You are on page 1of 356

2011

Products Guide V01


Bassano del Grappa Pieve díAlpago Pieve d'Alpago
(Vicenza) (Belluno) (Belluno)
Headquarters Climaveneta Productive area:
Productive area: Training centre 25.000m2
12.500m2 Productive area: Employees: 210
Employees: 230 7.000m2
Employees: 50

Production of: Production of: Production of:


 Chillers: air and water cooled, from 30 to 700kW  Air handling units  Chillers: air and water cooled, from 200 to 1700kW
 Reversible units: air and water cooled, up to 400kW  Heat pumps air and water cooled, up to 2400KW
 Multipurpose up to 400KW  Multipurpose up to 700KW
 Chillers with free-cooling up to 300kW  Chillers with free-cooling up to 1250kW
 Shell & tube evaporators  Roof-top units up to 500kW
Sometimes numbers
say more than a thousand words

And sometimes even a thousand words Head offices and foreign branches
- Climaveneta SpA in Italy
are not enough. Because it is hard to list - Climaveneta France
all the reasons that explain why - Climaveneta Deutschland
Climaveneta is the preferred partner air - Climaveneta España
- Climaveneta Poland
conditioning in the most challenging - Climaveneta Chat Union Refrig. Equipment Co Ltd in China
projects all around the world.
Distributors
In fact our success is a delicate balance of vision, Over 55 distributors in more than 100 countries of the
experience and cutting-edge technology. It is not just world for a truly complete market coverage.
comfort, it is a question of flexibility and care,
adapting the system to the requirements of each Service
building and application, emulating their users’ needs. Service is assured in all countries through the assistance
All over the world, no matter how harsh the climate, networks of our subsidiaries and distributors with highest
how demanding each project can be, every single expertise, a wide range of after sales service contracts for
choice is focussed on offering the most efficient, a truly complete support.
reliable and sustainable solution.

Climaveneta. There are many reasons.

Mignagola Shanghai Parets del Valles


(Treviso) (China) (Spain)
Productive area: Sales department for Productive area:
20.000m2 China and far east 2.500m2
Employees: 160 Productive area: Employees: 45
25.000m2
Employees: 330

Production of: Production of: Production of:


 Split systems, multisplit  Air cooled chillers & heat pumps  Direc expansion units
 Chillers and Heat pumps up to 150kW from 40 to 1700kW  Compact units
 Hydronic fan coils from 1 to 30kW  Water cooled chillers & heat pumps  Rooftop units for small and medium applications
 Close control units from 10 to 3070kW
 Telecommunications units
Mission
“To develop efficient and reliable air conditioning solutions in order to
emulate our customers’ expectations”.

Climaveneta is aware that the HVACR systems are among the most crucial in modern buildings.
The use, energy efficiency and environmental sustainability of such spaces depend upon these
systems, as well as the health and well-being of the people who spend their time there, whatever is
the purpose - offices, residential, commercial centres, hotels, hospitals, leisure areas.

1st in Europe and 5th in the world


This mission and values have been at the core of our activity for 40 years and have
enabled us to become the 1st European manufacturer and the 5th world group in
the HVACR industry. Achievements proven by the numbers of our group:

 188 milions Euro


turnover 2009

 23 milions Euro
EBITDA 2009
For 40 years
mission and values have been
leading our activity and are the
basis of our results.

Values
Every strategic- and organizational
choice is based upon fundamental
values:

 Energy efficiency:
continuous strive towards the most intelligent
and sustainable use of energy resources,
extended to all solutions, for both cooling and
heating, with every type of product: complete
efficiency, 365 days a year.

 Comfort:
well-being created in enevery application with
maximum efficiency and minimum
environmental impact, thanks to the
uncompromising attention to the specific
requirements of each project.

 “Custom Made” approach:


conjugate tailor-made solutions with advanced
industrial processes, to ensure the answer to
the needs of every user, application and
building features, with the quality and
advantages of a modern manufacturing
organization.

 Environment and Social


responsibility:
continuously improve the sustainability of its
activities and products, particularly in terms of
energy consumption and environmental
impact. A value which is witnessed by
Climaveneta with the ISO 14001 certification,
successfully obtained in December 2009.
A complete range of
products from 1 to
2400kW, a brand that is
synonymous for reliability
and quality, with all the
advantages that only a
leading group, De’Longhi,
can offer, as far as Complete and
manufacturing, know-how specialized
Organization
and customer orientation
are concerned.
Climaveneta qualifies itself for the
consistency of both its proposal
and organization. Specific
approaches stem from such
consistent yet broad offer, namely

All this is in Operations and R&D: the


production is implemented in 5
focus factories, each specializing
Climaveneta. in terms of product types.
Lean From the product
Manufacturing to the system

The whole production is structured according We have integrated products into plug&play
to lean thinking principles. It represents one of rational and efficient systems, complete with
the best examples of lean manufacturing all the necessary components in order to
implementation in Europe. ensure:
This commitment enables several advantages:
 Perfect comfort and complete adaptability
 Increased efficiency, to specific applications,
 Higher quality standardsi,  High efficiency,
 Best process integration.  Lower installation costs,
 Smooth and easy on site operations,
 Efficient project management thanks to
Climaveneta as unique project leader.
Integrated quality - envirionment - safety policy

Climaveneta, consistently with the De’Longhi Group Policy – believes in the integrated Quality, Environment, Safety
System as the best guarantee for all stakeholders in achieving the highest quality, reliability and competitiveness of
the products and in complying with highest standards of safeguarding the environment and human resource safety.
For further information www.climaveneta.com

This company participates Climaveneta S.p.A.:


in the Eurovent Certification Programme.
The products are listed in the Environmental Management System complying
Directory of certified products. with the requirements of UNI EN ISO14001:2004 norm
The Eurovent certificate, for the applicable units,
refers to products with cooling capacity up to 600 kW,
Quality System complying with
voluntarily extended up to 1500 kW, the requirements of UNI EN ISO9001:2008 norm
for air-cooled models and up to 1500 kW
for water-cooled models.
Legenda

Functions Fan
Cooling Axial fan

Heating Centrifugal fan

Combined production of heating, cooling and


Plug fan
domestic hot water
REVERSIBLE

Combined production of heating and cooling Tangential fan


HEAT PUMP

Domestic hot water production


Recovery
Free-cooling Plate heat recovery

Humidification Rotary enthalpy recovery


ROTARY

Reheat
Further features
Thermodynamic effect Integrated electronic controller (can be optional)

2 PIPES
Suitable for 2-pipe system Class A Energy efficiency
ENERGY CLASS

4 PIPES
Suitable for 4-pipe system Leakage class B according to BS EN 1886

Compressor Eurovent Certification


Centrifugal compressor
VSpeed
Scroll compressor
VAir
Reciprocating compressor
VPF
Rotary compressor

Patent Pending
Screw compressor

4 patents pending
Refrigerant
Refrigerant
Water heat exchanger
Tipologia
Plate heat exchanger
Wall split
Shell & tube heat exchanger
WALL

Cassette
CASSETTE

Duct
DUCT

Vertical/Orizzontal
FAN COIL

The functions and characteristics are subject to each model’s size, configuration, optional.
Performance data, pictures, schematics and other features contained in this document are provided exclusively on informa-
tional purpose about our product range. They refer to standard execution, applicable to the European Union market. They
can be varied any time without notice.
For further information please contact Climaveneta Sales/Marketing Offices or visit www.climaveneta.it.
Index

Hydronic - residential
Heat
Functions Refrig. Compressors Fan
Exchangers

Pag. Product Capacity


COOLING HEATING SCROLL AXIAL CENTRIFUGAL PLATES

Chillers, air source


16 BRAT 4,9 - 32,9 kW • R410A • • •
20 MICS 18,2 - 44,7 kW • R410A • • •
22 BRA 4,9 - 15,4 kW • R410A • • •
24 MICS-C 18,2 - 31,8 kW • R410A • • •
Chillers, water source
26 BRH 5,5 - 35,1 kW • R410A • •
Condenserless chillers
30 HE FF 4,7 - 32,4 kW • R407C • •
32 NHCR 8,6 - 41,9 kW •
Reversible units, air source
34 BRAN 4,6 - 35,5 kW • • R410A • • •
38 MICS-N 17,3 - 47,9 kW • • R410A • • •
40 BRN 4,6 - 16,8 kW • • R410A • • •
42 MICS-CN 17,3 - 33,9 kW • • R410A • • •
Reversible units, water source
44 WWr MTD 5,2 - 41,7 kW • • R410A • •

PRANA
Heat
Functions Refrig. Compressors Fan
Exchangers

Pag. Product Capacity


COOLING HEATING HOT WATER SCROLL AXIAL EC FAN PLATES

Reversible heat pump with inverter compressor, total heat recovery, air source
48 i-NRG 16,3 kW • • • R410A • • • •
50 AWR-DHW 7,7 - 33,5 kW • • • R407C • • •
Reversible heat pump, air source
52 AWR-MTD1 6,9 - 17,4 kW • • • R410A • • •

54 AWR-MTD-XE 6,3 - 17,9 kW • • • R410A • • •


Heat pump, air source
56 AW-HT 10,4 - 19,7 kW • • R407C • • •
Reversible heat pump, water source
58 WWR-MTD 7,2 - 43,8 kW • • • R410A • •
60 WWR-HT Slim 8,3 - 14,1 kW • • • R407C • •
62 WWR-HT Cube 8,3 - 35,9 kW • • • R407C • •
Reversible heat pump, total heat recovery, water source
64 WWR-DHW 6,0 - 40,5 kW • • • R407C • •
Reversible heat pump, geothermal source
66 BWR-MTD 5,4 - 33,3 kW • • • R410A • •
68 BWR-HT Slim 6,2 - 10,6 kW • • • R407C • •
70 BWR-HT Cube 6,2 - 27,0 kW • • • R407C • •
Reversible heat pump, total heat recovery, geothermal source
72 BWR-DHW 4,5 - 29,7 kW • • • R407C • •
Hydronic - chiller
Functions Refrig. Compressors Fan Heat Exchangers

Pag. Product Capacity


COOLING HEATING FREE COOLING CENTRIFUGAL SCROLL SCREW AXIAL CENTRIFUGAL PLATES SHELL & TUBES

Chillers, air source for outdoor installation


76 NECS 33,8 - 341 kW • R410A • • •
82 NECS 53,0 - 159 kW • R410A • • •

86 NECS 354 - 885 kW • R410A • • •


90 NECS-ST 104 - 341 kW • R410A • • •
94 FOCS 145 - 516 kW • R134a • • •
98 FOCS 277 - 516 kW • R134a • • •
100 FOCS 294 - 1744 kW • R134a • • •
104 FOCS-XL 272 - 1180 kW • R134a • • •
106 FOCS-CA 310 - 1381 kW • R134a • • •
110 i-FOCS 511 - 842 kW • R134a • • •
112 TECS2 Vision 2.0 220 - 1325 kW • R134a • • •
114 NECS-FC 41,5 - 377 kW • • R410A • • •
120 FOCS-FC 329 - 1229 kW • • R134a • • •
124 NECS-C 37,1 - 325 kW • R410A • • •
Chiller, water source
128 NECS-W 43,4 - 371 kW • • R410A • •
130 FOCS-W 87,0 - 447 kW • • R134a • •
132 FOCS2-W 321 - 1299 kW • • R134a • •

136 TECS2-W Vision 2.0 241 - 1949 kW • • R134a • •

Condenserless chiller
138 NECS-ME 39,5 - 432 kW • R410A • •
140 FOCS-ME 79,2 - 410 kW • R134a • •
142 FOCS-ME 219 - 2240 kW • R134a • •

Hydronic - reversible
Functions Refrig. Compressors Fan Heat Exchangers

Pag. Product Capacity


COOLING HEATING FREE COOLING CENTRIFUGAL AXIAL CENTRIFUGAL PLATES SHELL & TUBES

Reversible units, air source


146 NECS-N 35,8 - 322 kW • • R410A • •
152 NECS-N 50,3 - 169 kW • • R410A • •

154 NECS-N 339 - 898 kW • • R410A • •


158 NECS-ST-N 103 - 322 kW • • R410A • •
162 RECS 195 - 385 kW • • R134a • •
166 RECS 195 - 385 kW • • R134a • •
170 FOCS-N 439 - 1160 kW • • R134a • •
174 NECS-CN 36,0 - 303 kW • • R410A • •
Reversible units, water source
176 NECS-WN 43,4 - 371 kW • • R410A •
178 RECS-W 174 - 801 kW • • R134a •
Reversible units, NRG line, total heat recovery, air source
180 NECS-NR 36 - 311 kW • • R410A • •
184 NECS-NR 353 - 823 kW • • R410A • •

188 FOCS-NR 200 - 826 kW • • R134a • •


Reversible units, NRG line, total heat recovery, water source
192 NECS-WNR 5,7 - 491 kW • • R410A •

194 FOCS-WNR 194 - 891 kW • • R134a •


INTEGRA
Functions Refrig. Compressors Fan Heat Exchangers

4 PIPE

Pag. Product Capacity


SYSTEM SCROLL SCREW AXIAL PLATES SHELL & TUBES

INTEGRA unit for 4-pipe systems, air source


198 NECS-Q 36 - 311 kW • R410A • • •
202 NECS-Q 353 - 823 kW • R410A • • •

206 ERACS2-Q 200 - 826 kW • R134a • • •

210 i-FX-Q 479 - 811 kW • R134a • •


INTEGRA unit for 4-pipe systems, water source
214 NECS-WQ 45,7 - 491 kW • R410A • •

216 ERACS2-WQ 194 - 891 kW • R134a • •

Hydronic terminals
Type Functions Fan

Pag. Product Capacity


WALL FAN COIL CASSETTE DUCT 2 PIPES 4 PIPES TANGENZIALE CENTRIFUGAL

Fan-coils
220 a-LIFE 1,45 - 22,42 kW • • • •
230 a-LIFE HP 2,83 - 19,38 kW • • • • •
234 i-LIFE 1,41 - 7,47 kW • • • •
240 NFT 0,86 - 4,25 kW • • • •
Hi-wall type terminals
244 MHD 1,9 - 4,6 kW • • •
Ducted type terminals
250 HWD 4,8 - 29 kW • • • •
254 HWD-HP 16,8 - 60,4 kW • • • •
Heat recuperators
256 HRD 290 - 4000 m3/h •

HPAC
Functions Refrig. Compressors Fan

Pag. Product Capacity


COOLING FREE COOLING SCROLL AXIAL CENTRIFUGAL EC FAN

Close control unit, direct expansion


260 i-AX 7 - 100 kW • R410A • •

262 i-AW 7 - 100 kW • R410A •


264 ACCURATE AX 7 - 90 kW • R410A • •
266 ACCURATE AW 7 - 90 kW • R410A • •
268 ACCURATE AD 20-100kW • R410A • •
270 ACCURATE AT 20-100kW • R410A • •
272 ACCURATE AF 20-100kW • • R410A • •
Close control units, chilled water
274 ACCURATE AC 8 - 185 kW • •
278 ACCURATE AB 20-110 kW • •
Remote condensers
280 BRE R410A •
282 BRC R407C •
284 ARCC R407C •
Dry cooler
286 BDC •
Packaged
Com-
Functions Refrig. Recupero Sez. Int. Sez. Est.
pressors

Pag. Product Capacity


COOLING HEATING FREE COOLING THERMODYNAMIC SCROLL PLATE ROTARY CENTRIFUGAL PLUG FAN AXIAL

Rooftop units, for medium crowding applications


290 WORK 37,4 - 198 kW • • • • R410A • • •
292 WORK-T 34,7 - 200 kW • • • R410A • • •
294 WHISPER 35,7 - 197 kW • • • • R410A • • •
296 WHISPER-T 35,8 - 197 kW • • • R410A • • •
Rooftop units with enthalpy recovery for medium crowding applications
298 i-WHISPER ENTHALPY 87,0 - 338 kW • • • • R410A • • •

300 WHISPER ENTHALPY 47,4 - 243 kW • • • • R410A • • • •


302 WHISPER ENTHALPY-T 47,4 - 243 kW • • • R410A • • • •
304 WHISPER HALL 45,9 - 146 kW • • • • R410A • • • •
Rooftop units for medium crowding applications
306 WISDOM 34,5 - 355 kW • • • R410A • • •
308 WISDOM-T 34,7 - 357 kW • • R410A • • •
Rooftop units with heat recovery for medium crowding applications
310 WISDOM-R 43,0 - 422 kW • • • R410A • • • •
312 WISDOM-T-R 43,5 - 425 kW • • R410A • • • •
WET line units for water loop systems
314 WET-RMT 7,2 - 34,4 kW • • R410A • •
316 WET ENTHALPY 50,6 - 262 kW • • • R410A • • •
318 WET-RTF 37,2 - 396 kW • • • R410A • •
320 WET-RTF-R 44,8 - 468 kW • • • R410A • • •

Systems
Pag. Product
Group devices
324 MANAGER 3000
325 SEQUENCER
Metering devices
326 DEMETRA
Supervision devices
327 FWS3
328 FWS3000
IDRORELAX
330 IDRORELAX

AHU
Functions Fan Elettr.

Pag. Product Capacity


COOLING HEATING RE-HEATING HUMIDIFICATION CENTRIFUGAL PLUG FAN CONTROLLER

Air handling units


334 WIZARD 0-115000 m3/h • • • • • • •

Other
Functions Refrig. Compressors Fan

Pag. Product Capacity


COOLING SCROLL RECIPROCATING AXIAL

Condensing units
338 BRAT-MC 4,9 - 32,9 kW • R-410A • •
340 HCAT 38 - 160 kW • R407C • •
344 MCAT 119 - 325 kW • R407C • •
348 NCE 55 - 389 kW R-410A •
352 FCE 79 - 894 kW R234A •
RO
ONIC - REE
O

14
residential
hydronic
ESIDENTIAL
hydronic - residential

15
Hydronic - residential

BRAT 0011÷0121
Versions
FF base version, with built-in hydronic kit
FF-SL super-low noise version, with built-in
hydronic kit
FFT base version without hydronic kit
FFT-SL super-low noise version without hydronic
kit

Features
Coil protection grid for models 0011÷0061.
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Phase sequence controller for models 0071÷0121
Differential pressure switch.
Air vent valve.
The hydronic circuit on the FF models includes:

Chillers, air source for outdoor installation Circulating pump for models 0011÷0061.
Multistage centrifugal pump for models 0071÷0121.
Expansion tank.
Safety valve.
4,9 - 32,9 kW Manual filling assembly.
Pressure gauge.
Unit Description
BRAT is the Climaveneta range of air-cooled chillers with gas R410A. It is an outdoor unit with Drain valve.
axial fans, hermetic Scroll compressors and Full Floating technology. The latter is an intelligent
electronic unit providing the perfect answer to residential market requirements: compactness, Main accessories
ease of installation and quietness. UÊRemovable metal mesh water filter kit
UÊRubber anti-vibration mounting kit
Commands UÊCoil protection grid for models 0071÷0121
Full Floating features UÊAdditional circulating pump kit for models 0041÷0061
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and UÊExternal main switch kit
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of UÊExternal buffer tank and hydronic connecting kit
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts. UÊHSW10 remote keyboard

16
r HFC
R-410A
PLATES AXIAL SCROLL COOLING

BRAT / FF
Models 0011 0021 0025 0031 0041 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 4,90 5,60 6,90 8,60 11 5,60 7 8,70
Total absorbed power (1) kW 1,90 2,10 2,50 3,40 4,10 2 2,40 3,10
Absorbed current A 9,24 9,84 12,4 15,6 18,6 4,24 4,44 5,94
EER 2,58 2,67 2,76 2,53 2,68 2,80 2,92 2,81
ESEER 3,11 3,35 3,33 3,28 3,17 3,37 3,37 3,34
Nominal water flow m3/h 0,80 1 1,20 1,50 1,90 1 1,20 1,50
Operational weight kg 80 85 100 105 125 85 100 105
No. fans N. 1 1 1 1 2 1 1 1
Useful head kPa 49 46 42 41 43 46 42 41
Airflow m3/h 2400 3500 3500 4200 6800 3500 3500 4200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4”
Sound pressure level (2) dB(A) 54 55 55 55 58 55 55 55
Sound power dB(A) 65 66 66 66 69 66 66 66
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940
P mm 370 370 370 370 370 370 370 370

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 11,4 13,2 15,4 19,3 21,9 26,4 32,9
Total absorbed power (1) kW 4,20 4,70 5,20 6,80 7,80 8,70 11,1
Absorbed current A 8,38 8,98 9,68 14,6 15,8 21,7 24,6
EER 2,71 2,81 2,96 2,84 2,81 3,03 2,96
ESEER 3,30 3,25 3,51 3,37 3,28 3,47 3,41
Nominal water flow m3/h 2 2,30 2,70 3,30 3,80 4,50 5,70
Operational weight kg 125 145 155 245 250 320 325
No. fans N. 2 2 2 1 1 2 2
Useful head kPa 43 35 32 116 90 130 108
Airflow m3/h 6800 6800 6400 9800 9800 14000 14000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 58 58 58 65 65 65 65
Sound power dB(A) 69 69 69 76 76 79 79
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 1450 1450 1450 1450
H mm 1240 1240 1390 1200 1200 1700 1700
P mm 370 370 420 550 550 550 550

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

17
BRAT / FFT
Models 0011 0021 0025 0031 0041 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 4,90 5,60 6,90 8,60 11 5,60 7 8,70
Total absorbed power (1) kW 1,90 2,10 2,50 3,40 4,10 2 2,40 3,10
Absorbed current A 9,24 9,84 12,4 15,6 18,7 4,24 4,44 5,94
EER 2,58 2,67 2,76 2,53 2,68 2,80 2,92 2,81
ESEER 3,11 3,35 3,33 3,28 3,17 3,37 3,37 3,34
Nominal water flow m3/h 0,80 1 1,20 1,50 1,90 1 1,20 1,50
Operational weight kg 80 85 100 105 125 85 100 105
No. fans N. 1 1 1 1 2 1 1 1
Airflow m3/h 2400 3500 3500 4200 6800 3500 3500 4200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4”
Sound pressure level (2) dB(A) 54 55 55 55 58 55 55 55
Sound power dB(A) 65 66 66 66 69 66 66 66
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940
P mm 370 370 370 370 370 370 370 370

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 11,4 13,2 15,4 19,3 21,9 26,4 32,9
Total absorbed power (1) kW 4,20 4,70 5,20 6,80 7,80 8,70 11,1
Absorbed current A 8,38 8,98 9,68 14,6 15,8 21,7 24,6
EER 2,71 2,81 2,96 2,84 2,81 3,03 2,96
ESEER 3,30 3,25 3,51 3,37 3,28 3,47 3,41
Nominal water flow m3/h 2 2,30 2,70 3,30 3,80 4,50 5,20
Operational weight kg 125 145 155 245 250 320 325
No. fans N. 2 2 2 1 1 2 2
Airflow m3/h 6800 6800 6400 9800 9800 14000 14000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 58 58 58 65 65 65 65
Sound power dB(A) 69 69 69 76 76 79 79
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 1450 1450 1450 1450
H mm 1240 1240 1390 1200 1200 1700 1700
P mm 370 370 420 550 550 550 550

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

18
BRAT / FF-SL
Models 0071 0091 0101 0121
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 19,3 21,9 26,4 32,9
Total absorbed power (1) kW 6,50 7,50 7,95 10,4
Absorbed current A 12,4 13,6 18,6 21,5
EER 2,96 2,92 3,32 3,18
ESEER 3,51 3,41 3,85 3,66
Nominal water flow m3/h 3,30 3,80 4,50 5,70
Operational weight kg 245 250 320 325
No. fans N. 2 2 3 3
Useful head kPa 116 90 130 108
Airflow m3/h 7000 7000 10500 10500
Compressor type SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 62 62 63 63
Sound power dB(A) 73 73 74 74
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1450 1450 1450 1450
H mm 1200 1200 1700 1700
P mm 550 550 550 550
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

BRAT / FFT-SL
Models 0071 0091 0101 0121
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 19,3 21,9 26,4 32,9
Total absorbed power (1) kW 6,50 7,50 7,95 10,4
Absorbed current A 12,4 13,6 18,6 21,5
EER 2,96 2,92 3,32 3,18
ESEER 3,51 3,41 3,85 3,66
Nominal water flow m3/h 3,30 3,80 4,50 5,70
Operational weight kg 245 250 320 325
No. fans N. 2 2 3 3
Airflow m3/h 7000 7000 10500 10500
Compressor type SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 62 62 63 63
Sound power dB(A) 73 73 74 74
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1450 1450 1450 1450
H mm 1200 1200 1700 1700
P mm 550 550 550 550
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

Dimension

H
H H

P
P
P
L L L

19
Hydronic - residential

MICS 0072÷0182
Versions
FF base version, with built-in hydronic kit
FFT base version without hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Electronic expansion valve
Available water pipe fittings in case of installation under
appliance
Differential pressure switch.
Drain valve.
The hydronic circuit on the FF models includes:
Multistage centrifugal pump
Air vent valve.
Expansion tank.
Modular chillers, air source for outdoor Safety valve.
Pressure gauge.
installation
18,2 - 44,7 kW Main accessories
UÊRubber anti-vibration mounting kit
Unit Description UÊRemovable metal mesh water filter kit
MICS is the Climaveneta range of air-cooled liquid chillers. They are outdoor units with axial
UÊKit for connecting the KMC keyboard
fans, hermetic Scroll compressors and Full Floating technology. The latter is an intelligent
electronic unit providing the perfect answer to residential market requirements: compactness, UÊCoil protection grids
ease of installation and quietness. UÊKMC keyboard for modular system
UÊRemote control kit
Commands
Modular design
MICS features an innovative design that optimises the possibilities of connecting up several units, reducing the necessary
access space to a minimum and thereby the overall size of the units.
Increasingly better capacity control
The possibility of controlling up to six units as a single product means that MICS can increase the number of available control
steps, thereby ensuring practically perfect adaptation to the real heat load trend.
Keyboard Master Control
KMC is the central control of the cascade modules. Its main function is to supervise operation of all the modules, making
them operate synergically. As a user interface it has a graphic display and a keypad for navigating in the pull-down menus.
Full Floating technology
The full floating technology with automatic control of the airflow rate, water flow rate and water temperature gains a new
function: Flex Energy, used to manage the capacity control steps in linear or alternating sequence in installations with several
modules.

20
r HFC
R-410A
PLATES AXIAL SCROLL COOLING

MICS / FF
Models 0072 0092 0122 0152 0182
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 18,2 23 31,8 39,4 44,7
Total absorbed power (1) kW 6,50 9,30 10,7 13,5 15,5
EER 2,80 2,47 2,97 2,92 2,88
ESEER 4,05 3,93 3,98 4,12 4,17
Absorbed current A 14 19,1 22,2 27,8 31,5
Nominal water flow m3/h 3,10 4 5,50 6,80 7,70
Operational weight kg 310 330 410 450 480
No. fans N. 1 1 2 2 2
No. Compressors N. 2 2 2 2 2
Airflow m3/h 9000 9000 18000 18000 18000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL
Hydraulic connections inches 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Refrigerant R410A R410A R410A R410A R410A
Sound pressure level (2) dB(A) 68 68 71 71 71
Sound power dB(A) 80 80 83 83 83
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630 1630 1630
H mm 1630 1630 1630 1630 1630
P mm 790 790 790 790 790

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

MICS / FFT
Models 0072 0092 0122 0152 0182
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 18,2 23 31,8 39,4 44,7
Total absorbed power (1) kW 6,50 9,30 10,7 13,5 15,5
EER 2,80 2,47 2,97 2,92 2,88
ESEER 4,05 3,93 3,98 4,12 4,17
Absorbed current A 14 19,1 22,2 27,8 31,5
Nominal water flow m3/h 3,10 4 5,50 6,80 7,70
Operational weight kg 310 330 410 450 480
No. fans N. 1 1 2 2 2
No. Compressors N. 2 2 2 2 2
Airflow m3/h 9000 9000 18000 18000 18000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL
Hydraulic connections inches 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Refrigerant R410A R410A R410A R410A R410A
Sound pressure level (2) dB(A) 68 68 71 71 71
Sound power dB(A) 80 80 83 83 83
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630 1630 1630
H mm 1630 1630 1630 1630 1630
P mm 790 790 790 790 790

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

Dimension

P L

21
Hydronic - residential

BRA 0011÷0061
Versions
FF base version, with built-in hydronic kit
FFT base version without hydronic kit

Features
Coil protection grid for all models.
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
The circuit includes:
Air vent valve.
Water circulator.
Differential pressure switch.
Expansion tank.
Safety valve.
Pressure gauge.
Chillers, air source for indoor installation Manual filling assembly.
Drain valve.

