GRUNDFOS INSTRUCTIONS

Unilift AP35B, AP50B


Installation and operating instructions

Other languages

http://net.grundfos.com/qr/i/96004693
English (GB) Installation and operating instructions
English (GB)

Original installation and operating instructions 1. Symbols used in this document


CONTENTS Warning
Page If these safety instructions are not
observed, it may result in personal injury.
1. Symbols used in this document 2
2. General description 2
If these safety instructions are not
2.1 Applications 3 Caution observed, it may result in malfunction or
2.2 Storage and operating conditions 3 damage to the equipment.
2.3 Sound pressure level 3
3. Electrical connection 4 Note
Notes or instructions that make the job
3.1 Checking the direction of rotation 4 easier and ensure safe operation.

4. Installation 5
4.1 Pipe connection
2. General description
5
4.2 Pump location 5 Handle
4.3 Installation on auto coupling 6 with clamp
4.4 Free-standing installation 6
4.5 Setting of level switch 6
5. Startup 7
Level
6. Maintenance and service 7 switch
6.1 Oil 7
6.2 Construction 7
6.3 Service kits 7 Outlet
6.4 Contaminated pumps 7
7. Fault finding the product 8
8. Disposal 9

TM03 4189 1806


Warning
Prior to installation, read these installation
and operating instructions. Installation and
operation must comply with local Inlet
regulations and accepted codes of good
practice. Fig. 1 Unilift AP35B, AP50B

Warning
The use of this product requires
experience with and knowledge of the
product.
Persons with reduced physical, sensory or
mental capabilities must not use this
product, unless they are under supervision
or have been instructed in the use of the
product by a person responsible for their
safety.
Children must not use or play with this
product.

2
2.1 Applications 2.2 Storage and operating conditions

English (GB)
The Grundfos Unilift AP pump is are single-stage
submersible pumps designed for the pumping of Storage temperature Down to -30 °C
wastewater. Minimum liquid
0 °C
The pump is capable of pumping water which temperature
contains a limited quantity of solids, however not
Maximum liquid
stones and similar materials, without being blocked 40 °C
temperature
or damaged.
The pump is available for automatic as well as Maximum 7 metres below
Installation depth
manual operation and can be installed in a liquid level
permanent installation (on auto coupling or as a free- pH value 4-10
standing pump) or used as a portable pump.
Density Maximum 1100 kg/m3
The pump is suitable for these applications:
Viscosity Maximum 10 mm2/s
Unilift Unilift Technical data See pump nameplate.
Applications
AP35B AP50B

Groundwater lowering ● ● Always have at least 3 m free cable above


liquid level. This limits installation depth to
Pumping in drainage pits ● ● Caution
7 m for pumps with 10 m cable and to 2 m
Pumping in surface water pits for pumps with 5 m cable.
with inflow from roof gutters, ● ●
shafts, tunnels, etc. Pumps with 3 m cable are for industrial
Caution
Emptying of ponds, tanks, etc. ● ● applications only.

Pumping of fibre-containing 2.3 Sound pressure level


wastewater from laundries ● ●
and industries The sound pressure level of the pump is lower than
the limiting values stated in the EC Council Directive
Pumping of domestic 2006/42/EC relating to machinery.
wastewater from septic tanks ● ●
and sludge treating systems
Pumping of domestic
wastewater without discharge ● ●
from water closets
Pumping of domestic
wastewater with discharge ●
from water closets
Maximum particle size [mm] 35 50

Warning
The pump must not be used in or at
swimming pools, garden ponds, etc. when
there are persons in the water.
Incorrect application of the pump (e.g. resulting in
blocking of the pump) and wear are not covered by
the warranty.

