PROJECT NAME : ASAHIMAS WAREHOUSE PROJECT

PANEL NAME : MDP-WH TR


FEEDER CCT. MCCB CAPACITY (K
CONNECTION LOAD
NO NO. TYPE POLE AF AT R S

MAIN CIRCUIT BREAKER MM MCCB 3 500 500

F1-1 LP-SP MCCB 3 125 100


F1-2 LP-CH MCCB 3 50 50
F1-3 LP-BAG MCCB 3 25 25
F1-4 MP-WH MCCB 3 250 250

PRODUCTION 380-220V
PRODUCTION 200V
SUB TOTAL PRODUCTION 100V
MOTOR
LIGHING and SO

INITIAL : 241.76725 DEMAND FACTOR : 0.85


MAX DF. : 205.5021625 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PROJECT NAME : ASAHIMAS WAREHOUSE PROJECT
PROJECT NAME : ASAHIMAS WORKSHOP PROJECT
PANEL NAME : MDP-WS TR
FEEDER CCT. MCCB CAPACITY (K
CONNECTION LOAD
NO NO. TYPE POLE AF AT R S

MAIN CIRCUIT BREAKER MM MCCB 3 630 630

F1-1 LP-MW MCCB 3 125 100


F1-2 LP-O-1 MCCB 3 50 30
F1-3 LP-O-2 MCCB 3 125 125
F1-4 MP-O-1 MCCB 3 150 150
F1-5 MP-O-2 MCCB 3 400 400
F1-6 MP-MW MCCB 3 50 30

PRODUCTION 380-220V
PRODUCTION 200V
SUB TOTAL PRODUCTION 100V
MOTOR
LIGHING and SO

INITIAL : 359.24725 DEMAND FACTOR : 0.85


MAX DF. : 305.3601625 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
ORIGINAL
400-231V
CAPACITY (KW)
SIZE OF CABEL REMARK
T 3PHASE

37.76575 NYY 4C-35, E16


37.77 NYY 4C-16, E16
37.77 NYY 4C-6, E6
128.47 NYY 4C-95, E50

( 0.00 )kVA Df= 0.60


( )kVA Df=
( )kVA Df=
( )kVA Df=
241.77 ( 241.77 )kVA Df= 0.85
( )kVA Df=
TOTAL LOAD ( 241.77 )kVA
ORIGINAL
ORIGINAL
400-231V
CAPACITY (KW)
SIZE OF CABEL REMARK
T 3PHASE

37.76575 NYY 4C-35, E16


37.77 NYY 4C-6, E6
37.77 NYY 4C-50, E25
66.68 NYY 4C-50, E25
172.26 NYY 4C-185, E95
7.01 NYY 4C-6, E6

( 0.00 )kVA Df= 0.60


( )kVA Df=
( )kVA Df=
( )kVA Df=
359.25 ( 359.25 )kVA Df= 0.85
( )kVA Df=
TOTAL LOAD ( 359.25 )kVA
PROJECT NAME : ASAHIMAS WAREHOUSE PROJECT
PANEL NAME : LP-SP MCCB AT 100 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-WH MAIN CIRCUIT BREAKER MCCB 3P 125 100

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.65
L2 LIGHITNG -2 MCB 2P 16 0.72
L3 LIGHITNG -3 MCB 2P 16 0.86
L4 LIGHITNG -4 MCB 2P 16 0.43
L5 LIGHITNG -5 MCB 2P 16 0.81
L6 LIGHITNG -6 MCB 2P 16 0.81
L7 LIGHITNG -7 MCB 2P 16 0.41
L8 LIGHITNG -8 MCB 2P 16 0.54
L9 SPARE MCB 2P 16 0.00
L10 SPARE MCB 2P 16 0.00
L11 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.20
R2 SOCKET OUTLET MCB 2P 16 1.20
R3 SOCKET OUTLET MCB 2P 16 1.50
R4 SOCKET OUTLET MCB 2P 16 1.20
R5 SOCKET OUTLET MCB 2P 16 1.50
R6 SOCKET OUTLET MCB 2P 16 1.20
R7 SPARE MCB 2P 16 0.00
R8 SPARE MCB 2P 16 0.00
R9 SPARE MCB 2P 16 0.00
P1 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P2 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P3 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P4 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET 19.72
OTHER
SPARE
INITIAL : 37.76575 DEMAND FACTOR :
MAX DF. : 17.813175 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : LP-CH MCCB AT 50 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD CONTROL BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-WH MAIN CIRCUIT BREAKER MCCB 3P 50 50