4,9 - 15,4 kW Main accessories


UÊHSW10 remote keyboard
Unit Description UÊExternal buffer tank and hydronic connecting kit
BRA is the Climaveneta range of air-cooled liquid chillers with R410A refrigerant. They are UÊExternal main switch kit
fitted with hermetic Scroll compressors and Full Floating technology. The latter is an intelligent
electronic unit providing the perfect answer to residential market requirements: compactness, UÊAdditional circulating pump kit for models 0041÷0061
ease of installation and quietness. UÊRubber anti-vibration mounting kit
UÊRemovable metal mesh water filter kit
Commands
Full Floating features
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts.

22
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL COOLING

BRA / FF
Models 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 4,9 5,6 6,9 8,6 11,0 5,6 7,0 8,7 11,4 13,2 15,4
Total absorbed power (1) kW 2,5 2,6 3,1 4,0 5,2 2,6 3,0 3,7 5,3 5,8 6,4
EER 1,96 2,15 2,23 2,15 2,11 2,15 2,33 2,35 2,15 2,28 2,41
ESEER 2,24 2,48 2,68 2,60 2,39 2,54 2,76 2,70 2,48 2,53 2,78
Absorbed current A 11,9 12,5 15,1 18,3 24,6 6,90 7,10 8,60 13,7 14,3 15
Nominal water flow m3/h 0,80 1 1,20 1,50 1,90 1 1,20 1,50 2 2,30 2,70
Useful head kPa 49 46 42 41 43 46 42 41 43 35 32
Operational weight kg 100 105 115 125 165 105 115 125 165 185 195
No. fans N. 1 1 1 1 2 1 1 1 2 2 2
Airflow m3/h 3200 3200 3600 3600 6800 3200 3600 3600 6800 6800 6800
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1”1/4 3/4” 3/4” 3/4” 1”1/4 1”1/4 1”1/4
Sound pressure level (2) dB(A) 55 55 55 55 60 55 55 55 60 60 60
Sound power dB(A) 68 68 68 68 71 68 68 68 71 71 71
Electrical power supply V-Ph~Hz 230V~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940 1240 1240 1390
P mm 580 580 580 580 580 580 580 580 580 580 630
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

BRA / FFT
Modelli 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 4,9 5,6 6,9 8,6 11 5,6 7 8,7 11,4 13,2 15,4
Total absorbed power (1) kW 2,5 2,6 3,1 4 5,2 2,6 3 3,7 5,3 5,8 6,4
Absorbed current A 1,96 2,15 2,23 2,15 2,11 2,15 2,33 2,35 2,15 2,28 2,41
EER 2,24 2,48 2,68 2,6 2,39 2,54 2,76 2,7 2,48 2,53 2,78
ESEER 11,9 12,5 15,1 18,3 24,6 6,9 7,1 8,6 13,71 14,3 15
Nominal water flow m3/h 0,80 1 1,20 1,50 1,90 1 1,20 1,50 2 2,3 2,7
Operational weight kg 100 105 115 125 165 105 115 125 165 185 195
No. fans N. 1 1 1 1 2 1 1 1 2 2 2
Airflow m3/h 3200 3200 3600 3600 6800 3200 3600 3600 6800 6800 6800
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4” 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 55 55 55 55 60 55 55 55 60 60 60
Sound power dB(A) 68 68 68 68 71 68 68 68 71 71 71
Electrical power supply V-Ph~Hz 230V~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940 1240 1240 1390
P mm 580 580 580 580 580 580 580 580 580 580 630

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

Dimension

23
Hydronic - residential

MICS-C 0072÷0122
Versions
FF base version, with built-in hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Electronic expansion valve
Available water pipe fittings in case of installation under
appliance
The circuit includes:
Multistage centrifugal pump
Air vent valve.
Differential pressure switch.
Expansion tank.
Safety valve.
Pressure gauge.
Chillers, air source for indoor installation Drain valve.

Main accessories
UÊRubber anti-vibration mounting kit
18,2 - 31,8 kW UÊRemovable metal mesh water filter kit
Unit Description UÊCoil protection grids
MICS-C is the Climaveneta range of air-cooled liquid chillers with gas R410A. They are fitted UÊRemote control kit
with hermetic Scroll compressors and Full Floating technology. The latter is an intelligent
electronic unit providing the perfect answer to residential market requirements: compactness,
ease of installation and quietness.

Commands
Full Floating technology
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts.

24
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL COOLING

MICS-C / FF
Models 0072 0092 0122
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 18,2 23 31,8
Total absorbed power (1) kW 6,50 9,31 10,7
EER 2,80 2,47 2,97
ESEER 4,05 3,93 3,98
Absorbed current A 16,1 19,8 27,3
Nominal water flow m3/h 3,10 4 5,50
Operational weight kg 330 350 450
No. fans N. 1 1 2
No. Compressors N. 2 2 2
Airflow m3/h 9000 9000 18000
Compressor type SCROLL SCROLL SCROLL
Hydraulic connections inches 1”1/4 1”1/4 1”1/4
Refrigerant R410A R410A R410A
Sound pressure level (2) dB(A) 74 74 77
Sound power dB(A) 86 86 89
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630
H mm 2000 2000 2000
P mm 790 790 790

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

Dimension

L P

25
Hydronic - residential

BRH 0011÷0121
Versions
FF base version, with built-in hydronic kit
FFT base version without hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops (exchanger on plant side
fitted with heating element for frost protection).
External access to control with anti-tamper device.
The safety of the unit is guaranteed by a door lock
isolator on the electrical power switchboard and by active
protection devices on the main components.
The circuit includes:
Modulating valve to reduce water consumptions
(source side, FF versions only).
Circulating pump (plant side, FF versions only).
Air vent valve (plant side).
Expansion vessel (plant side).
Safety valve (plant side).
Differential pressure switch on plant circuit only.
Drain valve on both plant and source circuits.

Chiller, water source


Main accessories
UÊRemovable metal mesh water filter kit
UÊHSW10 remote keyboard
5,5 - 35,1 kW
Unit Description
BRH is a range of water-source liquid chillers operating with R410A refrigerant. These are
indoor units with hermetic Scroll compressors and Full Floating technology. The latter is an
intelligent electronic unit providing the perfect answer to residential market requirements:
compactness, ease of installation and quietness.

Commands
Floating Set
Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the compressor operating
time and the temperatures of the water in the system. he water storage tank is no longer indispensable because it is
compensated by the Floating Set function, with resulting reduction in: size; weight; installation times; system setting-up
times.
Floating Flow
The controller manages the modulation of the active components (pump and electronic flow valve) through pressure
transducers and temperature sensors. The performance of the unit may thus be optimised for different operating conditions,
such as traditional fan coil system and panel heating system, ensuring: broader operating limits; easier start-up of
installations with both high and low water temperatures; faster system setup.

26
r HFC
R-410A
PLATES SCROLL COOLING

BRH / FF
Models 0011 0021 0025 0031 0041 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 5,50 5,90 7,60 9,20 11,9 5,90 7,70 9,30
Total power input (1) kW 1,50 1,70 2 2,60 3,20 1,60 1,90 2,40
EER 3,67 3,47 3,80 3,54 3,72 3,69 4,05 3,88
ESEER 4,23 3,92 4,47 4,15 4,10 4 4,61 4,38
Water flow rate plant side (1) m3/h 0,90 1 1,20 1,50 1,90 1 1,30 1,50
Absorbed current A 7,50 8 8,90 12,3 15,6 4,60 5 6,10
Operational weight kg 148 148 150 152 160 148 150 152
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches G 3/4” G 3/4” G 3/4” G 3/4” G 1”1/4 G 3/4” G 3/4” G 3/4”
Sound pressure level (2) dB(A) 41 41 42 42 47 41 42 42
Sound power dB(A) 52 52 53 53 58 52 53 53
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 560 560 560 560 560 560 560 560
H mm 980 980 980 980 980 980 980 980
P mm 575 575 575 575 575 575 575 575

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 12,4 13,9 16,5 20,8 24 27,3 35,1
Total power input (1) kW 3,20 3,80 4 5,10 5,80 6,80 8,40
EER 3,88 3,66 4,13 4,08 4,14 4,01 4,18
ESEER 4,28 4,22 4,74 4,62 4,84 4,55 4,59
Water flow rate plant side (1) m3/h 2 2,30 2,70 3,40 3,90 4,50 5,70
Absorbed current A 7,40 8,10 8,80 12,2 13,4 16,1 19,2
Operational weight kg 160 170 175 220 230 235 250
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4
Sound pressure level (2) dB(A) 47 47 48 55 55 59 59
Sound power dB(A) 58 58 59 66 66 70 70
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 560 560 560 680 680 680 680
H mm 980 980 980 1150 1150 1150 1150
P mm 575 575 575 780 780 780 780

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Noise level measured at 1 m in open field conditions

27
BRH / FFT
Models 0011 0021 0025 0031 0041 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 5,50 5,90 7,60 9,20 11,9 5,90 7,70 9,30
Total power input (1) kW 1,50 1,70 2 2,60 3,20 1,60 1,90 2,40
EER 3,67 3,47 3,80 3,54 3,72 3,69 4,05 3,88
ESEER 4,23 3,92 4,47 4,15 4,10 4 4,61 4,38
Water flow rate plant side (1) m3/h 0,90 1 1,20 1,50 1,90 1 1,30 1,50
Absorbed current A 7,50 8 8,90 12,3 15,6 4,60 5 6,10
Operational weight kg 148 148 150 152 160 148 150 152
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches G 3/4” G 3/4” G 3/4” G 3/4” G 1”1/4 G 3/4” G 3/4” G 3/4”
Sound pressure level (2) dB(A) 41 41 42 42 47 41 42 42
Sound power dB(A) 52 52 53 53 58 52 53 53
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 560 560 560 560 560 560 560 560
H mm 980 980 980 980 980 980 980 980
P mm 575 575 575 575 575 575 575 575

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 12,4 13,9 16,5 20,8 24 27,3 35,1
Total power input (1) kW 3,20 3,80 4 5,10 5,80 6,80 8,40
EER 3,88 3,66 4,13 4,08 4,14 4,01 4,18
ESEER 4,28 4,22 4,74 4,62 4,84 4,55 4,59
Water flow rate plant side (1) m3/h 2 2,30 2,70 3,40 3,90 4,50 5,70
Absorbed current A 7,40 8,10 8,80 12,2 13,4 16,1 19,2
Operational weight kg 160 170 175 220 230 235 250
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4
Sound pressure level (2) dB(A) 47 47 48 55 55 59 59
Sound power dB(A) 58 58 59 66 66 70 70
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 560 560 560 680 680 680 680
H mm 980 980 980 1150 1150 1150 1150
P mm 575 575 575 780 780 780 780

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Noise level measured at 1 m in open field conditions

Dimension

L P

28
29
Hydronic - residential

HE FF 0011÷0121
Versions
FF base version, with built-in hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Differential pressure switch.
The remote condenser may be installed up to a distance
of 50 metres from the cooling unit.
The safety of the unit is guaranteed by a door lock
isolator on the electrical power switchboard and by active
protection devices on the main components.

Main accessories
UÊBuffer tank plus pump
UÊHydronic kit plus pump
UÊRemovable metal mesh water filter kit
UÊModulating pump kit
UÊControl board for the modulating pump kit
Condenserless units

4,7 - 32,4 kW
Unit Description
HH FF is the Climaveneta range of cooling units. These are indoor units that may be
combined with remote outdoor condensers to guarantee maximum flexibility and compliance
with any architectural restriction. These units have hermetic Scroll compressors and Full
Floating technology. The latter is an intelligent electronic unit providing the perfect answer to
residential market requirements: compactness, ease of installation and quietness.

Commands
Full Floating features
Once every 3 minutes an algorithm automatically optimises the water set point in relation to the compressor operating
time and the temperatures of the water in the system. The water storage tank is no longer indispensable because it is
compensated by the Floating Set function, with resulting reduction in: size; weight; installation times; system setting-up times.

30
r HFC
R-407C
PLATES SCROLL COOLING

HE FF
Models 0011 0021 0025 0031 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 4,70 6,10 7 8,20 6,10 7 8,20
Total absorbed power (1) kW 1,60 2,10 2,50 2,90 2,10 2,40 2,90
EER 2,84 2,89 2,80 2,79 2,94 2,86 2,86
ESEER 3,20 3,32 3,22 3,27 3,41 3,30 3,38
Absorbed current A 7,67 9,81 11,6 13,7 3,77 4,56 5,22
Water flow in cooling m3/h 0,90 1,10 1,30 1,50 1,10 1,30 1,50
Pressure drop kPa 22 24 26 27 24 26 27
Operational weight kg 68 70 71 74 70 71 74
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R407C R407C R407C R407C R407C R407C R407C
Hydraulic connections inches 3/8” 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
Gas connection inches 1/2” 1/2” 5/8” 5/8” 1/2” 5/8” 5/8”
In/out gas water fittings inches 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
Sound pressure level (2) dB(A) 43 43 48 48 43 48 48
Sound power dB(A) --- --- --- --- --- --- ---
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 400 400 400 400 400 400 400
H mm 960 960 960 960 960 960 960
P mm 450 450 450 450 450 450 450

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 10,5 12,5 15 19,1 22,2 26,8 32,4
Total absorbed power (1) kW 3,40 4,20 4,90 6,30 7,80 8,90 10,9
EER 3,06 2,97 3,07 3,03 2,86 3 2,96
ESEER 3,54 3,36 3,81 3,45 3,22 3,43 3,32
Absorbed current A 6,20 7,60 8,81 12 14,1 16,2 18,9
Water flow in cooling m3/h 1,90 2,30 2,80 3,40 4,10 4,80 5,90
Pressure drop kPa 19 20 20 23 22 23 23
Operational weight kg 85 87 90 177 180 187 190
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R407C R407C R407C R407C R407C R407C R407C
Hydraulic connections inches 1/2” 1/2” 1/2” 5/8” 5/8” 3/4” 3/4”
Gas connection inches 3/4” 3/4” 3/4” 7/8” 7/8” 7/8” 7/8”
In/out gas water fittings inches 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Sound pressure level (2) dB(A) 52 52 52 52 52 53 53
Sound power dB(A) --- --- --- --- --- --- ---
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 400 400 400 600 600 600 600
H mm 960 960 960 960 960 960 960
P mm 450 450 450 600 600 600 600
Note:
1 Evaporator water (in/out): 12/7°C; Condensation temperature: 47°C.
2 Noise level measured at 1 m in open field conditions

Dimension

P
L

31
Hydronic - residential

NHCR 0011÷0121
Versions
NHCR base version

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
The remote condenser may be installed up to a distance
of 50 metres from the cooling unit.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area.

Remote condenser with axial fans

8,6 - 41,9 kW
Unit Description
NHCR are remote condensers with axial fans for condenserless units.

32
COOLING

NHCR
Models 0011 0021 0025 0031 0041 0051 0061 0071 0091 0101 0121
Nominal Cooling capacity (1) kW 8,6 8,6 17,2 17,2 17,2 18,9 25,8 28,3 28,3 37,5 41,9
Fan Diameter mm 1 x 400 1 x 400 2 x 400 2 x 400 2 x 400 2 x 400 3 x 400 3 x 400 3 x 400 2 x 500 2 x 500
Airflow m3/h 2283 2283 4570 4570 4570 4058 6850 6080 6080 10440 9690
RPM n°/min 940 940 940 940 940 940 940 940 940 890 890
Total absorbed power (1) kW 1 x 0,12 1 x 0,12 2 x 0,12 2 x 0,12 2 x 0,12 2 x 0,12 3 x 0,12 3 x 0,12 3 x 0,12 2 x 0,29 2 x 0,29
Absorbed current A 1 x 0,46 1 x 0,46 2 x 0,46 2 x 0,46 2 x 0,46 2 x 0,46 3 x 0,46 3 x 0,46 3 x 0,46 2 x 1,15 2 x 1,15
Current input at maximum
n° x A 1 x 0,55 1 x 0,55 2 x 0,55 2 x 0,55 2 x 0,55 2 x 0,55 3 x 0,55 3 x 0,55 3 x 0,55 2 x 1,25 2 x 1,25
conditions
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
Inlet connections mm 14 14 20 20 20 22 24 28 28 35 35
Outlet connections mm 12 12 18 18 18 20 22 22 22 28 28
Operational weight kg 33 33 37 37 37 46 66 66 73 93 101
Attacco presa pressione inch 1/4” 1/4” 1/4” 1/4” 1/4” 1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
No. fans N. 1 1 2 2 2 2 3 3 3 2 2
COOLING ONLY VERSION
Sound pressure level (2) dB(A) 35 35 38 38 38 38 40 40 40 42 42
DIMENSION
L mm 780 780 1380 1380 1380 1380 1830 1830 1830 2042 2042
H mm 555 555 555 555 555 555 555 555 555 828 828
P mm 362 362 362 362 362 362 362 362 362 554 554

Note:
1 The nominal capacity refers to a ∆t = 15°K.
2 Sound pressure measured at 10 m in open field conditions

Dimension

33
Hydronic - residential

BRAN 0011÷0121
Versions
FF base version, with built-in hydronic kit
FF-SL super-low noise version, with built-in
hydronic kit
FFT base version without hydronic kit
FFT-SL super-low noise version without hydronic
kit

Features
Condensate collecting tray for models 0011 ÷ 0061.
Coil protection grid for models 0011÷0061.
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Phase sequence controller for models 0071÷0121
Differential pressure switch.
Air vent valve.

reversible unit, air source for outdoor The hydronic circuit on the FF models includes:
Water circulator for models 0011 ÷ 0061
installation Multistage centrifugal pump for models 0071 ÷ 0121.
Expansion tank.
4,6 - 35,5 kW Safety valve.
Manual filling assembly.
Unit Description
BRAN is the Climaveneta range of air-cooled reversible heat pumps with gas R410A. They Pressure gauge.
are outdoor units with axial fans, hermetic Scroll compressors and Full Floating technology. Drain valve.
The latter is an intelligent electronic unit providing the perfect answer to residential market
requirements: compactness, ease of installation and quietness. Main accessories
UÊRemovable metal mesh water filter kit
Commands UÊRubber anti-vibration mounting kit
Full Floating features UÊCondensate collecting tray for models 0071 ÷ 0121
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and UÊCoil protection grid for models 0071÷0121
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of UÊAdditional circulating pump kit for models 0041÷0061
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts. UÊExternal main switch kit
UÊExternal buffer tank and hydronic connecting kit
UÊHSW10 remote keyboard

34
r HFC
R-410A
PLATES AXIAL SCROLL HEATING COOLING

BRAN / FF
Models 0011 0021 0025 0031 0041 0021 0025 0031
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 4,6 5,4 6,6 8,2 10,4 5,3 6,7 8,2
Total absorbed power (1) kW 1,9 2,1 2,5 3,4 4,1 2,0 2,4 3,1
EER 2,42 2,57 2,64 2,41 2,53 2,65 2,79 2,64
ESEER 2,96 3,19 3,16 3,01 3,01 3,21 3,41 3,17
Nominal Heating power (2) kW 5,7 6,5 8,1 10,0 12,4 6,4 8,0 9,7
Total absorbed power (2) kW 2,3 2,4 2,9 3,6 4,5 2,4 2,7 3,2
COP 2,48 2,71 2,79 2,78 2,76 2,67 2,96 3,03
Absorbed current A 10,6 11,3 13,9 16,1 21,2 4,84 4,94 6,14
Nominal water flow (1) m3/h 0,80 0,90 1,10 1,40 1,80 0,90 1,20 1,40
Useful head (1) kPa 49 46 42 41 43 46 42 41
Operational weight kg 90 95 110 115 140 95 110 115
No. fans N. 1 1 1 1 2 1 1 1
Airflow m3/h 2400 3500 3500 4200 6800 3500 3500 4200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4”
Sound pressure level (3) dB(A) 54 55 55 55 58 55 55 55
Sound power dB(A) 65 66 66 66 69 66 66 66
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940
P mm 370 370 370 370 370 370 370 370

Models 0041 0051 0061 0071 0091 0101 0121


HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 10,8 12,6 14,6 18,4 20,8 25,1 31,3
Total absorbed power (1) kW 4,2 4,7 5,2 6,8 7,8 8,7 11,1
EER 2,57 2,68 2,81 2,71 2,67 2,88 2,82
ESEER 3,13 3,08 3,33 3,20 3,12 3,36 3,24
Nominal Heating power (2) kW 12,8 14,4 16,8 21,0 23,6 28,8 35,5
Total absorbed power (2) kW 4,7 5,0 5,4 7,1 7,8 10,1 11,8
COP 2,72 2,88 3,11 2,96 3,03 2,85 3,01
Absorbed current A 9,28 9,48 9,98 15,1 15,8 24,4 25,8
Nominal water flow (1) m3/h 1,90 2,20 2,50 3,20 3,60 4,30 5,40
Useful head (1) kPa 43 35 32 116 90 130 108
Operational weight kg 140 160 170 265 270 340 345
No. fans N. 2 2 2 1 1 2 2
Airflow m3/h 6800 6800 6400 9800 9800 14000 14000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (3) dB(A) 58 58 58 65 65 65 65
Sound power dB(A) 69 69 69 76 76 79 79
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 1450 1450 1450 1450
H mm 1240 1240 1390 1200 1200 1700 1700
P mm 370 370 420 550 550 550 550

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

35
BRAN / FFT
Models 0011 0021 0025 0031 0041 0021 0025 0031
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 4,6 5,4 6,6 8,2 10,4 5,3 6,7 8,2
Total absorbed power (1) kW 1,9 2,1 2,5 3,4 4,1 2,0 2,4 3,1
EER 2,42 2,57 2,64 2,41 2,53 2,65 2,79 2,64
ESEER 2,96 3,19 3,16 3,01 3,01 3,21 3,41 3,17
Nominal Heating power (2) kW 5,70 6,50 8,10 10 12,4 6,40 8 9,70
Total absorbed power (2) kW 2,30 2,40 2,90 3,60 4,50 2,40 2,70 3,20
COP 2,48 2,71 2,79 2,78 2,76 2,67 2,96 3,03
Absorbed current A 10,6 11,3 13,9 16,1 21,2 4,84 4,94 6,14
Nominal water flow (1) m3/h 0,80 0,90 1,10 1,40 1,80 0,90 1,20 1,40
Operational weight kg 90 95 110 115 140 95 110 115
No. fans N. 1 1 1 1 2 1 1 1
Airflow m3/h 2400 3500 3500 4200 6800 3500 3500 4200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4”
Sound pressure level (3) dB(A) 54 55 55 55 58 55 55 55
Sound power dB(A) 65 66 66 66 69 66 66 66
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940
P mm 370 370 370 370 370 370 370 370

Models 0041 0051 0061 0071 0091 0101 0121


HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 10,8 12,6 14,6 18,4 20,8 25,1 31,3
Total absorbed power (1) kW 4,2 4,7 5,2 6,8 7,8 8,7 11,1
EER 2,57 2,68 2,81 2,71 2,67 2,88 2,82
ESEER 3,13 3,08 3,33 3,20 3,12 3,36 3,24
Nominal Heating power (2) kW 12,8 14,4 16,8 21 23,6 28,8 35,5
Total absorbed power (2) kW 4,70 5 5,40 7,10 7,80 10,1 11,8
COP 2,72 2,88 3,11 2,96 3,03 2,85 3,01
Absorbed current A 9,28 9,48 9,98 15,1 15,8 24,4 25,8
Nominal water flow (1) m3/h 1,90 2,20 2,50 3,20 3,60 4,30 5,40
Operational weight kg 140 160 170 265 270 340 345
No. fans N. 2 2 2 1 1 2 2
Airflow m3/h 6800 6800 6400 9800 9800 14000 14000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (3) dB(A) 58 58 58 65 65 65 65
Sound power dB(A) 69 69 69 76 76 79 79
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 1450 1450 1450 1450
H mm 1240 1240 1390 1200 1200 1700 1700
P mm 370 370 420 550 550 550 550

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

36
BRAN / FF-SL
Models 0071 0091 0101 0121
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 18,4 20,8 25,1 31,3
Total absorbed power (1) kW 6,5 7,5 7,95 10,35
EER 2,83 2,77 3,16 3,02
ESEER 3,36 3,26 3,68 3,47
Nominal Heating power (2) kW 21,0 23,6 28,8 35,5
Total absorbed power (2) kW 6,8 7,6 9,4 11,1
COP 3,09 3,11 3,06 3,2
Absorbed current A 12,9 13,6 21,3 22,7
Nominal water flow (1) m3/h 3,20 3,60 4,30 4,90
Useful head (1) kPa 116 90 130 108
Operational weight kg 265 270 340 345
No. fans N. 2 2 3 3
Airflow m3/h 7000 7000 10500 10500
Compressor type SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (3) dB(A) 62 62 63 63
Sound power dB(A) 73 73 74 74
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1450 1450 1450 1450
H mm 1200 1200 1700 1700
P mm 550 550 550 550
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

BRAN / FFT-SL
Models 0071 0091 0101 0121
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 18,4 20,8 25,1 31,3
Total absorbed power (1) kW 6,5 7,5 7,95 10,35
EER 2,83 2,77 3,16 3,02
ESEER 3,36 3,26 3,68 3,47
Nominal Heating power (2) kW 21,0 23,6 28,8 35,3
Total absorbed power (2) kW 6,8 7,6 9,4 11,1
COP 3,09 3,11 3,06 3,2
Absorbed current A 12,9 13,6 21,3 22,7
Nominal water flow (1) m3/h 3,20 3,60 4,30 5,40
Operational weight kg 265 280 340 345
No. fans N. 2 2 3 3
Airflow m3/h 7000 7000 10500 10500
Compressor type SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A
Hydraulic connections inches 1” 1/4 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (3) dB(A) 62 62 63 63
Sound power dB(A) 73 73 74 74
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1450 1450 1450 1450
H mm 1200 1200 1700 1700
P mm 550 550 550 550

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

Dimension

H
H H

P
P
A
L L P

37
Hydronic - residential

MICS-N 0072÷0182
Versions
FF base version, with built-in hydronic kit
FFT base version without hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Electronic expansion valve
Available water pipe fittings in case of installation under
appliance
Differential pressure switch.
Air vent valve.
The hydronic circuit on the FF models includes:
Multistage centrifugal pump
Expansion tank.
Safety valve.
Modular reversible unit, air source for outdoor Pressure gauge.
Drain valve.
installation
Main accessories
17,3 - 47,9 kW UÊRemote control kit
Unit Description UÊKit for connecting the KMC keyboard
MICS-N is the Climaveneta range of reversible air-cooled heat pumps. They are outdoor UÊKMC keyboard for modular system
units with axial fans, hermetic Scroll compressors and Full Floating technology. The latter is UÊCoil protection grids
an intelligent electronic unit providing the perfect answer to residential market requirements:
UÊRemovable metal mesh water filter kit
compactness, ease of installation and quietness.
UÊRubber anti-vibration mounting kit

Commands
Keyboard Master Control
MICS features an innovative design that optimises the possibilities of connecting up several units, reducing the necessary
access space to a minimum and thereby the overall size of the units.
Increasingly better capacity control
The possibility of controlling up to six units as a single product means that MICS can increase the number of available control
steps, thereby ensuring practically perfect adaptation to the real heat load trend.
Modular design
KMC is the central control of the cascade modules. Its main function is to supervise operation of all the modules, making
them operate synergically. As a user interface it has a graphic display and a keypad for navigating in the pull-down menus.
Full Floating technology
The full floating technology with automatic control of the airflow rate, water flow rate and water temperature gains a new
function: Flex Energy, used to manage the capacity control steps in linear or alternating sequence in installations with several
modules.