3
3. Electrical connection 3.1 Checking the direction of rotation
English (GB)

Three-phase pumps only


Depending on local regulations, a pump
with 10 metres of mains cable must be Check the direction of rotation every time the pump
Note
used if the pump is used as a portable is connected to a new installation.
pump for different applications. 1. Position the pump so that you can observe the
impeller.
The electrical connection must be carried out in
accordance with local regulations. 2. Start the pump for a short period.
The operating voltage and frequency are marked on 3. Observe the rotation of the impeller. The correct
the pump nameplate. Make sure that the motor is direction of rotation is indicated by an arrow on
suitable for the power supply on which it will be used. the top of the motor (clockwise when seen from
the bottom). If the impeller rotates in the wrong
Warning direction, reverse the direction of rotation by
As a precaution, the pump must be interchanging two of the phases to the motor.
connected to a socket with earth If the pump is connected to a pipe system, check the
connection. The installation must be fitted direction of rotation in this way:
with an earth leakage circuit breaker 1. Start the pump and check the quantity of water or
(ELCB) with a tripping current less then 30 the pressure.
mA. 2. Stop the pump and interchange two of the
The pump must be connected to an phases to the motor.
external mains switch with a minimum 3. Start the pump and check the quantity of water or
contact gap of 3 mm in all poles. If the the pressure.
pump is not installed close to the switch,
the switch must be of a lockable type. 4. Stop the pump.
5. Compare the results taken under points 1 and 3.
Warning The connection which gives the larger quantity of
water or the higher pressure is the correct
The protective earth of the socket outlet
direction of rotation.
must be connected to the protective earth
of the pump. The plug must therefore have
the same PE connection system as that of
the socket outlet. If not, use a suitable
adapter.
Three-phase pumps must be connected to an
external motor-protective circuit breaker with
differential release. The rated current of the motor-
protective circuit breaker must correspond to the
electrical data marked on the pump nameplate.
If a level switch is connected to a three-phase pump,
the motor-protective circuit breaker must be
magnetically operated.
Single-phase pumps incorporate thermal overload
protection and require no additional motor
protection.

If the motor is overloaded, it will stop


Note
automatically. When the motor has cooled
to normal temperature, it restarts
automatically.

4
4. Installation 4.2 Pump location

English (GB)
The pump can be used in vertical or horizontal
Warning position. See fig. 3.
The installation of the pump must be During continuous operation, the motor and the
carried out by specially trained persons. pump inlet must always be completely covered by
Care must be taken to ensure that persons the pumped liquid.
cannot come into contact with the pump
impeller.

According to EN 60335-2-41/A2:2010, this

TM03 4191 1806


Note product with 5 metres of mains cable may
be used only for indoor applications.

4.1 Pipe connection


For permanent installation, we recommend that you
fit a union, a non-return valve and an isolating valve
in the outlet pipe. Fig. 3 Position of pump
If the pump is installed in a pit with a minimum free When the pipe/hose has been connected, place the
cable length of 100 mm, see fig. 5, the minimum pit pump in its operating position.
dimensions must be as shown in fig. 2.
Furthermore, the pit must be dimensioned according Never lift the pump by the power supply
Note
to the relation between the water flow to the pit and cable.
the pump performance. Position the pump so that the pump inlet will not be
blocked or partly blocked by sludge, mud or similar
materials.
We recommend that you place the pump on a solid
base. See fig. 4.
600 mm

∙ ∙ ∙ · ·
∙ ∙ ∙ · · ·
∙ ∙ · · ·
∙ · · · ·
∙ ∙ ∙ ∙ · · ·
∙ · ·
∙ ∙ · · · ·
∙ ∙ · · ·
·
∙ · ·

TM01 3597 4998


∙ ∙ ∙ · · · · ·
∙ ∙ · ·
∙ ∙ ∙ ∙ ∙ ∙ · · ·
∙ · ·
∙ ∙ · · · ·
∙ ∙ · · ·
∙ ∙ · · ·
∙ ·
∙ ∙ ∙ · ∙ ∙ · ·
∙ ·
∙ · ·
∙ ·
∙ ∙ · ∙ ·
∙ ·
·
∙ ∙ ∙ · · · · ·
∙ · ·
∙ ∙ · ∙ ·
∙ ∙ · · ·
∙ ∙ ∙ ∙ · · · · · ·
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙


∙ ∙ ∙

∙ ∙ ∙
∙ ∙

∙ ∙
∙ ∙
∙ ∙

∙ ∙
∙ ∙ ∙ ∙
∙ ∙
∙ ∙

∙ ∙ ∙
∙ ∙ ∙ ∙


∙ ∙ ∙
∙ ∙

∙ ∙ ∙
∙ ∙
∙ ∙

∙ ∙
TM03 4190 1806

∙ ∙ ∙ ∙ ∙

∙ ∙ ∙ ∙ ∙
∙ ∙

∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙

∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙

∙ ∙ ∙ ∙

∙ ∙ ∙ ∙

∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙

∙ ∙ ∙

∙ ∙ ∙
∙ ∙

∙ ∙
∙ ∙ ∙

∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙

∙ ∙ ∙ ∙ ∙ ∙

∙ ∙
∙ ∙ ∙


∙ ∙ ∙

∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙ ∙ ∙


∙ ∙ ∙ ∙
∙ ∙ ∙ ∙

∙ ∙
∙ ∙ ∙ ∙ ∙

∙ ∙ ∙
∙ ∙
∙ ∙
∙ ∙ ∙

∙ ∙ ∙ ∙
∙ ∙
∙ ∙
∙ ∙
∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙ ∙
∙ ∙ ∙
∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙

∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙
∙ ∙ ∙ ∙ ∙ ∙

550 mm
Fig. 4 Place pump on a solid base

Fig. 2 Minimum pit dimensions in pit if In the case of permanent installation, the pit must be
minimum free cable length is 100 mm cleared of sludge, pebbles, etc. before the pump is
installed.

5
4.3 Installation on auto coupling 4.4 Free-standing installation
English (GB)

See figs A and B, pages 10 and 11. See fig. C, page 12.
Pumps for permanent installation can be installed on For free-standing installation of the pumps, fit a 90 °
a stationary auto coupling and operated completely elbow to the outlet. The pump can be installed with a
or partially submerged in the pumped liquid. hose or rigid pipe and valves.
1. Drill mounting holes for guide rail bracket on the In order to facilitate service of the pump, fit a flexible
inside of the pit and fasten the guide rail bracket union or coupling to the outlet pipe for easy
provisionally with two screws. separation.
2. Place the auto coupling base unit on the bottom If a hose is used, make sure that the hose does not
of the pit. Use a plumb line to establish the buckle and that the inside diameter of the hose
correct positioning. Fasten with heavy-duty matches that of the outlet.
expansion bolts. If the bottom of the pit is If a rigid pipe is used, the union or coupling, non-
uneven, the auto coupling base unit must be return valve and isolating valve must be fitted in the
supported so that it is level when being fastened. sequence mentioned, as seen from the pump side.
3. Assemble the outlet line in accordance with the Lower the pump into the liquid.
generally accepted procedures and without
If the pump is installed in muddy conditions or on
exposing the line to distortion or tension.
uneven ground, we recommend that you support the
4. Knock the guide rails on to the spigots of the pump on bricks.
bottom part of the auto coupling. Bevel the inside
of the guide rails to facilitate installation. The 4.5 Setting of level switch
guide rails must fit tightly on the spigots. We
recommend 3/4" medium size pipes as guide Intermittent operation
rails. For pumps supplied with a level switch, the
5. Adapt the length of the guide rails to fit precisely difference in level between start and stop can be set
the bracket at the top. by adjusting the free cable between the level switch
6. Unscrew the provisionally fastened guide rail and the pump handle.
bracket, fit it on top of the guide rails and finally The longer the length of free cable, the larger the
fasten it firmly to the pit wall. difference in level between start and stop.
The pump is allowed to run for maximum 5 minutes
The guide rails must not have any axial per 30 minutes without the motor being submerged
Note play as this would cause noise during in the liquid.
pump operation.
7. Clean out debris from the pit before lowering the
pump into the pit.
8. Fit the auto-coupling half on to the outlet of the
pump. Then slide the guide bar of this coupling
half between the guide rails and lower the pump
into the pit by means of a chain. When the pump
reaches the auto-coupling base unit, the pump
will automatically connect tightly. Stop