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.54
L2 LIGHITNG -2 MCB 2P 16 0.54
L3 LIGHITNG -3 MCB 2P 16 0.54
L4 LIGHITNG -4 MCB 2P 16 0.54
L5 LIGHITNG -5 MCB 2P 16 0.54
PC = Photo Cell L6 OUTDOOR LIGHTING PC+TIMER MCB 2P 16 0.27
L7 SPARE MCB 2P 16 0.00
L8 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.20
R2 SPARE MCB 2P 16 0.00
R3 SPARE MCB 2P 16 0.00
P1 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P2 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P3 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93
P4 SOCKET OUTLET 3P MCCB 3P 20 3.94 4.93

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET 19.72
OTHER
SPARE
INITIAL : 25.147 DEMAND FACTOR :
MAX DF. : 11.6613 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : LP-BAG MCCB AT 25 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD CONTROL BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-WH MAIN CIRCUIT BREAKER MCCB 3P 25 25

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.81
L2 LIGHITNG -2 MCB 2P 16 0.54
PC = Photo Cell L3 OUTDOOR LIGHT PC+TIMER MCB 2P 16 0.23
L4 SPARE MCB 2P 16 0.00
L5 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.20
R2 SPARE MCB 2P 16 0.00
R3 SPARE MCB 2P 16 0.00

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET
OTHER
SPARE
INITIAL : 4.025 DEMAND FACTOR :
MAX DF. : 2.5125 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : LP-REST MCCB AT 25 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MAIN CIRCUIT BREAKER MCCB 3P 25 25

E1 EMERGENCY LIGHT MCB 2P 10 0.12


L1 LIGHITNG -1 MCB 2P 16 0.00
L2 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.20
R2 SOCKET OUTLET MCB 2P 16 1.20
R3 SPARE MCB 2P 16 0.00

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET
OTHER
SPARE
INITIAL : 3.55 DEMAND FACTOR :
MAX DF. : 1.335 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PROJECT NAME : ASAHIMAS WORKSHOP PROJECT
PANEL NAME : LP-MW MCCB AT 100 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD CONTROL BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-MW MAIN CIRCUIT BREAKER MCCB 3P 125 100

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.99
L2 LIGHITNG -2 MCB 2P 16 0.65
L3 LIGHITNG -3 MCB 2P 16 0.58
L4 LIGHITNG -4 MCB 2P 16 1.01
L5 LIGHITNG -5 MCB 2P 16 1.15
L6 LIGHITNG -6 MCB 2P 16 1.01
L7 LIGHITNG -7 MCB 2P 16 0.65
L8 LIGHITNG -8 MCB 2P 16 1.15
L9 LIGHITNG -9 MCB 2P 16 0.68
L10 LIGHITNG -10 MCB 2P 16 0.54
L11 LIGHITNG -11 MCB 2P 16 0.54
L12 LIGHITNG -12 MCB 2P 16 0.81
L13 LIGHITNG -13 MCB 2P 16 0.41
L14 LIGHITNG -14 MCB 2P 16 0.81
PC = Photo Cell L15 OUTDOOR LIGHTING PC+TIMER MCB 2P 16 0.36
L16 OUTDOOR LIGHTING PC+TIMER MCB 2P 16 0.36
L17 SPARE MCB 2P 16 0.00
L18 SPARE MCB 2P 16 0.00
L19 SPARE MCB 2P 16 0.00
L20 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.20
R2 SOCKET OUTLET MCB 2P 16 1.20
R3 SOCKET OUTLET MCB 2P 16 1.50
R4 SOCKET OUTLET MCB 2P 16 1.20
R5 SOCKET OUTLET MCB 2P 16 1.20
R6 SOCKET OUTLET MCB 2P 16 1.20
R7 SPARE MCB 2P 16 0.00
R8 SPARE MCB 2P 16 0.00
R9 SPARE MCB 2P 16 0.00
P1 ROLLING DOOR MCCB 3P 20 2.20 3.14
P2 ROLLING DOOR MCCB 3P 20 2.20 3.14
P3 ROLLING DOOR MCCB 3P 20 2.20 3.14
P4 ROLLING DOOR MCCB 3P 20 2.20 3.14
P5 ROLLING DOOR MCCB 3P 20 2.20 3.14
P6 ROLLING DOOR MCCB 3P 20 2.20 3.14
P7 ROLLING DOOR MCCB 3P 20 2.20 3.14