38
r HFC
R-410A
PLATES AXIAL SCROLL HEATING COOLING

MICS-N / FF
Models 0072 0092 0122 0152 0182
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 17,3 21,8 30,3 37,4 42,5
Total absorbed power (1) kW 6,50 9,30 10,7 13,4 15,5
EER 2,66 2,34 2,83 2,79 2,74
ESEER 3,86 3,75 3,78 3,92 3,96
Nominal water flow m3/h 3 3,80 5,20 6,40 7,30
Nominal Heating power (2) kW 20,2 26,1 33,9 42,6 47,9
Total absorbed power (2) kW 6,50 8,60 11,2 14 15,4
COP 3,11 3,02 3,03 3,04 3,11
Absorbed current A 14 17,7 23,9 29,3 31,3
Nominal water flow m3/h 3,50 4,50 5,90 7,40 8,30
Hydraulic connections inches 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Operational weight kg 310 330 410 450 480
No. fans N. 1 1 2 2 2
Airflow m3/h 9000 9000 18000 18000 18000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A
Sound pressure level (3) dB(A) 68 68 71 71 71
Sound power dB(A) 80 80 83 83 83
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630 1630 1630
H mm 1630 1630 1630 1630 1630
P mm 790 790 790 790 790
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

MICS-N / FFT
Models 0072 0092 0122 0152 0182
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 17,3 21,8 30,3 37,4 42,5
Total absorbed power (1) kW 6,50 9,30 10,7 13,4 15,5
EER 2,66 2,34 2,83 2,79 2,74
ESEER 3,86 3,75 3,78 3,92 3,96
Nominal water flow m3/h 3 3,80 5,20 6,40 7,30
Nominal Heating power (2) kW 20,2 26,1 33,9 42,6 47,9
Total absorbed power (2) kW 6,50 8,60 11,2 14 15,4
COP 3,11 3,02 3,03 3,04 3,11
Absorbed current A 14 17,7 23,9 29,3 31,3
Nominal water flow m3/h 3,50 4,50 5,90 7,40 8,30
Hydraulic connections inches 1”1/4 1”1/4 1”1/4 1”1/4 1”1/4
Operational weight kg 310 330 410 450 480
No. fans N. 1 1 2 2 2
Airflow m3/h 9000 9000 18000 18000 18000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A
Sound pressure level (3) dB(A) 68 68 71 71 71
Sound power dB(A) 80 80 83 83 83
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630 1630 1630
H mm 1630 1630 1630 1630 1630
P mm 790 790 790 790 790
Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

Dimension

P L

39
Hydronic - residential

BRN 0011÷0061
Versions
FF base version, with built-in hydronic kit
FFT base version without hydronic kit

Features
Condensate collecting tray for all models
Coil protection grid for all models.
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
The circuit includes:
Air vent valve.
Water circulator.
Differential pressure switch.
Expansion tank.
Safety valve.
Reversible unit, air source for indoor Pressure gauge.
Manual filling assembly.
installation Drain valve.

4,6 - 16,8 kW Main accessories


Unit Description UÊHSW5 remote keyboard
BRN is the Climaveneta range air-cooled heat pumps with gas R410A. They are fitted with UÊExternal buffer tank and hydronic connecting kit
hermetic Scroll compressors and Full Floating technology. The latter is an intelligent electronic UÊExternal main switch kit
unit providing the perfect answer to residential market requirements: compactness, ease of UÊAdditional circulating pump kit for models 0041÷0061
installation and quietness.
UÊRubber anti-vibration mounting kit
UÊRemovable metal mesh water filter kit
Commands
Full Floating features
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts.

40
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL HEATING COOLING

BRN / FF
Models 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 4,6 5,4 6,6 8,2 10,4 5,3 6,7 8,2 10,8 12,6 14,6
Total absorbed power (1) kW 2,5 2,6 3,1 4,0 5,2 2,6 3,0 3,7 5,3 5,8 6,4
EER 1,84 2,08 2,13 2,05 2,04 2,23 2,22 2 2,04 2,17 2,28
ESEER 2,11 2,37 2,53 2,48 2,44 2,62 2,58 2,27 2,36 2,40 2,62
Nominal Heating power (2) kW 5,7 6,5 8,1 10,0 12,4 6,4 8,0 9,7 12,8 14,4 16,8
Total absorbed power (2) kW 2,8 2,9 3,5 4,2 5,7 2,9 3,3 3,8 5,9 6,1 6,5
COP 2,04 2,24 2,31 2,38 2,21 2,42 2,55 2,17 2,17 2,36 2,58
Absorbed current A 13,3 14 16,6 18,8 26,6 7,50 7,60 8,80 14,6 14,8 15,3
Nominal water flow m3/h 1 1,40 1,70 1,10 1,70 1,10 2,20 1,40 2,20 2,50 2,90
Useful head kPa 49 46 42 41 43 46 42 41 43 35 32
Operational weight kg 110 125 135 115 135 115 180 125 180 200 210
No. fans N. 1 1 1 1 2 1 1 1 2 2 2
Airflow m3/h 2200 2700 2400 3100 2x3100 2700 2400 3100 2x3100 2x3000 2x3200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1”1/4 3/4” 3/4” 3/4” 1”1/4 1”1/4 1”1/4
Sound pressure level (3) dB(A) 55 55 55 55 60 55 55 55 60 60 60
Sound power dB(A) 68 68 68 68 68 68 68 71 71 71 71
Electrical power supply V-Ph~Hz 230V~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940 1240 1240 1390
P mm 580 580 580 580 580 580 580 580 580 580 630

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

BRN / FFT
Models 0011 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 4,6 5,4 6,6 8,2 10,4 5,3 6,7 8,2 10,8 12,6 14,6
Total absorbed power (1) kW 5,7 6,5 8,1 10 12,4 6,4 8 9,7 12,8 14,4 16,8
EER 1,84 2,08 2,13 2,05 2,04 2,23 2,22 2 2,04 2,17 2,28
ESEER 2,11 2,37 2,53 2,48 2,44 2,62 2,58 2,27 2,36 2,4 2,62
Nominal Heating power kW 5,7 6,5 8,1 10 12,4 6,4 8 9,7 12,8 14,4 16,8
Total absorbed power kW 2,8 2,9 3,5 4,2 5,7 2,9 3,3 3,8 5,9 6,1 6,5
COP 2,04 2,24 2,31 2,38 2,21 2,42 2,55 2,17 2,17 2,36 2,58
Absorbed current A
Nominal water flow m3/h 1 1,4 1,7 1,1 1,7 1,1 2,2 1,4 2,2 2,5 2,9
Operational weight kg 110 125 135 115 135 115 180 125 180 200 210
No. fans N. 1 1 1 1 2 1 1 1 2 2 2
Airflow m3/h 2200 2700 2400 3100 2x3100 2700 2400 3100 2x3100 2x3000 2x3200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches 3/4” 3/4” 3/4” 3/4” 1” 1/4 3/4” 3/4” 3/4” 1” 1/4 1” 1/4 1” 1/4
Sound pressure level (2) dB(A) 55 55 55 55 60 55 55 55 60 60 60
Sound power dB(A) 68 68 68 68 68 68 68 71 71 71 71
Electrical power supply V-Ph~Hz 230V~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940 1240 1240 1390
P mm 580 580 580 580 580 580 580 580 580 580 630

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Noise level measured at 1 m in open field conditions

Dimension

41
Hydronic - residential

MICS-CN 0072÷0122
Versions
FF base version, with built-in hydronic kit

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Electronic expansion valve
Available water pipe fittings in case of installation under
appliance
The circuit includes:
Multistage centrifugal pump
Air vent valve.
Differential pressure switch.
Expansion tank.
Safety valve.
Pressure gauge.
Reversible unit, air source for indoor Drain valve.

installation Main accessories


UÊRubber anti-vibration mounting kit
17,3 - 33,9 kW UÊRemovable metal mesh water filter kit
Unit Description UÊCoil protection grids
MICS-CN is the Climaveneta range air-cooled heat pumps with gas R410A. These are indoor UÊRemote control kit
units that, thanks to the ducted centrifugal fans, may also be installed outdoors. They are
fitted with hermetic Scroll compressors and Full Floating technology. The latter is an intelligent
electronic unit providing the perfect answer to residential market requirements: compactness,
ease of installation and quietness.

Commands
Full Floating technology
The new generation electronic controller allows to manage the chiller by using the Full Floating technology, designed by
Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump (Floating Flow) and
finally for the working temperature (Floating Setpoint). This also allows to achieve all the following benefits: improvement of
efficiency in both standard and extreme conditions, much lower operating noise in part load conditions, lower installation
time, lower time for system set-up, broader operating limits, faster transient after defrosts.

42
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL HEATING COOLING

MICS-CN / FF
Models 0072 0092 0122
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 17,3 21,8 30,3
Total absorbed power (1) kW 6,50 9,32 10,7
EER 2,66 2,34 2,83
ESEER 3,86 3,75 3,78
Nominal water flow m3/h 3 3,80 5,20
Nominal Heating power (2) kW 20,2 26 33,9
Total absorbed power (2) kW 6,50 8,61 11,2
COP 3,11 3,02 3,03
Absorbed current A 16,1 19,8 27,3
Nominal water flow m3/h 3,50 4,50 5,90
Hydraulic connections inches 1”1/4 1”1/4 1”1/4
Operational weight kg 310 330 410
No. fans N. 1 1 2
Airflow m3/h 9000 9000 18000
Compressor type SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A
Sound pressure level (3) dB(A) 74 74 77
Sound power dB(A) 86 86 89
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1040 1040 1630
H mm 2000 2000 2000
P mm 790 790 790

Note:
1 Evaporator water (in/out) 12/7°C, condenser air (in) 35°C, based on Eurovent standard
2 Condenser water (in/out) 40/45°C, evaporator air (in) 7°C (r.h. 87%), based on Eurovent standard
3 Noise level measured at 1 m in open field conditions

Dimension

L P

43
Hydronic - residential

WWr MTD 011m÷121t


Versions
WWr MTD base version

Features
Structure and base in hot-dip galvanised steel with epoxy
powder paint finish.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
External access to control with anti-tamper device.
User interface with display.
The safety of the unit is guaranteed by a door lock
isolator on the electrical power switchboard and by active
protection devices on the main components.
The circuit includes:
Circulating pump (plant side, FF versions only).
Air vent valve (plant side).
Modulating valve to reduce water consumptions
(source side, FF versions only).
Expansion vessel (plant side).
Safety valve (plant side).
Differential pressure switch on both plant and source
circuits.
Drain valve on both plant and source circuits.

Reversible unit, water source Main accessories


UÊRemovable metal mesh water filter kit
UÊExternal temperature sensor (mandatory with HSW12
5,2 - 41,7 kW remote keyboard)
UÊHSW12 remote keyboard
Unit Description
WWr MTD is the Climaveneta range of water-cooled heat pumps provided with R410A
refrigerant. These are indoor units with hermetic Scroll compressors and Full Floating
technology. The latter is an intelligent electronic unit providing the perfect answer to residential
market requirements: compactness, ease of installation and quietness.

Commands
Floating Set
Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the compressor operating
time and the temperatures of the water in the system. he water storage tank is no longer indispensable because it is
compensated by the Floating Set function, with resulting reduction in: size; weight; installation times; system setting-up
times.
Floating Flow
The controller manages the modulation of the active components (pump and electronic flow valve) through pressure
transducers and temperature sensors. The performance of the unit may thus be optimised for different operating conditions,
such as traditional fan coil system and panel heating system, ensuring: broader operating limits; easier start-up of
installations with both high and low water temperatures; faster system setup.

44
r HFC
R-410A
PLATES SCROLL HEATING COOLING

WWr MTD
Models 011m 021m 025m 031m 041m
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 5,20 5,60 7,20 8,80 11,3
Total power input (1) kW 1,50 1,70 2 2,60 3,20
EER 3,47 3,29 3,60 3,38 3,53
ESEER 4,03 3,73 4,26 3,95 3,90
Water flow rate plant side (1) m3/h 0,90 1 1,20 1,50 1,90
Heating capacity (2) 6,80 7,50 9,20 11,6 14,6
Total absorbed power (2) kW 1,70 1,90 2,30 3 3,60
COP 4 3,95 4 3,87 4,06
Water flow rate plant side (2) 1,20 1,30 1,60 2 2,50
Absorbed current A 7,50 8 8,90 12,3 15,6
Operational weight kg 148 148 150 152 160
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A
Hydraulic connections inches G 3/4” G 3/4” G 3/4” G 3/4” G 1”1/4
Sound pressure level (3) dB(A) 41 41 42 42 47
Sound power dB(A) 52 52 53 53 58
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
L mm 560 560 560 560 560
H mm 980 980 980 980 980
P mm 575 575 575 575 575

Models 021t 025t 031t 041t 051t 061t 071t 091t 101t 121t
HEAT PUMP MODEL
Nominal Cooling capacity (1) kW 5,60 7,30 8,90 11,8 13,2 15,7 19,8 22,9 26 33,4
Total power input (1) kW 1,60 1,90 2,40 3,20 3,80 4 5,10 5,80 6,80 8,40
EER 3,50 3,84 3,71 3,69 3,47 3,93 3,88 3,95 3,82 3,98
ESEER 3,81 4,39 4,17 4,08 4,02 4,51 4,40 4,61 4,33 4,37
Water flow rate plant side (1) m3/h 1 1,30 1,50 2 2,30 2,70 3,40 3,90 4,50 5,70
Heating capacity (2) 7,40 9,20 11,4 15,3 17,1 20 24,8 28,8 33 41,7
Total absorbed power (2) kW 1,90 2,20 2,70 3,70 4,20 4,60 5,80 6,40 7,60 9,50
COP 3,89 4,18 4,22 4,14 4,07 4,35 4,28 4,50 4,34 4,39
Water flow rate plant side (2) 1,30 1,60 2 2,60 2,90 3,40 4,30 5 5,70 7,20
Absorbed current A 4,60 5 6,10 7,40 8,10 8,80 12,2 13,4 16,1 19,2
Operational weight kg 148 150 152 160 170 175 220 230 235 250
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
Hydraulic connections inches G 3/4” G 3/4” G 3/4” G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4 G 1”1/4
Sound pressure level (3) dB(A) 41 42 42 47 47 48 55 55 59 59
Sound power dB(A) 52 53 53 58 58 59 66 66 70 70
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 560 560 560 560 560 560 680 680 680 680
H mm 980 980 980 980 980 980 1150 1150 1150 1150
P mm 575 575 575 575 575 575 780 780 780 780

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out), 10/5°C, condenser water (in/out) 40/45°C, based on Eurovent standard
3 Sound pressure measured at 1 m in open field conditions

Dimension

L P

45
PRANA

i-NRG 0061m÷0061t
Versioni
i-NRG Reversible heat pump with inverter compressor,
total heat recovery, air source for indoor/outdoor
installation

Features

Structure and base in hot galvanised epoxy powder coated


steel.
Stainless steel (AISI 316) with high efficiency and low
pressure drop plate to plate exchanger (at the domestic hot
water side). It is positioned next after the compressor, it
ensures the domestic hot water production. That can work
either in full recovery or in part, with the constant
optimization of efficiency through logic advanced adjusting
controller
Exchangers plant side plate of stainless steel AISI 316 with
high efficiency and low pressure drop meets the supply of
both hot or cold water for the facility, regardless of the
domestic hot water
DC inverter scroll compressor with self-adaptive capacity
adjustment.
Electronic expansion valve
Finned coils made with copper pipes and aluminium fins
Reversible heat pump with inverter with large exchange surface area (100% fully quality tested)
Axial electric fan in continuous current housed in
compressor, total heat recovery, air source aerodynamic conveyor profile with safety grill.
Low external air temperature device: continuous fan speed
for indoor/outdoor installation 16,3 kW regulation with pressure switch
The water circuit comes complete with:
Unit description • Variable flow circulating pump in continuous current,
The new i-NRG heat pump provides exactly the energy required by the system, plant side.
perfectly following the real load of the building, thanks to the modulation of the DC • Variable flow circulating pump in continuous current,
inverter fan. One single unit for the highest efficiency, sustainability and huge savings, hot water side.
thanks to the advantages of DC frequency driven fans and circulating pumps (inverter) • Expansion tank 10 lt.
for both plant and domestic hot water circuits. • Safety valve 3 bar.
i-NRG is the new generation heat pump for all year round operation in any operating • Differential pressure swich plant side.
mode: single cycle (air conditioning, heating, domestic hot water) as well as combined • Pressure gauge.
cycle (domestic hot water together with heating or cooling). Domestic hot water • Manual filling assembly.
production is guaranteed by the dedicated exchanger for heat recovery: total, for free
domestic hot water production, or partial. Domestic hot water is stored in a properly
dimensioned storage tank. Main accessories
The unit can be installed indoor or outdoor, thus ensuring complete flexibility. • Room terminal with temperature and humidity probe
• Expansion module for plant circuits additional
• Expansion module for solar thermal collector
Commands • Buffer tank 35,100,200 liters
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and • Hot water cylinder 300,500 liters
increasing the energy efficienty. The electronic board allows you to manage: • 300 litres thermal store for domestic hot water, for kit
- a zone of direct heating for radiator, floor heating or fan coil DOMH2O
- zone with mix valve for floor heating
- outdoor temperature sensor for water plant side modular set point compensation • 300, 500, 1000 litres thermal store for domestic hot
- electrical heating element for possible integration and anti-legionellosis cycle for cylinder water with solar heat exchanger, for kit DOMH2O
- boiler in substitution or in additional • DOMH2O15 e DOMH2O24 kit for domestic hot water
- integration by solar panels with extension module (accessorie)
- several solutions through appropriate configurations of the controller and use of dedicated extension modules with external heat exchanger plate-to-plate
(accessories) and pump
• Removable metal mesh water filter kit
• Kit acoustic insulationg casing kit (mandatory for
outdoor installation)
• KIt rectangular air ducts and grills for indoor installation

48
i-NRG
Models 0061m 0061t
Nominal heating power (1) kW 16,3 16,3
Total absorbed power (2) kW 4,0 4,0
COP EN 14511 3,91 3,94
Cooling capacity (3) kW 19,6 19,7
Total absorbed power (2) kW 5,40 5,40
EER EN 14511 3,62 3,66
Total absorbed power (4) kW 17,9 18
Total absorbed power kW 4,9 4,9
Recovery heating capacity kW 22,6 22,6
Compressor type SCROLL INVERTER DC SCROLL INVERTER DC
N. Compressors N. 1 1
Refrigerant R410A R410A
N. fans N. 1 1
Plant side pump type (5) i-Ci i-Ci
Recovery side pump type (5) i-Ci i-Ci
Electrical power supply V-Ph~Hz 230-1~50 400-3N~50
Sound power (6) dB(A) 68 68
Sound pressure (7) dB(A) 52 52
DIMENSION
L (8) mm 750 750
L (9) mm 1535 1535
H mm 1600 1600
P mm 1050 1050
Operational weight kg 260 260

NOTE
(1) Water in-out 30/35°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u.
(2) Total input is obtained from compressor input and fan input.
(3) Water in-out 23/18°C (plant side), outdoor air temperature 35°C b.s.
(4) Water in-out 23/18°C (plant side), water in-out 45/50°C (total recovery side)
(5) i-Ci= Circolatore inverter corrente continua H
(6) Sound power level according to ISO 9614 and Eurovent 8/1
(7) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
(8) Indoor installation
(9) Outdoor installation P
L (8)
L (9)

49
PRANA

AWR DHW 0021m÷0101ts


Versioni
AWR DHW Air source reversible heat pump with
domestic hot water supply with total heat
recovery
AWR DHW - SL Air source reversible heat pump with
domestic hot water supply with total heat
recovery

Features

Structure and base in hot galvanised epoxy powder coated


steel.
Stainless steel (AISI 316) with high efficiency and low
pressure drop plate to plate exchanger (at the domestic hot
water side). It is positioned next after the compressor, it
ensures the domestic hot water production. That can work
either in full recovery or in part, with the constant
optimization of efficiency through logic advanced adjusting
controller.
Exchangers plant side plate of stainless steel AISI 316 with
high efficiency and low pressure drop meets the supply of
both hot or cold water for the facility, regardless of the
domestic hot water
Hermetic scroll type compressors, equipped with the
Reversible heat pump, total heat crankcase heater and thermal protection
Finned coils made with copper pipes and aluminium fins
recovery, air source for outdoor with large exchange surface area (100% fully quality tested)
Axial electric fans, external rotor, electric motor with a 6-pole
installation 7,7 ÷ 33,5 kW fitted with thermal protection, housed in aerodynamic
conveyor profile with safety grill
Low external air temperature device: continuous fan speed
Unit description regulation with pressure switch
PRANA DHW is the heat pump new generation able to operate throughout the year in any Coil protection grille
operating mode: either a single cycle (cooling, heating, hot water) and combined cycle (hot Soft starter for 230V units /ms and 400V units /ts
water along with air conditioning or heating). Energy efficiency is highest during the summer The water circuit comes complete with:
cycle, when, thanks to the full recovery of the heat, the production of hot water is free. • Variable flow circulator for 0021÷0025 models and
During the combined use, the DHW exchanger uses the temperature of the discharge multistage centrifugal variable flow pump for models
gases to gets inside the accumulation sanitary water as high as 65° C. The advanced 0041÷0101, plant side
electronic regulation developed by Climaveneta ensures the highest operational flexibility, fast • Domestic hot water side water pump
working condition a significant increase in the overall COP, which go hand in hand with • Expansion tank
electricity and space reduction. Advantages, combined with the possibility of completely • Safety valve
eliminating the traditional boiler, making heat pumps PRANA DHW the ideal solution for • Manual filling assembly
energy saving applications in residential, hotel and small sector. • Pressure gauge
• Air vent valve
Comando accessibile dallesterno con dispositivo
Commands antimanomissione
AWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit,
which independently controls the modes of operation. The appliance can operate throughout the year in any
mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with
cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat
recovery. This energy is completely free of charge with regard to the production of hot water.
Main accessories
• Buffer tank 35,100,200 liters
• Hot water cylinder 300,500 liters
• 300 litres thermal store for domestic hot water, for kit
DOMH2O
• 300,500,1000 litres thermal store for domestic hot water
with solar heat exchanger, for kit DOMH2O
• DOMH2O15 e DOMH2O24 kit for domestic hot water
with external heat exchanger plate-to-plate and pump
• Remote keyboard
• Rubber anti-vibration mounting kit
• Removable metal mesh water filter kit
• Condensate collecting tray for models 0065÷0101

50
AWR DHW
Models 0021m 0025m 0041m 0021ms 0025ms 0041ms 0025t 0041t 0065t 0101t 0025ts 0041ts 0065ts 0101ts
Nominal heating power (1) kW 7,70 9,10 13 7,70 9,10 13 9,10 13 21,3 33,5 9,10 13 21,3 33,5
Total absorbed power (2) kW 2,30 2,70 3,70 2,30 2,70 3,70 2,70 3,70 5,60 8,50 2,70 3,70 5,60 8,50
COP * 3,35 3,37 3,51 3,35 3,37 3,51 3,37 3,51 3,80 3,94 3,37 3,51 3,80 3,94
Cooling capacity (3) kW 7,60 8,90 12,7 7,60 8,90 12,7 8,90 12,7 21,1 33 8,90 12,7 21,1 33
Total absorbed power (2) kW 2,40 2,70 3,80 2,40 2,70 3,80 2,70 3,80 5,80 9,40 2,70 3,80 5,80 9,40
EER * 3,17 3,30 3,34 3,17 3,30 3,34 3,30 3,34 3,64 3,51 3,30 3,34 3,64 3,51
Total absorbed power (4) kW 7,40 8,50 11,8 7,40 8,50 11,8 8,40 11,9 18,2 33,1 8,40 11,9 18,2 33,1
Total absorbed power kW 2,30 2,70 4 2,30 2,70 4 2,60 4 6,10 9,40 2,60 4 6,10 9,40
Recovery heating capacity kW 9,60 11,0 15,5 9,60 11,0 15,5 10,9 15,6 23,9 42,0 10,9 15,6 23,9 42,0
Heating capacity (5) kW 7,60 9 12,8 7,60 9 12,8 9,10 12,9 20,9 32,6 9,10 12,9 20,9 32,6
Total absorbed power (2) kW 2,90 3,40 4,60 2,90 3,40 4,60 3,40 4,60 7 10,3 3,40 4,60 7 10,3
COP * 2,66 2,68 2,78 2,66 2,68 2,78 2,68 2,81 2,99 3,17 2,68 2,81 2,99 3,17
Cooling capacity (6) kW 5,40 6,30 9,10 6,40 7,30 11,2 6,30 9,00 15,1 23,7 7,30 11,2 17 27,7
Total absorbed power (2) kW 2,40 2,70 3,70 2,40 2,70 3,80 2,70 3,60 5,40 9,00 2,70 3,80 5,90 9,50
EER * 2,25 2,33 2,46 2,25 2,33 2,46 2,33 2,50 2,80 2,63 2,33 2,50 2,80 2,63
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
N. fans N. 2 2 2 2 2 2 2 2 1 2 2 2 1 2
Plant side pump type (7) Ci Ci Ce Ci Ci Ce Ci Ce Ce Ce Ci Ce Ce Ce
Recovery side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Corrente di spunto A 61 78 114 29 34 45 40 50 101 127 22 28 56 70
Sound power (8) dB(A) 68 69 70 68 69 70 69 70 76 77 69 70 76 77
Sound pressure (9) dB(A) 53 54 55 53 54 55 54 55 60 61 54 55 60 61
DIMENSION
L mm 1125 1125 1250 1125 1125 1250 1125 1250 1700 1700 1125 1250 1700 1700
H mm 1125 1125 1125 1125 1125 1125 1125 1125 1200 1700 1125 1125 1200 1700
P mm 370 370 420 370 370 420 370 420 650 650 370 420 650 650
Operational weight kg 144 144 168 144 144 168 144 168 295 378 144 168 295 378

AWR DHW SL
Models 0065t 0101t 0065ts 0101ts
Nominal heating power (1) kW 21,3 33,5 21,3 33,5
Total absorbed power (2) kW 5,60 8,50 5,60 8,50
COP * 3,80 3,94 3,80 3,94
Cooling capacity (3) kW 21,1 33 21,1 33
Total absorbed power (2) kW 5,80 9,40 5,80 9,40
EER * 3,64 3,51 3,64 3,51
Total absorbed power (4) kW 18,2 33,1 18,2 33,1
Total absorbed power kW 6,10 9,40 6,10 9,40
Recovery heating capacity kW 23,9 42,0 23,9 42,0
Heating capacity (5) kW 21 32,9 21 32,9
Total absorbed power (2) kW 7,10 10,5 7,10 10,5
COP * 2,97 3,15 2,97 3,15
Cooling capacity (6) kW 15,2 23,9 15,2 23,9
Total absorbed power (2) kW 5,30 8,80 5,30 8,80
EER * 2,87 2,72 2,87 2,72
Compressor type SCROLL SCROLL SCROLL SCROLL
N. Compressors N. 1 1 1 1
Refrigerant R407C R407C R407C R407C
N. fans N. 2 3 2 3
Plant side pump type (7) Ce Ce Ce Ce
Recovery side pump type (7) Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 101 127 56 70
Sound power (8) dB(A) 73 74 73 74
Sound pressure (9) dB(A) 57 58 57 58
DIMENSION
L mm 1700 1700 1700 1700
H mm 1200 1700 1200 1700
P mm 650 650 650 650
Operational weight kg 295 378 295 378

NOTE
(1) Water in-out 30/35°C (plant side), outdoor air temperature (6) Water in-out 12/7°C (plant side), outdoor air temperature 35°C b.s.
7°C b.s./ 6°C b.u. (7) Ci=Circolatore; Ce=Centrifuga
(2) Total input is obtained from compressor input and fan input (8) Sound power level according to ISO 9614 and Eurovent 8/1 H
(3) Water in-out 23/18°C (plant side), outdoor air temperature 35°C b.s. (9) Average sound pressure level above one reflecting surface (Q=2)
(4) Water in-out 23/18°C (plant side), water in-out 45/50°C at 1 meter from the outside dimensions of the unit.
(total recovery side)
(5) Water in-out 40/45°C (plant side), outdoor air temperature * secondo Eurovent
7°C b.s./ 6°C b.u.
P
L

