GT Seal oil system startup

Title
OPS-SOP-0011- 00 Oct 2019 1 of 5 OPS/TNB REMACO
WI-0002 Balloki1223MW
Document no. Revision Date of Page Issuing Department
Issuance

APPROVAL

Name Designation Signature

Prepared by: Muhammad Salim Shift Charge Engineer

Mohammad Abu
Reviewed by: Head (Operations)
Huzaifah Magbool

Approved by: Wong Kok Kiong Plant General Manager

AMMENDMENTS

Amendments (if any):


Revision Revision Page Revision Issuance Issue Effective
Designation
No. By Amended Date No. Date Date

Issue: 00 Next Review Date: Oct 2020


GT Seal oil system startup
Title
OPS-SOP-0011- 00 Oct 2019 2 of 5 OPS/TNB REMACO
WI-0002 Balloki1223MW
Document no. Revision Date of Page Issuing Department
Issuance

JOB GT seal oil system startup while generator has been purged with air and gas
turbine is standstill
STATE OF PLANT 1. Gas turbine is stand still
2. Gas turbine generator is purged with air
3. Gas turbine lube oil system is OFF
4. Gas turbine seal oil system “group control” is OFF

Conditions  Need to start seal oil system.


Required to  Need to fill H2 gas inside the generator
start the GT seal  In case of Low seal oil DP
oil system  In case of gas turbine cool down is OFF

Pre requisite  Lube Oil tank level is Normal.


 Both AC and DC seal oil pumps are available.
 Both AC and DC lube oil pumps are available.
 Gas turbine should be standstill and turning gear motor breaker
must put OFF.
 PEECC Electric supplies are energized.
 Both AC and DC seal oil and lube oil pump breaker are normal and
on remote position.
 PEECC DC and UPS system is normal in operation.
 Lube oil heat exchanger is lineup.
 Lube oil filter is lineup.
 CCCW system is in service.
 Lube oil tank temperature should be more than lower temperature
to start seal oil pump 10C.
 All system related isolation valves are in correct position.

References  P & ID GT lube oil system


 P & ID GT seal oil system
 GT Manual (RTM)
 Practices observed by HEI

Issue: 00 Next Review Date: Oct 2020


GT Seal oil system startup
Title
OPS-SOP-0011- 00 Oct 2019 3 of 5 OPS/TNB REMACO
WI-0002 Balloki1223MW
Document no. Revision Date of Page Issuing Department
Issuance

Startup of GT seal oil system while Gas turbine is on standstill position.

Action Verification / Remarks

1. Do the setting of analyzer of


Valves lineup must be for air filling
generator and other valve lineup

2. Open the air filling isolation and fill Make sure the air flow and ask CCR keep
instrument air into the generator observing the generator pressure

Lube oil tank level can be verified from


3. Check lube oil tank level is normal
CCR and local tank gauge

4. Fill air inside generator at pressure Pressure can be verified by ccr and local
more than 7 psi gauge
5. Make sure seal oil “GROUP
CONTROL” is now permitted to start Verify from CCR
the seal oil

6. Turn “ON” the gas turbine seal oil Make sure seal oil pumps are started
group control from field as well

7. Auxiliary AC seal oil pump will start


and also emergency seal oil pump Emergency pump will stop master reset
will start

8. Lube oil tank mist eliminator fan will Adjust the lube oil tank negative
start pressure s per requirement

9. Lube oil tank cooling fan 88BL1/2


Can be verified from local
will start

10. Gas turbine generator seal oil DP is


Gas turbine generator seal oil all
around 0.5bar and TE&CE side drain
parameters can be verified from the
enlargement tank level is around
CCR
145mm of both

Issue: 00 Next Review Date: Oct 2020


GT Seal oil system startup
Title
OPS-SOP-0011- 00 Oct 2019 4 of 5 OPS/TNB REMACO
WI-0002 Balloki1223MW
Document no. Revision Date of Page Issuing Department
Issuance

11. Make sure seal oil flow and position


Can be verified from CCR
of the DP control valve is normal

Gas turbine Seal oil system HMI :-

GT seal oil system group control:-