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET 21.98
OTHER
SPARE
INITIAL : 44.77625 DEMAND FACTOR :
MAX DF. : 22.731125 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : LP-O-1 MCCB AT 30 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-MW MAIN CIRCUIT BREAKER MCCB 3P 50 30

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.73
L2 LIGHITNG -2 MCB 2P 16 0.77
L3 SPARE MCB 2P 16 0.00
L4 SPARE MCB 2P 16 0.00
L5 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.50
R2 SOCKET OUTLET MCB 2P 16 1.80
R3 SOCKET OUTLET MCB 2P 16 1.20
R4 SPARE MCB 2P 16 1.50
R5 SPARE MCB 2P 16 0.00
R6 SPARE MCB 2P 16 0.00

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET
OTHER
SPARE
INITIAL : 10.43 DEMAND FACTOR :
MAX DF. : 4.827 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : LP-O-2 MCCB AT 125 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD CONTROL BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

MDP-MW MAIN CIRCUIT BREAKER MCCB 3P 125 125

E1 EMERGENCY LIGHT MCB 2P 16 0.12


L1 LIGHITNG -1 MCB 2P 16 0.84
L2 LIGHITNG -2 MCB 2P 16 0.72
L3 LIGHITNG -3 MCB 2P 16 0.65
L4 LIGHITNG -4 MCB 2P 16 0.76
L5 LIGHITNG -5 MCB 2P 16 0.24
L6 LIGHITNG -6 MCB 2P 16 0.99
L7 SPARE MCB 2P 16 0.00
L8 SPARE MCB 2P 16 0.00
R1 SOCKET OUTLET MCB 2P 16 1.80
R2 SOCKET OUTLET MCB 2P 16 1.80
R3 SOCKET OUTLET MCB 2P 16 1.20
R4 SOCKET OUTLET MCB 2P 16 1.20
R5 SOCKET OUTLET MCB 2P 16 1.20
R6 SOCKET OUTLET MCB 2P 16 0.90
R7 SOCKET OUTLET MCB 2P 16 1.20
R8 SOCKET OUTLET MCB 2P 16 1.50
R9 SOCKET OUTLET MCB 2P 16 1.50
R10 SOCKET OUTLET MCB 2P 16 1.50
R11 SOCKET OUTLET MCB 2P 16 1.50
R12 SOCKET OUTLET MCB 2P 16 1.50
R13 SOCKET OUTLET MCB 2P 16 1.50
R14 SOCKET OUTLET MCB 2P 16 1.50
R15 SOCKET OUTLET MCB 2P 16 1.50
R16 SOCKET OUTLET MCB 2P 16 1.50
R17 SOCKET OUTLET MCB 2P 16 1.50
R18 SOCKET OUTLET MCB 2P 16 1.50
R19 SOCKET OUTLET MCB 2P 16 1.50
R20 SOCKET OUTLET MCB 2P 16 1.50
R21 SOCKET OUTLET MCB 2P 16 1.20
R22 SOCKET OUTLET MCB 2P 16 1.20
R23 SOCKET OUTLET MCB 2P 16 1.20
R24 SOCKET OUTLET MCB 2P 16 1.20
R25 SOCKET OUTLET MCB 2P 16 1.20
R26 SOCKET OUTLET MCB 2P 16 1.50
R27 SOCKET OUTLET MCB 2P 16 0.90
R28 SOCKET OUTLET MCB 2P 16 1.50
R29 SOCKET OUTLET MCB 2P 16 1.50
R30 SOCKET OUTLET MCB 2P 16 1.50
R31 SOCKET OUTLET MCB 2P 16 1.50
R32 SOCKET OUTLET MCB 2P 16 1.20
R33 SPARE MCB 2P 16 0.00
R34 SPARE MCB 2P 16 0.00
R35 SPARE MCB 2P 16 0.00
R36 SPARE MCB 2P 16 0.00