51
PRANA

AWR MTD1 0021ms÷0061t


Versioni
AWR MTD1 Medium temperature air source reversible heat
pump for water heating up to 55°C

Features
Structure and base in hot galvanised epoxy powder coated
steel.
High efficiency and low pressure drop stainless steel (AISI 316)
water exchangers complete with closed-cell insulation with
vapour barrier,antifreeze heating element and differencial
pressure switch
Hermetic scroll type compressors, equipped with the crankcase
heater and thermal protection
Finned coils made with copper pipes and aluminium fins with
large exchange surface area (100% fully quality tested)
Axial electric fans, external rotor, electric motor with a 6-pole
fitted with thermal protection, housed in aerodynamic conveyor
profile with safety grill
Low external air temperature device: - continuous fan speed
regulation with pressure switch
Condensate collecting tray
Coil protection grille
Soft starter for 230V/1/50Hz units
The water circuit comes complete with:
• Variable flow circulator for all models
• Water side differential pressure switch
• Expansion tank
• Safety valve
• Manual filling assembly
• Pressure gauge
• Air vent valve
Reversible heat pump, air source for Control with foolproof device accessible from the outside

outdoor installation
Main accessories
6,9 ÷ 17,4 kW • Valvola deviatrice a 3 vie per produzione acqua calda sanitaria
• Disgiuntore idraulico da 35, 100, 200 litri
• Bollitore acqua calda sanitaria da 300, 500 litri
Unit description • Termoaccumulo per acqua calda sanitaria da 300 litri, da
Heat pumps AWR-MTD1 are reversible outdoor units with axial fans, hermetic scroll abbinare al kit preparatore istantaneo DOMH2O
compressors and Full Floating technology. Full Floating is advanced electronics which • Termoaccumulo per acqua calda sanitaria da 300, 500 litri con
has been developed by CLIMAVENETA in order to meet the needs of typical residential serpentino solare, da abbinare al kit preparatore istantaneo
small size and small/medium tertiary sector, thanks to the accumulation. Another DOMH2O
advantage that, together with the Hydraulic module components it make extremely • Kit gestione caldaia in sostituzione
simple the installation of heat pump: simply by connecting the unit to water plant and • Kit preparatore istantaneo acqua calda sanitaria DOMH2O15 e
electricity so that it can be put into operation. DOMH2O24
• Kit resistenza elettrica da 1, 2, 3 kW
Commands • Accumulo esterno e kit di collegamento idraulico
The new generation electronic controller allows to manage the heat pump by using the Full Floating technology, • Kit filtro acqua a rete metallica estraibile
designed by Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump • Supporti antivibranti in gomma
(Floating Flow) and finally for the working temperature (Floating Setpoint). This also allows to achieve all the
following benefits: chiller operation even with larger operating limits, improvement of efficiency in both standard • Tastiera remota HSW11
and extreme conditions, much lower operating noise in part load conditions, lower installation time, lower time for
system set-up, broader operating limits, faster transient after defrosts.
The electronic menu allows to manage:
- domestic hot water production by external three-way valve (accessory)
- a zone of direct heating
- outdoor temperature sensor for water plant side modular set point compensation
- electrical heating element for possible integration and anti-legionellosis cycle for cylinder
- boiler or electric heater management

52
AWR MTD1
Models 0021ms 0031ms 0041ms 0051ms 0041t 0051t 0061t
Nominal heating power (1) kW 6,90 10,2 12,9 13,4 13 15,2 17,4
Total absorbed power (2) kW 1,70 2,60 3,40 3,20 3,50 3,90 4,10
COP Eurovent * 3,95 3,94 3,82 4,14 3,77 3,88 4,27
Cooling capacity (3) kW 6,80 10,3 12,9 13,9 13,4 15,9 18,4
Total absorbed power (2) kW 2 3,40 4,10 4 4,20 4,60 5,40
EER Eurovent * 3,40 2,98 3,06 3,37 3,20 3,25 3,38
Heating capacity (4) kW 6,80 10,1 12,7 13,1 13 14,6 17
Total absorbed power (2) kW 2,20 3,30 4,20 4 4,40 4,70 5
COP Eurovent * 3,09 3,06 3,02 3,27 2,95 3,11 3,40
Cooling capacity (5) kW 5,10 7,80 9,90 10,5 10,3 11,9 13,9
Total absorbed power (2) kW 2 3,30 3,90 3,80 4 4,50 5
EER Eurovent * 2,55 2,36 2,54 2,76 2,58 2,64 2,78
ESEER 3,15 2,98 3,06 3,37 3,20 3,25 3,38
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
N. fans N. 1 1 2 2 2 2 2
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 27 44 45 45 64 64 74
Sound power (7) dB(A) 66 66 69 69 69 69 69
Sound pressure (8) dB(A) 52 52 54 54 54 54 54
DIMENSION
L mm 900 900 900 900 900 900 900
H mm 640 940 1240 1240 1240 1240 1390
P mm 370 370 370 370 370 370 420
Operational weight kg 95 115 140 160 140 160 170

NOTE
(1) Water in-out 30/35°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u.
(2) Total input is obtained from compressor input and fan input
(3) Water in-out 23/18°C (plant side), outdoor air temperature 35°C b.s.
H
(4) Water in-out 40/45°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u.
(5) Water in-out 12/7°C (plant side), outdoor air temperature 35°C b.s. H
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the P
P
outside dimensions of the unit. L L

* secondo Eurovent

53
PRANA

AWR MTD XE 0011ms÷0091t


Versioni
AWR MTD XE Medium temperature air source reversible
heat pump for water heating up to 55°C and
operating limits down to -15°C external air
temperature

AWR MTD XE/H Medium temperature air source reversible


heat pump for water heating up to 55°C and
operating limits down to -15°C external air
temperature

Features
Structure and base in hot galvanised epoxy powder coated steel.
High efficiency and low pressure drop stainless steel (AISI 316) water
exchangers complete with closed-cell insulation with vapour
barrier,antifreeze heating element and differencial pressure switch
Hermetic scroll type compressors, equipped with the crankcase
heater and thermal protection
Finned coils made with copper pipes and aluminium fins with large
exchange surface area (100% fully quality tested)
Axial electric fans, external rotor, electric motor with a 6-pole fitted
with thermal protection, housed in aerodynamic conveyor profile with
safety grill
Low external air temperature device: continuous fan speed regulation
with pressure switch
Electrical resistance modulating antifreeze to the base located
between wing and base exchanger to improve and facilitate the flow
of water during defrosting
Condensate collecting tray
Coil protection grille
Soft starter for 230V/1/50Hz units
Phase sequence control relay
The water circuit comes complete with:
• Variable flow circulator for all models
High efficiency reversible heat pump, air • Water side differential pressure switch
• Expansion tank
source for outdoor installation • Safety valve
• Manual filling assembly
6,3 ÷ 17,9 kW • Pressure gauge
• Air vent valve
Control with foolproof device accessible from the outside
Unit description
Heat pumps AWR-MTD-XE reversible units are able to provide heating, cooling and
domestic hot water. Particular attention was paid to the winter, thanks to special Main accessories
technological devices is guaranteed beyond the normal limits of traditional units. Prana
• Main accessories
AWR-MTD-XE Air can be combined with traditional systems or radiant panels, ensuring a
• Three-way valve for domestic hot water
high energy efficiency. All units are certified in accordance with the Class A classification
• Buffer tank 35,100,200 liters
Eurovent energy in heating. This makes them particularly suitable for use radiant
• Hot water cylinder 300,500 liters
installations. The installation is greatly simplified through the integration of the group and
• 300 litres thermal store for domestic hot water, for kit DOMH2O
hydraulic technology Full floating simply by connecting the unit to water plant and
• 300,500 litres thermal store for domestic hot water with solar
electricity so that it can be put into operation. heat exchanger, for kit DOMH2O
• Kit boiler control
Commands • DOMH2O15 e DOMH2O24 kit for domestic hot water with
The new generation electronic controller allows to manage the heat pump by using the Full Floating technology, external heat exchanger plate-to-plate and pump
designed by Climaveneta for improving the system´s efficiency for the fans (Floating Fans), for the circulating pump
(Floating Flow) and finally for the working temperature (Floating Setpoint). This also allows to achieve all the
• 1,2,3 kW single-phase electric heater kit
following benefits: chiller operation even with larger operating limits, improvement of efficiency in both standard • External buffer tank and hydronic connecting kit
and extreme conditions, much lower operating noise in part load conditions, lower installation time, lower time for • Removable metal mesh water filter kit
system set-up, broader operating limits, faster transient after defrosts.
The electronic menu allows to manage:
• Rubber anti-vibration mounting kit
- domestic hot water production by external three-way valve (accessory) • HSW11 Remote keyboard
- a zone of direct heating
- outdoor temperature sensor for water plant side modular set point compensation
- electrical heating element for possible integration and anti-legionellosis cycle for cylinder
- boiler or electric heater management

54
AWR MTD XE
Models 0011ms 0025ms 0031ms 0041ms 0031t 0041t 0051t 0061t 0091t
Nominal heating power (1) kW 6,30 7,40 11,2 14 10,9 14 15,9 17,9 25,10
Total absorbed power (2) kW 1,50 1,80 2,60 3,30 2,60 3,30 3,80 4,20 6
COP Eurovent * 4,20 4,11 4,31 4,24 4,19 4,24 4,18 4,26 4,18
COP EN14511 4,13 4,15 4,22 4,16 4,15 4,15 4,11 4,25 4,19
Cooling capacity (3) kW 7,20 8,30 12,3 15,7 11,7 15,8 17,7 20,2 29,2
Total absorbed power (2) kW 1,90 2,20 3,30 4,10 3,10 4,20 4,70 5,30 7,80
EER Eurovent * 3,79 3,77 3,73 3,83 3,77 3,76 3,77 3,81 3,74
EER EN 14511 3,82 3,82 3,81 3,84 3,84 3,81 3,81 3,81 3,85
Heating capacity (4) kW 6,10 7,30 10,8 13,6 10,6 13,8 15,4 17,5 24,60
Total absorbed power (2) kW 1,90 2,30 3,30 4,10 3,20 4,30 4,60 5,20 7,40
COP Eurovent * 3,21 3,17 3,27 3,32 3,31 3,21 3,35 3,37 3,32
Cooling capacity (5) kW 5,20 6,30 9,20 11,7 8,60 11,9 13,2 15,2 22,10
Total absorbed power (2) kW 1,70 2,20 3,10 4,00 3,00 4,00 4,60 5,00 7,20
EER Eurovent * 3,06 2,86 2,97 2,93 2,87 2,98 2,87 3,04 3,07
ESEER 3,62 3,63 3,52 3,46 3,42 3,65 3,24 3,55 3,57
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
N. fans N. 1 1 2 2 2 2 2 2 3
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 27 30 45 45 48 64 64 75 111
Sound power (7) dB(A) 69 69 71 71 71 71 71 72 74
Sound pressure (8) dB(A) 54 54 56 56 56 56 56 57 58
DIMENSION
L mm 900 900 900 900 900 900 900 1550 1550
H mm 1240 1240 1240 1390 1240 1390 1390 1200 1700
P mm 420 420 420 420 420 420 420 450 450
Operational weight kg 145 150 155 170 155 170 180 250 335

AWR MTD XE/H


Models 0011ms 0025ms 0031ms 0041ms 0031t 0041t 0051t 0061t 0091t
Nominal heating power (1) kW 6,30 7,40 11,2 14 10,9 14 15,9 17,9 25,10
Total absorbed power (2) kW 1,50 1,80 2,60 3,30 2,60 3,30 3,80 4,20 6
COP Eurovent * 4,20 4,11 4,31 4,24 4,19 4,24 4,18 4,26 4,18
COP EN14511 4,13 4,15 4,22 4,16 4,15 4,15 4,11 4,25 4,19
Cooling capacity (3) kW 7,20 8,30 12,3 15,7 11,7 15,8 17,7 20,2 29,2
Total absorbed power (2) kW 1,90 2,20 3,30 4,10 3,10 4,20 4,70 5,30 7,8
EER Eurovent * 3,79 3,77 3,73 3,83 3,77 3,76 3,77 3,81 3,74
EER EN 14511 3,82 3,82 3,81 3,84 3,84 3,81 3,81 3,81 3,85
Heating capacity (4) kW 6,10 7,30 10,8 13,6 10,6 13,8 15,4 17,5 24,6
Total absorbed power (2) kW 1,90 2,30 3,30 4,10 3,20 4,30 4,60 5,20 7,4
COP Eurovent * 3,21 3,17 3,27 3,32 3,31 3,21 3,35 3,37 3,32
Cooling capacity (5) kW 5,20 6,30 9,20 11,7 8,60 11,9 13,2 15,2 22,1
Total absorbed power (2) kW 1,70 2,20 3,10 4,00 3,00 4,00 4,60 5,00 7,2
EER Eurovent * 3,06 2,86 2,97 2,93 2,87 2,98 2,87 3,04 3,07
ESEER 3,62 3,63 3,52 3,46 3,42 3,65 3,24 3,55 3,57
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
N. fans N. 1 1 2 2 2 2 2 2 3
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 27 30 45 45 48 64 64 75 111
Sound power (7) dB(A) 69 69 71 71 71 71 71 72 74
Sound pressure (8) dB(A) 54 54 56 56 56 56 56 57 58
DIMENSION
L mm 900 900 900 900 900 900 900 1550 1550
H mm 1240 1240 1240 1390 1240 1390 1390 1200 1700
P mm 420 420 420 420 420 420 420 450 450
Operational weight kg 145 150 155 170 155 170 180 250 335

NOTE
(1) Water in-out 30/35°C (plant side), outdoor air temperatur (6) Ci=Circulator; Ce=Centrifugal
7°C b.s./ 6°C b.u. (7) Sound power level according to ISO 9614 and
(2) Total input is obtained from compressor input and Eurovent 8/1
fan input. (8) Average sound pressure level above one reflecting H
(3) Water in-out 23/18°C (plant side), outdoor air temperature surface (Q=2) at 1 meter from the outside dimensions
35°C b.s. of the unit. H
(4) Water in-out 40/45°C (plant side), outdoor air temperature
7°C b.s./ 6°C b.u. * secondo Eurovent
(5) Water in-out 12/7°C (plant side), outdoor air temperature P P
35°C b.s. L L

55
PRANA

AW HT 0031ms÷0071ts
Versioni
AW HT High temperature air source heat pump for water
heating up to 65°C, and operating limits down to
-20° external air temperature

Features
Structure and base in hot-dip galvanised steel with epoxy
powder coating finish.
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for
frost protection.
High efficiency cycle EVI Hermetic Scroll Compressor (with
hot gas direct injection into the compressor) to reach 65°
C, with the crankcase heater and thermal protection
Finned coils made with copper pipes and aluminium fins
with large exchange surface area (100% fully quality
tested); sub cooling circuit to prevent the icing at the
basement
A condense collecting tray within water discharge
Coil protection grille
Soft starter for 230V/1/50Hz units
The water circuit comes complete with:
Heat pump, air source for outdoor • Circulating pump for all models
• Expansion tank
installation, high water temperature • Safety valve
• Manual filling assembly
10,4 ÷ 19,7 kW • Pressure gauge
• Air vent valve
• Outside air sensor wired
Unit description
AW HT is an ideal solution for systems with heating radiators, where the water high
temperature is needed. The EVI technology compressor with additional steam
injection in the compressing cycle assures a water temperature of 65°C and operating Main accessories
limits as low as -20°C. Neither probes nor connections pipes to wells are needed; the • Three-way valve for domestic hot water
installation is simple, this is a suitable solution for all applications. • Buffer tank 35,100,200 liters
• Hot water cylinder 300,500 liters
Commands • 300 litres thermal store for domestic hot water, for kit
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor DOMH2O
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and • 300,500 litres thermal store for domestic hot water with
increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: solar heat exchanger, for kit DOMH2O
- domestic hot water production by external three-way valve (accessory)
- circulator on system side • DOMH2O15 e DOMH2O24 kit for domestic hot water
- a zone of direct heating with external heat exchanger plate-to-plate and pump
- outdoor temperature sensor for water plant side modular set point compensation • Control kit for heat pump with boiler
- electrical heating element for possible integration and anti-legionellosis cycle for cylinder
- integrated boiler with heat pump • 1,2,3 kw single-phase electric heater kit
- several solutions through appropriate configurations of the controller and use of dedicated extension • Radiant panels or radiator management kit Second zone
modules (accessories) • Control kit for underfloor heating with hydronic
components
• Removable metal mesh water filter kit
• Rubber anti-vibration mounting kit
• Room unit wired
• Room thermostat wired based

56
AW HT

Models 0031ms 0041ms 0041t 0061t 0071t 0041ts 0061ts 0071ts


Nominal heating power (1) kW 10,4 14,9 14,1 19,7 26,6 14,1 19,7 26,6
Total absorbed power (2) kW 2,50 3,50 3,30 4,70 6,1 3,30 4,70 6,1
COP EN14511 4,10 4,12 4,14 4,12 4,26 4,14 4,12 4,26
Heating capacity (3) kW 10,4 14,3 14,3 19,7 27,1 14,3 19,7 27,1
Total absorbed power (2) kW 3 4 4 5,60 7,4 4 5,60 7,4
COP EN14511 3,30 4,48 3,48 3,45 3,58 3,48 3,45 3,58
Heating capacity (4) kW 9,10 12,5 12,5 17,5 23,5 12,5 17,5 23,5
Total absorbed power (2) kW 2,50 3,30 3,30 4,60 5,9 3,30 4,60 5,9
COP EN 14511 3,44 3,66 3,66 3,72 3,88 3,66 3,72 3,88
Heating capacity (5) kW 7,80 11,4 11,4 14,8 21,2 11,4 14,8 21,2
Total absorbed power (2) kW 3,80 5,40 5,40 7,60 10,4 5,40 7,60 10,4
COP EN 14511 1,97 2,06 2,06 1,91 1,99 2,06 1,91 1,99
Compressor type SCROLL EVI
N. Compressors N. 1
Refrigerant R407C
N. fans N. 2 2 2 2 3 2 2 3
Plant side pump type (6) Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 44 45 64 101 99 35 55 99
Sound power (7) dB(A) 70 70 70 71 74 70 71 74
Sound pressure (8) dB(A) 55 55 55 56 59 55 56 59
DIMENSION
L mm 900 900 900 900 1470 900 900 1470
H mm 1240 1390 1390 1390 1700 1390 1390 1700
P mm 420 420 420 420 570 420 420 570
Operational weight kg 150 160 160 170 320 160 170 320

NOTE
(1) Water in-out 30/35°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u.
(2) Total input is obtained from compressor input and fan input.
(3) Water in-out 40/45°C (plant side), outdoor air temperature 7°C b.s./ 6°C b.u.
H
(4) Water in-out 30/35°C (plant side), outdoor air temperature 2°C b.s./ 1°C b.u.
(5) Water 65°C, outdoor air temperature -7°C b.s./ 1°C b.u.
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter P
from the outside dimensions of the unit. L

57
PRANA

WWR MTD 0011m÷0121t


Versioni
WWR MTD High temperature air source heat pump for water
heating up to 65°C, and operating limits down to
-20° external air temperature

Features
Structure and base in hot galvanised epoxy powder coated
steel.
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for frost
protection.
Hermetic scroll type compressors, equipped with the
crankcase heater and thermal protection
Case panels are insulated within low noise material for
further improvement of silence
Rubber vibration damper.
Soft starter for 230V/1/50Hz units /ms
Phase sequence control relay
The water circuit comes complete with:
Variable flow circulator for 0011÷0031 models and
multistage centrifugal variable flow pump for models
0071÷0121, plant side
Modulating valve to reduce water consumptions, source
side
Reversible heat pump, water source • Safety valve.
• Expansion tank.
7,2 ÷ 43,8 kW • Manual filling assembly
• Pressure gauge.
• Air vent valve.
• Drain valve on both plant and source circuits.
• Differential pressure switch on source side and system
Unit description side
The MTD water-cooled heat pump are reversible units for heating, cooling and
domestic hot water by external three-way valve (accessory). Both heat pumps MTD
are suitable for traditional heating systemsand radiant panels. The latter, working with Main accessories
water at lower temperatures, ensure a higher yield and are a particularly appreciated • HSW12 remote keyboard
for new buildings with low energy consumption that point on using renewable energy • External temperature sensor (mandatory with HSW12
resources. remote keyboard)
The installation is greatly simplified through the integration of the group and hydraulic • Three-way valve for domestic hot water
technology Full floating simply by connecting the unit to water plant and electricity so • Buffer tank 35,100,200 liters
that it can be put into operation. • Hot water cylinder 300,500 liters
• 300 litres thermal store for domestic hot water, for kit
Commands DOMH2O
User interface unit on board, accessible from the outside with a not touch system
• 300,500,1000 litres thermal store for domestic hot water
with solar heat exchanger, for kit DOMH2O
Floating Set Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the • DOMH2O15 e DOMH2O24 kit for domestic hot water
compressor operating time and the temperatures of the water in the system. He water storage tank is no longer with external heat exchanger plate-to-plate and pump
indispensable because it is compensated by the Floating Set function, with resulting reduction in: size; weight; • 1,2,3 kw single-phase electric heater kit
installation times; system setting-up times.

Floating Flow The controller manages the modulation of the active components (pump and electronic flow
valve) through pressure transducers and temperature sensors. The performance of the unit may thus be optimised
for different operating conditions, such as traditional fan coil system and panel heating system, ensuring: broader
operating limits; easier start-up of installations with both high and low water temperatures; faster system setup.
The electronic menu allows to manage:
- domestic hot water production by external three-way valve (accessory)
- a zone of direct heating
- circulator on system side and modulating valve
- outdoor temperature sensor for water plant side modular set point compensation (accessory)

58
WWR MTD
Models 0011m 0021m 0025m 0031m 0041m 0011ms 0021ms 0025ms 0031ms 0041ms
Nominal heating power (1) kW 7,20 7,80 9,70 12,1 15,3 7,20 7,80 9,70 12,1 15,3
Total absorbed power (2) kW 1,40 1,49 1,81 2,30 2,88 1,40 1,49 1,81 2,30 2,88
COP * 5,14 5,23 5,36 5,26 5,31 5,14 5,23 5,36 5,26 5,31
Cooling capacity (3) kW 7,10 7,60 9,80 12 15,1 7,10 7,60 9,80 12 15,1
Total absorbed power (2) kW 1,60 1,70 2 2,50 3,30 1,60 1,70 1,96 2,53 3,27
EER * 4,44 4,47 4,90 4,80 4,58 4,44 4,47 5 4,74 4,62
Heating capacity (4) kW 6,80 7,50 9,20 11,6 14,6 6,80 7,50 9,20 11,6 14,6
Total absorbed power (2) kW 1,70 1,90 2,30 3 3,60 1,70 1,90 2,30 3 3,60
COP * 4 3,95 4 3,87 4,06 4 3,95 4 3,87 4,06
Cooling capacity (5) kW 5,20 5,60 7,20 8,80 11,3 5,20 5,60 7,20 8,80 11,3
Total absorbed power (2) kW 1,53 1,70 2 2,60 3,20 1,53 1,70 2 2,60 3,20
EER * 3,47 3,29 3,60 3,38 3,53 3,40 3,29 3,60 3,38 3,53
ESEER 4,03 3,73 4,26 3,95 3,90 4,03 3,73 4,26 3,95 3,90
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50
Start-up current A 58 61 82 97 130 26 27 37 44 59
Sound power (7) dB(A) 52 52 53 53 58 52 52 53 53 58
Sound pressure (8) dB(A) 38 38 39 39 44 38 38 39 39 44
DIMENSION
L mm 560
H mm 980
P mm 575
Operational weight kg 148 148 150 152 160 148 148 150 152 160

WWR MTD
Models 0021t 0025t 0031t 0041t 0051t 0061t 0071t 0091t 0101t 0121t
Nominal heating power (1) kW 7,80 9,80 12,1 15,9 18,1 21,1 26,2 30,5 35 43,8
Total absorbed power (2) kW 1,40 1,73 2,17 2,90 3,40 3,70 4,60 5,20 6 7,60
COP * 5,57 5,66 5,58 5,48 5,32 5,70 5,70 5,87 5,83 5,76
Cooling capacity (3) kW 7,60 9,50 12 15,7 18 21,3 26,9 30,7 34,8 44,8
Total absorbed power (2) kW 1,60 1,80 2,50 3,30 3,80 4,10 5,20 6 7 8,80
EER * 4,75 5,28 4,80 4,76 4,74 5,20 5,17 5,12 4,97 5,09
Heating capacity (4) kW 7,40 9,20 11,4 15,3 17,1 20 24,8 28,8 33 41,7
Total absorbed power (2) kW 1,90 2,20 2,70 3,70 4,20 4,60 5,80 6,40 7,60 9,50
COP * 3,89 4,18 4,22 4,14 4,07 4,35 4,28 4,50 4,34 4,39
Cooling capacity (5) kW 5,60 7,30 8,90 11,8 13,2 15,7 19,8 22,9 26 33,4
Total absorbed power (2) kW 1,60 1,90 2,40 3,20 3,80 4 5,10 5,80 6,80 8,39
EER * 3,50 3,84 3,71 3,70 3,47 3,93 3,88 3,95 3,82 3,98
ESEER 3,97 4,54 4,33 4,08 3,92 4,51 4,40 4,61 4,33 4,37
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ce Ce Ce Ce
Electrical power supply V-Ph~Hz 400-3N~50
Start-up current A 32 35 48 64 64 75 95 111 118 140
Sound power (7) dB(A) 52 52 52 58 58 59 66 66 70 70
Sound pressure (8) dB(A) 38 38 38 44 44 45 51 51 55 55
DIMENSION
L mm 560 560 560 560 560 560 680 680 680 680
H mm 980 980 980 980 980 980 1150 1150 1150 1150
P mm 575 575 575 575 575 575 780 780 780 780
Operational weight kg 148 150 152 160 170 175 220 230 235 250

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in 10°C (source side)
(2) Total input is obtained from compressor input and fan input.
(3) Temperatura acqua impianto 23/18°C, temperatura acqua sorgente 30/35°C
(4) Temperatura acqua impianto 40/45°C, temperatura acqua sorgente ingresso 10°C H
(5) Temperatura acqua impianto 12/7°C, temperatura acqua sorgente 30/35°C
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
* secondo Eurovent
L P

59
PRANA

WWR HT Slim Z1M6÷Z1T11


Versioni
WWR HT Slim High temperature heat pump, water source
for water heating up to 60°C, reversible

Features
Structure and base in hot galvanised epoxy powder coated
steel.
180-litre tank with built-in coil for domestic hot water, with
fittings for connecting solar panels or hightemperature
fixtures (e.g. fan coils)
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for frost
protection.
High-efficiency single-and three-phase SCROLL compressor
to allow water up to 60 °C to be produced.
Also suitable for traditional radiator systems.
The compressor and plate heat exchangers are housed in
a suitably insulated enclosure to limit vibrations and noise.
This enclosure can be removed from the unit to make
maintenance easier
Case panels are insulated within low noise material for
further improvement of silence
Rubber vibration damper.
Soft starter for 230V/1/50Hz units
Phase sequence control relay
The water circuit comes complete with:
• Circulator on system side
• Three-way valve for domestic hot water
• Safety valve
• 180Xlt domestic hot water storage tank
• Expansion tank built into the heat pumps tank
• Manual filling assembly
• Pressure gauge
• Air vent valve
• Drain valve
• Differential pressure switch on source side and system
side
Reversible heat pump, water source, high • Outside air sensor wired

water temperature with buffer tank Main accessories


• Room unit wired
8,3 ÷ 14,1 kW • Room thermostat wired based
• Room unit wireless
• Outside air sensor wireless
Unit description
• NTC probe for select plant diagram or solar panel
The Prana Slim heat pump is designed for heating, cooling, and domestic hot water.
• Heating element kit
It is an indoor unit with elegant design and thanks to a special sound insulation, the
unit is suitable for a living comfort.

Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and
increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage:
- domestic hot water production by three-way valve
- circulator on system side
- a zone of direct heating
- zone with mix valve for floor heating
- outdoor temperature sensor for water plant side modular set point compensation
- integration by solar panels
- several solutions through appropriate configurations of the controller

60
WWR HT Slim
Models Z1M6 Z1M9 Z1M11 Z1T6 Z1T9 Z1T11
Nominal heating power (1) kW 8,30 11,6 14,1 8,20 11,4 14
Total absorbed power (2) kW 1,60 2,22 2,68 1,56 2,14 2,61
COP * 5,19 5,23 5,26 5,24 5,34 5,35
Cooling capacity (3) kW 9,55 13,2 15,5 9,36 12,9 15,6
Total absorbed power (2) kW 1,46 2,11 2,72 1,45 2,06 2,64
EER * 6,54 6,25 5,71 6,46 6,27 5,92
Heating capacity (4) kW 7,95 11,1 13,6 7,87 11 13,5
Total absorbed power (2) kW 2,02 2,80 3,37 1,98 2,72 3,27
COP * 3,94 3,96 4,02 3,97 4,04 4,11
Cooling capacity (5) kW 6,67 9,24 11,1 6,58 9,12 11,1
Total absorbed power (2) kW 1,53 2,17 2,67 1,49 2,09 2,59
EER * 4,36 4,26 4,16 4,42 4,36 4,28
Hot water tank l 180
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (6) Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 37 60 68 32 46 50
Sound power (7) dB(A) 42 42 46 42 42 46
Sound pressure (8) dB(A) 28 28 32 28 28 32
DIMENSION
L mm 600
H mm 1940
P mm 570
Operational weight kg 286 293 300 286 293 300

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in 10°C (source side) with identical flow rate that in the
cooling mode
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Condenser water in-out 40/45°C (plant side), water in 10°C (source side) with identical flow rate that in the cooling mode
(5) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side) H
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
P
* secondo Eurovent
L

61
PRANA

WWR HT Cube Z1M6÷Z1T28


Versioni
WWR HT Cube High temperature heat pump, water source
for water heating up to 60°C, reversible

Features
Structure and base in hot galvanised epoxy powder coated
steel.
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for frost
protection.
High-efficiency single-and three-phase SCROLL
compressor to allow water up to 60 °C to be produced.
Also suitable for traditional radiator systems.
The compressor and plate heat exchangers are housed in a
suitably insulated enclosure to limit vibrations and noise.
This enclosure can be removed from the unit to make
maintenance easier
Case panels are insulated within low noise material for
further improvement of silence
Rubber vibration damper.
Soft starter for 230V/1/50Hz units
Phase sequence control relay
The water circuit comes complete with:
• Circulator on system side
• Drain valve
• Differential pressure switch on source side and system
side
• Outside air sensor wired

Main accessories
Reversible heat pump, water source, • Room unit wired
• Room thermostat wired based
high water temperature • Room unit wireless
• Outside air sensor wireless
8,3 ÷ 35,9 kW • NTC probe for select plant diagram or solar panel
• Heating element kit
Unit description • Three-way valve for domestic hot water
The Prana Cube heat pump is designed for heating, cooling, and domestic hot water, • Buffer tank 35,100,200 liters
with external three-way valve. It is an indoor unit with elegant design and thanks to a • Hot water cylinder 300,500 liters
• 300 litres thermal store for domestic hot water, for kit
special sound insulation, the unit is suitable for a living comfort.
DOMH2O
• 300,500,1000 litres thermal store for domestic hot water
Commands with solar heat exchanger, for kit DOMH2O
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor • DOMH2O15 e DOMH2O24 kit for domestic hot water
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and
increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: with external heat exchanger plate-to-plate and pump
- domestic hot water production by external three-way valve (accessory)
- circulator on system side
- a zone of direct heating
- zone with mix valve for floor heating
- outdoor temperature sensor for water plant side modular set point compensation
- integration by solar panels
- several solutions through appropriate configurations of the controller

62
WWR HT Cube
Models Z1M6 Z1M9 Z1M11 Z1T6 Z1T9 Z1T11 Z1T13 Z1T17 Z1T24 Z1T28
Nominal heating power (1) kW 8,30 11,6 14,1 8,20 11,4 14 17,1 22,6 31,1 35,9
Total absorbed power (2) kW 1,60 2,22 2,68 1,56 2,14 2,61 3,28 4,30 5,84 6,59
COP * 5,19 5,23 5,26 5,24 5,34 5,35 5,22 5,27 5,33 5,45
Cooling capacity (3) kW 9,55 13,2 15,5 9,36 12,9 15,6 19 24,9 34,7 40
Total absorbed power (2) kW 1,46 2,11 2,72 1,45 2,06 2,64 3,76 4,95 6,14 7
EER * 6,54 6,25 5,71 6,46 6,27 5,92 5,04 5,02 5,65 5,71
Heating capacity (4) kW 7,95 11,1 13,6 7,87 11 13,5 16,4 21,8 29,9 34,5
Total absorbed power (2) kW 2,02 2,80 3,37 1,98 2,72 3,27 4,07 5,39 7,28 8,29
COP * 3,94 3,96 4,02 3,97 4,04 4,11 4,02 4,04 4,11 4,16
Cooling capacity (5) kW 6,67 9,24 11,1 6,58 9,12 11,1 13,4 17,5 24,3 28,2
Total absorbed power (2) kW 1,53 2,17 2,67 1,49 2,09 2,59 3,38 4,53 6,01 6,77
EER * 4,36 4,26 4,16 4,42 4,36 4,28 3,97 3,87 4,05 4,16
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 37 60 68 32 46 50 66 101 123 127
Sound power (7) dB(A) 42 42 46 42 42 46 47 51 55 55
Sound pressure (8) dB(A) 28 28 32 28 28 32 33 37 41 41
DIMENSION
L mm 600 600 600 600 600 600 600 600 900 900
H mm 940 940 940 940 940 940 940 940 1117 1117
P mm 570 570 570 570 570 570 570 570 648 648
Operational weight kg 160 180 190 160 180 190 200 220 240 250

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in 10°C (source side) with identical flow rate that in the
cooling mode
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side) H
(4) Condenser water in-out 40/45°C (plant side), water in 10°C (source side) with identical flow rate that in the cooling mode
(5) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1 P
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
L
* secondo Eurovent

63
PRANA

WWR DHW 0011m÷0121t


Versioni
WWR MTD Water source reversible heat pump with
domestic hot water supply with total heat
recovery

Features
Structure and base in hot galvanised epoxy powder coated
steel
Case panels are insulated within low noise material for
further improvement of silence
Rubber vibration damper
Hermetic scroll type compressors, equipped with the
crankcase heater and thermal protection
Stainless steel (AISI 316) with high efficiency and low
pressure drop plate to plate exchanger (at the domestic hot
water side). It is positioned next after the compressor, it
ensures the domestic hot water production. That can work
either in full recovery or in part, with the constant
optimization of efficiency through logic advanced adjusting
controller
Exchangers plant side plate of stainless steel AISI 316 with
high efficiency and low pressure drop meets the supply of
both hot or cold water for the facility, regardless of the
domestic hot water
Reversible heat pump, total heat High efficiency and low pressure drop stainless steel (AISI
316) source side plate exchanger
recovery, water source Soft starter for 230V/1/50Hz units /ms
The water circuit comes complete with:
6,0 ÷ 40,5 kW • Variable flow circulator for 0011÷0031 models and
multistage centrifugal variable flow pump for models
0071÷0121, plant side
Unit description • Domestic hot water, water side, variable flow pump
PRANA DHW is the heat pump new generation able to operate throughout the year in • Modulating valve to reduce water consumptions,
any operating mode: either a single cycle (air conditioning, heating, hot water) and source side
combined cycle (hot water along with air conditioning or heating). Energy efficiency is • Safety valve
highest during the summer cycle, when, thanks to the full recovery of the heat, the • Expansion tank
production of hot water is free. During the combined use, the DHW exchanger uses • Drain valve on both plant and source circuits
the temperature of the hot exhaust gases to gets inside the accumulation sanitary
water as high as 65° C. The advanced CLIMAVENETA fully patented electronic ensures
the highest flexibility of operation, a rapid speed and a significant increase in the overall Main accessories
COP, which go hand in hand with electricity and space reduction. Advantages, • Buffer tank 35,100,200 liters
combined with the possibility of completely eliminating the traditional boiler, making • Hot water cylinder 300,500 liters
heat pumps PRANA DHW the ideal solution for energy saving applications in • 300 litres thermal store for domestic hot water, for kit
residential, hotel and small sector. DOMH2O
• 300,500,1000 litres thermal store for domestic hot water
Commands with solar heat exchanger, for kit DOMH2O
User interface unit on board, accessible from the outside with a not touch system
• DOMH2O15 e DOMH2O24 kit for domestic hot water
WWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit, with external heat exchanger plate-to-plate and pump
which independently controls the modes of operation. The appliance can operate throughout the year in any • Remote keyboard
mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with
cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat
• Removable metal mesh water filter kit
recovery. This energy is completely free of charge with regard to the production of hot water.

64
WWR DHW
Models 0011m 0021m 0025m 0031m 0041m 0011ms 0021ms 0025ms 0031ms 0041ms
Nominal heating power (1) kW 6 7,60 9 10,5 12,9 6 7,60 9 10,5 12,9
Total absorbed power (2) kW 1,30 1,70 2 2,40 2,90 1,30 1,70 2 2,40 2,90
COP 4,49 4,48 4,51 4,36 4,50 4,49 4,48 4,51 4,36 4,50
Cooling capacity (3) kW 7,30 9,20 11 12,5 15,3 7,30 9,20 11 12,5 15,3
Total absorbed power (2) kW 1,30 1,70 2 2,40 2,90 1,30 1,70 2 2,40 2,90
EER 5,62 5,41 5,50 5,21 5,28 5,62 5,41 5,50 5,21 5,28
Total absorbed power (4) kW 6 7,80 9,20 10,3 12,9 6 7,80 9,20 10,3 12,9
Total absorbed power kW 1,90 2,40 2,90 3,40 4,20 1,90 2,40 2,90 3,40 4,20
Recovery heating capacity (4) kW 7,90 10 11,9 13,5 16,8 7,90 10 11,9 13,5 16,8
Heating capacity (5) kW 5,70 7,30 8,70 10,1 12,4 5,60 7,20 8,50 9,90 12,2
Total absorbed power (2) kW 1,70 2,20 2,60 3,10 3,60 1,70 2,20 2,60 3,10 3,60
COP 3,33 3,35 3,37 3,28 3,40 3,33 3,35 3,37 3,28 3,40
Cooling capacity (6) kW 5,10 6,50 7,70 8,90 11 5,10 6,50 7,70 8,90 11
Total absorbed power (2) kW 1,30 1,70 2 2,40 2,90 1,30 1,70 2 2,40 2,90
EER 3,92 3,82 3,85 3,71 3,79 3,92 3,82 3,85 3,71 3,79
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Recovery side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50
Start-up current A 47 61 76 100 114 21 27 34 45 51
Sound power (8) dB(A) 52 52 53 53 58 52 52 53 53 58
Sound pressure (9) dB(A) 38 38 39 39 44 38 38 39 39 44
DIMENSION
L mm 560 560 560 560 560 560 560 560 560 560
H mm 980 980 980 980 980 980 980 980 980 980
P mm 575 575 575 575 575 575 575 575 575 575
Operational weight kg 188 188 190 195 215 188 188 190 195 215

Models 0021t 0025t 0031t 0041t 0051t 0061t 0071t 0091t 0101t 0121t
Nominal heating power (1) kW 7,50 8,90 10,3 12,7 15,6 18,7 25,3 28,4 32,6 40,5
Total absorbed power (2) kW 1,70 2 2,30 2,80 3,40 3,90 5,30 5,90 6,90 8,80
COP 4,55 4,58 4,44 4,57 4,58 4,75 4,73 4,84 4,69 4,59
Cooling capacity (3) kW 9,20 10,9 12,4 15,4 19,1 22,5 30,2 34,4 38,9 49,7
Total absorbed power (2) kW 1,60 1,90 2,30 2,80 3,60 4,10 5,50 6,10 7,30 9,30
EER 5,75 5,74 5,39 5,50 5,31 5,49 5,49 5,64 5,33 5,34
Total absorbed power (4) kW 7,70 9,10 10,3 13,1 16 18,9 25,5 29 32,7 41,1
Total absorbed power kW 2,30 2,80 3,30 4 4,90 5,70 7,70 8,40 10,2 12,8
Recovery heating capacity (4) kW 9,90 11,7 13,4 16,9 20,6 24,2 32,7 36,9 42,4 53,1
Heating capacity (5) kW 7,20 8,60 9,90 12,3 14,9 17,9 24 27,1 31,1 38,3
Total absorbed power (2) kW 2,10 2,50 3 3,50 4,30 4,90 6,80 7,30 8,70 11,1
COP 3,41 3,42 3,34 3,48 3,50 3,62 3,55 3,69 3,55 3,45
Cooling capacity (6) kW 6,50 7,70 8,80 10,9 13,4 16,1 21,7 24,6 28 34,8
Total absorbed power (2) kW 1,70 2 2,30 2,80 3,40 4 5,40 5,90 7 8,90
EER 3,82 3,85 3,83 3,89 3,94 4,03 4,02 4,17 4,00 3,91
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (7) Ci Ci Ci Ci Ci Ce Ce Ce Ce Ce
Recovery side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 400-3N~50
Start-up current A 32 40 46 50 66 74 95 111 118 140
Sound power (8) dB(A) 52 52 52 58 58 59 66 66 70 70
Sound pressure (9) dB(A) 38 38 38 44 44 45 51 51 55 55
DIMENSION
L mm 560 560 560 560 560 560 680 680 680 680
H mm 980 980 980 980 980 980 1150 1150 1150 1150
P mm 575 575 575 575 575 575 780 780 780 780
Operational weight kg 188 190 195 215 228 233 260 270 280 305

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in 10°C (source side) with identical flow rate that in the cooling mode
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Water in-out 23/18°C (plant side), water in-out 45/50°C (total recovery side)
(5) Condenser water in-out 40/45°C (plant side), water in 10°C (source side) with identical flow rate that in the cooling mode H
(6) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(7) Ci=Circulator; Ce=Centrifugal
(8) Sound power level according to ISO 9614 and Eurovent 8/1
(9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.

L P

65
PRANA

BWR MTD 0011m÷0121t


Versioni
BWR MTD Medium temperature geothermal reversible heat
pump for water heating up to 55°C

Features
Structure and base in hot galvanised epoxy powder
coated steel.
High-efficiency plate exchangers in AISI 316 stainless
steel with low pressure drops, fitted with heating element
for frost protection.
Hermetic scroll type compressors, equipped with the
crankcase heater and thermal protection
Case panels are insulated within low noise material for
further improvement of silence
Rubber vibration damper.
Soft starter for 230V/1/50Hz units /ms
Phase sequence control relay
The water circuit comes complete with:
• Variable flow circulator for 0011÷0031 models and
multistage centrifugal variable flow pump for
models 0071÷0121, plant side
• Variable flow circulator for 0011÷0031 models,
multistage centrifugal variable flow pump for models
Reversible heat pump, 0071-0121 on source side (for geothermal systems,
closed vertical or horizontal loops)
geothermal source • Safety valve.
• Expansion tank.
5,4 ÷ 33,3 kW • Manual filling assembly
• Pressure gauge.
• Air vent valve.
Unit description • Drain valve on both plant and source circuits.
The MTD heat pump optimized for geothermal systems are reversible units for heating, • Differential pressure switch on source side and
cooling and domestic hot water by external three-way valve (accessory). Both heat system side
pumps MTD are suitable for traditional heating systemsand radiant panels. The latter,
working with water at lower temperatures, ensure a higher yield and are a particularly
appreciated for new buildings with low energy consumption that point on using Main accessories
renewable energy resources. • HSW12 remote keyboard
The installation is greatly simplified through the integration of the group and hydraulic • External temperature sensor (mandatory with HSW12
technology Full floating simply by connecting the unit to water plant and electricity so remote keyboard)
that it can be put into operation. • Three-way valve for domestic hot water
• Buffer tank 35,100,200 liters
Commands • Hot water cylinder 300,500 liters
User interface unit on board, accessible from the outside with a not touch system
• 300 litres thermal store for domestic hot water, for kit
Floating Set Once ever y 3 minutes an algorithm automatically optimises the water set point in relation to the DOMH2O
compressor operating time and the temperatures of the water in the system. he water storage tank is no longer • 300,500,1000 litres thermal store for domestic hot
indispensable because it is compensated by the Floating Set function, with resulting reduction in: size; weight; water with solar heat exchanger, for kit DOMH2O
installation times; system setting-up times.
• DOMH2O15 e DOMH2O24 kit for domestic hot water
Floating Flow The controller manages the modulation of the active components (pump and electronic flow
valve) through pressure transducers and temperature sensors. The performance of the unit may thus be optimised
with external heat exchanger plate-to-plate and pump
for different operating conditions, such as traditional fan coil system and panel heating system, ensuring: broader • 1,2,3 kw single-phase electric heater kit
operating limits; easier start-up of installations with both high and low water temperatures; faster system setup.
The electronic menu allows to manage:
- domestic hot water production by external three-way valve (accessory)
- a zone of direct heating
- circulator on system and source side
- outdoor temperature sensor for water plant side modular set point compensation (accessory)

66
BWR MTD
Models 0011m 0021m 0025m 0031m 0041m 0011ms 0021ms 0025ms 0031ms 0041ms
Nominal heating power (1) kW 5,40 5,90 7,30 9,20 11,7 5,40 5,90 7,30 9,20 11,7
Total absorbed power (2) kW 1,34 1,50 1,82 2,35 2,80 1,34 1,50 1,82 2,35 2,80
COP * 4,03 3,93 4 3,92 4,18 4,03 3,93 4 3,92 4,18
Cooling capacity (3) kW 7,10 7,60 9,80 12 15,1 7,10 7,60 9,80 12 15,1
Total absorbed power (2) kW 1,60 1,70 1,96 2,53 3,27 1,60 1,70 1,96 2,53 3,27
EER * 4,44 4,47 5 4,74 4,62 4,44 4,47 5 4,74 4,62
Heating capacity (4) kW 5,20 5,70 7,10 9 11,3 5,20 5,70 7,10 9 11,3
Total absorbed power (2) kW 1,70 1,90 2,30 3 3,60 1,70 1,90 2,30 3 3,60
COP * 3,06 3 3,09 3 3,14 3,06 3 3,09 3 3,14
Cooling capacity (5) kW 5,20 5,60 7,20 8,80 11,3 5,20 5,60 7,20 8,80 11,3
Total absorbed power (2) kW 1,53 1,70 2 2,60 3,20 1,53 1,70 2 2,60 3,20
EER * 3,40 3,29 3,60 3,38 3,53 3,40 3,29 3,60 3,38 3,53
ESEER 4,03 3,73 4,26 3,95 3,90 4,03 3,73 4,26 3,95 3,90
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Source side pump type (6) Ci Ci Ci Ci Ce Ci Ci Ci Ci Ce
Electrical power supply V-Ph~Hz 230-1~50
Start-up current A 58 61 82 97 130 26 27 37 44 59
Sound power (7) dB(A) 52 52 53 53 58 52 52 53 53 58
Sound pressure (8) dB(A) 38 38 39 39 44 38 38 39 39 44
DIMENSION
L mm 560
H mm 980
P mm 575
Operational weight kg 148 148 150 152 160 148 148 150 152 160

Models 0021t 0025t 0031t 0041t 0051t 0061t 0071t 0091t 0101t 0121t
Nominal heating power (1) kW 5,90 7,50 9,10 12,2 13,7 16 19,8 23 26,5 33,3
Total absorbed power (2) kW 1,40 1,74 2,10 2,80 3,40 3,50 4,40 4,90 5,80 7,30
COP * 4,21 4,31 4,33 4,36 4,03 4,57 4,50 4,69 4,57 4,56
Cooling capacity (3) kW 7,60 9,50 12 15,7 18 21,3 26,9 30,7 34,8 44,8
Total absorbed power (2) kW 1,60 1,84 2,50 3,30 3,70 4,10 5,15 5,95 7 8,80
EER * 4,75 5,16 4,80 4,76 4,86 5,20 5,22 5,16 4,97 5,09
Heating capacity (4) kW 5,70 7 8,70 11,8 12,9 15,2 18,8 21,8 25,1 31,9
Total absorbed power (2) kW 1,90 2,20 2,70 3,70 4,10 4,40 5,60 6,20 7,40 9
COP * 3 3,18 3,22 3,19 3,15 3,45 3,36 3,52 3,39 3,54
Cooling capacity (5) kW 5,60 7,30 8,90 11,8 13,2 15,7 19,8 22,9 26 33,4
Total absorbed power (2) kW 1,63 1,90 2,41 3,19 3,80 4 5,10 5,80 6,80 8,40
EER * 3,44 3,84 3,69 3,70 3,47 3,93 3,88 3,95 3,82 3,98
ESEER 3,97 4,54 4,33 4,08 3,92 4,51 4,40 4,61 4,33 4,37
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R410A
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ce Ce Ce Ce
Source side pump type (6) Ci Ci Ci Ce Ce Ce Ce Ce Ce Ce
Electrical power supply V-Ph~Hz 400-3N~50
Start-up current A 32 35 48 64 64 75 95 111 118 140
Sound power (7) dB(A) 52 52 52 58 58 59 66 66 70 70
Sound pressure (8) dB(A) 38 38 38 44 44 45 51 51 55 55
DIMENSION
L mm 560 560 560 560 560 560 680 680 680 680
H mm 980 980 980 980 980 980 1150 1150 1150 1150
P mm 575 575 575 575 575 575 780 780 780 780
Operational weight kg 148 150 152 160 170 175 220 230 235 250

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in-out 0/-3°C (source side)
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Condenser water in-out 40/45°C (plant side), Evaporator water in-out 0/-3°C (source side) H
(5) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(6) Ci=Circulator; Ce=Centrifugal
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
L P
* secondo Eurovent

67
PRANA

BWR HT Slim Z1M6÷Z1T11


Versioni
BWR HT Slim High temperature heat pump, geothermal
source, for water heating up to 60°C,
reversible

Features
Structure and base in hot galvanised epoxy powder coated
steel
180-litre tank with built-in coil for domestic hot water, with
fittings for connecting solar panels or hightemperature fixtures
(e.g. fan coils)
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for frost
protection
High-efficiency single-and three-phase SCROLL compressor
to allow water up to 60 °C to be produced
Also suitable for traditional radiator systems
The compressor and plate heat exchangers are housed in a
suitably insulated enclosure to limit vibrations and noise. This
enclosure can be removed from the unit to make
maintenance easier
Case panels are insulated within low noise material for further
improvement of silence
Rubber vibration damper
Soft starter for 230V/1/50Hz units
Phase sequence control relay
The water circuit comes complete with:
• Circulator on system side
• Circulator on source side (for geothermal systems,
closed vertical or horizontal loops)
• Three-way valve for domestic hot water
• 180Xlt domestic hot water storage tank
• Safety valve
• Expansion tank built into the heat pumps tank
• Manual filling assembly
• Pressure gauge
• Drain valve
• Air vent valve
Reversible heat pump, geothermal source, • Differential pressure switch on source side and system
side
high water temperature with buffer tank • Outside air sensor wired

6,2 ÷ 10,6 kW
Main accessories
• Room unit wired
Unit description
• Room thermostat wired based
The Prana Slim heat pump is designed for heating, cooling, and domestic hot water.
• Room unit wireless
It is an indoor unit with elegant design and thanks to a special sound insulation, the
• Outside air sensor wireless
unit is suitable for a living comfort. • NTC probe for select plant diagram or solar panel
• Heating element kit
Commands
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and
increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage:
- domestic hot water production by three-way valve
- circulator on system and source side
- a zone of direct heating
- zone with mix valve for floor heating
- outdoor temperature sensor for water plant side modular set point compensation
- integration by solar panels
- several solutions through appropriate configurations of the controller

68
BWR HT Slim
Models Z1M6 Z1M9 Z1M11 Z1T6 Z1T9 Z1T11
Nominal heating power (1) kW 6,21 8,66 10,6 6,04 8,43 10,5
Total absorbed power (2) kW 1,60 2,22 2,68 1,55 2,13 2,60
COP * 3,88 3,90 3,96 3,90 3,96 4,02
Cooling capacity (3) kW 9,55 13,2 15,5 9,36 12,9 15,6
Total absorbed power (2) kW 1,46 2,11 2,72 1,45 2,06 2,64
EER * 6,54 6,25 5,71 6,46 6,27 5,92
Heating capacity (4) kW 6,04 8,41 10,3 5,89 8,20 10,2
Total absorbed power (2) kW 2,02 2,80 3,35 1,97 2,71 3,24
COP * 2,99 3 3,08 2,99 3,03 3,14
Cooling capacity (5) kW 6,67 9,24 11,1 6,58 9,12 11,1
Total absorbed power (2) kW 1,53 2,17 2,67 1,49 2,09 2,59
EER * 4,36 4,26 4,16 4,42 4,36 4,28
Hot water tank l 180
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (6) Ci Ci Ci Ci Ci Ci
Source side pump type (6) Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 37 60 68 32 46 50
Sound power (7) dB(A) 42 42 46 42 42 46
Sound pressure (8) dB(A) 28 28 32 28 28 32
DIMENSION
L mm 600
H mm 1940
P mm 570
Operational weight kg 286 293 300 286 293 300

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in-out 0/-3°C (source side)
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Condenser water in-out 40/45°C (plant side), Evaporator water in-out 0/-3°C (source side)
(5) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(6) Ci=Circulator; Ce=Centrifugal H
(7) Sound power level according to ISO 9614 and Eurovent 8/1
(8) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.