TM03 4192 1806


9. Hang up the end of the chain on a suitable hook
at the top of the pit. 270 mm

10. Adjust the length of the motor cable by coiling it


up on a relief fitting, so the cable is not damaged
during operation. Fasten the relief fitting to a
suitable bracket at the top of the pit. Make sure
that the cables are not sharply bent or pinched. Fig. 5 Setting of level switch

The end of the cable must not be Continuous operation


Note submerged, as water may penetrate During continuous operation, the pump must always
through the cable into the motor. be completely covered by the pumped liquid.

6
5. Startup 6.2 Construction

English (GB)
Before starting the pump, submerge the pump inlet The construction of the pump will appear from the
in the pumped liquid. table below and fig. D, page 13.
Open the isolating valve, if fitted, and check the level
switch setting. Pos. Description

The pump may be run briefly to check the 50 Pump housing


Note direction of rotation without being 37a O-ring
submerged in the pumped liquid.
49 Impeller
6. Maintenance and service 150 Motor with flange
66 Washer
Warning
84 Base
Before starting any work on the product,
make sure that the power supply has been 67 Lock nut
switched off and that it cannot be
6 Inlet part
accidentally switched on.
105a Shaft seal
Before carrying out maintenance and service, it must
be ensured that the pump has been thoroughly 182 Level switch
flushed with clean water. Rinse the pump parts in
water after dismantling. 6.3 Service kits
Check the pump and replace the oil once a year. If
the pump is used for pumping liquids containing Service kit Part number
abrasive particles or it is operating continuously, the
pump must be checked at shorter intervals. Shaft seal, standard 96429307
Shaft seal, FKM 96429308
Warning
Oil 96010646
Out of consideration for the personal
safety and health, this work must be
carried out by specially trained persons. 6.4 Contaminated pumps
Furthermore, all rules and regulations
covering safety, health and environment If a pump has been used for a liquid which
must be observed. is injurious to health or toxic, the pump will
Be careful during dismantling as you will be classified as contaminated.
get access to sharp edges, etc., which
may cause cuts. Wear protective gloves. If you request Grundfos to service the pump, contact
Grundfos with details about the pumped liquid, etc.
A possible replacement of the cable or the
before you return the pump for service. Otherwise
level switch must be carried out by an
Grundfos can refuse to accept the pump for service.
authorised Grundfos service workshop.
Possible costs of returning the pump are paid by the
6.1 Oil customer.
However, any application for service (no matter to
The pump contains approx. 60 ml non-poisonous oil.
whom it may be made) must include details about
Used oil must be disposed of in accordance with the pumped liquid if the pump has been used for
local regulations. liquids which are injurious to health or toxic.
If the drained oil contains water or other impurities,
we recommend that you replace the shaft seal.

7
7. Fault finding the product
English (GB)

Warning
Before starting any work on the product,
make sure that the power supply has been
switched off and that it cannot be
accidentally switched on.

