You are on page 1of 18

3.

BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B3TBBL-1 Connected To DDC No.: B3DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Drainage Pump (B3EDP01)

DNP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Pump (B3EDP03)

DNP-05 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-06 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Pump (B3EDP04)

DNP-07 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-08 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Pump (B3EDP05)

DNP-09 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-10 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Pump (B3EDP06)

DNP-11 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-12 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

PD - Page 1
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B3TBBL-1 (Cont.) Connected To DDC No.: B3DDCBL-1 (Cont.)

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Sewage Pump (B3ESWP01)

SWP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SWP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Sump with petrol interceptor sump

Drainage Sump 1 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Drainage Sump 3 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Drainage Sump 4 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Drainage Sump 5 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Drainage Sump 6 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Sewage Sump

Sewage Sump 1 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

PD - Page 2
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B3TBBL-2 Connected To DDC No.: B3DDCBL-2

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Water Supply Pump (B3EWSP01)

WSP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-04 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-05 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-06 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-07 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

WSP-08 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Raw Water Tank

Raw Water Tank 1 Monitor Low level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Raw Water Tank 2 Monitor Low level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Treated Water Tank 1 Monitor Low level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Treated Water Tank 2 Monitor Low level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

PD - Page 3
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B3TBBL-2 (Cont.) Connected To DDC No.: B3DDCBL-2 (Cont.)

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Drainage Pump (B3EDP02)

DNP-03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

DNP-04 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Drainage Sump with petrol interceptor sump

Drainage Sump 2 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

PD - Page 4
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B3TBBL-3 Connected To DDC No.: B3DDCBL-3

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Waste Water Treatment Plant

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

Spare DI 1 Volt - free Relay N/C

PD - Page 5
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B2TBBL-2 Connected To DDC No.: B2DDCBL-2

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Sewage Pump (B2ESWP01)

SWP-07 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SWP-08 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Grease Sump

Grease Sump Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

PD - Page 6
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: B1TBBL-1 Connected To DDC No.: B1DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading
Operation Schedule
Control Point Reset

Fuel Oil High Level


Fuel Oil Low Level

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Fuel Oil Pump (B1FOP01)

FOP01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

FOP02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Fuel Oil Pump (B1FOP02)

FOP03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

FOP04 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Fuel Oil Storage Tank

Generator Fuel Oil Storage tank Monitor Level Indicator AI 1 Level transmitter 4-20 mA. - - Urgent X X X X X X

Boiler Fuel Oil Storage tank Monitor Level Indicator AI 1 Level transmitter 4-20 mA. - - Urgent X X X X X X

Sewage Pump (B1ESWP01)

SWP-03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SWP-04 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Sewage Pump (B1ESWP02)

SWP-05 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SWP-06 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Kitchen Sump

Kitchen Sump No.1 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Kitchen Sump No.2 Monitor Low level DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Cold Water Meter

Fun Pub Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Street Bar Kitchen Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Hot Water Meter

Fun Pub Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Street Bar Kitchen Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

PD - Page 7
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: L4TBBL-1 Connected To DDC No.: L4DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Cold Water Meter

Western Kitchen Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Chinese Kitchen Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Hot Water Meter

Western Kitchen Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Chinese Kitchen Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

PD - Page 8
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: T1TBBL-1 Connected To DDC No.: T1DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Boiler Pump (T1BLP01)

FWP01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

FWP02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

FOP05 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

FOP06 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

BCP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

BCP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot water Boiler

BL-01 Monitor Boiler On/Off Status DI 1 Volt-free Contact N/O Off On - X X X

Control Boiler On/Off Control DO 1 Volt-free Contact N/O Stop Start -

Monitor Auto/Manual Status DI 1 Volt-free Contact N/O Auto Manual - X X X

Monitor Boiler Normal/Fault Status DI 1 Volt-free Contact N/O Normal Fault - X X X

