000 1.862 0.008
Switchgear (SWG)
3 Switchgear (SWG) to Riser 22,000 1.862 0.008
Pole Incoming
4 Riser Pole Incoming to TR 22,000 37.789 0.172
Riser Pole
5 TR Riser Pole to 22,000 0.355 0.002
Transformer
6 TR to Inverter (INV) 405 1.539 0.380
7 INV to SCB 752 7.326 0.974
8 SCB to PV-string 752 4.197 0.558

Total Voltage Drop 1.914

Table 3-2: Results of voltage drop calculation


Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

CABLE SELECTION AND COORDINATION WITH OVERCURRENT PROTECTION

The PV modules are current limited sources but because they will be connected in parallel that
can be subjected to overcurrent caused by either multiple parallel adjacent strings as refer to
Figure 3-1: PV array diagram. In this report will provide a selection protection for DC system only,
except AC system that will descript in relay protection calculation report.

Figure 3-1: PV array diagram

String overcurrent protection shall be used:

((np - 1) x ISC_MOD) > IMOD_MAX_OCPR

The sizing of overcurrent protection shall be used for; PV string overcurrent protection:
In > 1.5 x ISC_MOD and
In < 2.4 x ISC_MOD and
In ≤ IMOD_MAX_OCPR

Where;
np : Number of parallel connected strings in a PV array
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

IMOD_MAX_OCPR : PV module maximum overcurrent protection rating


ISC_MOD : Short circuit current of a PV module or PV string at Standard Test
Conditions (STC)
In : Nominal rating of an overcurrent protection device

The minimum cable sizes for PV array wiring, based on current carrying capacity, shall be based
upon a current rating calculated from In above.

The rating of overcurrent protection given formula from above are summarize in following 3-3
below.

No. Feeder Name ISC_MOD IMOD_MAX_OCPR 1.5 x ISC_MOD < In < 2.4 x Selected
(A) (A) protection
ISC_MOD
devices

1 PV string junction 9.24 (22-1) x 9.24 = 13.86 < In < 22.18 Fuse = 15A
box (SCB) 194.04

Table 3-3: Protection Devices rating for DC System


Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

4. POWER LOSS CALCULATION

POWER LOSS CALCULATION

The Power losses in a cable is mainly due to resistance heating of cable. It is given by the following
formula:
a) For three phase system

3 ^2

Where,
I = Full load current in circuit (A)
R = AC resistance of cable (ohms/km)
L = Length of cable (km)

b) For DC system

Where,
I = Full load current in circuit (A)
R = DC resistance of cable (ohms/km)
L = Length of cable (km)

Plant Capacity Factor (CF) = Guarantee Annual Output x 100% / Installed Capacity x (365 x 24)

Plant Capacity Factor (CF) = 7223782 x 100% (kWh)/ 4998.4 kW x (365 x24) = 16.50%

The power loss calculation which are calculated of loss in any cables using the data given from
voltage drop section. The results are summarized on following Table 4-1 below;

No. System Power Losses


(kW)

1 22kV System 5.309


2 400kV System 10.726
3 DC system 38.963
Total Losses 55.00
Table 4-1: Power losses of each circuit

Percent power losses = Plant Capacity Factor (CF) x Total power losses (kW) x (365 x24) /
Guarantee Annual Output (kWh)

Percent power losses = 16.50 % x 55.00 x (365 x 24) / 7223782 = 1.10 %

As per RFP, the design of the cable system should be the total losses are less than 1.5% on an
annual average basis, including the DC and the AC circuits.
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

ANNEXURE I: CURRENT CARRYING CAPACITY CALCULATION


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

CURRENT CARRYING CAPACITY OF SINGLE CORE, XLPE INSULATED,

DIRECT BURIED POWER CABLES IN HDPE, TREFOIL FORMATION

ARRANGEMENT, SHEATHS BONDED AT ONE SIDE

CABLE TYPE: 22kV XLPE cable, 1x120sqmm/10, copper conductor,


copper-wire screened
CONNECTION: 22kV Switchgear to Riser Pole

GENERAL DATA: MATERIAL PERMITTIVITY tan-delta THERMAL RESISTIVITY


εr tanδ ρi
XLPE 2.5 0.008 3.5
PE 2.3 0.001 3.5
PVC 8.0 0.1 6.0
OFC-Paper,L.P. 3.3 0.004 5.0
Concrete 1.0
PVC-Pipes 7.0
RESISTIVITY TEMP. COEFFICIENT

20x10^-8 20
LEAD 21.4 0.004
COPPER 1.7241 0.00393
ALU(cond) 2.8264 0.00403
STEEL 13.8 0.0045
BRONZE 3.5 0.003
ALU(sheath) 2.84 0.00403

ASSUMPTIONS:

U  22000 (phase to phase voltage, V)


f  50 (system frequency, Hz)
ω  2  π f (angular frequency of system, Hz)
ω  314.159
dc  13.2 (external diameter of conductor, mm)
dc1  13.8 (diameter of conductor, including screen,mm)
tc  90 (max. operation temperature of the conductor, degC)
ts  70 (max. screen temperature, degC)
3
Rdc0  0.153  10 (D.C.resistance of the conductor at 20degC, /m)
3
Rdcs0  1.83 10 (D.C.resistance of the copper screen at 20degC, Ohm/m)
ks  1 (skin effect coefficient acc.to IEC60287-1-1-Table II)
kp  1 (proximity effect coefficient acc.to IEC60287-1-1-Table II)
3
αc  3.93 10 (temperature coefficient of copper at 20degC/K, IEC60287-1-1-Table I)
20

Cable sizing calculation 22kV Page 1/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

8
ρms  1.7241 10 (electrical resistivity of metallic sheath at 20 degC, Ohm x m
20
IEC60287-1-1-Table I)
Di  25.1 (external diameter of insulation, excluding screen, mm)
εr  2.5 (relative permittivity of insulation, 50Hz, 60degC)
ρi  3.5 (thermal resistivity of insulation, Kxm/W)

tanδ  0.008 (loss factor of insulation)


D  25.7 (diameter below metallic sheath, mm)
tms  0.1 (thickness of metallic sheath, mm)
D  dc (thickness of insulation, conductor to metallic sheath, mm)
ti 
2

ti  6.25

dms  25.9 (outer diameter of metallic sheath, mm)


tcs  2 (thickness of outer covering, mm)
ρc  6 (thermal resisivity of outer covering, Kxm/W)
De  30.9 (external diameter of the cable, mm)
ρe  1.2 (thermal resistivity of earth, Kxm/W)
Lg  900 (distance from ground surface to cable axis, mm)
Dec  110 (external diameter of the pipe, mm)
ρp  3.5 (thermal resisivity of pipe, Kxm/W)
s1  110 (axial separation between two adjacent groups, mm)

te  30 (max. earth temperature, degC)


s2  De (axial spacing of the conductors, mm)

s2  30.9

n  1 (number of load-carrying conductors in the cable)

Doc  110 (the outside diameter of the duct, mm)

Dic  97.4 (the inside diameter of the duct, mm)

Nc  3 (number of number of loaded cables in the duct bank)

CALCULATIONS:

1 Calculation of losses
1.1. DC resistance of conductor

Δθ  tc  te (temperature rise of the conductor above the ambient temperature, degC)

Δθ  60

Rdc  Rdc0 1  αc  ( tc  20) (D.C.resistance of conductor at max.operating temperature, /m)


 20 

Cable sizing calculation 22kV Page 2/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

4
Rdc  1.951  10

1.1.1 Skin effect factor ys

8  π f 7 (argument of a Bessel function used to calculate skin effect


xs   10  ks
Rdc

2
xs  0.644

4
xs 3
y s  y s  2.157  10
4
192  0.8 xs

1.1.2. Proximity effect factor yp for three-core cables and for three single-core cables

8  π f 7
xp   10  kp (argument of a Bessel function used to calculate proximity effect
Rdc

2
xp  0.644

4  2 2 
 
dc 
 0.312  
xp dc  1.18
y p      (proximity effect factor)

192  0.8 xp     s2 
4 s2 4
xp
 0.27
 192  0.8 xp
4 
3
y p  1.729  10

1.1.3 AC resistance of conductor


Rac  Rdc 1  y s  y p  (A.C. resistance of conductor at max. operating temperature, /m)

4
Rac  1.958  10

1.2 Dielectric losses (applicable to a.c. cables only)


The capacitance for circular conductors is given by:
εr 9 (capacitance of each conductor against the screen surrounding, F/m/phase)
Cc   10
18 ln
Di 

 dc 
 10
Cc  2.161  10

U
Uo  (voltage between conductor and metallic sheath, V)
3

Cable sizing calculation 22kV Page 3/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

4
Uo  1.27  10

The dielectric loss per unit length in each phase is given by:
2
Wd  ω Cc Uo  tanδ (dielectric losses per unit length per phase, W/m)

Wd  0.088

1.3 Loss factor for sheath and screen (applicable to power frequency a.c. cables only)

λ11  0 (ratio of the losses in one sheath caused by circulating currents in the
sheath / losses in one conductor)

[for one end bonding, no circulation current can flow]

1.4 Single-core cables, with sheaths bonded at a single point or cross-bonded

Eddy-current losses

Rdcs  Rdcs0 1  ( ts  20)  Rdcs0 (D.C. resistance of the metallic sheath at 'ts' degC, Ohm/m)
 
3
Rdcs  1.997  10

ρmsts  ρms  1  ( ts  20)  αc


20
(electrical resistivity of the metallic sheath at ts degC)
20  
8
ρmsts  2.063  10

Formulae for β is given below:


1

in which:
4  π ω
β  β  138.338
1 7 1
ρmsts 10

Formulae for λ0, Δ and Δ are given below:


1 2

ω 7
in which: m1   10
Rdcs for m1is least than or equal 0.1, Δ and Δ
1 2
m1  0.016 can be neglected

Three single-core cables in trefoil formation

 m12   dms  2
λ0  3    4
 1  m12   2  s2 
λ0  1.303  10
 

Δ  0 Δ  0
1 2

Cable sizing calculation 22kV Page 4/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

Formulae for gs is given below:

1.74
gs  1   tms    β  De 10
3
 1.6 gs  1
   1 
 De 

For single-core cables with sheaths bonded at a single point or cross-bonded the eddycurrent
loss factor is given by:

 β  tms 

4
Rdcs (ratio of the losses in one sheath caused by
 
 gs  λ0   1  Δ  Δ  
1
λ12  eddy currents in the sheath / losses in one
Rac 

1 2 12 
12 10    conductor)

3
λ12  1.329  10

λ1  λ11  λ12 (ratio of total losses in the metallic sheath)

3
λ1  1.329  10

NOTE: For cables with a wire screen and an equalising tape, or foil screen over the wires, the
eddycurrent losses are considered negligible.