Fault Cause Remedy

1. The motor does not a) No power supply. Connect the power supply.
start.
b) The pump was stopped by the level
Adjust or replace the level switch.
switch.
c) The fuses have blown. Replace the fuses.
d) The motor protection/thermal relay has Wait until the motor protection
tripped. trips in again/reset the relay.
e) The impeller is blocked by impurities. Clean the impeller.
f) Short circuit in the cable or motor. Replace the defective part.
2. The motor protection/ a) The liquid temperature is too high. Use another pump type.
thermal relay trips
b) Impeller blocked or partly blocked by
after a short time of Clean the pump.
impurities.
operation.
c) Phase failure. Call an electrician.
d) Too low voltage. Call an electrician.
e) Overload setting of the motor-protective
Adjust the setting.
circuit breaker too low.
f) Incorrect direction of rotation. See
section 3.1 Checking the direction of Reverse the direction of rotation.
rotation.
3. The pump runs a) The pump is partly blocked by
Clean the pump.
constantly or gives impurities.
too little water.
b) The outlet pipe or valve is partly
Clean the outlet pipe.
blocked by impurities.
c) The impeller is not properly fixed to the
Tighten the impeller.
shaft.
d) Incorrect direction of rotation. See
section 3.1 Checking the direction of Reverse the direction of rotation.
rotation.
e) Incorrect setting of level switch. Adjust the level switch.
f) The pump is too small for the
Replace the pump.
application.
g) The impeller is worn. Replace the impeller.
4. The pump runs but a) The pump is blocked by impurities. Clean the pump.
gives no water.
b) The outlet pipe or non-return valve is
Clean the outlet pipe.
blocked by impurities.
c) The impeller is not properly fixed to the
Tighten the impeller.
shaft.
d) Air in pump. Vent the pump and the outlet
pipe.
e) The liquid level is too low. The pump
Submerge the pump in the liquid
inlet is not completely submerged in the
or adjust the level switch.
pumped liquid.
f) The level switch does not move freely. Make the level switch move
freely.

8
8. Disposal

English (GB)
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest
Grundfos company or service workshop.

Subject to alterations.

9
Appendix 1
Appendix

1-pump installation on auto-coupling

Fig. A







• •
• •
• •

• • • •

J



• • •
• • • •
Z


• •
• • •
• •
• • • •
• •

• • • • • • • •
• • •
• • •
• • •
• • • •
• • • •
• • • • • •
U

• • •
• • •
• • • •
• • • • •• •
• •
• • • • • •
• • • • • •
• •
• • • • • •
• • •
• • • • • • • • • •
• • •
• •
• • • • • • • • •
• • •
• • • •
• • • •
• • • • • • •
• •
• • •