FAN,PUMP
A/C
SUB TOTAL LIGHITNG
SOCKET OUTLET
OTHER
SPARE
INITIAL : 65.5575 DEMAND FACTOR :
MAX DF. : 25.94175 VOLTAGE SYSTEM :
MAIN NFB : MAIN CABLE :
PANEL NAME : MCCB BOX FOR ROLLING DOOR (x7) MCCB AT 20 TOTAL CAP
FEEDER CCT. BRANCH
CONNECTION LOAD BREAKER 3Phase
NO NO. TYPE POLE AF AT KW kVA KW

LP-MW MAIN CIRCUIT BREAKER MCCB 3P 20 20


37.77 Cable NYY 4C-35, E16
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-35, E16

0.15 NYM3C-2.5
0.82 NYM3C-2.5
0.90 NYM3C-2.5
1.08 NYM3C-2.5
0.54 NYM3C-2.5
1.01 NYM3C-2.5
1.01 NYM3C-2.5
0.51 NYM3C-2.5
0.68 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
1.50 NYM3C-2.5
1.50 NYM3C-2.5
1.88 NYM3C-2.5
1.50 NYM3C-2.5
1.88 NYM3C-2.5
1.50 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
2.24 1.86 2.59 ( 6.69 )kVA Df= 0.90
3.00 3.38 3.38 ( 29.47 )kVA Df= 0.40
( )kVA Df= 0.60
0.50 0.50 0.60 ( 1.60 )kVA Df=
0.47 TOTAL LOAD ( 37.77 )kVA
Rate Current 57.45 A
37.77 Cable NYY 4C-16, E16
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-16, E16

0.15 NYM3C-2.5
0.68 NYM3C-2.5
0.68 NYM3C-2.5
0.68 NYM3C-2.5
0.68 NYM3C-2.5
0.68 NYM3C-2.5
0.34 NYM3C-2.5
0.00
0.00
1.50 NYM3C-2.5
0.00
0.00

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
0.83 1.35 1.35 ( 3.53 )kVA Df= 0.90
1.50 0.00 0.00 ( 21.22 )kVA Df= 0.40
( )kVA Df= 0.60
0.20 0.10 0.10 ( 0.40 )kVA Df=
0.46 TOTAL LOAD ( 25.15 )kVA
Rate Current 38.25 A
37.77 Cable NYY 4C-6, E6
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-6, E6

0.15 NYM3C-2.5
1.01 NYM3C-2.5
0.68 NYM3C-2.5
0.29 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
1.50 NYM3C-2.5
0.00
0.00

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
0.44 1.01 0.68 ( 2.13 )kVA Df= 0.90
1.50 0.00 0.00 ( 1.50 )kVA Df= 0.40
( )kVA Df= 0.60
0.20 0.10 0.10 ( 0.40 )kVA Df=
0.62 TOTAL LOAD ( 4.03 )kVA
Rate Current 6.12 A
37.77 Cable NYY 4C-6, E6
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-6, E6

0.15 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
1.50 NYM3C-2.5
1.50 NYM3C-2.5
0.00

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
0.15 0.00 0.00 ( 0.15 )kVA Df= 0.90
1.50 1.50 0.00 ( 3.00 )kVA Df= 0.40
( )kVA Df= 0.60
0.20 0.20 0.00 ( 0.40 )kVA Df=
0.38 TOTAL LOAD ( 3.55 )kVA
Rate Current 5.40 A
37.77 Cable NYY 4C-35, E16
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-35, E16

0.15 NYM3C-2.5
1.24 NYM3C-2.5
0.81 NYM3C-2.5
0.72 NYM3C-2.5
1.26 NYM3C-2.5
1.44 NYM3C-2.5
1.26 NYM3C-2.5
0.81 NYM3C-2.5
1.44 NYM3C-2.5
0.84 NYM3C-2.5
0.68 NYM3C-2.5
0.68 NYM3C-2.5
1.01 NYM3C-2.5
0.51 NYM3C-2.5
1.01 NYM3C-2.5
0.45 NYM3C-2.5
0.45 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
1.50 NYM3C-2.5
1.50 NYM3C-2.5
1.88 NYM3C-2.5
1.50 NYM3C-2.5
1.50 NYM3C-2.5
1.50 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5
NYM3C-2.5