Monitor Flow Rate AI 1 Flow Meter 4-20 mA - - - X X X

Control Control Valve On/Off Control DO 1 Volt-free Contact N/O On Off -

Monitor Control Valve On/Off Status DI 1 Volt-free Contact N/O On Off - X X X

Monitor Hot water supply temperature AI 1 Temperature sensor 4-20 mA - - - X X X

Monitor Hot water return temperature AI 1 Temperature sensor 4-20 mA - - - X X X

BL-02 Monitor Boiler On/Off Status DI 1 Volt-free Contact N/O Off On - X X X

Control Boiler On/Off Control DO 1 Volt-free Contact N/O Stop Start -

Monitor Auto/Manual Status DI 1 Volt-free Contact N/O Auto Manual - X X X

Monitor Boiler Normal/Fault Status DI 1 Volt-free Contact N/O Normal Fault - X X X

Monitor Flow Rate AI 1 Flow Meter 4-20 mA - - - X X X

Control Control Valve On/Off Control DO 1 Volt-free Contact N/O On Off -

Monitor Control Valve On/Off Status DI 1 Volt-free Contact N/O On Off - X X X

Monitor Hot water supply temperature AI 1 Temperature sensor 4-20 mA - - - X X X

Monitor Hot water return temperature AI 1 Temperature sensor 4-20 mA - - - X X X

PD - Page 9
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: T1TBBL-1 (Cont.) Connected To DDC No.: T1DDCBL-1 (Cont.)

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Hot Water Boiler Day Tank
Monitor Low fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Hot Water Pump (T1HWSP01)

HCP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-04 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-05 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot Water Pump (T1HWSP01)

HCP-06 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-07 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-08 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-09 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-10 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot water tank

HWS-02 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

HWS-03 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

HWS-04 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

HWS-05 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

CLT-01 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

Cold Water Meter

Ball Room Kitchen Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/ Totalizer 4-20 mA - - Urgent X X

Hot Water Meter

Ball Room Kitchen Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/ Totalizer 4-20 mA - - Urgent X X

PD - Page 10
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: T2TBBL-1 Connected To DDC No.: T2DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Irrigation Pump (T2IRP01)

IRP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

IRP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Swimming Pool Pump (T2SPP01)

SPP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SPP-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SPP-03 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SC-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

SC-02 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

JCP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Generator Day Tank

Day Tank 1 Monitor Low fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Day Tank 2 Monitor Low fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High fuel level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

PD - Page 11
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: L6TBBL-1 Connected To DDC No.: L6DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Alarm and Status


Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling

Water Billing
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Cold Water Meter

Pool Side Café Kitchen Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Health Club Cold Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Hot Water Meter

Pool Side Café Kitchen Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

Health Club Hot Water Meter Monitor Water Usage Reading AI 1 Transmitter/Totalizer 4-20 mA - - Urgent X X

PD - Page 12
Ref. Code

Hot Water Meter


Cold Water Meter
BMS POINT SCHEDULE

Terminal Box No.: L7TBBL-1

Spa Hot Water Meter


Spa Cold Water Meter
Sub-System Equipment
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

Monitor
Monitor
BMS Function
Connected To DDC No.: L7DDCBL-1

Point/Subject

Water Usage Reading


Water Usage Reading

AI
AI

Point Type
1
1

Point Number

Contact Type
Transmitter/Totalizer
Transmitter/Totalizer

Interface Method
4-20 mA
4-20 mA
Hardware

-
-

Normal Status
-
-

Changes Status

PD - Page 13
Alarm Class
Urgent
Urgent

Alarm Limit

Scale Range

Control Point Reset

Event Initiation

Operation Schedule
X
X

Water Usage Reading

Enthalpy Control

Energy Measurement and Metering

Load cycling

Power Failure Restart

Run Time Totalization

Alarm and Status


Software

Fuel Oil Volume Calculate

Autochangeover Duty and Standby

Drives
X
X

Water Billing

Maintenance Scheduling

Alarm Acknowledgement

Interlock

Maintenance Programme

Diagrammatic Slide or Graphic


3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: 26TBBL-1 Connected To DDC No.: 26DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Volume Calculated
Alarm and Status
Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Hot Water Pump (26HWSP01)

HCP-11 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-12 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-13 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-14 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot water tank

CLT-02 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

PD - Page 14
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: 33TBBL-1 Connected To DDC No.: 33DDCBL-1

Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Volume Calculated
Alarm and Status
Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Hot Water Pump (33HWSP01)

HCP-15 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-16 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-17 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-18 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot water tank