TM03 4194 1806


G

K L

N O

A B C D E F G I J K
∅600 ∅600 304 135 82 85 65 100 63 150

L M N O P R S T U Z
400 200 300 700 500 - R2 3/4" 130 261

10
2-pump installation on auto-coupling

Appendix
Fig. B
B

· ·
· ·
·
·
· ·
·
·
· · · ·
·
· · · ·
· · ·
· · ·
· ·
· ·
· · · · · · · · ·

· · · · · · · ·
· ·
· · · ·
· ·
· · · ·
· · ·

TM01 3592 0399


I

M M

P R P
A B C D E F G I J K
600 600 304 135 82 85 26 100 63 150

L M N O P R S T U Z
400 200 300 700 335 330 R2 3/4" 130 261

11
Free-standing Installation
Appendix

Fig. C

TM03 4196 1806

A C D S d1 d2

Unilift AP35B ≤ 600 W 430 116 73 R2 234 210

Unilift AP35B > 600 W


455 116 73 R2 234 210
Unilift AP50B

12
Fig. D

TM03 4209 1806

13
Appendix
Argentina China Hong Kong
Grundfos companies

Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Pumps (Hong Kong) Ltd.
Ruta Panamericana km. 37.500 Centro 10F The Hub, No. 33 Suhong Road Unit 1, Ground floor
Industrial Garin Minhang District Siu Wai Industrial Centre
1619 Garín Pcia. de B.A. Shanghai 201106 29-33 Wing Hong Street &
Phone: +54-3327 414 444 PRC 68 King Lam Street, Cheung Sha Wan
Telefax: +54-3327 45 3190 Phone: +86 21 612 252 22 Kowloon
Telefax: +86 21 612 253 33 Phone: +852-27861706 / 27861741
Australia Telefax: +852-27858664
GRUNDFOS Pumps Pty. Ltd. COLOMBIA
P.O. Box 2040 GRUNDFOS Colombia S.A.S. Hungary
Regency Park Km 1.5 vía Siberia-Cota Conj. Potrero GRUNDFOS Hungária Kft.
South Australia 5942 Chico, Park u. 8
Phone: +61-8-8461-4611 Parque Empresarial Arcos de Cota Bod. H-2045 Törökbálint,
Telefax: +61-8-8340 0155 1A. Phone: +36-23 511 110
Cota, Cundinamarca Telefax: +36-23 511 111
Austria Phone: +57(1)-2913444
GRUNDFOS Pumpen Vertrieb Telefax: +57(1)-8764586 India
Ges.m.b.H. GRUNDFOS Pumps India Private
Grundfosstraße 2 Croatia Limited
A-5082 Grödig/Salzburg GRUNDFOS CROATIA d.o.o. 118 Old Mahabalipuram Road
Tel.: +43-6246-883-0 Buzinski prilaz 38, Buzin Thoraipakkam
Telefax: +43-6246-883-30 HR-10010 Zagreb Chennai 600 096
Phone: +385 1 6595 400 Phone: +91-44 2496 6800
Belgium Telefax: +385 1 6595 499
N.V. GRUNDFOS Bellux S.A. www.hr.grundfos.com Indonesia
Boomsesteenweg 81-83 PT. GRUNDFOS POMPA
B-2630 Aartselaar GRUNDFOS Sales Czechia and Graha Intirub Lt. 2 & 3
Tél.: +32-3-870 7300 Slovakia s.r.o. Jln. Cililitan Besar No.454. Makasar,
Télécopie: +32-3-870 7301 Čajkovského 21 Jakarta Timur
779 00 Olomouc ID-Jakarta 13650
Belarus Phone: +420-585-716 111 Phone: +62 21-469-51900
Представительство ГРУНДФОС в Telefax: +62 21-460 6910 / 460 6901