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
2.97 3.98 4.37 ( 11.32 )kVA Df= 0.90
3.00 3.00 3.38 ( 31.36 )kVA Df= 0.40
( )kVA Df= 0.60
0.60 0.70 0.80 ( 2.10 )kVA Df=
0.51 TOTAL LOAD ( 44.78 )kVA
Rate Current 68.11 A
37.77 Cable NYY 4C-6, E6
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-6, E6

0.15 NYM3C-2.5
0.91 NYM3C-2.5
0.97 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
0.00 NYM3C-2.5
1.88 NYM3C-2.5
2.25 NYM3C-2.5
1.50 NYM3C-2.5
1.88 NYM3C-2.5
0.00
0.00

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
0.15 0.91 0.97 ( 2.03 )kVA Df= 0.90
3.75 2.25 1.50 ( 7.50 )kVA Df= 0.40
( )kVA Df= 0.60
0.40 0.30 0.20 ( 0.90 )kVA Df=
0.46 TOTAL LOAD ( 10.43 )kVA
Rate Current 15.87 A
37.77 Cable NYY 4C-50, E25
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYY 4C-50, E25

0.15 NYM3C-2.5
1.05 NYM3C-2.5
0.90 NYM3C-2.5
0.81 NYM3C-2.5
0.95 NYM3C-2.5
0.31 NYM3C-2.5
1.24 NYM3C-2.5
0.00
0.00
2.25 NYM3C-2.5
2.25
1.50
1.50 NYM3C-2.5
1.50
1.13
1.50 NYM3C-2.5
1.88
1.88
1.88 NYM3C-2.5
1.88
1.88
1.88 NYM3C-2.5
1.88
1.88
1.88 NYM3C-2.5
1.88
1.88
1.88 NYM3C-2.5
1.88
1.50
1.50 NYM3C-2.5
1.50
1.50
1.50 NYM3C-2.5
1.88
1.13
1.88 NYM3C-2.5
1.88
1.88
1.88 NYM3C-2.5
1.50
0.00
0.00 NYM3C-2.5
0.00
0.00

( 0.00 )kVA Df= 1.00


( 0.00 )kVA Df= 0.80
0.96 1.99 1.21 ( 4.16 )kVA Df= 0.90
19.50 19.88 16.13 ( 55.50 )kVA Df= 0.40
( )kVA Df= 0.60
2.00 2.20 1.70 ( 5.90 )kVA Df=
0.40 TOTAL LOAD ( 65.56 )kVA
Rate Current 99.72 A
37.77 Cable NYM 3C-2.5
CAPACITY
1Phase (kVA) SIZE OF CABEL REMARK
R S T

NYM 3C-2.5
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓

MP-WH F-102 Main Breaker MCCB 3P+N 380 250 250 115.60 128.47

P1 AC-W-1-1 OUTDOOR UNIT AC AC MCB 3P 380 15 2.60 2.89 -

P2 AC-W-1-2 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89 -

P3 AC-W-1-2 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89 -

P4 AC-W-1-3 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78 -

P5 AC-W-1-3 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78 -

P6 AC-W-1-3 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78 -

P7 AC-W-1-4 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78

P8 AC-W-1-4 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78

P9 AC-W-1-4 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78

P10 AC-W-1-5 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89

P11 AC-W-1-5 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89

P12 AC-W-1-6 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89

P13 AC-W-1-6 OUTDOOR UNIT AC AC MCB 3P 380 30 7.10 7.89

P14 AC-W-2-1 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78

P15 AC-W-2-1 OUTDOOR UNIT AC AC MCB 3P 380 30 8.80 9.78

P16 SPARE MCB 3P 380 30 -

P17 SPARE MCB 3P 380 15 -

- -

Total 115.60 128.47

I= 195.19 [ A ]
PF = 90%
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓
DF = 80%