1.5 Magnetic armour or reinforcement

λ2  0

2. Calculation of thermal resistances


2.1 Thermal resistance of the constituent parts of a cable, T1, T2 and T3

2.1.1 Thermal resistance between one conductor and sheath T1

 ln 1 
ρi 2  ti 
T1   (thermal resistance between one conductor and metallic sheath, Kxm/W)
2 π  dc 
T1  0.371

2.1.2 Thermal resistance between sheath and armour T2

T2  0 (thermal resistance per unit length of the bedding between sheath and armour, Kxm/W)

2.1.3 Thermal resistance of outer covering (serving) T3

De  dms
t  t  2.5
3 2 3

 2 t
ρc 3
T3   ln 1   (thermal resistance of outer covering, Kxm/W)
2 π  dms 

T3  0.169

Cable sizing calculation 22kV Page 5/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.2 External thermal resistance T4

2.2.1 Thermal resistance between cable and duct (or pipe) T41
Constants, depending on the installations the values of which are given in IEC60287-2-1 table 4

Uc  1.87 Vc  0.312 Yc  0.0037

Uc (thermal restistance of soil,Kxm/W)


T41 
1  0.1( Vc  Yc te)  De

T41  0.811

2.2.2 Thermal resistance of the duct (or pipe) itself T42

  ln
ρp Doc   (thermal restistance induced by other group, Kxm/W)
T42  0.5 
π   Dic  

T42  0.068

2.2.3 External thermal resistance of the duct (or pipe) T43

2  Lg
u  u  16.364
Doc

T43  0.5
Nc ( ρe) 
 ln u 
2
u 1 
π

T43  1.998

T4  T41  T42  T43 (total thermal restistance of soil Kxm/W)

T4  2.876

3. Permissible current rating of cables

Δθ  Wd  [ 0.5 T1  n  ( T2  T3  T4 ) ]
I 
Rac  T1  n  Rac  ( 1  λ1 )T2  n  Rac  ( 1  λ1  λ2 )  ( T3  T4 )

I  299 A

Cable sizing calculation 22kV Page 6/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

CURRENT CARRYING CAPACITY OF SINGLE CORE, XLPE INSULATED,

DIRECT BURIED POWER CABLES IN HDPE, TREFOIL FORMATION

ARRANGEMENT, SHEATHS BONDED AT ONE SIDE

CABLE TYPE: 22kV XLPE cable, 1x95sqmm/10, copper conductor, copper-wire


screened
CONNECTION: 22kV Transformer to Transformer Riser Pole

GENERAL DATA: MATERIAL PERMITTIVITY tan-delta THERMAL RESISTIVITY


εr tanδ ρi
XLPE 2.5 0.008 3.5
PE 2.3 0.001 3.5
PVC 8.0 0.1 6.0
OFC-Paper,L.P. 3.3 0.004 5.0
Concrete 1.0
PVC-Pipes 7.0
RESISTIVITY TEMP. COEFFICIENT

20x10^-8 20
LEAD 21.4 0.004
COPPER 1.7241 0.00393
ALU(cond) 2.8264 0.00403
STEEL 13.8 0.0045
BRONZE 3.5 0.003
ALU(sheath) 2.84 0.00403

ASSUMPTIONS:

U  22000 (phase to phase voltage, V)


f  50 (system frequency, Hz)
ω  2  π f (angular frequency of system, Hz)
ω  314.159
dc  11.6 (external diameter of conductor, mm)
dc1  12.2 (diameter of conductor, including screen,mm)
tc  90 (max. operation temperature of the conductor, degC)
ts  70 (max. screen temperature, degC)
3
Rdc0  0.193  10 (D.C.resistance of the conductor at 20degC, /m)
3
Rdcs0  1.83 10 (D.C.resistance of the copper screen at 20degC, Ohm/m)
ks  1 (skin effect coefficient acc.to IEC60287-1-1-Table II)
kp  1 (proximity effect coefficient acc.to IEC60287-1-1-Table II)
3
αc  3.93 10 (temperature coefficient of copper at 20degC/K, IEC60287-1-1-Table I)
20

Cable sizing calculation 22kV 95Sqmm Page 1/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

8
ρms  1.7241 10 (electrical resistivity of metallic sheath at 20 degC, Ohm x m
20
IEC60287-1-1-Table I)
Di  23.6 (external diameter of insulation, excluding screen, mm)
εr  2.5 (relative permittivity of insulation, 50Hz, 60degC)
ρi  3.5 (thermal resistivity of insulation, Kxm/W)

tanδ  0.008 (loss factor of insulation)


D  24.2 (diameter below metallic sheath, mm)
tms  0.1 (thickness of metallic sheath, mm)

D  dc (thickness of insulation, conductor to metallic sheath, mm)


ti 
2

ti  6.3

dms  24.4 (outer diameter of metallic sheath, mm)


tcs  1.9 (thickness of outer covering, mm)
ρc  6 (thermal resisivity of outer covering, Kxm/W)
De  29.2 (external diameter of the cable, mm)
ρe  1.2 (thermal resistivity of earth, Kxm/W)
Lg  900 (distance from ground surface to cable axis, mm)
Dec  110 (external diameter of the pipe, mm)
ρp  3.5 (thermal resisivity of pipe, Kxm/W)
s1  110 (axial separation between two adjacent groups, mm)
te  30 (max. earth temperature, degC)
s2  De (axial spacing of the conductors, mm)

n  1 (number of load-carrying conductors in the cable)

Doc  110 (the outside diameter of the duct, mm)

Dic  97.4 (the inside diameter of the duct, mm)

Nc  3 (number of number of loaded cables in the duct bank)

CALCULATIONS:

1 Calculation of losses

1.1. DC resistance of conductor

Δθ  tc  te (temperature rise of the conductor above the ambient temperature, degC)

Δθ  60
Rdc  Rdc0 1  αc  ( tc  20) (D.C.resistance of conductor at max.operating temperature, /m)
 20 
4
Rdc  2.461  10

Cable sizing calculation 22kV 95Sqmm Page 2/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

1.1.1 Skin effect factor ys

8  π f 7 (argument of a Bessel function used to calculate skin effect)


xs   10  ks
Rdc

2
xs  0.511

4
xs 3
y s  y s  1.357  10
4
192  0.8 xs

1.1.2. Proximity effect factor yp for three-core cables and for three single-core cables

8  π f 7
xp   10  kp (argument of a Bessel function used to calculate proximity effect
Rdc

2
xp  0.511

4  2 2 
 
dc 
 0.312  
xp dc  1.18
y p      (proximity effect factor)

192  0.8 xp     s2 
4 s2 4
xp
 0.27
 192  0.8 xp
4 
4
y p  9.415  10

1.1.3 AC resistance of conductor


Rac  Rdc 1  y s  y p  (A.C. resistance of conductor at max. operating temperature, /m)

4
Rac  2.467  10

1.2 Dielectric losses (applicable to a.c. cables only)


The capacitance for circular conductors is given by:
εr 9 (capacitance of each conductor against the screen surrounding, F/m/phase)
Cc   10
18 ln
Di 

 dc 
 10
Cc  1.956  10

U
Uo  (voltage between conductor and metallic sheath, V)
3

4
Uo  1.27  10

Cable sizing calculation 22kV 95Sqmm Page 3/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

The dielectric loss per unit length in each phase is given by:
2
Wd  ω Cc Uo  tanδ (dielectric losses per unit length per phase, W/m)

Wd  0.079

1.3 Loss factor for sheath and screen (applicable to power frequency a.c. cables only)

λ11  0 (ratio of the losses in one sheath caused by circulating currents in the
sheath / losses in one conductor)

[for one end bonding, no circulation current can flow]

1.4 Single-core cables, with sheaths bonded at a single point or cross-bonded

Eddy-current losses

Rdcs  Rdcs0 1  ( ts  20)  Rdcs0 (D.C. resistance of the metallic sheath at 'ts' degC, Ohm/m)
 
3
Rdcs  1.997  10

ρmsts  ρms  1  ( ts  20)  αc


20
(electrical resistivity of the metallic sheath at ts degC)
20  
8
ρmsts  2.063  10

Formulae for β is given below:


1

in which:
4  π ω
β  β  138.338
1 7 1
ρmsts 10

Formulae for λ0, Δ and Δ are given below:


1 2

ω 7
in which: m1   10
Rdcs for m1is least than or equal 0.1, Δ and Δ
1 2
m1  0.016 can be neglected
Three single-core cables in trefoil formation

 m12   dms  2
λ0  3   
 1  m12   2  s2 
4
λ0  1.295  10
 

Δ  0 Δ  0
1 2

Formulae for gs is given below:

1.74
 tms    β  De 10
3
 1.6
gs  1     1 
gs  1
 De 

Cable sizing calculation 22kV 95Sqmm Page 4/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

For single-core cables with sheaths bonded at a single point or cross-bonded the eddycurrent
loss factor is given by:

 β  tms 

4
Rdcs (ratio of the losses in one sheath caused by
 
 gs  λ0   1  Δ  Δ  
1
λ12  eddy currents in the sheath / losses in one
Rac 

1 2 12 
12 10    conductor

3
λ12  1.049  10

λ1  λ11  λ12 (ratio of total losses in the metallic sheath)

3
λ1  1.049  10

NOTE: For cables with a wire screen and an equalising tape, or foil screen over the wires, the
eddycurrent losses are considered negligible.

1.5 Magnetic armour or reinforcement

λ2  0

2. Calculation of thermal resistances


2.1 Thermal resistance of the constituent parts of a cable, T1, T2 and T3

2.1.1 Thermal resistance between one conductor and sheath T1

 ln 1 
ρi 2  ti 
T1   (thermal resistance between one conductor and metallic sheath, Kxm/W)
2 π  dc 
T1  0.41

2.1.2 Thermal resistance between sheath and armour T2

T2  0 (thermal resistance per unit length of the bedding between sheath and armour, Kxm/W)

2.1.3 Thermal resistance of outer covering (serving) T3

De  dms
t  t  2.4
3 2 3

 2 t
ρc 3
T3   ln 1   (thermal resistance of outer covering, Kxm/W)
2 π  dms 

T3  0.171

Cable sizing calculation 22kV 95Sqmm Page 5/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.2 External thermal resistance T4

2.2.1 Thermal resistance between cable and duct (or pipe) T41
Constants, depending on the installations the values of which are given in IEC60287-2-1 table 4

Uc  1.87 Vc  0.312 Yc  0.0037

Uc (thermal restistance of soil,Kxm/W)


T41 
1  0.1( Vc  Yc te)  De

T41  0.837

2.2.2 Thermal resistance of the duct (or pipe) itself T42

  ln
ρp Doc   (thermal restistance induced by other group, Kxm/W)
T42  0.5 
π   Dic  

T42  0.068

2.2.3 External thermal resistance of the duct (or pipe) T43

2  Lg
u  u  16.364
Doc

T43  0.5
Nc ( ρe) 
 ln u 
2
u 1 
π

T43  1.998

T4  T41  T42  T43 (total thermal restistance of soil Kxm/W)

T4  2.902

3. Permissible current rating of cables

Δθ  Wd  [ 0.5 T1  n  ( T2  T3  T4 ) ]
I 
Rac  T1  n  Rac  ( 1  λ1 )T2  n  Rac  ( 1  λ1  λ2 )  ( T3  T4 )

I  264 A

Cable sizing calculation 22kV 95Sqmm Page 6/6


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

CURRENT CARRYING CAPACITY OF SINGLE CORE, XLPE INSULATED,

POWER CABLES, IN TREFOIL FORMATION ARRANGEMENT AND IN

FREE AIR

CABLE TYPE: 1.8/3(3.6)kV XLPE cable, 1x240sqmm, copper conductor

CONNECTION: Step up Transformer to Inverter

GENERAL DATA: MATERIAL PERMITTIVITY tan-delta THERMAL RESISTIVITY


εr tanδ ρi
XLPE 2.5 0.008 3.5
PE 2.3 0.001 3.5
PVC 8.0 0.1 6.0
OFC-Paper,L.P. 3.3 0.004 5.0
Concrete 1.0
PVC-Pipes 7.0
RESISTIVITY TEMP. COEFFICIENT

20x10^-8 20
LEAD 21.4 0.004
COPPER 1.7241 0.00393
ALU(cond) 2.8264 0.00403
STEEL 13.8 0.0045
BRONZE 3.5 0.003
ALU(sheath) 2.84 0.00403

ASSUMPTIONS:

U  405 (phase to phase voltage, V)


f  50 (system frequency, Hz)
ω  2  π f (angular frequency of system, Hz)
ω  314.159
dc  18.7 (external diameter of conductor, mm)
dc1  18.7 (diameter of conductor, including screen,mm)
tc  90 (max. operation temperature of the conductor, degC)
ts  70 (max. screen temperature, degC)
3
Rdc0  0.0754 10 (D.C.resistance of the conductor at 20degC, /m)
3
Rdcs0  1.83 10 (D.C.resistance of the copper screen at 20degC, Ohm/m)
ks  1 (skin effect coefficient acc.to IEC60287-1-1-Table II)
kp  0.8 (proximity effect coefficient acc.to IEC60287-1-1-Table II)
3
αc  3.93 10 (temperature coefficient of copper at 20degC/K, IEC60287-1-1-Table I)
20
8
ρms  1.7241 10 (electrical resistivity of metallic sheath at 20 degC, Ohm x m
20
IEC60287-1-1-Table I)

Cable sizing calculation 405V 240 Page 1/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

Di  22.7 (external diameter of insulation, excluding screen, mm)


εr  2.5 (relative permittivity of insulation, 50Hz, 60degC)
ρi  3.5 (thermal resistivity of insulation, Kxm/W)

tanδ  0.008 (loss factor of insulation)


D  22.7 (diameter below metallic sheath, mm)
tms  0.1 (thickness of metallic sheath, mm)
D  dc (thickness of insulation, conductor to metallic sheath, mm)
di 
2

di  2

dms  22.9 (outer diameter of metallic sheath, mm)


tcs  1.8 (thickness of outer covering, mm)
ρc  6 (thermal resisivity of outer covering, Kxm/W)
De  27.7 (external diameter of the cable, mm)

s2  1De (axial spacing of the conductors, mm)

s2  27.7
s1  2De (axial separation between two adjacent groups, mm)
n  1 (number of load-carrying conductors in the cable)

Nc  4 (number cable circuits)

ta  40 (max. air temperature, degC)

Constants for three cables in trefoil formation in free air:


Z  0.96 (constant [IEC60287-2-1, Table 2])
E  1.25 (constant [IEC60287-2-1, Table 2])
g1  0.2 (constant [IEC60287-2-1, Table 2])

CALCULATIONS:
1 Calculation of losses
1.1. DC resistance of conductor

Δθ  tc  ta (temperature rise of the conductor above the ambient


temperature, degC)
Δθ  50

Rdc  Rdc0 1  αc  ( tc  20) (D.C.resistance of conductor at max.operating temperature, /m)


 20 
5
Rdc  9.614  10

Cable sizing calculation 405V 240 Page 2/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

1.1.1 Skin effect factor ys

8  π f 7 (argument of a Bessel function used to calculate skin effect


xs   10  ks
Rdc
2
xs  1.307
4
xs 3
y s  y s  8.835  10
4
192  0.8 xs

1.1.2. Proximity effect factor yp for three-core cables and for three single-core cables

(argument of a Bessel function used to calculate proximity effect


8  π f 7
xp   10  kp
Rdc

2
xp  1.046

4  2 2 
 
dc 
 0.312  
xp dc  1.18
y p      (proximity effect factor)

192  0.8 xp     s2 
4 s2 4
xp
 0.27
 192  0.8 xp
4 
y p  0.011

1.1.3 AC resistance of conductor


Rac  Rdc 1  y s  y p  (A.C. resistance of conductor at max. operating temperature,
/m)

5
Rac  9.809  10

1.2 Dielectric losses (applicable to a.c. cables only)

0.0241 εr 9 (capacitance of each conductor against the screen surrounding,


Cc   10
F/m/phase)
log 
Di

 dc1 
 10
Cc  7.157  10

U
Uo  (voltage between conductor and metallic sheath, V)
3

Uo  233.827

2
Wd  ω Cc Uo  tanδ (dielectric losses per unit length per phase, W/m)

5
Wd  9.835  10

Cable sizing calculation 405V 240 Page 3/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

1.3 Loss factor for sheath and screen (applicable to power frequency a.c. cables only)

(ratio of the losses in one sheath caused by circulating currents in


λ11  0
the sheath/losses in one conductor (for one end bonding, no
circulation current can flow)

1.4 Single-core cables, with sheaths bonded at a single point or cross-bonded

Eddy-current losses

Rdcs  Rdcs0 1  ( ts  20)  Rdcs0 (D.C. resistance of the metallic sheath at 'ts' degC, Ohm/m)
 
3
Rdcs  1.997  10

ρmsts  ρms  1  ( ts  20)  αc


20
(electrical resistivity of the metallic sheath at ts degC)
20  
8
ρmsts  2.063  10

Formulae for β is given below:


1

in which:
4  π ω
β  β  138.338
1 7 1
ρmsts 10

Formulae for λ0, Δ and Δ are given below:


1 2

ω 7
in which: m1   10
Rdcs for m1is least than or equal 0.1, Δ and Δ
1 2
m1  0.016 can be neglected

Three single-core cables in trefoil formation

 m12   dms  2
λ0  3   
 1  m12   2  s2 
4
λ0  1.268  10
 

Δ  0 Δ  0
1 2

Formulae for gs is given below:

1.74
gs  1  
tms 
  β  De 10  1.6
3
  1 
gs  1
 De 

Cable sizing calculation 405V 240 Page 4/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

For single-core cables with sheaths bonded at a single point or cross-bonded the eddycurrent
loss factor is given by:

 β  tms 

4
Rdcs (ratio of the losses in one sheath caused by
 
 gs  λ0   1  Δ  Δ  
1
λ12  eddy currents in the sheath / losses in one
Rac 

1 2 12 
12 10    conductor

3
λ12  2.582  10

λ1  λ11  λ12 (ratio of total losses in the metallic sheath)

3
λ1  2.582  10

NOTE: For cables with a wire screen and an equalising tape, or foil screen over the wires, the
eddycurrent losses are considered negligible.

1.5 Magnetic armour or reinforcement

λ2  0

2. Calculation of thermal resistances


2.1 Thermal resistance of the constituent parts of a cable, T1, T2 and T3

2.1.1 Thermal resistance between one conductor and sheath T1

 ln 1 
ρi 2  di 
T1   (thermal resistance between one conductor and metallic sheath, Kxm/W)
2 π  dc 
T1  0.108

2.1.2 Thermal resistance between sheath and armour T2

T2  0 (thermal resistance per unit length of the bedding between sheath and
armour, Kxm/W)

2.1.3 Thermal resistance of outer covering (serving) T3

De  dms
t  t  2.4
3 2 3

 2 t
ρc 3 (thermal resistance of outer covering, Kxm/W)
T3   ln 1  
2 π  dms 

T3  0.182

Cable sizing calculation 405V 240 Page 5/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.2 External thermal resistance T4


Cables laid in free air
Cables protected from direct solar radiation
the heat dissipation coefficient obtained either from the above formula using the
appropriate values of constants Z, E and g given in table 2, IEC60287-2-1

 Z E (heat dissipation coefficient)


h   
 
g1
 De 10 3 
 

h  3.217

 π De h  10   T1 
3
KA        T2  ( 1  λ1 )  T3  ( 1  λ1  λ2 )
 ( 1  λ1  λ2 )   n  

KA  0.081

Δθd  Wd 


1   1  T1  n λ2  T2 
   (factor for cables protected from solar
 ( 1  λ1  λ2 ) 2 ( 1  λ1  λ2 )  radiation)

6
Δθd  5.282  10

k1  2.538 (factor has to be changed until k3<0.001, starting with k1=2)

 1
 
  4

k  
Δθ Δθd 

  1  KA k1
k  2.538

k3  k  k1 (factor should be <0.001)

k3  0.0003

The thermal resistance T4 of the surroundings of a cable in air and protected from solar
radiation is given by the formula:
1
T4 
 
π De 10 3  h k (external thermal resistance, kxm/W)

T4  1.408

Cable sizing calculation 405V 240 Page 6/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

3. Permissible current rating of cables

Nc Δθ  Wd [ 0.5 T1  n  ( T2  T3  T4 ) ]
I 
Rac  T1  n  Rac  ( 1  λ1 )T2  n  Rac  ( 1  λ1  λ2 )  ( T3  T4 )

I  2189 A

Cable sizing calculation 405V 240 Page 7/7


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

CURRENT CARRYING CAPACITY OF SINGLE CORE, XLPE INSULATED,

DIRECT BURIED POWER CABLES IN HDPE, FLAT FORMATION

ARRANGEMENT

CABLE TYPE: 0.6/1 kV XLPE cable, 1x95sqmm

CONNECTION: SCB to Inverter

GENERAL DATA: MATERIAL PERMITTIVITY tan-delta THERMAL RESISTIVITY


εr tanδ ρi
XLPE 2.5 0.008 3.5
PE 2.3 0.001 3.5
PVC 8.0 0.1 6.0
OFC-Paper,L.P. 3.3 0.004 5.0
Concrete 1.0
PVC-Pipes 7.0
RESISTIVITY TEMP. COEFFICIENT

20x10^-8 20
LEAD 21.4 0.004
COPPER 1.7241 0.00393
ALU(cond) 2.8264 0.00403
STEEL 13.8 0.0045
BRONZE 3.5 0.003
ALU(sheath) 2.84 0.00403

ASSUMPTIONS:

U  752 (phase to phase voltage, V)

dc  11.6 (external diameter of conductor, mm)


dc1  11.6 (diameter of conductor, including screen,mm)
tc  90 (max. operation temperature of the conductor, degC)
3
Rdc20  0.193  10 (D.C.resistance of the conductor at 20degC, /m)

3
αc  3.93 10 (temperature coefficient of copper at 20degC/K, IEC60287-1-1-Table I)
20

ρi  3.5 (thermal resistivity of insulation, Kxm/W)

tanδ  0.008 (loss factor of insulation)

D  13.6 (diameter below sheath, mm)

D  dc (thickness of insulation, conductor to sheath, mm)


ti 
2
ti  1
dms  13.6 (outer diameter of metallic sheath, mm)

Cable sizing calculation 750Vdc Page 1/4


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

ts  1.5 (thickness of outer covering, mm)

ρc  6 (thermal resisivity of outer covering, Kxm/W)

De  17.30 (external diameter of the cable, mm)

ρp  3.5 (thermal resisivity of pipe, Kxm/W)

Dec  63 (external diameter of the pipe, mm)

ρe  1.2 (thermal resistivity of earth, Kxm/W)

Lg  600 (distance from ground surface to cable axis, mm)

s1  63 (axial separation between two adjacent groups, mm)


te  30 (max. earth temperature, degC)

n  1 (number of load-carrying conductors in the cable)

Doc  63 (the outside diameter of the duct, mm)

Dic  55.8 (the inside diameter of the duct, mm)

Nc  2 (number of number of loaded cables in the duct bank)

CALCULATIONS:

1. DC resistance of conductor

The d.c. resistance per unit length of the conductor at its maximum operating temperature

Δθ  tc  te (temperature rise of the conductor above the ambient


temperature, degC)
Δθ  60

Rdc  Rdc20 1  αc  ( tc  20) (D.C.resistance of conductor at max.operating temperature, /m)


 20 
4
Rdc  2.461  10

2. Calculation of thermal resistances


2.1 Thermal resistance of the constituent parts of a cable, T1, T2 and T3

2.1.1 Thermal resistance between one conductor and sheath T1

2  ti 
 ln 1 
ρi
T1   (thermal resistance between one conductor and sheath, Kxm/W)
2 π  dc 

T1  0.089

2.1.2 Thermal resistance between sheath and armour T2

T2  0 (thermal resistance per unit length of the bedding between sheath and armour, Kxm/W)

Cable sizing calculation 750Vdc Page 2/4


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.1.3 Thermal resistance of outer covering (serving) T3

De  dms
t  t  1.85
3 2 3

 2 t
ρc 3
T3   ln 1   (thermal resistance of outer covering, Kxm/W)
2 π  dms 

T3  0.23

2.2 External thermal resistance T4

2.2.1 Thermal resistance between cable and duct (or pipe) T41
Constants, depending on the installations the values of which are given in IEC60287-2-1 table 4