Минске Denmark
220125, Минск GRUNDFOS DK A/S Ireland
ул. Шафарнянская, 11, оф. 56, БЦ Martin Bachs Vej 3 GRUNDFOS (Ireland) Ltd.
«Порт» DK-8850 Bjerringbro Unit A, Merrywell Business Park
Тел.: +7 (375 17) 286 39 72/73 Tlf.: +45-87 50 50 50 Ballymount Road Lower
Факс: +7 (375 17) 286 39 71 Telefax: +45-87 50 51 51 Dublin 12
E-mail: minsk@grundfos.com E-mail: info_GDK@grundfos.com Phone: +353-1-4089 800
www.grundfos.com/DK Telefax: +353-1-4089 830
Bosnia and Herzegovina
GRUNDFOS Sarajevo Estonia Italy
Zmaja od Bosne 7-7A, GRUNDFOS Pumps Eesti OÜ GRUNDFOS Pompe Italia S.r.l.
BH-71000 Sarajevo Peterburi tee 92G Via Gran Sasso 4
Phone: +387 33 592 480 11415 Tallinn I-20060 Truccazzano (Milano)
Telefax: +387 33 590 465 Tel: + 372 606 1690 Tel.: +39-02-95838112
www.ba.grundfos.com Fax: + 372 606 1691 Telefax: +39-02-95309290 / 95838461
e-mail: grundfos@bih.net.ba
Finland Japan
Brazil OY GRUNDFOS Pumput AB GRUNDFOS Pumps K.K.
BOMBAS GRUNDFOS DO BRASIL Trukkikuja 1 1-2-3, Shin-Miyakoda, Kita-ku,
Av. Humberto de Alencar Castelo FI-01360 Vantaa Hamamatsu
Branco, 630 Phone: +358-(0) 207 889 500 431-2103 Japan
CEP 09850 - 300 Phone: +81 53 428 4760
São Bernardo do Campo - SP France Telefax: +81 53 428 5005
Phone: +55-11 4393 5533 Pompes GRUNDFOS Distribution S.A.
Telefax: +55-11 4343 5015 Parc d’Activités de Chesnes Korea
57, rue de Malacombe GRUNDFOS Pumps Korea Ltd.
Bulgaria F-38290 St. Quentin Fallavier (Lyon) 6th Floor, Aju Building 679-5
Grundfos Bulgaria EOOD Tél.: +33-4 74 82 15 15 Yeoksam-dong, Kangnam-ku, 135-916
Slatina District Télécopie: +33-4 74 94 10 51 Seoul, Korea
Iztochna Tangenta street no. 100 Phone: +82-2-5317 600
BG - 1592 Sofia Germany Telefax: +82-2-5633 725
Tel. +359 2 49 22 200 GRUNDFOS GMBH
Fax. +359 2 49 22 201 Schlüterstr. 33 Latvia
email: bulgaria@grundfos.bg 40699 Erkrath SIA GRUNDFOS Pumps Latvia
Tel.: +49-(0) 211 929 69-0 Deglava biznesa centrs
Canada Telefax: +49-(0) 211 929 69-3799 Augusta Deglava ielā 60, LV-1035, Rīga,
GRUNDFOS Canada Inc. e-mail: infoservice@grundfos.de Tālr.: + 371 714 9640, 7 149 641
2941 Brighton Road Service in Deutschland: Fakss: + 371 914 9646
Oakville, Ontario e-mail: kundendienst@grundfos.de
L6H 6C9 Lithuania
Phone: +1-905 829 9533 Greece GRUNDFOS Pumps UAB
Telefax: +1-905 829 9512 GRUNDFOS Hellas A.E.B.E. Smolensko g. 6
20th km. Athinon-Markopoulou Av. LT-03201 Vilnius
P.O. Box 71 Tel: + 370 52 395 430
GR-19002 Peania Fax: + 370 52 395 431
Phone: +0030-210-66 83 400
Telefax: +0030-210-66 46 273
Malaysia Serbia Turkey