I (DF) = 156.15 [ A ]
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓

MP-O-1 F-102 Main Breaker MCCB 3P+N 380 150 150 60.00 66.68

P1 AC-WO-1-1 OUTDOOR AC UNIT AC MCB 3P 380 20 5.30 5.89 -

P2 AC-WO-1-1 OUTDOOR AC UNIT AC MCB 3P 380 20 5.30 5.89 -

P3 AC-WO-1-2 OUTDOOR AC UNIT AC MCB 3P 380 30 8.80 9.78 -

P4 AC-WO-1-2 OUTDOOR AC UNIT AC MCB 3P 380 30 8.80 9.78

P5 AC-WO-1-3 OUTDOOR AC UNIT AC MCB 3P 380 30 8.80 9.78

P6 AC-WO-1-4 OUTDOOR AC UNIT AC MCB 3P 380 30 8.80 9.78

P7 AC-WO-1-5 OUTDOOR AC UNIT AC MCB 3P 380 30 7.10 7.89

P8 AC-WO-1-5 OUTDOOR AC UNIT AC MCB 3P 380 30 7.10 7.89

P9 SPARE MCB 3P 380 20 -

P10 SPARE MCB 3P 380 30 -

- -

Total 60.00 66.68

I= 101.31 [ A ]

PF = 90%

DF = 80%

I (DF) = 81.05 [ A ]
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓

MP-O-2 F-102 Main Breaker MCCB 3P+N 380 400 400 155.00 172.26

P1 AC-WO-2-1 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78 -

P2 AC-WO-2-2 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78 -

P3 AC-WO-2-2 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78 -

P4 AC-WO-2-2 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P5 AC-WO-2-3 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P6 AC-WO-2-4 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78 -

P7 AC-WO-2-4 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78 -

P8 AC-WO-2-4 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P9 AC-WO-2-5 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P10 AC-WO-2-5 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P11 AC-WO-2-5 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P12 AC-WO-2-6 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P13 AC-WO-2-6 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P14 AC-WO-2-7 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P15 AC-WO-2-7 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P16 AC-WO-2-7 OUTDOOR UNI T AC AC MCB 3P 380 30 8.80 9.78

P17 AC-WO-2-8 OUTDOOR UNI T AC AC MCB 3P 380 30 7.10 7.89

P18 AC-WO-2-8 OUTDOOR UNI T AC AC MCB 3P 380 30 7.10 7.89

P19 SPARE MCB 3P 380 30 -

P20 SPARE MCB 3P 380 30 -


- -
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓
Total 155.00 172.26

I= 261.72 [ A ]

PF = 90%

DF = 80%

I (DF) = 209.38 [ A ]
Load Name

Branch Breaker Capacity Control System


Panel Feeder Connection Circuit Equipment Starter COS
Name No. No. No. System On/Off Interlock On/Off Fault Am
Type Pole V AF AT [ kW ] [ kVA ] Status -mater
Input Load Type ↓

MP-MW F-102 Main Breaker MCCB 3P+N 380 50 30 4.76 7.01

P1 EF-WO-1-11 INDUSTRIAL FAN M MCB 3P 380 20 4.08 5.67 DOL O O ─ O O O

P2 EF-WO-1-13 INDUSTRIAL FAN M MCB 3P 380 15 0.68 1.34 DOL O O ─ O O O

P3 SPARE M MCB 3P 380 15 - -

P4 SPARE MCB 3P 220 20 -

P5 SPARE MCB 3P 220 30 -

- -

Total 4.76 7.01

I= 10.65 [ A ]

PF = 68%

DF = 80%

I (DF) = 8.52 [ A ]
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type

NYY 4C-150 E95

NYY 4C-2.5 E2.5

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type

NYY 4C-70 E35

NYY 4C-4 E4

NYY 4C-4 E4

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type

NYY 1C-240 x3 E120

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6

NYY 4C-6 E6
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type
Control System Cable Size Piping
Remarks
High Low
Alarm Alarm
Size Neutral Ground Type

NYY 4C-6 E6

NYY 4C-4 E4

NYY 3C-16 E16

NYY 3C-16 E16

NYM 3C-2.5

NYM 3C-2.5