* secondo Eurovent
P
L

69
PRANA

BWR HT Cube Z1M6÷Z1T28


Versioni
BWR HT Cube High temperature heat pump, geothermal
source, for water heating up to 60°C,
reversible

Features
Structure and base in hot galvanised epoxy powder coated
steel
High-efficiency plate exchangers in AISI 316 stainless steel
with low pressure drops, fitted with heating element for frost
protection
High-efficiency single-and three-phase SCROLL compressor
to allow water up to 60 °C to be produced
Also suitable for traditional radiator systems
The compressor and plate heat exchangers are housed in a
suitably insulated enclosure to limit vibrations and noise. This
enclosure can be removed from the unit to make
maintenance easier
Case panels are insulated within low noise material for further
improvement of silence
Rubber vibration damper
Soft starter for 230V/1/50Hz units
Phase sequence control relay
The water circuit comes complete with:
• Circulator on system side
• Circulator on source side (for geothermal systems,
closed vertical or horizontal loops)
• Drain valve
• Differential pressure switch on source side and system
side
• Outside air sensor wired

Reversible heat pump, geothermal source,


high water temperature Main accessories
• Room unit wired
6,2 ÷ 27,0 kW • Room thermostat wired based
• Room unit wireless
Unit description • Outside air sensor wireless
The Prana Cube heat pump is designed for heating, cooling, and domestic hot water, • NTC probe for select plant diagram or solar panel
with external three-way valve. It is an indoor unit with elegant design and thanks to a • Heating element kit
• Three-way valve for domestic hot water
special sound insulation, the unit is suitable for a living comfort.
• Buffer tank 35,100,200 liters
• Hot water cylinder 300,500 liters
Commands • 300 litres thermal store for domestic hot water, for kit
Electronic control provides great application flexibility. The remote keyboard kit wired indoor and outdoor DOMH2O
temperature sensors allow dynamic control of delivery temperature water, optimizing comfort in the room and
increasing the energy efficienty. The electronic board PRO EXTENDED allows you to manage: • 300,500,1000 litres thermal store for domestic hot water
- domestic hot water production by three-way valve with solar heat exchanger, for kit DOMH2O
- circulator on system and source side • DOMH2O15 e DOMH2O24 kit for domestic hot water
- a zone of direct heating
- zone with mix valve for floor heating with external heat exchanger plate-to-plate and pump
- outdoor temperature sensor for water plant side modular set point compensation
- integration by solar panels
- several solutions through appropriate configurations of the controller

70
BWR HT Cube
Models Z1M6 Z1M9 Z1M11 Z1T6 Z1T9 Z1T11 Z1T13 Z1T17 Z1T24 Z1T28
Nominal heating power (1) kW 6,21 8,66 10,6 6,04 8,43 10,5 12,6 16,9 23,3 27
Total absorbed power (2) kW 1,60 2,22 2,68 1,55 2,13 2,60 3,17 4,14 5,74 6,53
COP * 3,88 3,90 3,96 3,90 3,96 4,02 3,96 4,09 4,06 4,14
Cooling capacity (3) kW 9,55 13,2 15,5 9,36 12,9 15,6 19 24,9 34,7 40
Total absorbed power (2) kW 1,46 2,11 2,72 1,45 2,06 2,64 3,76 4,95 6,14 7
EER * 6,54 6,25 5,71 6,46 6,27 5,92 5,04 5,02 5,65 5,71
Heating capacity (4) kW 6,04 8,41 10,3 5,89 8,20 10,2 12,2 16,4 22,6 26,2
Total absorbed power (2) kW 2,02 2,80 3,35 1,97 2,71 3,24 3,94 5,24 7,12 8,12
COP * 2,99 3 3,08 2,99 3,03 3,14 3,09 3,14 3,18 3,23
Cooling capacity (5) kW 6,67 9,24 11,1 6,58 9,12 11,1 13,4 17,5 24,3 28,2
Total absorbed power (2) kW 1,53 2,17 2,67 1,49 2,09 2,59 3,38 4,53 6,01 6,77
EER * 4,36 4,26 4,16 4,42 4,36 4,28 3,97 3,87 4,05 4,16
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Source side pump type (6) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 37 60 68 32 46 50 66 101 123 127
Sound power (7) dB(A) 42 42 46 42 42 46 47 51 55 55
Sound pressure (8) dB(A) 28 28 32 28 28 32 33 37 41 41
DIMENSION
L mm 600 600 600 600 600 600 600 600 900 900
H mm 940 940 940 940 940 940 940 940 1117 1117
P mm 570 570 570 570 570 570 570 570 648 648
Operational weight kg 160 180 190 160 180 190 200 220 240 250

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in-out 0/-3°C (source side)
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Condenser water in-out 40/45°C (plant side), Evaporator water in-out 0/-3°C (source side) H
(5) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(6) Ci=Circulator; Ce=Centrifugal
(8) Sound power level according to ISO 9614 and Eurovent 8/1
(9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit. P

* secondo Eurovent L

71
PRANA

BWR DHW 0011m÷0121t


Versioni
BWR DHW Geothermal reversible heat pump with domestic
hot water supply with total heat recovery

Features
Structure and base in hot galvanised epoxy powder coated
steel.
Case panels are insulated within low noise material for further
improvement of silence
Rubber vibration damper.
Hermetic scroll type compressors, equipped with the
crankcase heater and thermal protection
Stainless steel (AISI 316) with high efficiency and low pressure
drop plate to plate exchanger (at the domestic hot water side).
It is positioned next after the compressor, it ensures the
domestic hot water production. That can work either in full
recovery or in part, with the constant optimization of efficiency
through logic advanced adjusting controller
Exchangers plant side plate of stainless steel AISI 316 with
high efficiency and low pressure drop meets the supply of both
hot or cold water for the facility, regardless of the domestic hot
water
High efficiency and low pressure drop stainless steel (AISI 316)
Reversible heat pump, total heat source side plate exchanger
Soft starter for 230V/1/50Hz units /ms
recovery, geothermal source The water circuit comes complete with:
• Variable flow circulator for 0011÷0031 models and
4,5 ÷ 29,7 kW multistage centrifugal variable flow pump for
models 0071÷0121, plant side
• Domestic hot water, water side, variable flow pump
Unit description • Variable flow circulator for 0011÷0031 models, multistage
PRANA DHW is the heat pump new generation able to operate throughout the year in centrifugal variable flow pump for models
any operating mode: either a single cycle (air conditioning, heating, hot water) and 0071-0121 on source side (for geothermal systems,
combined cycle (hot water along with air conditioning or heating). Energy efficiency is closed vertical or horizontal loops)
highest during the summer cycle, when, thanks to the full recovery of the heat, the • Safety valve
production of hot water is free. During the combined use, the DHW exchanger uses • Expansion tank
the temperature of the hot exhaust gases to gets inside the accumulation sanitary • Drain valve on both plant and source circuits
water as high as 65° C.
The advanced CLIMAVENETA fully patented electronic ensures the highest flexibility of
operation, a rapid speed and a significant increase in the overall COP, which go hand Main accessories
in hand with electricity and space reduction. Advantages, combined with the possibility • Buffer tank 35,100,200 liters
of completely eliminating the traditional boiler, making heat pumps PRANA DHW the • Hot water cylinder 300,500 liters
ideal solution for energy saving applications in residential, hotel and small sector. • 300 litres thermal store for domestic hot water, for kit
DOMH2O
Commands • 300,500,1000 litres thermal store for domestic hot water
User interface unit on board, accessible from the outside with a not touch system
with solar heat exchanger, for kit DOMH2O
BWR-DHW heats water stored in the tank as energy storage. It also comes with a state-of-the-art electronic unit, • DOMH2O15 e DOMH2O24 kit for domestic hot water
which independently controls the modes of operation. The appliance can operate throughout the year in any with external heat exchanger plate-to-plate and pump
mode, both with single cycle (cooling, heating, hot water) and with combined cycle (hot water together with
cooling or hot water together heating).During the summer cycle there is maximum energy saving through total heat
• Remote keyboard
recovery. This energy is completely free of charge with regard to the production of hot water. • Removable metal mesh water filter kit

72
BWR DHW
Models 0011m 0021m 0025m 0031m 0041m 0011ms 0021ms 0025ms 0031ms 0041ms
Nominal heating power (1) kW 4,50 5,70 6,70 7,80 9,70 4,50 5,70 6,70 7,80 9,70
Total absorbed power (2) kW 1,30 1,60 1,90 2,30 2,80 1,30 1,60 1,90 2,30 2,80
COP 3,44 3,45 3,48 3,39 3,51 3,44 3,45 3,48 3,39 3,51
Cooling capacity (3) kW 7,30 9,20 11 12,5 15,3 7,30 9,20 11 12,5 15,3
Total absorbed power (2) kW 1,30 1,70 2 2,40 2,90 1,30 1,70 2 2,40 2,90
EER 5,62 5,41 5,50 5,21 5,28 5,62 5,41 5,50 5,21 5,28
Total absorbed power (4) kW 6 7,80 9,20 10,3 12,9 6 7,80 9,20 10,3 12,9
Total absorbed power kW 1,90 2,40 2,90 3,40 4,20 1,90 2,40 2,90 3,40 4,20
Recovery heating capacity (4) kW 7,90 10 11,9 13,5 16,8 7,90 10 11,9 13,5 16,8
Heating capacity (5) kW 4,30 5,50 6,60 7,70 9,40 4,30 5,50 6,60 7,70 9,40
Total absorbed power (2) kW 1,70 2,10 2,50 3 3,50 1,70 2,10 2,50 3 3,50
COP 2,60 2,63 2,64 2,59 2,69 2,60 2,63 2,64 2,59 2,69
Cooling capacity (6) kW 5,10 6,50 7,70 8,90 11 5,10 6,50 7,70 8,90 11
Total absorbed power (2) kW 1,30 1,70 2 2,40 2,90 1,30 1,70 2 2,40 2,90
EER 3,92 3,82 3,85 3,71 3,79 3,92 3,82 3,85 3,71 3,79
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Recovery side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Source side pump type (7) Ci Ci Ci Ci Ce Ci Ci Ci Ci Ce
Electrical power supply V-Ph~Hz 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50 230-1~50
Start-up current A 47 61 76 100 114 21 27 34 45 51
Sound power (8) dB(A) 52 52 53 53 58 52 52 53 53 58
Sound pressure (9) dB(A) 38 38 39 39 44 38 38 39 39 44
DIMENSION
L mm 560
H mm 980
P mm 575
Operational weight kg 188 188 190 195 215 188 188 190 195 215

Models 0021t 0025t 0031t 0041t


0051t 0061t 0071t 0091t 0101t 0121t
Nominal heating power (1) kW 5,60 6,60 7,70 9,50
11,4 13,9 18,8 21,2 24,4 29,7
Total absorbed power (2) kW 1,60 1,90 2,20 2,70
3,20 3,70 5,10 5,60 6,60 8,30
COP 3,50 3,51 3,44 3,56
3,57 3,72 3,70 3,81 3,72 3,57
Cooling capacity (3) kW 9,20 10,9 12,4 15,4
19,1 22,5 30,2 34,4 38,9 49,7
Total absorbed power (2) kW 1,60 1,90 2,30 2,80
3,60 4,10 5,50 6,10 7,30 9,30
EER 5,75 5,74 5,39 5,50
5,31 5,49 5,49 5,64 5,33 5,34
Total absorbed power (4) kW 7,70 9,10 10,3 1613,1 18,9 25,5 29 32,7 41,1
Total absorbed power kW 2,30 2,80 3,30 4,90 4 5,70 7,70 8,40 10,2 12,8
Recovery heating capacity (4) kW 9,90 11,7 13,4 16,9
20,6 24,2 32,7 36,9 42,4 53,1
Heating capacity (5) kW 5,40 6,50 7,50 9,30
11,1 13,3 17,9 20,5 23,5 28,4
Total absorbed power (2) kW 2 2,40 2,90 43,40 4,70 6,50 7 8,30 10,5
COP 2,67 2,67 2,63 2,75
2,78 2,86 2,77 2,95 2,84 2,69
Cooling capacity (6) kW 6,50 7,70 8,80 10,9
13,4 16,1 21,7 24,6 28 34,8
Total absorbed power (2) kW 1,70 2 2,30 2,80
3,40 4 5,40 5,90 7 8,90
EER 3,82 3,85 3,83 3,89
3,94 4,03 4,02 4,17 4,00 3,91
Compressor type SCROLL
N. Compressors N. 1
Refrigerant R407C
Plant side pump type (7) Ci Ci Ci Ci Ci Ci Ce Ce Ce Ce
Recovery side pump type (7) Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci
Source side pump type (7) Ci Ci Ci Ce Ce Ce Ce Ce Ce Ce
Electrical power supply V-Ph~Hz 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50 400-3N~50
Start-up current A 32 40 46 50 66 74 95 111 118 140
Sound power (8) dB(A) 52 52 52 58 58 59 66 66 70 70
Sound pressure (9) dB(A) 38 38 38 44 44 45 51 51 55 55
DIMENSION
L mm 560 560 560 560 560 560 680 680 680 680
H mm 980 980 980 980 980 980 1150 1150 1150 1150
P mm 575 575 575 575 575 575 780 780 780 780
Operational weight kg 188 190 195 215 228 233 260 270 280 305

NOTE
(1) Condenser water in-out 30/35°C (plant side), Evaporator water in-out 0/-3°C (source side)
(2) According to Eurovent
(3) Evaporator water in-out 23/18°C (plant side), Condenser water in-out 30/35°C (source side)
(4) Water in-out 23/18°C (plant side), water in-out 45/50°C (total recovery side) H
(5) Condenser water in-out 40/45°C (plant side), Evaporator water in-out 0/-3°C (source side)
(6) Evaporator water in-out 12/7°C (plant side), Condenser water in-out 30/35°C (source side)
(7) Ci=Circolatore; Ce=Centrifuga
(8) Sound power level according to ISO 9614 and Eurovent 8/1
(9) Average sound pressure level above one reflecting surface (Q=2) at 1 meter from the outside dimensions of the unit.
L P

73
DRONIC
R -
74
hydronic
chiller
CHILLER hydronic - chiller

75
Hydronic - chiller

NECS 0152÷1204
Versions
B base version
HL low noise, high efficiency, high outdoor
temperature version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta is the only company to offer units with Scroll
compressors in 5 versions and 3 different configurations
designed to satisfy all service system and application
Chiller, air source for outdoor installation requirements
STANDARD SUPPLY WITH WATER FILTER ALREADY
INSTALLED
The water filter is already installed as standard supply
on all units, including those without hydronic kit. This
33,8 - 341 kW simplifies installation procedures, while ensuring maximum
working reliability
Unit Description INTEGRATED HYDRONIC MODULE
Outdoor unit for the production of chilled water with hermetic rotary Scroll compressors The incorporated hydronic unit already contains the
dedicated for the use of R410A, axial-flow fans, braze-welded plate-type exchanger and main water circuit components; it is available in various
thermal expansion valve. External panels in Peraluman and structure in aluminium sections. configurations with one or two pumps with high or low
The range includes the single-circuit two-compressor versions and the dual circuit four- head and the buffer tank
compressor versions.
Main accessories
Commands UÊSet-up for remote connectivity with ModBus/Echelon/
W3000 Base / W3000SE Compact Bacnet protocol cards
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an UÊRemote keyboard (distance to 200m and to 500m)
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and UÊSoft starters
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
UÊElectronic expansion valve
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low UÊRubber anti-vibration mounting kit. Spring anti-vibration
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple mounting kit (4 compressors models only)
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

76
r HFC
R-410A
PLATES AXIAL SCROLL COOLING

NECS / B
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552
COOLING
Cooling capacity (1) kW 38,1 45,1 50,5 57 76 86,8 96,9 112 127 145
Total power input (1) kW 14,4 15,6 19,1 21,5 27,8 31,9 36,3 39,6 43,8 50,5
EER 2,65 2,89 2,64 2,65 2,73 2,72 2,67 2,83 2,90 2,87
ESEER 4,05 4,29 4,22 4,15 4,15 4,27 4,17 4,30 4,25 4,40
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 39,5 46,8 52,4 59,2 78,9 90,1 101 117 131 150
Total power input (2) kW 12,9 14,1 17,4 19,8 25,4 29,3 33,6 36,4 39,8 46
Desuperheater heating capacity (2) kW 11,9 13 16,1 18,3 23,5 27,1 31,1 33,6 36,8 42,6
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW
Total power input (3) kW
Heat recovery capacity (3) kW
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 84 84 84 84 85 86 86 86 87 87
Sound pressure (5) dB(A) 52 52 52 52 53 54 54 54 55 55
SIZE
A (6) mm 1695 1695 1695 1695 2195 2195 2745 2745 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1420 1420 1420 1620 1620
Operating weight (6) kg 380 410 420 430 630 660 740 800 950 970

Models 0612 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 159 113 136 154 177 200 223 255 293 325
Total power input (1) kW 58,7 45,6 53,8 59,7 67,8 74,9 84,2 94,1 106 121
EER 2,71 2,48 2,53 2,58 2,61 2,67 2,65 2,71 2,76 2,68
ESEER 4,20 4,10 3,60 3,79 3,91 4,08 4,15 3,96 4,10 4,16
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 165 118 141 160 183 207 232 265 304 337
Total power input (2) kW 54,2 40 43,8 49,6 57,2 64,2 73,3 78,7 90,4 105
Desuperheater heating capacity (2) kW 50,1 37 40,5 45,9 53 59,4 67,8 72,8 83,6 97
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 87 91 92 92 92 92 93 94 95 95
Sound pressure (5) dB(A) 55 59 60 60 60 60 61 62 63 63
SIZE
A (6) mm 3245 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 980 1230 1450 1620 1780 1890 2070 2220 2380 2530

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

77
NECS / HL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 118 136 151 172 201 222 249 290 326
Total power input (1) kW 43,7 49,8 58,1 66,7 72,8 83,8 91,9 102 117
EER 2,70 2,73 2,60 2,58 2,76 2,65 2,71 2,83 2,77
ESEER 3,93 4,04 4,02 4,15 4,02 4,04 4,14 4,37 4,16
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 123 141 157 178 209 231 258 301 338
Total power input (2) kW 42,4 48,4 56,2 64,4 70,7 81,1 88,8 99,1 104
Desuperheater heating capacity (2) kW 34,8 40,4 47,5 55,1 58,7 68,3 75,5 85,1 96,5
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 86 86 86 86 88 88 88 90 91
Sound pressure (5) dB(A) 54 54 54 54 56 56 56 58 59
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1710 1860 2120 2180 2320 2630 2770

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

78
NECS / HT
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
COOLING
Cooling capacity (1) kW 39,7 46,7 55 61,6 80,6 91,4 104 116 130
Total power input (1) kW 13,5 15,2 17,3 20,3 25,9 30,5 33,7 38,7 42,2
EER 2,94 3,07 3,18 3,03 3,11 3 3,09 3 3,08
ESEER 4,28 4,18 4,41 4,09 4,27 4,18 4,28 4,31 4,39
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 41,2 48,5 57 63,9 83,6 94,9 108 120 135
Total power input (2) kW 12,1 13,3 15,3 17,7 23,1 27,1 30,1 34,8 38,3
Desuperheater heating capacity (2) kW 11,2 12,3 14,1 16,3 21,3 25 27,8 32,2 35,5
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW
Total power input (3) kW
Heat recovery capacity (3) kW
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 84 85 85 86 86 87 87 87 87
Sound pressure (5) dB(A) 52 53 53 54 54 55 55 55 55
SIZE
A (6) mm 1695 2195 2195 2745 2745 3245 3245 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1620 1620 1620 1620
Operating weight (6) kg 400 460 490 550 710 800 880 930 960

Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 123 142 159 182 210 233 262 303 341
Total power input (1) kW 45,4 50,5 57,8 65 74,5 84,1 90,7 101 117
EER 2,71 2,81 2,75 2,80 2,82 2,77 2,89 2,99 2,91
ESEER 3,63 3,76 3,90 4,02 3,82 3,86 4,08 4,25 4,08
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 127 147 165 189 218 242 272 315 354
Total power input (2) kW 44 49,2 55,9 63 72,2 81,5 88,1 98,4 114
Desuperheater heating capacity (2) kW 32,9 37,7 43,9 50,5 55,1 63,8 69,8 85,8 97,1
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 92 92 92 92 94 94 94 96 97
Sound pressure (5) dB(A) 60 60 60 60 62 62 62 64 65
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1710 1860 2120 2180 2320 2630 2770

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

79
NECS / LN
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552
COOLING
Cooling capacity (1) kW 36,1 42,8 50,7 57,6 74,2 84,4 96,4 109 122 139
Total power input (1) kW 15 16,4 19 21,3 28,7 33,8 37,1 41,4 45,9 53,3
EER 2,41 2,61 2,67 2,70 2,59 2,50 2,60 2,63 2,66 2,61
ESEER 4,03 4,20 4,25 4,22 4,11 3,99 4,02 4,15 4,06 4,19
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 37,5 44,4 52,6 59,8 77 87,6 100 113 127 144
Total power input (2) kW 13,9 15,3 17,3 19,6 26,4 30,5 33,8 38 41,9 48,8
Desuperheater heating capacity (2) kW 12,9 14,1 16 18,1 24,4 28,3 31,3 35,2 38,7 45,2
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW
Total power input (3) kW
Heat recovery capacity (3) kW
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 79 79 80 80 81 83 83 83 84 84
Sound pressure (5) dB(A) 47 47 48 48 49 51 51 51 52 52
SIZE
A (6) mm 1695 1695 2195 2195 2745 2745 2745 2745 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1620 1620 1620 1620 1620
Operating weight (6) kg 380 410 470 510 680 730 800 840 950 970

Models 0612 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 151 104 129 147 167 187 208 242 275 306
Total power input (1) kW 62,4 47,9 53,5 60 69,6 77,6 87,8 95,3 109 125
EER 2,42 2,17 2,41 2,45 2,40 2,41 2,37 2,54 2,52 2,44
ESEER 3,96 3,93 3,84 3,91 4,01 3,99 4,07 4,01 4,15 4,06
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 157 108 134 153 173 194 216 251 286 317
Total power input (2) kW 57,8 46,6 51,8 58,2 67,1 75,3 85,2 92 106 121
Desuperheater heating capacity (2) kW 53,5 40,9 43,5 49,3 57,6 65,2 74,4 78,4 91,3 105
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 84 85 86 86 86 86 87 88 89 89
Sound pressure (5) dB(A) 52 53 54 54 54 54 55 56 57 57
SIZE
A (6) mm 3245 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 980 1230 1450 1620 1780 1890 2070 2220 2380 2530

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

80
NECS / SL
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
COOLING
Cooling capacity (1) kW 33,8 42,3 47,8 55,5 69,9 85,4 96,8 106 118
Total power input (1) kW 16,3 17,1 20,4 22,6 30,9 33,6 37,2 43,1 48,4
EER 2,07 2,47 2,34 2,46 2,26 2,54 2,60 2,46 2,44
ESEER 3,77 3,93 4,01 3,89 3,86 3,87 3,91 3,91 3,90
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 35 43,9 49,6 57,5 72,6 88,6 101 110 122
Total power input (2) kW 15,1 15,5 18,7 20,6 28,6 30 33,6 39,3 44
Desuperheater heating capacity (2) kW 14 14,3 17,3 19 26,4 27,8 31,1 36,3 40,7
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW
Total power input (3) kW
Heat recovery capacity (3) kW
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 76 77 77 78 78 81 81 81 82
Sound pressure (5) dB(A) 44 45 45 46 46 49 49 49 50
SIZE
A (6) mm 1695 2195 2195 2745 2745 3245 3245 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1620 1620 1620 1620
Operating weight (6) kg 400 460 490 550 710 800 880 930 960

Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 113 130 147 161 193 211 235 278 313
Total power input (1) kW 45,2 51,8 58,8 70,6 75,4 87,2 96,7 106 121
EER 2,50 2,51 2,50 2,28 2,56 2,42 2,43 2,61 2,58
ESEER 4,02 4,14 4,14 4,13 4,08 4,08 4,10 4,39 4,19
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 117 135 152 167 200 219 243 288 325
Total power input (2) kW 43,7 50,2 56,9 68,4 72,8 84,3 93,2 103 117
Desuperheater heating capacity (2) kW 37,2 43,2 49,5 60,1 62,6 73,2 81,5 90,2 102
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 325
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 298 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 82 82 82 82 83 83 83 85 86
Sound pressure (5) dB(A) 50 50 50 50 51 51 51 53 54
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1770 1860 2120 2180 2320 2630 2770

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-0512 0504-1204
Switchboard side mm 600 1100
Switchboard opposite side mm 600 1100
Condensation coil side mm 1000 2000

H H

A
A
B
B

81
Hydronic - chiller

NECS 0202T÷0612T
Versions
B base version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS
represents the best choice for all the hydronic application
on the residential, commercial and industrial markets.
INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main
water circuit components; it is available with single or twin
in-line, for achieving both low or high head.
MAXIMUM RELIABILITY
Unit with dual-circuit refrigerant section designed to
ensure maximum efficiency at full load, ensuring continuity
Chiller, air source for outdoor installation without interruption of operation in the event of temporary
stop of one of the 2 circuits.

53,0 - 159 kW Main accessories


UÊSet-up for remote connectivity with ModBus/Echelon/
Unit Description Bacnet protocol cards
Outdoor unit for the production of chilled water with hermetic rotary Scroll compressors, axial- UÊRemote keyboard (distance to 200m and to 500m)
flow fans, shell and tubes exchanger and thermostatic expansion valve. External panels in UÊLCD display keyboard type W3000Compact with multi-
Peraluman and structure in aluminium sections. The range is equipped with two compressors language user interface (refers to the shown picture)
on two independent refrigerant circuits. UÊSoft starters
UÊRubber anti-vibration mounting kit
Commands
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks. The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous operational
parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall energy
efficiency.

82
SHELL & TUBES AXIAL SCROLL COOLING

NECS / B
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T 0552T 0612T
COOLING
Cooling capacity (1) kW 53 58,1 76,0 86,8 96,9 112 127 145 159
Total power input (1) kW 18,3 21,5 27,8 31,9 36,3 39,7 43,7 50,2 58,6
EER 2,90 2,70 2,73 2,72 2,67 2,67 2,90 2,89 2,71
ESEER 3,72 3,47 3,52 3,49 3,41 3,59 3,65 3,66 3,44
COMPRESSORS
No. Compressors/No. Circuits N. 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02
NOISE LEVELS
Sound power (2) dB(A) 85 85 85 86 86 86 87 87 87
Sound pressure (3) dB(A) 53 53 53 54 54 54 55 55 55
SIZE
A (4) mm 1695 1695 2195 2195 2745 2745 3245 3245 3245
B (4) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (4) mm 1420 1420 1420 1420 1420 1420 1620 1620 1620
Operating weight (4) kg 625 625 665 765 920 990 1135 1180 1155
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

NECS / HT
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T
COOLING
Cooling capacity (1) kW 55 61,6 80,6 91,4 104 116 130
Total power input (1) kW 17,3 20,3 25,9 30,5 33,7 38,6 42,2
EER 3,18 3,03 3,11 3 3,09 3 3,08
ESEER 4,07 3,91 3,93 3,76 3,87 3,76 3,86
COMPRESSORS
No. Compressors/No. Circuits N. 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02
NOISE LEVELS
Sound power (2) dB(A) 85 86 86 87 87 87 87
Sound pressure (3) dB(A) 53 54 54 55 55 55 55
SIZE
A (4) mm 2195 2745 2745 3245 3245 3245 3245
B (4) mm 1120 1120 1120 1120 1120 1120 1120
H (4) mm 1420 1420 1420 1620 1620 1620 1620
Operating weight (4) kg 650 700 750 915 1050 1075 1115
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

NECS / LN
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T 0552T 0612T
COOLING
Cooling capacity (1) kW 50,7 57,6 74,2 84,4 96,4 109 122 0 0
Total power input (1) kW 18,9 21,2 28,6 33,7 37,1 41,4 45,9 53,1 62,4
EER 2,68 2,72 2,59 2,50 2,60 2,63 2,66 0 0
ESEER 3,50 3,51 3,37 3,22 3,33 3,36 3,38 3,34 3,11
COMPRESSORS
No. Compressors/No. Circuits N. 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02
NOISE LEVELS
Sound power (2) dB(A) 80 80 81 83 83 83 84 84 84
Sound pressure (3) dB(A) 48 48 49 51 51 51 52 52 52
SIZE
A (4) mm 2195 2195 2745 2745 2745 2745 3245 3245 3245
B (4) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (4) mm 1420 1420 1420 1620 1620 1620 1620 1620 1620
Operating weight (4) kg 625 650 715 840 965 1025 1135 1180 1155
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

83
NECS / SL
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T
COOLING
Cooling capacity (1) kW 47,8 55,5 69,9 85,4 96,8 106 118
Total power input (1) kW 20,3 22,6 30,9 33,6 37,3 43,2 48,1
EER 2,35 2,46 2,26 2,54 2,60 2,46 2,44
ESEER
COMPRESSORS
No. Compressors/No. Circuits N. 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02 02 / 02
NOISE LEVELS
Sound power (2) dB(A) 77 78 78 81 81 81 82
Sound pressure (3) dB(A) 45 46 46 49 49 49 50
SIZE
A (4) mm 2195 2745 2745 3245 3245 3245 3245
B (4) mm 1120 1120 1120 1120 1120 1120 1120
H (4) mm 1420 1420 1420 1620 1620 1620 1620
Operating weight (4) kg 650 700 750 915 1050 1075 1115

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0202T-0512T
Switchboard side mm 600
Switchboard opposite side mm 600
Condensation coil side mm 1000

84
85
Hydronic - chiller

NECS 1314÷3218
Versions
B base version
SL super-low noise version
CA Class A of efficiency
SL-CA Super Low noise version, Class A of efficiency