Uc  1.87 Vc  0.312 Yc  0.0037

Uc (thermal restistance of soil,Kxm/W)


T41 
1  0.1( Vc  Yc te)  De

T41  1.08

2.2.2 Thermal resistance of the duct (or pipe) itself T42

  ln
ρp Doc   (thermal restistance induced by other group, Kxm/W)
T42  0.5 
π   Dic  

T42  0.068

2.2.3 External thermal resistance of the duct (or pipe) T43

2  Lg
u  u  19.048
Doc

T43  0.5
Nc ( ρe) 
 ln u 
2
u 1 
π

T43  1.39

T4  T41  T42  T43 (total thermal restistance of soil Kxm/W)

T4  2.538

Cable sizing calculation 750Vdc Page 3/4


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.3 Permissible current rating of cables (A)

Δθ
I 
Rdc T1  n  Rdc T2  n  Rdc ( T3  T4 )

I  292 A

Cable sizing calculation 750Vdc Page 4/4


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

CURRENT CARRYING CAPACITY OF SINGLE CORE, XLPE INSULATED,

PV CABLE, IN FLAT FORMATION ARRANGEMENT AND IN

FREE AIR

CABLE TYPE: 1kV XLPE cable, 1x4sqmm, copper conductor,

CONNECTION: PV module to SCB

GENERAL DATA: MATERIAL PERMITTIVITY tan-delta THERMAL RESISTIVITY


εr tanδ ρi
XLPE 2.5 0.008 3.5
PE 2.3 0.001 3.5
PVC 8.0 0.1 6.0
OFC-Paper,L.P. 3.3 0.004 5.0
Concrete 1.0
PVC-Pipes 7.0
RESISTIVITY TEMP. COEFFICIENT

20x10^-8 20
LEAD 21.4 0.004
COPPER 1.7241 0.00393
ALU(cond) 2.8264 0.00403
STEEL 13.8 0.0045
BRONZE 3.5 0.003
ALU(sheath) 2.84 0.00403

ASSUMPTIONS:

U  750 (phase to phase voltage, V)

dc  2.4 (external diameter of conductor, mm)


dc1  2.4 (diameter of conductor, including screen,mm)
tc  90 (max. operation temperature of the conductor, degC)

3
Rdc0  5.09 10 (D.C.resistance of the conductor at 20degC, /m)

3
αc  3.93 10 (temperature coefficient of copper at 20degC/K, IEC60287-1-1-Table I)
20

ρi  3.5 (thermal resistivity of insulation, Kxm/W)

tanδ  0.008 (loss factor of insulation)


D  3.8 (diameter below sheath, mm)

D  dc (thickness of insulation, conductor to sheath, mm)


ti 
2
ti  0.7

dms  3.8 (outer diameter of sheath, mm)

Cable sizing calculation 750Vdc Page 1/3


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

ts  0.7 (thickness of outer covering, mm)


ρc  6 (thermal resisivity of outer covering, Kxm/W)
De  5.2 (external diameter of the cable, mm)
ta  60 (max. air temperature, degC)
n  1 (number of load-carrying conductors in the cable)

Constants for sigle cable in tclipped direct in free air:


Z  1.69 (constant [IEC60287-2-1, Table 2])
E  0.63 (constant [IEC60287-2-1, Table 2])
g1  0.25 (constant [IEC60287-2-1, Table 2])

CALCULATIONS:

1. DC resistance of conductor

Δθ  tc  ta (temperature rise of the conductor above the ambient


temperature, degC)
Δθ  30
(D.C.resistance of conductor at max.operating
Rdc  Rdc0 1  αc  ( tc  20)
 20  temperature, /m)

Rdc  0.00649

2. Calculation of thermal resistances


2.1 Thermal resistance of the constituent parts of a cable, T1, T2 and T3

2.1.1 Thermal resistance between one conductor and sheath T1


2  ti 
 ln 1 
ρi
T1   (thermal resistance between one conductor and metallic sheath, Kxm/W)
2 π  dc 
T1  0.256

2.1.2 Thermal resistance between sheath and armour T2

T2  0 (thermal resistance per unit length of the bedding between sheath and
armour, Kxm/W)

2.1.3 Thermal resistance of outer covering (serving) T3


De  dms
t  t  0.7
3 2 3

ρc  2 t
3 (thermal resistance of outer covering, Kxm/W)
T3   ln 1  
2 π  dms 

T3  0.3

Cable sizing calculation 750Vdc Page 2/3


5MW Solar Power Plant Cable Sizing Calculation
Revision No. C

2.2 External thermal resistance T4


2.2.1 Cables laid in free air; Cables protected from direct solar radiation
the heat dissipation coefficient obtained either from the above formula using the
appropriate values of constants Z, E and g given in table 2, IEC60287-2-1

h   Z E (heat dissipation coefficient)


 
 
g1
 De 10 3 
 
h  6.923

 π De h 10 3  T1
KA        T2  ( 1 )  T3
 ( 1)   n  

KA  0.063

Δθd  0 This is a factor, having the dimensions of temperature difference,


to account for the dielectric losses. If the dielectric losses are
neglected, Δθd = 0.

k1  2.3 (factor has to be changed until k3<0.001, starting with k1=2)

 1
 
Δθ  Δθd   
4

k   
  1  KA k1
k  2.263

k3  k  k1 (factor should be <0.001)

k3  0.0373

The thermal resistance T4 of the surroundings of a cable in air and protected from solar
radiation is given by the formula:

1
T4 
 
π De 10 3  h k (external thermal resistance, kxm/W)

T4  3.908

3. Permissible current rating of cables

Δθ
I 
Rdc T1  n  Rdc T2  n  Rdc ( T3  T4 )

I  32 A

Cable sizing calculation 750Vdc Page 3/3


Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

ANNEXURE II: VOLTAGE DROP AND POWER LOSSES CALCULATION


Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

22kV System

1 22kV to PEA Connection Riser Pole Outgoing 5000 131.22 1.25 164.02 3 x 1C-185 Sq.mm. AL, SAC Overhead 410 * 0.2088 0.414406 36.87 20 0.009 Satisfy 1.889 0.004176 215.70

2 Riser Pole Outgoing 22kV Switchgear 5000 131.22 1.25 164.02 3 x 1C-120 Sq.mm. Cu, XLPE Underground 110 HPDE 299 0.1958 0.1291 36.87 35 0.008 Satisfy 1.862 0.006853 353.98

3 22kV Switchgear Riser Pole Incoming 5000 131.22 1.25 164.02 3 x 1C-120 Sq.mm. Cu, XLPE Underground 110 HPDE 299 0.1958 0.1291 36.87 35 0.008 Satisfy 1.862 0.006853 353.98

4 Riser Pole Incoming Riser Pole TR.2 5000 131.22 1.25 164.02 3 x 1C-185 Sq.mm. AL, SAC Underground 110 HPDE 410 * 0.2088 0.414406 36.87 400 0.172 Satisfy 37.789 0.083520 4,314.05

Sum %VD 0.197 Satisfy 5,237.71

Transformer

5 Riser Pole TR.1 TR No.1 1250 32.80 1.25 41.00 3 x 1C-95 Sq.mm. Cu, XLPE Underground 110 HPDE 264 0.2467 0.1333 36.87 15 0.001 Satisfy 0.236 0.003701 11.95

6 Riser Pole TR.2 TR No.2 1250 32.80 1.25 41.00 3 x 1C-95 Sq.mm. Cu, XLPE Underground 110 HPDE 264 0.2467 0.1333 36.87 30 0.002 Satisfy 0.473 0.007401 23.89

5 Riser Pole TR.3 TR No.3 1250 32.80 1.25 41.00 3 x 1C-95 Sq.mm. Cu, XLPE Underground 110 HPDE 264 0.2467 0.1333 36.87 15 0.001 Satisfy 0.236 0.003701 11.95

6 Riser Pole TR.4 TR No.4 1250 32.80 1.25 41.00 3 x 1C-95 Sq.mm. Cu, XLPE Underground 110 HPDE 264 0.2467 0.1333 36.87 30 0.002 Satisfy 0.473 0.007401 23.89

Avg %VD 0.002 Satisfy 0.355 71.68

Inverter

7 1250kVA Transformer 1 Inverter 1 1000 1443.38 1.25 1804.22 3x 4 x 1C-240 Sq.mm. Cu, XLPE In Cable Ladder 2189 0.0245 0.025925 36.87 15 0.326 Satisfy 1.319 0.000368 2,298.52

8 1250kVA Transformer 2 Inverter 2 1000 1443.38 1.25 1804.22 3x 4 x 1C-240 Sq.mm. Cu, XLPE In Cable Ladder 2189 0.0245 0.025925 36.87 20 0.434 Satisfy 1.758 0.000490 3,064.69

9 1250kVA Transformer 3 Inverter 3 1000 1443.38 1.25 1804.22 3x 4 x 1C-240 Sq.mm. Cu, XLPE In Cable Ladder 2189 0.0245 0.025925 36.87 15 0.326 Satisfy 1.319 0.000368 2,298.52

10 1250kVA Transformer 4 Inverter 4 1000 1443.38 1.25 1804.22 3x 4 x 1C-240 Sq.mm. Cu, XLPE In Cable Ladder 2189 0.0245 0.025925 36.87 20 0.434 Satisfy 1.758 0.000490 3,064.69

Avg %VD 0.380 Satisfy 1.539 10,726.41

1000Vdc System

Page 1 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

11 Inverter 1 Combiner box 1 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 110.5 1.375 Satisfy 10.342 0.027194 983.35

12 Inverter 1 Combiner box 2 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 84 1.045 Satisfy 7.862 0.020672 747.53

13 Inverter 1 Combiner box 3 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 59 0.734 Satisfy 5.522 0.014520 525.05

14 Inverter 1 Combiner box 4 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 42 0.523 Satisfy 3.931 0.010336 373.76

15 Inverter 1 Combiner box 5 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 31 0.386 Satisfy 2.901 0.007629 275.87

16 Inverter 1 Combiner box 6 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 47 0.585 Satisfy 4.399 0.011567 418.26

17 Inverter 1 Combiner box 7 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 70 0.871 Satisfy 6.552 0.017227 622.94

18 Inverter 1 Combiner box 8 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 96 1.195 Satisfy 8.985 0.023626 854.32

19 Inverter 1 Combiner box 9 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 111 1.382 Satisfy 10.389 0.027317 987.80

20 Inverter 2 Combiner box 1 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 129.2 1.608 Satisfy 12.093 0.031796 1,149.77

21 Inverter 2 Combiner box 2 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 103 1.282 Satisfy 9.640 0.025348 916.61

22 Inverter 2 Combiner box 3 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 83.5 1.039 Satisfy 7.815 0.020549 743.08

23 Inverter 2 Combiner box 4 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 57 0.709 Satisfy 5.335 0.014028 507.25

24 Inverter 2 Combiner box 5 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 36 0.448 Satisfy 3.369 0.008860 320.37

25 Inverter 2 Combiner box 6 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 21 0.261 Satisfy 1.966 0.005168 186.88

26 Inverter 2 Combiner box 7 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 43 0.535 Satisfy 4.025 0.010582 382.66

27 Inverter 2 Combiner box 8 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 62.2 0.774 Satisfy 5.822 0.015307 553.53

28 Inverter 2 Combiner box 9 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 80 0.996 Satisfy 7.488 0.019688 711.93

29 Inverter 3 Combiner box 1 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 96 1.195 Satisfy 8.985 0.023626 854.32

30 Inverter 3 Combiner box 2 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 66 0.821 Satisfy 6.177 0.016243 587.34