Grundfos companies
GRUNDFOS Pumps Sdn. Bhd. Grundfos Srbija d.o.o. GRUNDFOS POMPA San. ve Tic. Ltd.
7 Jalan Peguam U1/25 Omladinskih brigada 90b Sti.
Glenmarie Industrial Park 11070 Novi Beograd Gebze Organize Sanayi Bölgesi
40150 Shah Alam Phone: +381 11 2258 740 Ihsan dede Caddesi,
Selangor Telefax: +381 11 2281 769 2. yol 200. Sokak No. 204
Phone: +60-3-5569 2922 www.rs.grundfos.com 41490 Gebze/ Kocaeli
Telefax: +60-3-5569 2866 Phone: +90 - 262-679 7979
Singapore Telefax: +90 - 262-679 7905
Mexico GRUNDFOS (Singapore) Pte. Ltd. E-mail: satis@grundfos.com
Bombas GRUNDFOS de México S.A. de 25 Jalan Tukang
C.V. Singapore 619264 Ukraine
Boulevard TLC No. 15 Phone: +65-6681 9688 Бізнес Центр Європа
Parque Industrial Stiva Aeropuerto Telefax: +65-6681 9689 Столичне шосе, 103
Apodaca, N.L. 66600 м. Київ, 03131, Україна
Phone: +52-81-8144 4000 Slovakia Телефон: (+38 044) 237 04 00
Telefax: +52-81-8144 4010 GRUNDFOS s.r.o. Факс.: (+38 044) 237 04 01
Prievozská 4D E-mail: ukraine@grundfos.com
Netherlands 821 09 BRATISLAVA
GRUNDFOS Netherlands Phona: +421 2 5020 1426 United Arab Emirates
Veluwezoom 35 sk.grundfos.com GRUNDFOS Gulf Distribution
1326 AE Almere P.O. Box 16768
Postbus 22015 Slovenia Jebel Ali Free Zone
1302 CA ALMERE GRUNDFOS LJUBLJANA, d.o.o. Dubai
Tel.: +31-88-478 6336 Leskoškova 9e, 1122 Ljubljana Phone: +971 4 8815 166
Telefax: +31-88-478 6332 Phone: +386 (0) 1 568 06 10 Telefax: +971 4 8815 136
E-mail: info_gnl@grundfos.com Telefax: +386 (0)1 568 06 19
E-mail: tehnika-si@grundfos.com United Kingdom
New Zealand GRUNDFOS Pumps Ltd.
GRUNDFOS Pumps NZ Ltd. South Africa Grovebury Road
17 Beatrice Tinsley Crescent GRUNDFOS (PTY) LTD Leighton Buzzard/Beds. LU7 4TL
North Harbour Industrial Estate Corner Mountjoy and George Allen Phone: +44-1525-850000
Albany, Auckland Roads Telefax: +44-1525-850011
Phone: +64-9-415 3240 Wilbart Ext. 2
Telefax: +64-9-415 3250 Bedfordview 2008 U.S.A.
Phone: (+27) 11 579 4800 GRUNDFOS Pumps Corporation
Norway Fax: (+27) 11 455 6066 17100 West 118th Terrace
GRUNDFOS Pumper A/S E-mail: lsmart@grundfos.com Olathe, Kansas 66061
Strømsveien 344 Phone: +1-913-227-3400
Postboks 235, Leirdal Spain Telefax: +1-913-227-3500
N-1011 Oslo Bombas GRUNDFOS España S.A.
Tlf.: +47-22 90 47 00 Camino de la Fuentecilla, s/n Uzbekistan
Telefax: +47-22 32 21 50 E-28110 Algete (Madrid) Grundfos Tashkent, Uzbekistan The Rep-
Tel.: +34-91-848 8800 resentative Office of Grundfos Kazakhstan
Poland Telefax: +34-91-628 0465 in Uzbekistan
GRUNDFOS Pompy Sp. z o.o. 38a, Oybek street, Tashkent
ul. Klonowa 23 Sweden Телефон: (+998) 71 150 3290 / 71 150
Baranowo k. Poznania GRUNDFOS AB 3291
PL-62-081 Przeźmierowo Box 333 (Lunnagårdsgatan 6) Факс: (+998) 71 150 3292
Tel: (+48-61) 650 13 00 431 24 Mölndal
Fax: (+48-61) 650 13 50 Tel.: +46 31 332 23 000 Addresses Revised 07.06.2017
Telefax: +46 31 331 94 60
Portugal
Bombas GRUNDFOS Portugal, S.A. Switzerland
Rua Calvet de Magalhães, 241 GRUNDFOS Pumpen AG
Apartado 1079 Bruggacherstrasse 10
P-2770-153 Paço de Arcos CH-8117 Fällanden/ZH
Tel.: +351-21-440 76 00 Tel.: +41-44-806 8111
Telefax: +351-21-440 76 90 Telefax: +41-44-806 8115

Romania Taiwan
GRUNDFOS Pompe România SRL GRUNDFOS Pumps (Taiwan) Ltd.
Bd. Biruintei, nr 103 7 Floor, 219 Min-Chuan Road
Pantelimon county Ilfov Taichung, Taiwan, R.O.C.
Phone: +40 21 200 4100 Phone: +886-4-2305 0868
Telefax: +40 21 200 4101 Telefax: +886-4-2305 0878
E-mail: romania@grundfos.ro Thailand
Russia GRUNDFOS (Thailand) Ltd.
ООО Грундфос Россия 92 Chaloem Phrakiat Rama 9 Road,
Shkolnaya, 39-41 Dokmai, Pravej, Bangkok 10250
Москва, RU-109544, Russia Phone: +66-2-725 8999
Тел. (+7) 495 564-88-00 (495) 737-30- Telefax: +66-2-725 8998
00
Факс (+7) 495 564 88 11
E-mail grundfos.moscow@grundfos.com
ECM: 1206635
96004693 0417