Configurazioni
- funzione base
D partial condensing heat recovery function
R total condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
ALUMINIUM MICRO-CHANNEL HEAT EXCHANGERS
The new NECS uses aluminium micro-channel
condensers that ensure a premium level of efficiency.
This solution also allows to reduce the refrigerant charge
with respect to traditional copper/aluminium coils as well
as improving the resistance against corrosion in saline or
corrosive atmospheres.
Chiller, air source for outdoor installation SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS
354 - 885 kW represents the best choice for all the hydronic application
on the residential, commercial and industrial markets.
Unit Description ELECTRONIC EXPANSION VALVE SUPPLIED
Outdoor unit for the production of chilled water with hermetic rotary Scroll compressors, STANDARD
ozone-friendly refrigerant R410A, axial-flow fans, shell and tubes exchanger and electronic The use of the electronic expansion valve generates
expansion valve. The range is composed by units equipped with four, six and eight considerable benefits, especially in cases of variable
compressors in multi-circuit configuration. demand and different external conditions. It was
introduced into these units as a result of accurate
design choices concerning the cooling circuit and the
Commands optimisation of operation in various different working
W3000SE Compact conditions
The W3000SE Compact controller offers advanced functions and algorithms. The keypad features an easy-to-use interface CLASS A EFFICIENCY
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, The full range is also available with the Class A efficiency
beneficial in low water content systems. As alternatives the proportional- or proportional-integral regulations are also rating. NECS/CA guaranties premium levels of efficiency
available. The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions for thanks to the generous sizing of the refrigerant-exchange
enhanced analysis of the unit operation. For multiple units systems, the regulation of the resources, via optional proprietary
devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed. Supervision can surface areas and to an accurate control of the fans.
be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols INTEGRATED HYDRONIC MODULE
as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units.
Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a The incorporated hydronic unit already contains the
proprietary self-adaptive logic, which features the monitoring of numerous operational parameters. This allows to reduce the main water circuit components; it is available in various
number and duration of the defrost cycles, with a benefit for the overall energy efficiency. configurations with one or two pumps with high or low
head and the buffer tank

Main accessories
UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
UÊRemote keyboard (distance to 200m and to 500m)
UÊSoft starters

86
ENERGY CLASS SHELL & TUBES AXIAL SCROLL COOLING

NECS / B
Models 1314 1414 1614 1715 2015 1816 2116
COOLING
Cooling capacity (1) kW 354 379 413 458 526 501 569
Total power input (1) kW 124 130 148 160 184 172 195
EER 2,85 2,91 2,80 2,86 2,86 2,92 2,91
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 5/2 5/2 6/2 6/2
NOISE LEVELS
Sound power (2) dB(A) 96 96 96 96 97 97 97
Sound pressure (3) dB(A) 64 64 64 64 65 65 65
SIZE
A (4) mm 3905 3905 3905 5080 5080 5080 6255
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *

Models 2316 2416 2418 2618 2818 3018 3218


COOLING
Cooling capacity (1) kW 604 635 665 708 759 794 827
Total power input (1) kW 214 219 234 249 261 279 296
EER 2,82 2,90 2,85 2,85 2,92 2,84 2,80
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 6/3 6/2 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (2) dB(A) 97 98 98 98 99 99 99
Sound pressure (3) dB(A) 65 66 65 65 66 66 66
SIZE
A (4) mm 6255 6255 7430 7430 7430 7430 7430
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

NECS / SL
Models 1314 1414 1614 1715 2015 1816 2116
COOLING
Cooling capacity (1) kW 334 358 397 432 498 465 532
Total power input (1) kW 129 137 153 168 192 183 206
EER 2,58 2,61 2,60 2,57 2,60 2,55 2,58
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 5/2 5/2 6/2 6/2
NOISE LEVELS
Sound power (2) dB(A) 88 88 88 88 90 89 90
Sound pressure (3) dB(A) 56 56 56 56 58 57 57
SIZE
A (4) mm 5080 5080 5080 6255 6255 6255 7430
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *
Models 2316 2416 2418 2618 2818 3018 3218
COOLING
Cooling capacity (1) kW 579 596 616 666 718 758 795
Total power input (1) kW 220 230 245 258 275 288 306
EER 2,63 2,59 2,52 2,58 2,61 2,63 2,60
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 6/3 6/2 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (2) dB(A) 91 91 91 91 92 92 92
Sound pressure (3) dB(A) 58 58 58 58 59 59 59
SIZE
A (4) mm 7430 7430 7430 8605 9780 9780 9780
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

87
NECS / CA
Models 1314 1414 1614 1715 2015 1816 2116
COOLING
Cooling capacity (1) kW 370 391 438 481 549 518 591
Total power input (1) kW 120 125 142 154 177 166 189
EER 3,10 3,13 3,10 3,12 3,10 3,11 3,12
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 5/2 5/2 6/2 6/2
NOISE LEVELS
Sound power (2) dB(A) 97 97 97 97 98 98 98
Sound pressure (3) dB(A) 65 65 65 65 66 66 65
SIZE
A (4) mm 5080 5080 5080 6255 6255 6255 7430
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *

Models 2316 2416 2418 2618 2818 3018 3218


COOLING
Cooling capacity (1) kW 633 657 702 740 785 831 885
Total power input (1) kW 204 212 225 239 250 267 283
EER 3,10 3,10 3,11 3,10 3,13 3,12 3,13
ESEER * * * * * * *
COMPRESSORS
No. Compressors/No. Circuits N. 6/3 6/2 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (2) dB(A) 99 99 99 99 100 100 100
Sound pressure (3) dB(A) 66 66 66 66 67 67 67
SIZE
A (4) mm 7430 7430 9780 9780 9780 9780 9780
B (4) mm 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1314-3218
Switchboard side mm 1500
Switchboard opposite side mm 1500
Plant exchagers opposite side mm 1500
Plant exchagers side mm 2000

88
NECS / SL-CA
Models 1314 1414 1614 1715 2015 1816 2116 2316 2416 2418
COOLING
Cooling capacity (1) kW 371 394 440 481 550 522 592 638 663 695
Total power input (1) kW 119 126 142 154 177 167 189 204 213 223
EER 3,11 3,12 3,11 3,12 3,11 3,12 3,13 3,12 3,11 3,12
ESEER 4,57 4,56 4,44 4,54 4,52 4,58 4,60 4,59 4,53 4,58
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 5/2 5/2 6/2 6/2 6/3 6/2 8/4
NOISE LEVELS
Sound power (2) dB(A) 86 86 86 87 87 87 87 88 88 88
Sound pressure (3) dB(A) 53 53 53 54 54 54 54 55 55 55
SIZE
A (4) mm 6255 6255 6255 7430 7430 7430 8605 8605 8605 9780
B (4) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (4) kg 3490 3700 3730 4400 4510 4650 4990 5360 5360 6100

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1314-2418
Switchboard side mm 1500
Switchboard opposite side mm 1500
Plant exchagers opposite side mm 1500
Plant exchagers side mm 2000

B A

89
Hydronic - chiller

NECS-ST 0504÷1204
Versions
B base version
HL low noise, high efficiency, high outdoor
temperature version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta is the only company to offer units with Scroll
compressors in 5 versions and 3 different configurations
designed to satisfy all service system and application
Chiller, air source for outdoor installation requirements
SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS
104 - 341 kW represents the best choice for all the hydronic application
on the residential, commercial and industrial markets.
Unit Description INTEGRATED HYDRONIC MODULE
Outdoor unit for the production of chilled water with hermetic rotary Scroll compressors, axial-
The built-in hydronic module already contains the main
flow fans, shell and tubes exchanger and thermostatic expansion valve. External panels in
water circuit components; it is available with single or twin
Peraluman and structure in aluminium sections. The range is equipped with four compressors
in-line, for achieving both low or high head.
on two independent refrigerant circuits.

Commands Main accessories


W3000SE Compact UÊSet-up for remote connectivity with ModBus/Echelon/
The W3000SE Compact controller offers advanced functions and algorithms. The keypad features an easy-to-use interface Bacnet protocol cards
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, UÊRemote keyboard (distance to 200m and to 500m)
beneficial in low water content systems. As alternatives the proportional- or proportional-integral regulations are also
available. The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions for
UÊSoft starters
enhanced analysis of the unit operation. For multiple units systems, the regulation of the resources, via optional proprietary UÊElectronic expansion valve
devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed. Supervision can
be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols UÊRubber anti-vibration mounting kit. Spring anti-vibration
as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. mounting kit
Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). All /R units adopt the
W3000 SE Large controller.

90
r HFC
R-410A
SHELL & TUBES AXIAL SCROLL COOLING

NECS-ST / B
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 113 136 154 177 200 223 255 293 325
Total power input (1) kW 45,6 53,8 59,7 67,8 74,9 84,2 94,1 106 121
EER 2,48 2,53 2,58 2,61 2,67 2,65 2,71 2,76 2,68
ESEER 4,10 3,60 3,79 3,91 4,08 4,15 3,96 4,10 4,16
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 118 141 160 183 207 232 265 304 337
Total power input (2) kW 40 43,8 49,6 57,2 64,2 73,3 78,7 90,4 105
Desuperheater heating capacity (2) kW 37 40,5 45,9 53 59,4 67,8 72,8 83,6 97
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 91 92 92 92 92 93 94 95 95
Sound pressure (5) dB(A) 59 60 60 60 60 61 62 63 63
SIZE
A (6) mm 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1230 1450 1620 1780 1890 2070 2220 2380 2530
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-ST / HL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 118 136 151 172 201 222 249 290 326
Total power input (1) kW 43,7 49,8 58,1 66,7 72,8 83,8 91,9 102 117
EER 2,70 2,73 2,60 2,58 2,76 2,65 2,71 2,83 2,77
ESEER 3,93 4,04 4,02 4,15 4,02 4,04 4,14 4,37 4,16
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 123 141 157 178 209 231 258 301 338
Total power input (2) kW 42,4 48,4 56,2 64,4 70,7 81,1 88,8 99,1 104
Desuperheater heating capacity (2) kW 34,8 40,4 47,5 55,1 58,7 68,3 75,5 85,1 96,5
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 86 86 86 86 88 88 88 90 91
Sound pressure (5) dB(A) 54 54 54 54 56 56 56 58 59
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1710 1860 2120 2180 2320 2630 2770
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

91
NECS-ST / HT
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 123 142 159 182 210 233 262 303 341
Total power input (1) kW 45,4 50,5 57,8 65 74,5 84,1 90,7 101 117
EER 2,71 2,81 2,75 2,80 2,82 2,77 2,89 2,99 2,91
ESEER 3,63 3,76 3,90 4,02 3,82 3,86 4,08 4,25 4,08
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 127 147 165 189 218 242 272 315 354
Total power input (2) kW 44 49,2 55,9 63 72,2 81,5 88,1 98,4 114
Desuperheater heating capacity (2) kW 32,9 37,7 43,9 50,5 55,1 63,8 69,8 85,8 97,1
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 92 92 92 92 94 94 94 96 97
Sound pressure (5) dB(A) 60 60 60 60 62 62 62 64 65
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1710 1860 2120 2180 2320 2630 2770

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-ST / LN
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 104 129 147 167 187 208 242 275 306
Total power input (1) kW 47,9 53,5 60 69,6 77,6 87,8 95,3 109 125
EER 2,17 2,41 2,45 2,40 2,41 2,37 2,54 2,52 2,44
ESEER 3,93 3,84 3,91 4,01 3,99 4,07 4,01 4,15 4,06
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 108 134 153 173 194 216 251 286 317
Total power input (2) kW 46,6 51,8 58,2 67,1 75,3 85,2 92 106 121
Desuperheater heating capacity (2) kW 40,9 43,5 49,3 57,6 65,2 74,4 78,4 91,3 105
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 333
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 299 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 85 86 86 86 86 87 88 89 89
Sound pressure (5) dB(A) 53 54 54 54 54 55 56 57 57
SIZE
A (6) mm 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1230 1450 1620 1780 1890 2070 2220 2380 2530
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

92
NECS-ST / SL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 113 130 147 161 193 211 235 278 313
Total power input (1) kW 45,2 51,8 58,8 70,6 75,4 87,2 96,7 106 121
EER 2,50 2,51 2,50 2,28 2,56 2,42 2,43 2,61 2,58
ESEER 4,02 4,14 4,14 4,13 4,08 4,08 4,10 4,39 4,19
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 117 135 152 167 200 219 243 288 325
Total power input (2) kW 43,7 50,2 56,9 68,4 72,8 84,3 93,2 103 117
Desuperheater heating capacity (2) kW 37,2 43,2 49,5 60,1 62,6 73,2 81,5 90,2 102
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 118 138 158 181 204 231 258 295 325
Total power input (3) kW 38,7 44,1 49,4 56,9 64,5 72,1 79,8 92,8 105
Heat recovery capacity (3) kW 155 179 204 234 264 298 333 382 431
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 82 82 82 82 83 83 83 85 86
Sound pressure (5) dB(A) 50 50 50 50 51 51 51 53 54
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1360 1570 1770 1860 2120 2180 2320 2630 2770

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0504-1204
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

A
B

93
Hydronic - chiller

FOCS 0751÷2632
Versions
B base version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C at full load; with total heat recovery, hot water
can be produced up to a temperature of 55°C.
INTEGRATED HYDRONIC MODULE
Chiller, air source for outdoor installation Optional pump unit also with storage tank, consisting of
1 or 2 pumps, 2 or 4-pole motor, with three head options
to satisfy different industrial applications and demands for
comfort
145 - 516 kW
Unit Description Main accessories
Outdoor unit for the production of chilled water with semi-hermetic screw compressors UÊSoft start
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
UÊCompressor power factor device
plate evaporator and thermostatic expansion valve. Frame with base in polyester-painted thick
hot-galvanised sheet steel and external panels in peraluman. Flexible and reliable unit; it easily UÊElectronic expansion valve
adapts itself to different thermal load conditions thanks to the precise thermoregulation. The UÊVariable speed condensation control (standard on /LN,
high performances level is achieved thanks to the accurate sizing of all internal components. /SL)
UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Bacnet protocol board
Commands UÊHydronic group with possible storage tank
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

94
r HFC
R-134a
PLATES AXIAL SCREW COOLING

FOCS / B
Models 0751 0851 0951 0961 1021 1301 1532 1732 1932 1952 2432 2632
COOLING
Cooling capacity (1) kW 145 163 182 201 234 266 277 329 366 398 466 516
Total power input (1) kW 51,6 61,1 68,4 75 85,1 93,3 103 121 138 154 178 193
EER 2,81 2,67 2,66 2,68 2,75 2,85 2,67 2,71 2,64 2,58 2,61 2,67
ESEER 3,50 3,42 3,52 3,63 3,49 3,54 3,64 3,57 3,56 3,58 3,61 3,49
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 150 169 189 209 243 276
Total power input (2) kW 49,9 59 66,5 72,7 82,7 90,5
Desuperheater heating capacity (2) kW 40,8 49,2 56,2 61,8 68,4 75,7
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 148 171 190 211 241 275
Total power input (3) kW 43,8 51 59,3 61,6 70,1 80,4
Heat recovery capacity (3) kW 190 220 246 269 307 351
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 94 94 94 94 96 96 97 97 97 97 99 99
Sound pressure (5) dB(A) 62 62 62 62 64 64 65 65 65 65 67 67
SIZE
A (6) mm 3110 3110 3110 3110 4610 4610 4610 4610 4610 4610 5610 5610
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 2150 2150 2150 2150 2150 2150 2150 2420 2420 2420 2430 2430
Operating weight (6) kg 1680 1710 1780 1860 2590 2720 2970 3160 3300 3320 4400 4620
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

FOCS / LN
Models 0751 0851 0951 0961 1021 1301 1532 1732 1932 1952 2432 2632
COOLING
Cooling capacity (1) kW 141 157 175 195 229 256 266 310 345 376 440 483
Total power input (1) kW 51,3 61,1 70 77,4 86,7 94,8 105 124 143 164 185 201
EER 2,75 2,57 2,50 2,52 2,64 2,70 2,51 2,50 2,40 2,29 2,37 2,40
ESEER 3,69 3,51 3,57 3,69 3,65 3,59 3,68 3,58 3,61 3,61 3,62 3,48
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 146 162 181 202 237 265
Total power input (2) kW 49,3 59 67,6 74,8 83,7 91,4
Desuperheater heating capacity (2) kW 42,5 51,4 59,4 66,1 72,7 79,9
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 139 157 172 205 231 247
Total power input (3) kW 51,5 60,6 71 73,7 87,3 98
Heat recovery capacity (3) kW 45,1 53,5 63,2 64,3 76,9 86,9
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 88 88 88 88 90 90 91 91 91 91 93 93
Sound pressure (5) dB(A) 56 56 56 56 58 58 59 59 59 59 61 61
SIZE
A (6) mm 3110 3110 3110 3110 4610 4610 4610 4610 4610 4610 5610 5610
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 2150 2150 2150 2150 2150 2150 2150 2420 2420 2420 2430 2430
Operating weight (6) kg 1680 1710 1780 1860 2590 2720 2970 3160 3300 3320 4400 4620
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

95
FOCS / SL
Models 0751 0851 0951 0961 1021 1301 1532 1732 1932 1952 2432 2632
COOLING
Cooling capacity (1) kW 134 151 166 197 223 238 252 296 334 377 443 484
Total power input (1) kW 53,2 62,7 73,8 76,1 90,3 101 111 128 149 164 183 199
EER 2,52 2,41 2,25 2,59 2,47 2,35 2,26 2,31 2,24 2,29 2,41 2,43
ESEER 3,54 3,41 3,40 3,69 3,58 3,32 3,50 3,47 3,46 3,62 3,69 3,52
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 148 172 190 211 241 275
Total power input (2) kW 43,8 51 59,3 61,6 70,1 80,4
Desuperheater heating capacity (2) kW 190 220 246 269 307 351
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 148 172 190 211 241 275
Total power input (3) kW 43,8 51 59,3 61,6 70,1 80,4
Heat recovery capacity (3) kW 190 220 246 269 307 351
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 84 84 84 84 86 86 86 87 87 87 89 89
Sound pressure (5) dB(A) 52 52 52 52 54 54 54 55 55 55 56 56
SIZE
A (6) mm 3110 3110 3110 4110 4610 4610 4610 4610 5610 5610 6610 6610
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 2150 2150 2150 2150 2150 2150 2150 2420 2430 2430 2430 2430
Operating weight (6) kg 1680 1770 1840 1980 2670 2720 3060 3270 3460 3640 4990 5250
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0751-1952 2432-2632
Switchboard side mm 1500 2000
Switchboard opposite side mm 1500 1800
Condensation coil side mm 2000 3000

96
97
Hydronic - chiller

FOCS 1542÷2642
Versions
B base version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C at full load; with total heat recovery, hot water
can be produced up to a temperature of 55°C.

Chiller, air source for outdoor installation


Main accessories
UÊSoft start
UÊCompressor power factor device
277 - 516 kW UÊElectronic expansion valve
Unit Description UÊVariable speed condensation control (standard on /LN,
Outdoor unit for the production of chilled water with semi-hermetic screw compressors /SL)
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins, UÊRemote keyboard (distance to 200m and to 500m)
shell and tubes evaporator designed by Climaveneta and thermostatic expansion valve. UÊSet-up for remote connectivity with ModBus, Echelon
Frame with base in polyester-painted thick hot-galvanised sheet steel and external panels in LonTalk, Bacnet protocol board
peraluman. Flexible and reliable unit; it easily adapts itself to different thermal load conditions
thanks to the precise thermoregulation. The high performances level is achieved thanks to the
accurate sizing of all internal components.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

98
r HFC
R-134a
SHELL & TUBES AXIAL SCREW COOLING

FOCS / B
Models 1542 1742 1942 1962 2442 2642
COOLING
Cooling capacity (1) kW 277 329 366 398 466 516
Total power input (1) kW 103 121 138 154 178 193
EER 2,67 2,71 2,64 2,58 2,61 2,67
ESEER 3,64 3,57 3,56 3,58 3,61 3,49
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 97 97 97 97 99 99
Sound pressure (3) dB(A) 65 65 65 65 67 67
SIZE
A (4) mm 4610 4610 4610 4610 4610 4610
B (4) mm 2220 2220 2220 2220 2220 2220
H (4) mm 2150 2150 2150 2150 2150 2150
Operating weight (4) kg 3490 3680 3810 4100 5140 5340
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

FOCS / LN
Models 1542 1742 1942 1962 2442 2642
COOLING
Cooling capacity (1) kW 266 310 345 376 440 483
Total power input (1) kW 105 124 143 164 185 201
EER 2,51 2,50 2,40 2,29 2,37 2,40
ESEER 3,68 3,58 3,61 3,61 3,62 3,48
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 91 91 91 91 93 93
Sound pressure (3) dB(A) 59 59 59 59 61 61
SIZE
A (4) mm 4610 4610 4610 4610 5610 5610
B (4) mm 2220 2220 2220 2220 2220 2220
H (4) mm 2150 2420 2420 2420 2430 2430
Operating weight (4) kg 3490 3680 3810 4100 5140 5340
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

FOCS / SL
Models 1542 1742 1942 1962 2442 2642
COOLING
Cooling capacity (1) kW 252 296 334 377 443 484
Total power input (1) kW 111 128 149 164 183 199
EER 2,26 2,31 2,24 2,29 2,41 2,43
ESEER 3,50 3,47 3,46 3,62 3,69 3,52
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 86 87 87 87 89 89
Sound pressure (3) dB(A) 54 55 55 55 56 56
SIZE
A (4) mm 4610 4610 5610 5610 6610 6610
B (4) mm 2220 2220 2220 2220 2220 2220
H (4) mm 2150 2420 2430 2430 2430 2430
Operating weight (4) kg 3580 3790 3960 4410 5730 5970
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1542-2642
Switchboard side mm 1500
Switchboard opposite side mm 1500
Condensation coil side mm 2000

99
Hydronic - chiller

FOCS 1502÷8404
Versions
B base version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C at full load; with total heat recovery, hot water
can be produced up to a temperature of 55°C.
INTEGRATED HYDRONIC MODULE
Chiller, air source for outdoor installation It consists of 2 pumps, 2 or 4-pole motor, fixed or variable
speed, with high or low head options to satisfy different
industrial applications and demands for comfort.

294 - 1744 kW
Unit Description Main accessories
Outdoor unit for the production of chilled water with semi-hermetic screw compressors UÊSoft start
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
UÊCompressor power factor device
shell and tubes evaporator designed by Climaveneta and thermostatic expansion valve.
Base and supporting structure and panels are of galvanized epoxy powder coated steel with UÊElectronic expansion valve
increased thickness. Flexible and reliable unit; it easily adapts itself to different thermal load UÊVariable speed condensation control (standard on /LN,
conditions thanks to the precise thermoregulation. The high performances level is achieved /SL)
thanks to the accurate sizing of all internal components. UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Bacnet protocol board
Commands UÊHydronic group
W3000SE Large UÊVPF (Variable Primary Flow) kit: variable flow pumps with
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources on board regulation
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic. As option (VPF package), the modulation of capacity is integrated with the modulation of the water flow, by means of
inverter and dedicated resources for the hydraulic circuit.

100
r HFC
R-134a
SHELL & TUBES AXIAL SCREW COOLING

FOCS / B
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722 3152 3602
COOLING
Cooling capacity (1) kW 294 328 364 414 439 480 529 562 598 625 681 730 785
Total power input (1) kW 101 120 133 146 156 160 184 195 207 217 221 259 289
EER 2,91 2,73 2,72 2,82 2,80 3 2,86 2,88 2,88 2,88 3,08 2,82 2,72
ESEER 3,86 3,75 3,74 3,85 3,84 3,88 3,76 3,88 3,98 3,89 4,07 3,94 3,94
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 305 340 378 429 456 498 549 583 621 648 707 757 814
Total power input (2) kW 98 116 129 143 151 155 179 189 201 210 215 252 280
Desuperheater heating capacity (2) kW 82 99 109 121 129 130 152 161 172 178 182 217 243
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 301 349 381 425 450 481 547 581 625 651 703 767 826
Total power input (3) kW 89 102 118 127 135 136 162 171 180 182 186 219 252
Heat recovery capacity (3) kW 385 445 492 545 577 609 699 741 793 823 878 973 1063
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 98 98 99 99 99 99 99 99 99 101 101 101 101
Sound pressure (5) dB(A) 66 66 67 67 67 67 67 67 67 69 69 69 69
SIZE
A (6) mm 4000 4000 4000 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 3760 3790 3880 4360 5050 5560 5560 5660 5770 5940 6270 7360 8040

Models 3902 4202 4212 4222 4822 5702 6002 6022 6903 7203 7223 8404
COOLING
Cooling capacity (1) kW 831 900 972 1039 1156 1213 1251 1338 1433 1485 1608 1744
Total power input (1) kW 302 321 334 346 384 423 441 473 519 536 593 643
EER 2,75 2,80 2,91 3 3,01 2,87 2,83 2,83 2,76 2,77 2,71 2,71
ESEER 3,78 3,79 3,78 3,90 4,14 3,99 3,85 3,99 3,68 3,82 3,79 3,66
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 862 934 1008 1078 1200 1259 1298 1388 1487 1541 1669 1809
Total power input (2) kW 292 311 323 335 372 409 427 458 504 519 574 622
Desuperheater heating capacity (2) kW 251 269 272 283 317 351 368 391 419 433 484 529
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 868 948 993 1056 1179 1267 1320 1382 1490 1544 1659 1861
Total power input (3) kW 262 279 283 295 334 368 379 408 439 453 493 556
Heat recovery capacity (3) kW 1115 1211 1260 1333 1494 1613 1676 1766 1903 1970 2123 2383
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3 4/4
NOISE LEVELS
Sound power (4) dB(A) 102 102 103 103 104 105 105 105 105 105 105 105
Sound pressure (5) dB(A) 69 69 70 70 71 72 72 72 72 72 72 72
SIZE
A (6) mm 7000 7000 9400 9400 9400 9400 9400 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 8470 8610 9430 9690 10110 * * * 12390 12530 12670 16360
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

101
FOCS / LN
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722 3152 3602
COOLING
Cooling capacity (1) kW 287 318 354 405 430 470 512 546 582 611 664 706 769
Total power input (1) kW 101 120 134 14 159 163 186 197 210 219 228 268 291
EER 2,84 2,65 2,64 28,9 2,70 2,88 2,75 2,77 2,77 2,79 2,91 2,63 2,64
ESEER 4,02 3,81 3,87 4 3,96 4,03 3,81 3,95 4,04 4,02 4,17 3,96 4,01
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 298 330 367 420 446 488 531 566 604 634 689 733 798
Total power input (2) kW 97,2 111 122 137 154 157 172 190 203 212 220 259 281
Desuperheater heating capacity (2) kW 85,2 116 129 144 136 138 180 168 180 187 194 230 250
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 301 349 381 425 450 481 547 581 625 651 703 767 826
Total power input (3) kW 89,1 102 118 127 135 136 162 171 180 183 186 219 252
Heat recovery capacity (3) kW 384 445 492 545 577 609 699 742 793 823 878 973 1063
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 92 92 93 93 93 93 93 93 93 95 95 95 95
Sound pressure (5) dB(A) 60 60 61 61 61 61 61 61 61 63 63 63 63
SIZE
A (6) mm 4000 4000 4000 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 3800 3830 3920 4410 5090 5630 5630 5730 5840 6010 6340 7330 7900

Models 3902 4202 4212 4222 4822 5702 6002 6022 6903 7203 7223 8404
COOLING
Cooling capacity (1) kW 808 872 950 1014 1130 1177 1212 1302 1367 1421 1568 1679
Total power input (1) kW 305 325 334 352 393 427 448 481 532 549 608 650
EER 2,65 2,68 2,84 2,88 2,88 2,75 2,71 2,71 2,57 2,59 2,58 2,58
ESEER 3,83 3,81 3,91 4 4,27 3,99 3,91 4,11 3,74 3,90 3,93 3,69
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 838 904 986 1052 1173 1221 1258 1351 1419 1475 1627 1742
Total power input (2) kW 295 314 323 340 380 413 432 465 515 530 588 628
Desuperheater heating capacity (2) kW 262 280 283 299 336 366 384 411 449 464 517 554
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 868 949 993 1056 1180 1267 1320 1382 1490 1544 1659 1861
Total power input (3) kW 262 279 284 295 334 368 379 408 440 453 493 556
Heat recovery capacity (3) kW 1114 1211 1260 1334 1494 1613 1676 1766 1903 1970 2123 2383
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3 4/4
NOISE LEVELS
Sound power (4) dB(A) 96 96 97 97 98 99 99 99 99 99 99 99
Sound pressure (5) dB(A) 63 63 64 64 65 66 66 66 66 66 66 66
SIZE
A (6) mm 7000 7000 9400 9400 9400 9400 9400 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 8550 8700 9530 9800 10210 * * * 12560 12690 12830 16110
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

102
FOCS / SL
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722 3152 3602
COOLING
Cooling capacity (1) kW 275 300 337 389 413 454 486 520 554 586 638 669 726
Total power input (1) kW 105 127 140 159 171 174 197 208 223 234 247 290 312
EER 2,62 2,36 2,41 2,45 2,42 2,61 2,47 2,50 2,48 2,50 2,58 2,31 2,33
ESEER 3,85 3,58 3,70 3,83 3,78 3,87 3,60 3,75 3,82 3,84 3,96 3,70 3,73
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 285 311 349 404 429 471 504 539 575 608 662 694 753
Total power input (2) kW 102 122 136 153 165 168 190 201 216 226 239 280 301
Desuperheater heating capacity (2) kW 90,1 109 120 137 148 149 169 180 193 202 213 251 271
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 301 349 381 425 450 481 547 581 625 651 703 767 826
Total power input (3) kW 89,1 102 118 127 135 136 162 171 180 183 186 219 252
Heat recovery capacity (3) kW 385 445 492 545 577 609 699 742 793 823 878 973 1063
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 87 87 88 88 88 89 89 89 89 90 90 90 90
Sound pressure (5) dB(A) 55 55 56 56 56 57 57 57 57 58 58 58 58
SIZE
A (6) mm 4000 4000 4000 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 3850 3880 3970 4460 5170 5700 5700 5800 5920 6080 6410 7410 8000

Models 3902 4202 4212 4222 4822 5702 6002 6022 6903 7203 7223 8404
COOLING
Cooling capacity (1) kW 768 822 909 975 1088 1150 1185 1279 1307 1358 1512 1590
Total power input (1) kW 323 346 354 376 426 439 460 491 557 577 653 682
EER 2,38 2,38 2,57 2,59 2,55 2,62 2,57 2,61 2,35 2,35 2,32 2,33
ESEER 3,61 3,56 3,73 3,81 4,08 3,69 3,63 3,88 3,61 3,76 3,80 3,51
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 797 852 943 1011 1129 1194 1229 1327 1357 1410 1569 1650
Total power input (2) kW 312 334 342 363 411 424 445 475 538 558 631 659
Desuperheater heating capacity (2) kW 280 300 303 323 368 377 369 424 478 496 564 590
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 868 949 993 1056 1180 1267 1320 1382 1490 1544 1659 1861
Total power input (3) kW 262 279 284 295 334 368 379 408 440 453 493 556
Heat recovery capacity (3) kW 1115 1211 1260 1334 1494 1613 1676 1766 1903 266 286 320
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3 4/4
NOISE LEVELS
Sound power (4) dB(A) 91 91 92 92 93 94 94 94 94 94 94 95
Sound pressure (5) dB(A) 58 58 59 59 60 61 61 61 61 61 61 62
SIZE
A (6) mm 7000 7000 9400 9400 9400 11200 11200 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 8640 8790 9620 9890 10300 * * * 12690 12830 12970 16290
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1502-8404
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

103
Hydronic - chiller

FOCS-XL 1502÷6002
Versions
XL extremely low noise version

Features
EXTREMELY SILENT OPERATION
As result of a sistematic design oriented to minimize the
noise level, XL version´s units give the best compromise
between silence and efficiency on the market.
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation: full load is granted up to
46°C and in partialization even over 50°C of external air
temperature.
INTEGRATED HYDRONIC MODULE
It consists of 2 pumps, 4-pole motor, fixed or variable
speed, with high or low head options to satisfy different
industrial applications and demands for comfort.