31 Inverter 3 Combiner box 3 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 44.5 0.554 Satisfy 4.165 0.010951 396.01

32 Inverter 3 Combiner box 4 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 26 0.324 Satisfy 2.434 0.006399 231.38

33 Inverter 3 Combiner box 5 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 53.4 0.665 Satisfy 4.998 0.013142 475.21

34 Inverter 3 Combiner box 6 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 83.4 1.038 Satisfy 7.806 0.020525 742.19

Page 2 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

35 Inverter 3 Combiner box 7 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 101 1.257 Satisfy 9.453 0.024856 898.81

36 Inverter 3 Combiner box 8 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 129 1.606 Satisfy 12.074 0.031747 1,147.99

37 Inverter 3 Combiner box 9 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 159 1.979 Satisfy 14.882 0.039130 1,414.96

38 Inverter 4 Combiner box 1 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 105 1.307 Satisfy 9.828 0.025841 934.41

39 Inverter 4 Combiner box 2 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 111 1.382 Satisfy 10.389 0.027317 987.80

40 Inverter 4 Combiner box 3 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 34 0.423 Satisfy 3.182 0.008367 302.57

41 Inverter 4 Combiner box 4 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 32 0.398 Satisfy 2.995 0.007875 284.77

42 Inverter 4 Combiner box 5 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 54 0.672 Satisfy 5.054 0.013289 480.55

43 Inverter 4 Combiner box 6 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 76 0.946 Satisfy 7.113 0.018704 676.33

44 Inverter 4 Combiner box 7 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 99 1.232 Satisfy 9.266 0.024364 881.01

45 Inverter 4 Combiner box 8 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 128 1.593 Satisfy 11.980 0.031501 1,139.09

46 Inverter 4 Combiner box 9 143 190.16 1.25 237.70 2 x 1C-95 Sq.mm. Cu, CV Underground 63 HPDE 292 0.2461 - - 155 1.929 Satisfy 14.507 0.038146 1,379.37