CLT-03 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - - X X X

PD - Page 15
Ref. Code

Hot Water Meter


Cold Water Meter
BMS POINT SCHEDULE

Terminal Box No.: L39TBBL-1


Sub-System Equipment

Sky Lounge Hot Water Meter


Sky Lounge Cold Water Meter
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

Monitor
Monitor
BMS Function
Connected To DDC No.: L39DDCBL-1
Point/Subject

Water Usage Reading


Water Usage Reading

AI
AI

Point Type
1
1

Point Number

Contact Type
Transmitter/Totalizer
Transmitter/Totalizer

Interface Method
4-20 mA
4-20 mA
Hardware

-
-

Normal Status
-
-

Changes Status

PD - Page 16
Alarm Class
Urgent
Urgent

Alarm Limit

Scale Range

Control Point Reset

Event Initiation

Operation Schedule
X
X

Water Usage Reading

Enthalpy Control

Energy Measurement and Metering

Load cycling

Power Failure Restart

Run Time Totalization

Alarm and Status


Software

Fuel Oil Volume Calculate

Autochangeover Duty and Standby

Drives
X
X

Water Billing

Maintenance Scheduling

Alarm Acknowledgement

Interlock

Maintenance Programme

Diagrammatic Slide or Graphic


3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

BMS POINT SCHEDULE

Terminal Box No.: RTBBL-1 Connected To DDC No.: RDDCBL-1


Ref. Code Sub-System Equipment BMS Function Point/Subject Hardware Software

Energy Measurement and Metering

Autochangeover Duty and Standby

Diagrammatic Slide or Graphic


Fuel Oil Volume Calculate

Maintenance Programme
Alarm Acknowledgement
Maintenance Scheduling
Water Usage Reading

Run Time Totalization


Power Failure Restart
Operation Schedule
Control Point Reset

Volume Calculated
Alarm and Status
Interface Method

Enthalpy Control
Changes Status

Event Initiation
Normal Status
Point Number

Contact Type

Scale Range

Load cycling
Alarm Class

Alarm Limit
Point Type

Interlock
Drives
Booster Pump (REWSP01)

BP-01 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Roof tank

Roof Tank 1 Monitor Low water level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High water level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Roof Tank 2 Monitor Low water level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor High water level alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Monitor Overflow alarm DI 1 Volt - free Relay N/O Normal Activated Urgent X X X

Hot Water Pump (RHWSP01)


HCP-19 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-20 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-21 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-22 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot Water Pump (RHWSP02)

HCP-23 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

HCP-24 Monitor Healthy / Power on / Fault DI 1 Volt - free Relay N/C Normal Fault Urgent X X X

Hot water tank

HWS-01 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - Urgent X X X

CLT-04 Monitor Hot Water temperature AI 1 Temperature sensor 4-20 mA - - Urgent X X X

PD - Page 17
Ref. Code

Hot Water Meter


Cold Water Meter
BMS POINT SCHEDULE

Terminal Box No.: L3(ANNEX)TBBL-1


Sub-System Equipment

Gartenstadt Kitchen Hot Water Meter


Gartenstadt Kitchen Cold Water Meter
3. BMS POINT SCHEDULE FOR PLUMBING SYSTEM

Monitor
Monitor
BMS Function
Point/Subject

Water Usage Reading


Water Usage Reading
Connected To DDC No.: L3(ANNEX)DDCBL-1

AI
AI

Point Type
1
1

Point Number

Contact Type
Transmitter/Totalizer
Transmitter/Totalizer

Interface Method
4-20 mA
4-20 mA
Hardware

-
-

Normal Status
-
-

Changes Status

PD - Page 18
Alarm Class
Urgent
Urgent

Alarm Limit

Scale Range

Control Point Reset

Event Initiation

Operation Schedule
X
X

Water Usage Reading

Enthalpy Control

Energy Measurement and Metering

Load cycling

Power Failure Restart

Run Time Totalization

Alarm and Status


Software

Fuel Oil Volume Calculate

Autochangeover Duty and Standby

Drives
X
X

Water Billing

Maintenance Scheduling

Alarm Acknowledgement

Interlock

Maintenance Programme

Diagrammatic Slide or Graphic