Avg %VD 0.974 Satisfy 7.326

Combiner box PV String

50 SCB-01-01-01 ST01010101 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

51 ST01010102 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

52 ST01010103 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

53 ST01010104 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

54 ST01010105 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

55 ST01010106 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

56 ST01010107 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

57 ST01010108 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

58 ST01010109 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

Page 3 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

59 ST01010110 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

60 ST01010111 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

61 ST01010112 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

62 ST01010113 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

63 ST01010114 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

64 ST01010115 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

65 ST01010116 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

66 ST01010117 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

67 ST01010118 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

68 ST01010119 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

69 ST01010120 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

70 ST01010121 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

71 ST01010122 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 71 1.059 Satisfy 7.966 0.460790 34.43

72 SCB-01-01-02 ST01010201 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 19 0.283 Satisfy 2.132 0.123310 9.21

73 ST01010202 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 19 0.283 Satisfy 2.132 0.123310 9.21

74 ST01010203 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 41 0.612 Satisfy 4.600 0.266090 19.88

75 ST01010204 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 41 0.612 Satisfy 4.600 0.266090 19.88

76 ST01010205 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

77 ST01010206 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

78 ST01010207 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

79 ST01010208 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

80 ST01010209 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

81 ST01010210 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

82 ST01010211 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

Page 4 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

83 ST01010212 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 7 0.104 Satisfy 0.785 0.045430 3.39

84 ST01010213 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 7 0.104 Satisfy 0.785 0.045430 3.39

85 ST01010214 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

86 ST01010215 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

87 ST01010216 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

88 ST01010217 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

89 ST01010218 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

90 ST01010219 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

91 ST01010220 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

92 ST01010221 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

93 ST01010222 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 45 0.671 Satisfy 5.049 0.292050 21.82

94 SCB-01-01-03 ST01010301 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

95 ST01010302 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

96 ST01010303 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

97 ST01010304 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

98 ST01010305 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

99 ST01010306 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

100 ST01010307 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

101 ST01010308 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

102 ST01010309 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

103 ST01010310 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

104 ST01010311 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

105 ST01010312 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

106 ST01010313 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

Page 5 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

107 ST01010314 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

108 ST01010315 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

109 ST01010316 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

110 ST01010317 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

111 ST01010318 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

112 ST01010319 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

113 ST01010320 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

114 ST01010321 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

115 ST01010322 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 22 0.328 Satisfy 2.468 0.142780 10.67

116 SCB-01-01-04 ST01010401 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 9 0.134 Satisfy 1.010 0.058410 4.36

117 ST01010402 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 31 0.463 Satisfy 3.478 0.201190 15.03

118 ST01010403 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 31 0.463 Satisfy 3.478 0.201190 15.03

119 ST01010404 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

120 ST01010405 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

121 ST01010406 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

122 ST01010407 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

123 ST01010408 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

124 ST01010409 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

125 ST01010410 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

126 ST01010411 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

127 ST01010412 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

128 ST01010413 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

129 ST01010414 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

130 ST01010415 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

Page 6 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

131 ST01010416 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

132 ST01010417 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

133 ST01010418 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

134 ST01010419 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

135 ST01010420 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

136 ST01010421 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 81 1.208 Satisfy 9.088 0.525690 39.28

138 SCB-01-01-05 ST01010501 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

139 ST01010502 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

140 ST01010503 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

141 ST01010504 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

142 ST01010505 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 70 1.044 Satisfy 7.854 0.454300 33.94

143 ST01010506 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

144 ST01010507 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

145 ST01010508 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

146 ST01010509 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

147 ST01010510 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 57 0.850 Satisfy 6.395 0.369930 27.64

148 ST01010511 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

149 ST01010512 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

150 ST01010513 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

151 ST01010514 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

152 ST01010515 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

153 ST01010516 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

154 ST01010517 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

155 ST01010518 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

Page 7 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

156 ST01010519 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

157 ST01010520 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

158 ST01010521 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

159 ST01010522

160 SCB-01-01-06 ST01010601 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 53 0.791 Satisfy 5.946 0.343970 25.70

161 ST01010602 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 75 1.119 Satisfy 8.415 0.486750 36.37

162 ST01010603 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

163 ST01010604 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

164 ST01010605 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

165 ST01010606 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

166 ST01010607 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

167 ST01010608 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

168 ST01010609 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 77 1.149 Satisfy 8.639 0.499730 37.34

169 ST01010610 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

170 ST01010611 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

171 ST01010612 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

172 ST01010613 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

173 ST01010614 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

174 ST01010615 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

175 ST01010616 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

176 ST01010617 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 19 0.283 Satisfy 2.132 0.123310 9.21

177 ST01010618 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

178 ST01010619 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

179 ST01010620 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

Page 8 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

180 ST01010621 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

182 SCB-01-01-07 ST01010701 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 53 0.791 Satisfy 5.946 0.343970 25.70

183 ST01010702 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 76 1.134 Satisfy 8.527 0.493240 36.85

184 ST01010703 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

185 ST01010704 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

186 ST01010705 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

187 ST01010706 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

188 ST01010707 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

189 ST01010708 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

190 ST01010709 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

191 ST01010710 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

192 ST01010711 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

193 ST01010712 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

194 ST01010713 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

195 ST01010714 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

196 ST01010715 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

197 ST01010716 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

198 ST01010717 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

199 ST01010718 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

200 ST01010719 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

201 ST01010720 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

202 ST01010721 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

204 SCB-01-01-08 ST01010801 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 63 0.940 Satisfy 7.068 0.408870 30.55

205 ST01010802 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

Page 9 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

206 ST01010803 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

207 ST01010804 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 42 0.627 Satisfy 4.712 0.272580 20.37

208 ST01010805 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 42 0.627 Satisfy 4.712 0.272580 20.37

209 ST01010806 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 65 0.970 Satisfy 7.293 0.421850 31.52

210 ST01010807 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 65 0.970 Satisfy 7.293 0.421850 31.52

211 ST01010808 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

212 ST01010809 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

213 ST01010810 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

214 ST01010811 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

215 ST01010812 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

216 ST01010813 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

217 ST01010814 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

218 ST01010815 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 71 1.059 Satisfy 7.966 0.460790 34.43

219 ST01010816 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 71 1.059 Satisfy 7.966 0.460790 34.43

220 ST01010817 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

221 ST01010818 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

222 ST01010819 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 94 1.402 Satisfy 10.546 0.610060 45.58

223 ST01010820 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 94 1.402 Satisfy 10.546 0.610060 45.58

224 ST01010821 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 71 1.059 Satisfy 7.966 0.460790 34.43

226 SCB-01-01-09 ST01010901 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 85 1.268 Satisfy 9.537 0.551650 41.21

227 ST01010902 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 64 0.955 Satisfy 7.180 0.415360 31.03

228 ST01010903 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 64 0.955 Satisfy 7.180 0.415360 31.03

229 ST01010904 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

230 ST01010905 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

Page 10 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

231 ST01010906 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

232 ST01010907 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

233 ST01010908 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

234 ST01010909 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

235 ST01010910 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

236 ST01010911 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

237 ST01010912 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

238 ST01010913 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

239 ST01010914 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

240 ST01010915 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

241 ST01010916 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

242 ST01010917 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

243 ST01010918 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 69 1.029 Satisfy 7.741 0.447810 33.46

244 ST01010919 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 69 1.029 Satisfy 7.741 0.447810 33.46

245 ST01010920 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

246 ST01010921 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

247 ST01010922

248 SCB-02-02-01 ST02020101 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 41 0.612 Satisfy 4.600 0.266090 19.88

249 ST02020102 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

250 ST02020103 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

251 ST02020104 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

252 ST02020105 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

253 ST02020106 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

254 ST02020107 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

Page 11 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

255 ST02020108 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

256 ST02020109 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

257 ST02020110 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

258 ST02020111 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

259 ST02020112 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

260 ST02020113 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

261 ST02020114 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

262 ST02020115 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

263 ST02020116 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

264 ST02020117 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

265 ST02020118 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

266 ST02020119 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

267 ST02020120 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

268 ST02020121 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

269 ST02020122 23

270 SCB-02-02-02 ST02020201 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

271 ST02020202 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

272 ST02020203 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

273 ST02020204 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

274 ST02020205 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

275 ST02020206 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

276 ST02020207 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

277 ST02020208 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

278 ST02020209 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

Page 12 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

279 ST02020210 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

280 ST02020211 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

281 ST02020212 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

282 ST02020213 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

283 ST02020214 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

284 ST02020215 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

285 ST02020216 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

286 ST02020217 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

287 ST02020218 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

288 ST02020219 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

289 ST02020220 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

290 ST02020221 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

291 ST02020222 14

292 SCB-02-02-03 ST02020301 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

293 ST02020302 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

294 ST02020303 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

295 ST02020304 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

296 ST02020305 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

297 ST02020306 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

298 ST02020307 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

299 ST02020308 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

300 ST02020309 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

301 ST02020310 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

302 ST02020311 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

Page 13 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

303 ST02020312 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

304 ST02020313 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

305 ST02020314 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

306 ST02020315 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

307 ST02020316 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

308 ST02020317 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

309 ST02020318 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

310 ST02020319 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

311 ST02020320 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

312 ST02020321 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

313 ST02020322 23

314 SCB-02-02-04 ST02020401 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 84 1.253 Satisfy 9.424 0.545160 40.73

315 ST02020402 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

316 ST02020403 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

317 ST02020404 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 77 1.149 Satisfy 8.639 0.499730 37.34

318 ST02020405 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

319 ST02020406 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

320 ST02020407 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

321 ST02020408 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

322 ST02020409 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

323 ST02020410 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

324 ST02020411 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

325 ST02020412 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

326 ST02020413 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

Page 14 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

327 ST02020414 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

328 ST02020415 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

329 ST02020416 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

330 ST02020417 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

331 ST02020418 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

332 ST02020419 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

333 ST02020420 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

334 ST02020421 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

335 ST02020422

336 SCB-02-02-05 ST02020501 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

337 ST02020502 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

338 ST02020503 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

339 ST02020504 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

340 ST02020505 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

341 ST02020506 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

342 ST02020507 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

343 ST02020508 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

344 ST02020509 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

345 ST02020510 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

346 ST02020511 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

347 ST02020512 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

348 ST02020513 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

349 ST02020514 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

350 ST02020515 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

Page 15 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

351 ST02020516 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

352 ST02020517 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

353 ST02020518 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

354 ST02020519 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

355 ST02020520 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

356 ST02020521 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

357 ST02020522

358 SCB-02-02-06 ST02020601 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

359 ST02020602 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

360 ST02020603 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

361 ST02020604 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

362 ST02020605 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

363 ST02020606 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

364 ST02020607 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

365 ST02020608 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

366 ST02020609 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

367 ST02020610 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

368 ST02020611 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

369 ST02020612 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

370 ST02020613 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

371 ST02020614 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

372 ST02020615 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

373 ST02020616 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

374 ST02020617 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

Page 16 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

375 ST02020618 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

376 ST02020619 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

377 ST02020620 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

378 ST02020621 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

379 ST02020622

380 SCB-02-02-07 ST02020701 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

381 ST02020702 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

382 ST02020703 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

383 ST02020704 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

384 ST02020705 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

385 ST02020706 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

386 ST02020707 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

387 ST02020708 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

388 ST02020709 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

389 ST02020710 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

390 ST02020711 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

391 ST02020712 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

392 ST02020713 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

393 ST02020714 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

394 ST02020715 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

395 ST02020716 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

396 ST02020717 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

397 ST02020718 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

398 ST02020719 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

Page 17 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

399 ST02020720 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

400 ST02020721 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

401 ST02020722

402 SCB-02-02-08 ST02020801 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

403 ST02020802 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

404 ST02020803 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

405 ST02020804 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

406 ST02020805 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

407 ST02020806 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

408 ST02020807 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

409 ST02020808 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

410 ST02020809 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

411 ST02020810 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

412 ST02020811 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

413 ST02020812 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

414 ST02020813 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

415 ST02020814 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

416 ST02020815 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

417 ST02020816 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

418 ST02020817 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

419 ST02020818 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

420 ST02020819 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

421 ST02020820 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

422 ST02020821 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

Page 18 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

423 ST02020822

424 SCB-02-02-09 ST02020901 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

425 ST02020902 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

426 ST02020903 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

427 ST02020904 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

428 ST02020905 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

429 ST02020906 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

430 ST02020907 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

431 ST02020908 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 32 0.477 Satisfy 3.590 0.207680 15.52

432 ST02020909 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

433 ST02020910 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 10 0.149 Satisfy 1.122 0.064900 4.85

434 ST02020911 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

435 ST02020912 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

436 ST02020913 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

437 ST02020914 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

438 ST02020915 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

439 ST02020916 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

440 ST02020917 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

441 ST02020918 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

442 ST02020919 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

443 ST02020920 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

444 ST02020921 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 14 0.209 Satisfy 1.571 0.090860 6.79

445 ST02020922

446 SCB-03-03-01 ST03030101 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

Page 19 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

447 ST03030102 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

448 ST03030103 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

449 ST03030104 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 25 0.373 Satisfy 2.805 0.162250 12.12

450 ST03030105 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 25 0.373 Satisfy 2.805 0.162250 12.12

451 ST03030106 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

452 ST03030107 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

453 ST03030108 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

454 ST03030109 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

455 ST03030110 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 35 0.522 Satisfy 3.927 0.227150 16.97

456 ST03030111 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

457 ST03030112 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

458 ST03030113 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

459 ST03030114 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

460 ST03030115 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

461 ST03030116 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

462 ST03030117 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

463 ST03030118 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

464 ST03030119 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

465 ST03030120 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

466 ST03030121 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

467 ST03030122 6.50 8.64 2.25 19.45 3 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

468 SCB-03-03-02 ST03030201 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

469 ST03030202 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 43 0.642 Satisfy 4.824 0.279070 20.85

470 ST03030203 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 43 0.642 Satisfy 4.824 0.279070 20.85

Page 20 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

471 ST03030204 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

472 ST03030205 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

473 ST03030206 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 88 1.313 Satisfy 9.873 0.571120 42.67

474 ST03030207 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

475 ST03030208 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

476 ST03030209 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

477 ST03030210 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

478 ST03030211 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

479 ST03030212 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

480 ST03030213 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

481 ST03030214 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

482 ST03030215 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

483 ST03030216 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

484 ST03030217 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

485 ST03030218 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

486 ST03030219 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

487 ST03030220 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

488 ST03030221 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 15 0.224 Satisfy 1.683 0.097350 7.27

489 ST03030222 6.50 8.64 1.25 10.80 3 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 15 0.224 Satisfy 1.683 0.097350 7.27

490 SCB-03-03-03 ST03030301 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

491 ST03030302 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

492 ST03030303 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

493 ST03030304 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 54 0.806 Satisfy 6.058 0.350460 26.18

494 ST03030305 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

Page 21 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

495 ST03030306 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

496 ST03030307 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

497 ST03030308 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

498 ST03030309 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

499 ST03030310 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

500 ST03030311 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

501 ST03030312 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

502 ST03030313 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

503 ST03030314 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

504 ST03030315 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

505 ST03030316 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

506 ST03030317 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

507 ST03030318 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

508 ST03030319 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

509 ST03030320 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

510 ST03030321 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

511 ST03030322 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

512 SCB-03-03-04 ST03030401 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

513 ST03030402 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 57 0.850 Satisfy 6.395 0.369930 27.64

514 ST03030403 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

515 ST03030404 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

516 ST03030405 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

517 ST03030406 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

518 ST03030407 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

Page 22 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

519 ST03030408 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

520 ST03030409 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

521 ST03030410 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

522 ST03030411 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

523 ST03030412 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 51 0.761 Satisfy 5.722 0.330990 24.73

524 ST03030413 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

525 ST03030414 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

526 ST03030415 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

527 ST03030416 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

528 ST03030417 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

529 ST03030418 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

530 ST03030419 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

531 ST03030420 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

532 ST03030421 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

533 ST03030422 32

534 SCB-03-03-05 ST03030501 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

535 ST03030502 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

536 ST03030503 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

537 ST03030504 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

538 ST03030505 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

539 ST03030506 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

540 ST03030507 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

541 ST03030508 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

542 ST03030509 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

Page 23 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

543 ST03030510 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

544 ST03030511 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

545 ST03030512 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

546 ST03030513 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 51 0.761 Satisfy 5.722 0.330990 24.73

547 ST03030514 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 51 0.761 Satisfy 5.722 0.330990 24.73

548 ST03030515 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

549 ST03030516 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

550 ST03030517 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

551 ST03030518 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

552 ST03030519 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 62 0.925 Satisfy 6.956 0.402380 30.06

553 ST03030520 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 62 0.925 Satisfy 6.956 0.402380 30.06

554 ST03030521 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

555 ST03030522 32

556 SCB-03-03-06 ST03030601 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 22 0.328 Satisfy 2.468 0.142780 10.67

557 ST03030602 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

558 ST03030603 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

559 ST03030604 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

560 ST03030605 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

561 ST03030606 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

562 ST03030607 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

563 ST03030608 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

564 ST03030609 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

565 ST03030610 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

566 ST03030611 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

Page 24 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

567 ST03030612 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

568 ST03030613 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

569 ST03030614 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

570 ST03030615 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

571 ST03030616 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

572 ST03030617 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 47 0.701 Satisfy 5.273 0.305030 22.79

573 ST03030618 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

574 ST03030619 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

575 ST03030620 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

576 ST03030621 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

577 ST03030622 32

578 SCB-03-03-07 ST03030701 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 57 0.850 Satisfy 6.395 0.369930 27.64

579 ST03030702 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 57 0.850 Satisfy 6.395 0.369930 27.64

580 ST03030703 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

581 ST03030704 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 12 0.179 Satisfy 1.346 0.077880 5.82

582 ST03030705 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

583 ST03030706 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

584 ST03030707 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

585 ST03030708 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

586 ST03030709 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

587 ST03030710 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

588 ST03030711 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 32 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

589 ST03030712 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 29 0.433 Satisfy 3.254 0.188210 14.06

590 ST03030713 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

Page 25 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

591 ST03030714 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

592 ST03030715 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

593 ST03030716 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

594 ST03030717 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

595 ST03030718 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

596 ST03030719 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

597 ST03030720 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

598 ST03030721 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

599 ST03030722

600 SCB-03-03-08 ST03030801 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 20 0.298 Satisfy 2.244 0.129800 9.70

601 ST03030802 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

602 ST03030803 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

603 ST03030804 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

604 ST03030805 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

605 ST03030806 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

606 ST03030807 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

607 ST03030808 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

608 ST03030809 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

609 ST03030810 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

610 ST03030811 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

611 ST03030812 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

612 ST03030813 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

613 ST03030814 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 19 0.283 Satisfy 2.132 0.123310 9.21

614 ST03030815 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 19 0.283 Satisfy 2.132 0.123310 9.21

Page 26 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

615 ST03030816 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

616 ST03030817 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

617 ST03030818 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

618 ST03030819 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

619 ST03030820 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

620 ST03030821 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 36 0.537 Satisfy 4.039 0.233640 17.46

621 ST03030822

622 SCB-03-03-09 ST03030901 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

623 ST03030902 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

624 ST03030903 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

625 ST03030904 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

626 ST03030905 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

627 ST03030906 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

628 ST03030907 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

629 ST03030908 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

630 ST03030909 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

631 ST03030910 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 113 1.686 Satisfy 12.678 0.733370 54.79

632 ST03030911 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 90 1.343 Satisfy 10.097 0.584100 43.64

633 ST03030912 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 90 1.343 Satisfy 10.097 0.584100 43.64

634 ST03030913 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 69 1.029 Satisfy 7.741 0.447810 33.46

635 ST03030914 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 69 1.029 Satisfy 7.741 0.447810 33.46

636 ST03030915 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

637 ST03030916 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 81 1.208 Satisfy 9.088 0.525690 39.28

638 ST03030917 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 81 1.208 Satisfy 9.088 0.525690 39.28

Page 27 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

639 ST03030918 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

640 ST03030919 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

641 ST03030920 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

642 ST03030921 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

643 ST03030922

644 SCB-04-04-01 ST04040101 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 97 1.447 Satisfy 10.883 0.629530 47.03

645 ST04040102 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 97 1.447 Satisfy 10.883 0.629530 47.03

646 ST04040103 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 74 1.104 Satisfy 8.302 0.480260 35.88

647 ST04040104 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 74 1.104 Satisfy 8.302 0.480260 35.88

648 ST04040105 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 90 1.343 Satisfy 10.097 0.584100 43.64

649 ST04040106 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 90 1.343 Satisfy 10.097 0.584100 43.64

650 ST04040107 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 67 1.000 Satisfy 7.517 0.434830 32.49

651 ST04040108 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 67 1.000 Satisfy 7.517 0.434830 32.49

652 ST04040109 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

653 ST04040110 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

654 ST04040111 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

655 ST04040112 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

656 ST04040113 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 76 1.134 Satisfy 8.527 0.493240 36.85

657 ST04040114 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

658 ST04040115 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

659 ST04040116 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

660 ST04040117 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

661 ST04040118 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

662 ST04040119 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

Page 28 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

663 ST04040120 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 25 0.373 Satisfy 2.805 0.162250 12.12

664 ST04040121 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

665 ST04040122 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

666 SCB-04-04-02 ST04040201 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

667 ST04040202 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

668 ST04040203 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 24 0.358 Satisfy 2.693 0.155760 11.64

669 ST04040204 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

670 ST04040205 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

671 ST04040206 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

672 ST04040207 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

673 ST04040208 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

674 ST04040209 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

675 ST04040210 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 39 0.582 Satisfy 4.376 0.253110 18.91

676 ST04040211 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

677 ST04040212 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

678 ST04040213 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

679 ST04040214 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

680 ST04040215 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

681 ST04040216 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

682 ST04040217 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

683 ST04040218 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

684 ST04040219 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 46 0.686 Satisfy 5.161 0.298540 22.30

685 ST04040220 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

686 ST04040221 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

Page 29 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

687 ST04040222 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 58 0.865 Satisfy 6.507 0.376420 28.12

688 SCB-04-04-03 ST04040301 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

689 ST04040302 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

690 ST04040303 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

691 ST04040304 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 23 0.343 Satisfy 2.580 0.149270 11.15

692 ST04040305 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

693 ST04040306 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

694 ST04040307 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

695 ST04040308 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

696 ST04040309 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

697 ST04040310 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

698 ST04040311 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

699 ST04040312 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

700 ST04040313 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

701 ST04040314 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

702 ST04040315 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

703 ST04040316 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 84 1.253 Satisfy 9.424 0.545160 40.73

704 ST04040317 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

705 ST04040318 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

706 ST04040319 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

707 ST04040320 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

708 ST04040321 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

709 ST04040322 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840

710 SCB-04-04-04 ST04040401 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 79 1.179 Satisfy 8.863 0.512710 38.31

Page 30 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

711 ST04040402 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

712 ST04040403 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 55 0.821 Satisfy 6.171 0.356950 26.67

713 ST04040404 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

714 ST04040405 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

715 ST04040406 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

716 ST04040407 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

717 ST04040408 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

718 ST04040409 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 48 0.716 Satisfy 5.385 0.311520 23.27

719 ST04040410 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 48 0.716 Satisfy 5.385 0.311520 23.27

720 ST04040411 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

721 ST04040412 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

722 ST04040413 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

723 ST04040414 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

724 ST04040415 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 83 1.238 Satisfy 9.312 0.538670 40.25

725 ST04040416 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

726 ST04040417 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 59 0.880 Satisfy 6.619 0.382910 28.61

727 ST04040418 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

728 ST04040419 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

729 ST04040420 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

730 ST04040421 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 16 0.239 Satisfy 1.795 0.103840 7.76

731 ST04040422 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 25 0.373 Satisfy 2.805 0.162250 12.12

732 SCB-04-04-05 ST04040501 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

733 ST04040502 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

734 ST04040503 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

Page 31 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

735 ST04040504 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

736 ST04040505 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

737 ST04040506 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

738 ST04040507 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 70 1.044 Satisfy 7.854 0.454300 33.94

739 ST04040508 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

740 ST04040509 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

741 ST04040510 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

742 ST04040511 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

743 ST04040512 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

744 ST04040513 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

745 ST04040514 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 83 1.238 Satisfy 9.312 0.538670 40.25

746 ST04040515 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

747 ST04040516 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

748 ST04040517 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

749 ST04040518 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

750 ST04040519 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

751 ST04040520 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

752 ST04040521 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

753 ST04040522

754 SCB-04-04-06 ST04040601 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

755 ST04040602 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

756 ST04040603 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

757 ST04040604 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

758 ST04040605 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

Page 32 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

759 ST04040606 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

760 ST04040607 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 70 1.044 Satisfy 7.854 0.454300 33.94

761 ST04040608 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

762 ST04040609 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

763 ST04040610 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

764 ST04040611 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

765 ST04040612 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

766 ST04040613 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

767 ST04040614 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 83 1.238 Satisfy 9.312 0.538670 40.25

768 ST04040615 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

769 ST04040616 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

770 ST04040617 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

771 ST04040618 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

772 ST04040619 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

773 ST04040620 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

774 ST04040621 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

775 ST04040622

776 SCB-04-04-07 ST04040701 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

777 ST04040702 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

778 ST04040703 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

779 ST04040704 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

780 ST04040705 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 33 0.492 Satisfy 3.702 0.214170 16.00

781 ST04040706 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 13 0.194 Satisfy 1.459 0.084370 6.30

782 ST04040707 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 70 1.044 Satisfy 7.854 0.454300 33.94

Page 33 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

783 ST04040708 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

784 ST04040709 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

785 ST04040710 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

786 ST04040711 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

787 ST04040712 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

788 ST04040713 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

789 ST04040714 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 83 1.238 Satisfy 9.312 0.538670 40.25

790 ST04040715 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

791 ST04040716 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

792 ST04040717 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

793 ST04040718 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 37 0.552 Satisfy 4.151 0.240130 17.94

794 ST04040719 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

795 ST04040720 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

796 ST04040721 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

797 ST04040722

798 SCB-04-04-08 ST04040801 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 88 1.313 Satisfy 9.873 0.571120 42.67

799 ST04040802 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

800 ST04040803 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 66 0.985 Satisfy 7.405 0.428340 32.00

801 ST04040804 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

802 ST04040805 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 44 0.656 Satisfy 4.937 0.285560 21.33

803 ST04040806 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 21 0.313 Satisfy 2.356 0.136290 10.18

804 ST04040807 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 78 1.164 Satisfy 8.751 0.506220 37.82

805 ST04040808 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

806 ST04040809 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 56 0.835 Satisfy 6.283 0.363440 27.15

Page 34 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

807 ST04040810 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

808 ST04040811 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 34 0.507 Satisfy 3.815 0.220660 16.49

809 ST04040812 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

810 ST04040813 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 11 0.164 Satisfy 1.234 0.071390 5.33

811 ST04040814 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 72 1.074 Satisfy 8.078 0.467280 34.91

812 ST04040815 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

813 ST04040816 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

814 ST04040817 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

815 ST04040818 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

816 ST04040819 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

817 ST04040820 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

818 ST04040821 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 26 0.388 Satisfy 2.917 0.168740 12.61

819 ST04040822

820 SCB-04-04-09 ST04040901 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 67 1.000 Satisfy 7.517 0.434830 32.49

821 ST04040902 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

822 ST04040903 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 50 0.746 Satisfy 5.610 0.324500 24.24

823 ST04040904 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

824 ST04040905 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 27 0.403 Satisfy 3.029 0.175230 13.09

825 ST04040906 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

826 ST04040907 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 5 0.075 Satisfy 0.561 0.032450 2.42

827 ST04040908 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 60 0.895 Satisfy 6.732 0.389400 29.09

828 ST04040909 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 40 0.597 Satisfy 4.488 0.259600 19.40

829 ST04040910 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 40 0.597 Satisfy 4.488 0.259600 19.40

830 ST04040911 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

Page 35 of 36
Cable Sizing Calculation Rev C

SSSA 5MW CABLE SIZING CALCULATION TABLE

Circuit Feeder LOAD CABLE


Current In Total Cable
Design Amp from VOLTAGE Voltage Drop Resistance
From To Capacity In Margine Calculation Select Type Max Carry R XL PF Length DROP RESULT Im>In (V) (Ohm) Power Loss (W)
IEC60287 Installation Application Current Im
(Calculation)
Item
2
No. kVA (A) core/mm (ohm/km) 0.8 (m) (%)

831 ST04040912 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 17 0.254 Satisfy 1.907 0.110330 8.24

832 ST04040913 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 51 0.761 Satisfy 5.722 0.330990 24.73

833 ST04040914 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 51 0.761 Satisfy 5.722 0.330990 24.73

834 ST04040915 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

835 ST04040916 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 28 0.418 Satisfy 3.141 0.181720 13.58

836 ST04040917 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 61 0.910 Satisfy 6.844 0.395890 29.58

837 ST04040918 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

838 ST04040919 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 38 0.567 Satisfy 4.263 0.246620 18.43

839 ST04040920 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

840 ST04040921 6.50 8.64 1.25 10.80 2 x 1C-4 Sq.mm. Cu, CV Along with PV mounting 34 6.49 - - 49 0.731 Satisfy 5.498 0.318010 23.76

841 ST04040922 -

Avg String Cable 0.558 Satisfy 4.197 38,963.08

Sum. AC %VD 0.579 Satisfy Total Energy Loss (kWh) 55.00

Sum. DC %VD 1.532 Satisfy Annual Energy Loss (kWh) 79.48

Total %VD 1.914 Satisfy Total Power Loss (%) 1.100

Page 36 of 36
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

ATTACHMENT I: CABLE SPECIFICATION


CABLE CHARACTERISTIC

Nominal cross-sectional area of conductor mm²


YK FD-0.6/1KV-CV
1x95 mm²
1.8/3KV-CV
1x240 mm²
12/20KV-CV
1x95 mm²
12/20KV-CV
1x120 mm²
25KV-CC
1x185 mm²

Min. number of wires in conductor 15 34 15 18 30


Diameter of conductor ± 1% mm. 11.6 18.7 11.6 13.2 16.1
Thickness of conductor screen (min. avg.) mm. - 0.3 0.3 0.3
Thickness of insulation (min. avg.) mm. 1.1 2 5.5 5.5 3.175
Range of diameter over insulation, approx. mm. 13.7 22.7 23.6 25.1 23.3
Thickness of insulation screen (min. avg.) mm. - - 0.3 0.3 -
Thickness of metallic screen, approx. mm - 0.1 0.1 0.1 -
Thickness of non-metallic sheath mm. 1.5 1.8 1.9 2 3.175
Overall diameter, approx. mm. 17.3 27.3 29.2 30.9 29.9
Max. dc resistance of conductor at 20°C Ω/km 0.193 0.0754 0.193 0.153 0.164
Maximum current rating in free air at 40°C
Laying Space A 391 715 463 537 467
Laying Trefoil A 298 567 406 470 -
Laying Touching A 311 586 416 481 -
Maximum current rating in ground at 30°C A 318 480 314 358 -
หมายเหตุ : ผลิตตามแบบข้อกําหนดทางวิศวกรรมของการไฟฟ้ านครหลวง
และอ้างอิงความหนาผนังท่อตามมาตรฐาน DIN 8074/8075 ท่อมาตรฐานอืน่ ๆ ผลิตตามสัง่
ID = เส้นผ่านศูนย์กลางภายใน (มม.) OD = เส้นผ่านศูนย์กลางภายนอก (มม.)
PN = ชัน้ แรงดัน (บาร์) T= ความหนา (มม.)

W= นํ้าหนัก (กก./ม.)

 
Revision C

ELECTRICAL ENGINEERING DIVISION


CABLE SIZING AND VOLTAGE DROP CALCULATION

ATTACHMENT II: IEC 60287 SUMMARIZE TABLE


– 30 – 60287-1-1 © IEC:2006

⎛ ⎞
⎜⎜ 1 − R λ1′ ⎟⎟
⎝ Rs ⎠

where λ1′ is obtained from 2.3.1.

2.4.3 Losses in steel pipes

The loss in steel pipes is given by two empirical formulae, one for cables where the cores are
bound in close trefoil formation and the other for cables where the cores are placed in a more
open configuration (cradled) on the bottom of the pipe. Actual cores in service probably
approximate to a configuration somewhere between the two. It is considered that the losses
should be calculated for each configuration and a mean value used:
NOTE These formulae have been empirically obtained in the United States of America and at present apply only
to pipe sizes and steel types used in that country.

⎛ 0,011 5 s − 0,001 485 d d ⎞ −5


λ 2 = ⎜⎜ ⎟⎟ 10 for closely bound triangular configurat ion
⎝ R ⎠

⎛ 0,004 38 s + 0,002 26 d d ⎞ −5
λ 2 = ⎜⎜ ⎟⎟ 10 for the open or cradled formation
⎝ R ⎠
where
s is the axial spacing of adjacent conductors (mm);
d d is the internal diameter of pipe (mm);
R is the a.c. resistance per unit length of the conductor at maximum operating temperature
(Ω/m).

The formulae given apply to a frequency of 60 Hz. For 50 Hz, each formula should be
multiplied by 0,76.

For pipe-type cables, where flat-wire armour is applied over all three cores after they are laid
up, the losses are independent of the presence of the pipe. For such cables, the losses in the
armour are to be calculated as for SL type cables (see 2.4.2.3.2 and the losses in the pipe are
to be ignored).

Table 1 – Electrical resistivities and temperature coefficients


of metals used

Material Resistivity (ρ) Temperature


ohm ⋅ m at 20 °C coefficient (α 20 )
per K at 20 °C

a) Conductors
Copper 1,724 1 10 –8 3,93 10 –3
Aluminium 2,826 4 10 –8 4,03 10 –3

b) Sheaths and armour


Lead or lead alloy 21,4 10 –8 4,0 10 –3
Steel 13,8 10 –8 4,5 10 –3
Bronze 3,5 10 –8 3,0 10 –3
Stainless steel 70 10 –8 Negligible
Aluminium 2,84 10 –8 4,03 10 –3

NOTE Values for copper conductors are taken from IEC 60028.
Value for aluminium conductors are taken from IEC 60889.
60287-1-1 © IEC:2006 – 31 –

Table 2 – Skin and proximity effects –


Experimental values for the coefficients k s and k p

Type of conductor Whether dried and ks kp


impregnated or not
Copper
Round, stranded Yes 1 0,8
Round, stranded No 1 1
Round, segmental a 0,435 0,37
Hollow, helical stranded Yes b 0,8
Sector-shaped Yes 1 0,8
Sector-shaped No 1 1
Aluminium d

Round, stranded Either 1


Round, 4 segment Either 0,28
Round, 5 segment Either 0,19
Round, 6 segment Either 0,12
Segmental with peripheral strands Either c

a The values given apply to conductors having four segments (with or without central duct) and sectional areas
less than 1 600 mm 2 . These values apply to conductors in which all the layers of wire have the same
direction of lay. The values are provisional and the subject is under consideration.
b The following formula should be used for k s :
2
⎛ d ′ − d i ⎞ ⎛ d c′ + 2d i ⎞
k s = ⎜⎜ c ⎟⎜
⎟⎜


⎝ d c′ + d i ⎠ ⎝ d c′ + d i ⎠
where
d i is the inside diameter of the conductor (central duct) (mm);
d c is the outside diameter of the equivalent solid conductor having the same central duct (mm).
c The following formula should be used to calculate k s for cables having a conductor which consists of a
central segmental portion surrounded by one or more layers of strands.

{
k s = 12c [(αc − 0,5)
2
] (
+ (αc − 0,5 )(ψ − α )c + 0,33(ψ − α )2 c 2 + b 3 − 6b + 4b 2 )} 0,5

where
b is the ratio of the total cross-sectional area of the peripheral strands to the total cross-sectional area of the
complete conductor;
c is the ratio of the total cross-sectional area of the segmental conductor to the total cross-sectional area of
the complete conductor, c = (1 −b ).
1
α=
(1 + sin π / n )2
2π / n + 2 / 3
ψ=
2(1 + π / n )
where
n is the number of segments.
This formula is applicable to aluminium conductors up to 1 600 mm 2 .
If the total cross-sectional area of the peripheral strands exceeds 30 % of the total cross-sectional area of
the conductor, then k s may be regarded as unity.
d Although there are no accepted experimental results dealing specifically with the coefficient k p for
aluminium conductors, it is recommended that, for stranded aluminium conductors, the values given for
similar copper conductors are used.
– 32 – 60287-1-1 © IEC:2006

Table 3 – Values of relative permittivity and loss factors for the insulation of high-
voltage and medium-voltage cables at power frequency

1 2 3

Type of cable ε tan δ*

Cables insulated with impregnated paper


Solid type, fully-impregnated, pre-impregnated or mass-impregnated non-draining 4 0,01
Oil-filled, self-contained a up to Uo = 36 kV 3,6 0,003 5
up to Uo = 87 kV 3,6 0,003 3
up to Uo = 160 kV 3,5 0,003 0
up to Uo = 220 kV 3,5 0,002 8

Oil-pressure, pipe-type b 3,7 0,004 5


External gas-pressure c 3,6 0,004 0
Internal gas-pressure d 3,4 0,004 5

Cable with other kinds of insulation


Butyl rubber 4 0,050

EPR e
up to and including 18/30 (36) kV cables 3 0,020
greater than 18/30 (36) kV cables 3 0,005

PVC e 8 0,1

PE (HD and LD) e 2,3 0,001

XLPE e
up to and including 18/30 (36) kV cables (unfilled) 2,5 0,004
greater than 18/30 (36) kV cables (unfilled) 2,5 0,001
greater than 18/30 (36) kV cables (filled) 3,0 0,005

PPL
equal to, or greater than 63/110 kV cables 2,8 0,001 4

* Safe values at maximum permissible temperature, applicable to the highest voltages normally specified for
each type of cable.
a See IEC 60141-1.
b See IEC 60141-4.
c See IEC 60141-3.
d See IEC 60141-2.
e See IEC 60502-1 and IEC 60502-2.
NOTE The dielectric loss should be taken into account for values of U o equal to or greater than the following:

Uo
Type of cable
kV

Cables insulated with impregnated paper


Solid-type 38
Oil-filled and gas-pressure 63,5
Cables with other types of insulation
Butyl rubber 18
EPR 63,5
PVC 6
PE (HD and LD) 127
XLPE (unfilled) 127
XLPE (filled) 63,5
60287-1-1 © IEC:2006 – 33 –

Table 4 – Absorption coefficient of solar radiation


for cable surfaces

Material σ

Bitumen/jute serving 0,8


Polychloroprene 0,8
PVC 0,6
PE 0,4
Lead 0,6

___________
60287-2-1 © IEC: 1994+A1:2001 – 55 –
+A2:2006

Table 1 – Thermal resistivities of materials

Material Thermal resistivity (ρ T )

Km/W

Insulating materials*
Paper insulation in solid type cables 6,0
Paper insulation in oil-filled cables 5,0
Paper insulation in cables with external gas pressure 5,5
Paper insulation in cables with internal gas pressure:
a) pre-impregnated 5,5
b) mass-impregnated 6,0
PE 3,5
XLPE 3,5
PPL 5,5
Polyvinyl chloride:
up to and including 3 kV cables 5,0
greater than 3 kV cables 6,0
EPR:
up to and including 3 kV cables 3,5
greater than 3 kV cables 5,0
Butyl rubber 5,0
Rubber 5,0

Protective coverings
Compounded jute and fibrous materials 6,0
Rubber sandwich protection 6,0
Polychloroprene 5,5
PVC:
up to and including 35 kV cables 5,0
greater than 35 kV cables 6,0
PVC/bitumen on corrugated aluminium sheaths 6,0
PE 3,5
Materials for duct installations
Concrete 1,0
Fibre 4,8
Asbestos 2,0
Earthenware 1,2
PVC 6,0
PE 3,5
* For the purposes of current rating calculations, the semiconducting screening materials
are assumed to have the same thermal properties as the adjacent dielectric materials.
Where plastic or elastomeric materials are used for protective coverings, the thermal
resistivities shall be taken to be the same as those for the insulating grades of the
materials given in this table.
– 56 – 60287-2-1 © CEI: 1994+A1:2001
+A2:2006

Tableau 2 – Valeurs des constantes Z , E et g pour les surfaces noires


des câbles à l'air libre

2 a) – Installation sur des consoles non continues, supports ou brides, De* inférieur à 0,15 m

N° Installation Z E d Mode

1 Un seul câble 1) 0,21 3,94 0,60

2 Deux câbles jointifs horizontaux 0,29 2,35 0,50

3 Trois câbles posés en trèfle 0,96 1,25 0,20

4 Trois câbles jointifs horizontaux 0,62 1.95 0,25

5 Deux câbles jointifs, verticaux 1,42 0,86 0,25

6 Deux câbles espacés de D e* , verticaux 0,75 2,80 0,30

7 Trois câbles jointifs, verticaux 1,61 0,42 0,20

8 Trois câbles espacés de D e* , verticaux 1,31 2,00 0,20

1) Les valeurs données pour «un seul câble» s'appliquent aussi à tous les câbles d'un groupe lorsqu'ils sont
séparés horizontalement par un intervalle d'au moins 0,75 voir le diamètre extérieur du câble.

2 b) – Attachés directement à une paroi verticale ( De* inférieur à 0,08 m)

9 Un seul câble 1,69 0,63 0,25

10 Trois câbles posés en trèfle 0,94 0,79 0,20


60287-2-1 © IEC: 1994+A1:2001 – 57 –
+A2:2006

Table 2 – Values for constants Z , E and g for black surfaces


of cables in free air

2 a) – Installation on non-continuous brackets, ladder supports or cleats, De* not greater


than 0,15 m
g
No. Installation Z E d Mode

1 Single cable 1) 0,21 3,94 0,60

2 Two cables touching, horizontal 0,29 2,35 0,50

3 Three cables in trefoil 0,96 1,25 0,20

4 Three cables touching, horizontal 0,62 1.95 0,25

5 Two cables touching, vertical 1,42 0,86 0,25

6 Two cables spaced, D e* vertical 0,75 2,80 0,30

7 Three cables touching, vertical 1,61 0,42 0,20

8 Three cables spaced, D e* vertical 1,31 2,00 0,20

1) Values for a "single cable" also apply to each cable of a group when they are spaced horizontally with a
clearance between cables of at least 0,75 times the cable overall diameter.

2 b) – Clipped direct to a vertical wall ( De* not greater than 0,08 m)

9 Single cable 1,69 0,63 0,25

10 Three cables in trefoil 0,94 0,79 0,20


– 58 – 60287-2-1 © CEI: 1994+A1:2001
+A2:2006

Tableau 3 – Coefficient d'absorption des rayons solaires pour les surfaces


de câble suivantes

Matériaux σ

Bitume/jute 0,8
Polychloroprène 0,8
PVC 0,6
PE 0,4
Plomb 0,6

Tableau 4 – Valeurs des constantes U, V et Y

Conditions d'installation U V Y
En conduit métallique 5,2 1,4 0,011
En fourreau de fibre dans l'air 5,2 0,83 0,006
En fourreau de fibre dans le béton 5,2 0,91 0,010
En fourreau d'amiante-ciment:
dans l'air 5,2 1,2 0,006
dans le béton 5,2 1,1 0,011
Câble à gaz en tuyau 0,95 0,46 0,0021
Câble à huile en tuyau 0,26 0,0 0,0026
Fourreaux en matière plastique 1,87 0,312 0,0037
Fourreaux en terre cuite 1,87 0,28 0,0036
60287-2-1 © IEC: 1994+A1:2001 – 59 –
+A2:2006

Table 3 – Absorption coefficient of solar radiation


for cable surfaces

Material σ

Bitumen/jute serving 0,8


Polychloroprene 0,8
PVC 0,6
PE 0,4
Lead 0,6

Table 4 – Values of constants U, V and Y

Installation condition U V Y
In metallic conduit 5,2 1,4 0,011
In fibre duct in air 5,2 0,83 0,006
In fibre duct in concrete 5,2 0,91 0,010
In asbestos cement:
duct in air 5,2 1,2 0,006
duct in concrete 5,2 1,1 0,011
Gas pressure cable in pipe 0,95 0,46 0,0021
Oil pressure pipe-type cable 0,26 0,0 0,0026
Plastic ducts 1,87 0,312 0,0037
Earthenware ducts 1,87 0,28 0,0036