Main accessories
UÊElectronic expansion valve
UÊSoft start

Chiller, air source for outdoor installation UÊRemote keyboard


UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Trend, Bacnet protocol board.
UÊHydronic group
UÊVPF (Variable Primary Flow) kit: variable flow pumps with
272 - 1180 kW on board regulation
Unit Description
Outdoor unit for the production of chilled water with semi-hermetic screw compressors
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
shell and tubes evaporator designed by Climaveneta and thermostatic expansion valve.
Base and supporting structure and panels are of galvanized epoxy powder coated steel with
increased thickness. Flexible and reliable unit; it easily adapts itself to different thermal load
conditions thanks to the precise thermoregulation. The high performances level is achieved
thanks to the accurate sizing of all internal components.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic. As option (VPF package), the modulation of capacity is integrated with the modulation of the water flow, by means of
inverter and dedicated resources for the hydraulic circuit.

104
r HFC
R-134a
SHELL & TUBES AXIAL SCREW COOLING

FOCS-XL / XL
Models 1502 1702 1902 2002 2402 2602 2702 3202 3602 4202 4802 5402 6002
COOLING
Cooling capacity (1) kW 272 310 348 391 456 488 550 645 737 861 952 1079 1180
Total power input (1) kW 105 123 137 143 169 192 227 254 313 332 363 411 471
EER 2,59 2,52 2,53 2,74 2,69 2,54 2,43 2,54 2,36 2,59 2,63 2,63 2,51
ESEER 4,15 3,94 4,11 4,19 4,21 3,92 3,89 3,98 4,07 3,94 4,24 3,76 3,56
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 82 82 83 84 85 85 85 85 85 86 87 90 91
Sound pressure (3) dB(A) 50 50 51 52 53 53 53 52 52 53 54 57 58
SIZE
A (4) mm 4900 4900 4900 5800 5800 5800 5800 7000 7000 9900 11700 11700 11700
B (4) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
Operating weight (4) kg 4420 4450 4540 6020 6170 6230 6350 8000 8640 9710 10460 10720 10730
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1502-6002
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

105
Hydronic - chiller

FOCS-CA 1502÷5424
Versions
B base version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
configurations and versions
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
HIGH EFFICIENCY
Unit in Class A as per Eurovent. High efficiency for low
energy consumption during the operating hours
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
High efficiency chiller, air source for outdoor up to 46°C at full load; with total heat recovery, hot water
can be produced up to a temperature of 55°C.
installation INTEGRATED HYDRONIC MODULE
It consists of 2 pumps, 2 or 4-pole motor, fixed or variable
310 - 1381 kW speed, with high or low head options to satisfy different
industrial applications and demands for comfort.
Unit Description
Outdoor unit for the production of chilled water with semi-hermetic screw compressors
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
shell and tubes evaporator designed by Climaveneta and thermostatic expansion valve. Main accessories
Base and supporting structure and panels are of galvanized epoxy powder coated steel with UÊSoft start
increased thickness. Flexible and reliable unit; it easily adapts itself to different thermal load
UÊVPF (Variable Primary Flow) kit: variable flow pumps with
conditions thanks to the precise thermoregulation. The high performances level is achieved
on board regulation
thanks to the accurate sizing of all internal components.
UÊCompressor power factor device
UÊElectronic expansion valve
Commands UÊVariable speed condensation control (standard on /LN,
W3000SE Large /SL)
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
UÊRemote keyboard (distance to 200m and to 500m)
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics UÊSet-up for remote connectivity with ModBus, Echelon
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit LonTalk, Bacnet protocol board
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via UÊHydronic group
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic. As option (VPF package), the modulation of capacity is integrated with the modulation of the water flow, by means of
inverter and dedicated resources for the hydraulic circuit.

106
r HFC
R-134a
ENERGY CLASS SHELL & TUBES AXIAL SCREW COOLING

FOCS-CA / B
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722
COOLING
Cooling capacity (1) kW 310 358 406 441 468 493 558 593 641 666 691
Total power input (1) kW 95,4 110 128 140 147 156 176 187 202 208 215
EER 3,25 3,23 3,15 3,15 3,18 3,16 3,17 3,17 3,17 3,20 3,21
ESEER 4,15 4,07 3,95 4 4,02 4,02 4,02 4,04 4,17 4,18 4,18
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 321 372 421 458 485 511 579 616 665 691 716
Total power input (2) kW 92,3 107 125 135 143 151 170 181 195 201 208
Desuperheater heating capacity (2) kW 77,4 88,3 103 112 119 127 144 152 164 170 176
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 303 349 396 436 463 489 554 589 647 676 703
Total power input (3) kW 86,6 99 115 124 132 136 158 166 176 178 181
Heat recovery capacity (3) kW 385 442 504 552 586 617 702 745 813 844 873
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 97 97 98 98 98 98 98 99 99 99 99
Sound pressure (5) dB(A) 65 65 66 66 66 66 66 67 67 67 67
SIZE
A (6) mm 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 4170 4250 4590 4670 5340 5750 6060 6140 6340 6400 6430

Models 3152 3602 3902 4202 4212 4802 4822 5403 5414 5424
COOLING
Cooling capacity (1) kW 780 849 924 963 1037 1088 1187 1261 1332 1381
Total power input (1) kW 245 272 288 302 314 338 365 405 416 428
EER 3,18 3,12 3,20 3,18 3,30 3,21 3,25 3,11 3,20 3,22
ESEER 4,21 4,15 4,04 3,97 4,01 4,20 4,19 4,21 4,18 4,18
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 809 881 959 999 1076 1130 1232 1309 1382 1433
Total power input (2) kW 237 263 280 294 304 329 353 389 402 415
Desuperheater heating capacity (2) kW 200 225 232 245 249 272 295 327 340 352
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 786 849 911 948 1008 1086 1179 1256 1353 1407
Total power input (3) kW 213 246 257 271 284 305 334 368 357 361
Heat recovery capacity (3) kW 987 1080 1152 1203 1275 1373 1494 1602 1688 1746
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 4/4 4/4
NOISE LEVELS
Sound power (4) dB(A) 100 100 102 102 102 102 102 103 103 103
Sound pressure (5) dB(A) 67 67 69 69 69 69 69 70 70 70
SIZE
A (6) mm 7000 7000 9400 9400 11200 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 7860 8660 9690 9920 10440 10280 10710 12180 12790 12860

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

107
FOCS-CA / LN
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722
COOLING
Cooling capacity (1) kW 304 351 397 433 460 484 545 579 625 651 676
Total power input (1) kW 94,1 109 126 138 146 157 175 186 202 210 218
EER 3,23 3,22 3,13 3,12 3,13 3,08 3,11 3,10 3,09 3,10 3,10
ESEER 4,35 4,28 4,19 4,24 4,24 4,19 4,15 4,20 4,32 4,32 4,32
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 315 364 412 449 477 502 566 601 648 675 702
Total power input (2) kW 91,1 105 123 135 142 152 170 180 196 203 211
Desuperheater heating capacity (2) kW 79,6 90,8 106 117 124 133 149 157 171 178 186
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 303 349 396 436 463 489 554 589 647 677 703
Total power input (3) kW 86,6 99 115 124 132 139 158 166 176 178 181
Heat recovery capacity (3) kW 385 442 504 553 586 620 702 745 813 844 873
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 91 91 92 92 92 92 92 93 93 93 93
Sound pressure (5) dB(A) 59 59 60 60 60 60 60 61 61 61 61
SIZE
A (6) mm 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 4200 4290 4670 4740 5410 5820 6130 6210 6420 6470 6500

Models 3152 3602 3902 4202 4212 4802 4822 5403 5414 5424
COOLING
Cooling capacity (1) kW 764 825 904 941 1019 1061 1167 1240 1302 1353
Total power input (1) kW 245 275 286 300 308 337 366 401 420 436
EER 3,11 3 3,16 3,13 3,30 3,14 3,18 3,09 3,10 3,10
ESEER 4,36 4,33 4,24 4,12 4,24 4,41 4,42 4,41 4,32 4,31
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 793 856 938 976 1055 1102 1211 1287 1350 1404
Total power input (2) kW 238 266 276 291 311 327 355 388 406 422
Desuperheater heating capacity (2) kW 209 235 240 253 269 284 309 340 357 371
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 786 849 911 949 1007 1086 1180 1256 1353 1407
Total power input (3) kW 214 246 257 271 306 305 334 368 357 361
Heat recovery capacity (3) kW 987 1080 1152 1203 1294 1373 1494 1602 1688 1746
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 4/4 4/4
NOISE LEVELS
Sound power (4) dB(A) 94 94 96 96 96 96 96 97 97 97
Sound pressure (5) dB(A) 61 61 63 63 63 63 63 64 64 64
SIZE
A (6) mm 7000 7000 9790 9790 11200 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 7940 8740 9790 10020 10580 10420 10850 12330 12930 13000

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

108
FOCS-CA / SL
Models 1502 1702 1902 1922 1972 2022 2602 2652 2702 2712 2722
COOLING
Cooling capacity (1) kW 294 340 383 420 447 470 523 557 599 626 653
Total power input (1) kW 97,7 111 131 145 155 167 184 194 213 222 234
EER 3,01 3,04 2,92 2,88 2,88 2,80 2,84 2,86 2,81 2,81 2,78
ESEER 4,23 4,17 4,10 4,14 4,14 4,05 3,97 4,05 4,14 4,14 4,13
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 305 352 397 436 464 488 542 578 621 649 678
Total power input (2) kW 94,3 108 127 141 150 162 177 188 206 216 227
Desuperheater heating capacity (2) kW 83,4 95 111 124 132 143 158 167 183 192 202
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 303 349 396 436 463 489 554 589 647 677 703
Total power input (3) kW 86,6 99 115 124 132 139 158 166 176 178 181
Heat recovery capacity (3) kW 385 442 504 553 586 620 702 745 813 844 873
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 87 87 88 88 88 89 89 89 89 90 90
Sound pressure (5) dB(A) 55 55 56 56 56 57 57 57 57 58 58
SIZE
A (6) mm 4900 4900 4900 4900 4900 4900 5800 5800 5800 5800 5800
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 4250 4350 4720 4790 5480 5900 6200 6280 6490 6540 6570

Models 3152 3602 3902 4202 4212 4802 4822 5403 5414 5424
COOLING
Cooling capacity (1) kW 735 791 873 905 990 1022 1133 1192 1252 1306
Total power input (1) kW 260 290 296 312 320 353 390 422 447 469
EER 2,82 2,72 2,94 2,90 3,09 2,89 2,90 2,82 2,80 2,78
ESEER 4,17 4,12 4,11 3,98 4,15 4,28 4,30 4,23 4,14 4,13
COOLING WITH PARTIAL RECOVERY
Cooling capacity (2) kW 763 820 905 939 1023 1060 1176 1236 1299 1355
Total power input (2) kW 252 281 287 302 326 342 377 408 432 454
Desuperheater heating capacity (2) kW 224 251 253 267 286 301 334 362 384 404
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 786 849 911 949 1007 1086 1180 1256 1353 1407
Total power input (3) kW 214 246 257 271 306 305 334 368 357 361
Heat recovery capacity (3) kW 987 1080 1152 1203 1294 1373 1494 1602 1688 1746
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 4/4 4/4
NOISE LEVELS
Sound power (4) dB(A) 90 90 91 91 92 93 93 94 94 94
Sound pressure (5) dB(A) 57 57 58 58 59 60 60 61 61 61
SIZE
A (6) mm 7000 7000 9400 9400 11200 11200 11200 11200 11200 11200
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (6) kg 8020 8830 9880 10110 10670 10510 10940 12460 13070 13140

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C; Desuperheater water (in/out) = 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1502-5424
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

109
Hydronic - chiller

i-FOCS 0052÷0082
Versions
E high efficiency version
SL-E super-low noise, high efficiency version

Features
SYSTEM EFFICIENCY
The unit is designed as a system: all components, with
very high operating efficiency, are synergically regulated
using proprietary controls logic, and the unit-system is
perfectly integrated with all other Climaveneta units
VERY HIGH EFFICIENCY AT PARTIAL LOAD
Very high efficiency at partial load thanks to the inverter
technology applied on screw compressors. Therefore,
operating costs are reduced to a minimum
TRUE SILENCE
Silence optimized for the most frequent operational
conditions, thanks to the accurate structures design, to
the use of EC fans (DC brushless) and to the adoption of
variable-speed driven compressors
HARMONY BETWEEN UNIT AND PLANT
Low inrush current and cos(phi) higher than 0.9, permit
an easy electrical installation which is not stressed
during start-up and with no need of extra devices for
power factor correction. The use of inverter allows the
unit partialize down to 15%, with consequent lower
High efficiency chiller, air source for outdoor fluctuations of leaving water temperature

installation Main accessories


UÊSet-up for remote connectivity with ModBus, Echelon
511 - 842 kW LonTalk, Trend, Bacnet protocol board.
UÊRemote keyboard (distance to 200m and to 500m)
Unit Description UÊVPF (Variable Primary Flow) kit: variable flow pumps with
Outdoor unit for the production of chilled water with inverter driven screw compressors
on board regulation
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
shell and tube evaporator designed by Climaveneta and electronic expansion valve. Base and
supporting structure and panels are of galvanized epoxy powder coated steel with increased
thickness. Flexible and reliable unit; it easily adapts itself to different thermal load conditions
thanks to the precise thermoregulation together with the use of inverter technology. The high
performances level, especially at partial load, is achieved thanks to the accurate units design
and to the use of innovative inverter motors in all key components of the unit (compressors,
fans and pumps).

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity by adjustment of the compressor speed. The modulation is based on PID algorithms and referring to
the leaving water temperature. This is combined with the management of the compressors status, with two selectable logics
(proportional referred to the return temperature or dead band referred to the leaving temperature). As option (VPF package),
the modulation of capacity is integrated with the modulation of the water flow, by means of inverter and dedicated resources
for the hydraulic circuit.

110
r HFC
R-134a
SHELL & TUBES EC FAN SCREW COOLING

i-FOCS / E
Models 0052 0062 0072 0082
COOLING
Cooling capacity (1) kW 511 670 737 842
Total power input (1) kW 203 263 294 335
EER * * * *
ESEER 4,69 4,70 4,74 4,71
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 97 98 98 99
Sound pressure (3) dB(A) 65 66 65 66
SIZE
A (4) mm 4900 5800 7000 7000
B (4) mm 2260 2260 2260 2260
H (4) mm 2430 2430 2430 2430
Operating weight (4) kg 5980 7190 8090 8580

Note:
1 Evaporator water (in/out): 15/7°C; Condenser Air (in): 35C°
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

i-FOCS / SL-E
Models 0052 0062 0072 0082
COOLING
Cooling capacity (1) kW 492 644 712 808
Total power input (1) kW 204 267 298 343
EER * * * *
ESEER 4,70 4,71 4,76 4,72
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 91 92 92 93
Sound pressure (3) dB(A) 59 60 59 60
SIZE
A (4) mm 4900 5800 7000 7000
B (4) mm 2260 2260 2260 2260
H (4) mm 2430 2430 2430 2430
Operating weight (4) kg 6090 7290 8200 8690

Note:
1 Evaporator water (in/out): 15/7°C; Condenser Air (in): 35C°
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0052-0082
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

111
Hydronic - chiller

TECS2 Vision 2.0 0211÷1154


Versions
SL-CA Super Low noise version, Class A of
efficiency
XL-CA eXtra Low noise version, Class A of
efficiency
SL-CA-E Super Low noise version, very high
efficiency, Class A enhanced

Configurations
- base function
D partial condensing heat recovery function

Features
VERY HIGH EFFICIENCY
Very high efficiency at full and partial load, to top market
levels, thanks to adopted technological solutions: large
capacity modulation and expanded exchanger, offering
minimum running costs of the unit in real working
conditions.
VERSION ´CA-E´ AVAILABLE
The version ´CA-E´ is characterized by efficiency beyond
the ´Class A´ for Eurovent. The technological choices
adopted assure the minimization of operating costs and
therefore a quick payback time.
High efficiency chiller, air source for outdoor EXTREMELY SILENT OPERATION
As result of a sistematic design oriented to minimize the
installation noise level, XL version´s units give the best compromise
between silence and efficiency on the market.
220 - 1325 kW LOW INRUSH CURRENTS
Reduced breakaway starting currents thanks to the
Unit Description revolutionary centrifugal compressor
Outdoor unit for the production of chilled water featuring oil-free centrifugal compressor,
with R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins, shell and
tube flooded evaporator and electronic regulation valve. Base and supporting structure and Main accessories
panels are of galvanized epoxy powder coated steel with increased thickness. Flexible and UÊVPF (Variable Primary Flow) kit: variable flow pumps with
reliable unit; it easily adapts itself to different thermal load conditions thanks to the precise on board regulation
thermoregulation together with the use of inverter technology. The compressor is radically UÊHydronic group
innovative: magnetic bearings and digital rotor speed control allow partial load efficiency levels
UÊEC fans with electronic DC brushless motor
to be reached that were hither to impossible.
UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
Commands
W3000 large
The controller W3000 large offers the latest control and functions specially developed for these units. The keypad is
generously sized with full operating status display. The controls and detailed LCD make access to machine settings easy and
safe. These resources permit to diirectly act on the unit settings through a multilevel menu, available in several languages.
The diagnostics includes full management of alarms with black-box functions and alarm record for better analysis of unit
performance. For multi-units plants a special device to coordinate and manage all the resources is available as an option;
energy metering device is even possible as an option. Supervision is easy through Climaveneta devices or with various
options for interfacing to ModBus, Bacnet, Echelon LonTalk protocols. Compatibility with remote keyboard (management up
to 10 units). Clock available with programming of operation (standard 4 days and 10 time bands). Temperature regulation
features the continuous capacity modulation, based on PID algorithms referring to water leaving temperature. This is
combined with the compressors´ on/off management with a proportional logic on the return water temperature. As option is
possible to choose the VPF system control integrated on-board to the units.

112
r HFC
R-134a
ENERGY CLASS SHELL & TUBES AXIAL CENTRIFUGAL COOLING

TECS2 Vision 2.0 / SL-CA


Models 0211 0351 0521 0452 0512 0552 0652 0712 0853 0913 1013 1054 1154
COOLING
Cooling capacity (1) kW 233 346 258 442 509 574 650 742 848 904 977 1065 1183
Total power input (1) kW 70,2 110 81,1 138 161 174 208 225 269 286 310 336 374
EER 3,31 3,13 3,18 3,20 3,16 3,30 3,13 3,30 3,15 3,15 3,15 3,17 3,17
ESEER 4,77 4,72 4,87 5,07 5,17 5,09 5,04 5,16 5,12 5,13 5,09 5,06 5,14
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/1 2/1 2/1 2/1 2/1 3/2 3/2 3/2 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 88 90 88 90 90 91 92 92 93 93 93 94 94
Sound pressure (3) dB(A) 56 58 56 58 58 59 60 60 61 61 61 62 62
SIZE
A (4) mm 3100 4000 3100 4900 4900 5800 7000 7000 8500 9700 10600 11200 11500
B (4) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (4) kg * * * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

TECS2 Vision 2.0 / XL-CA


Models 0211 0351 0521 0452 0512 0552 0652 0712 0853 0913 1013 1054 1154
COOLING
Cooling capacity (1) kW 220 341 254 435 526 579 640 739 874 900 972 1049 1174
Total power input (1) kW 68,5 109 79,8 136 166 173 206 226 279 290 312 331 377
EER 3,21 3,12 3,19 3,19 3,17 3,35 3,11 3,27 3,13 3,11 3,12 3,17 3,11
ESEER 4,75 4,84 4,99 5,19 5,23 5,17 5,19 5,24 5,24 5,30 5,24 5,19 5,23
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/1 2/1 2/1 2/1 2/1 3/2 3/2 3/2 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 82 83 82 83 84 85 85 86 86 86 87 87 88
Sound pressure (3) dB(A) 50 51 50 51 52 53 53 54 54 54 55 55 56
SIZE
A (4) mm 3100 4000 3100 4900 5800 7000 7000 7900 9400 9700 10600 11200 12400
B (4) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (4) kg * * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

TECS2 Vision 2.0 / SL-CA-E


Models 0211 0351 0521 0452 0512 0552 0652 0712 0853 0913 1013 1054 1154
COOLING
Cooling capacity (1) kW 229 384 285 455 527 590 703 796 902 969 1086 1177 1324
Total power input (1) kW 67,1 113 81,4 134 154 169 204 233 269 278 317 336 383
EER 3,41 3,40 3,50 3,41 3,41 3,50 3,45 3,41 3,35 3,48 3,42 3,50 3,46
ESEER 5,29 5,43 5,52 5,79 5,71 5,64 5,77 5,77 5,62 5,79 5,71 5,87 5,75
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/1 2/1 2/1 2/1 2/1 3/2 3/2 3/2 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 88 90 88 90 90 91 92 92 93 93 93 94 95
Sound pressure (3) dB(A) 56 58 56 58 58 59 60 60 61 61 61 62 63
SIZE
A (4) mm 3100 4000 3100 4900 4900 5800 7000 7900 8500 9700 10600 11200 12400
B (4) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (4) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (4) kg * * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0211-1154
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

113
Hydronic - chiller

NECS-FC 0152÷1204
Versions
B base version
SL super-low noise version

Configurations
- base function
NG function for free-cooling without use of
glycole

Features
OUTSTANDING VERSATILITY
The NECS FC units are available in two separate versions:
B (basic), SL (super low noise) in order to fully satisfy
special requirements and cope with the most complex
installation solutions in both the Industrial Process and the
Comfort sectors.
ELEVATED ENERGY EFFICIENCY
Thanks to the dedicated coils for Free-Cooling, the
R-410A optimised scroll compressors and the R-410A
refrigerant, the NECS FC units allow an average power
saving of 30% compared with standard European
consumption.
MAXIMUM FLEXIBILITY
Flexibility is achieved by the continuous modulation of
Chiller, air source with free-cooling the capacity provided by the compressors. The three-
way modulating valve (optional) on the water side offers
improved leaving water temperature control also at low
outdoor temperatures.
41,5 - 377 kW CUSTOMISED CONTROL
Customised adjustment constantly guarantees the
Unit Description required temperature of the chilled water whilst fully
External units for the production of chilled water, with Free-Cooling function, fitted with exploiting all the available resources (compressors, fans
hermetic Scroll compressors, axial fans, braze-welded plate exchanger and thermostat and water coils) in relation to the temperature of the
expansion valve in R410A. External panelling in peraluman and base in painted galvanised external air. This makes it possible to fully use the free-
steel. NECS Free-Cooling, a must when demand is high throughout the year, also during the cooling system even when external air temperatures are
cold season, therefore. In fact, the greater the difference between the temperature of the close to zero.
chilled water and the temperature of the external air, the greater the advantage of free-cooling. INTEGRATED HYDRONIC MODULE
It consists of 1 or 2 pumps with 2 or 4-pole motor,
with three head options to satisfy different industrial
applications and demands for comfort
Commands
W3000SE Large Main accessories
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
UÊRemote keyboard (distance to 200m and to 500m)
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics UÊCoils with FIN GUARD SILVER treatment
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented. UÊAutomatic circuit breakers on loads
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via UÊModulating valve for water temperature control in Free-
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an Cooling mode
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features a step-wise
regulation, referred to the return water temperature with selectable proportional- or proportional-integral logic.

114
r HFC
R-410A
PLATES AXIAL SCROLL FREE COOLING COOLING

NECS-FC / B
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
NECS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 43,6 51 61,9 68 88,5 104 115 131 149
Total power input (1) kW 14,1 15,5 19,5 22,5 28,3 30,9 35,8 41,1 43,8
EER 3,09 3,29 3,17 3,02 3,13 3,37 3,21 3,19 3,40
FREE-COOLING ON 100%
Cooling capacity (2) kW 43,3 51 61,9 68 88,5 104 115 131 149
Total power input (2) kW 1,50 1,50 4,20 4,20 4,20 4,20 4,20 6,30 6,30
Total Free-Cooling temperature (2) °C 1,40 1,10 0,80 0 -0,80 0,40 -0,70 -0,40 0,20
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 87 87 90 90 91 91 92 92 93
Sound pressure (4) dB(A) 55 55 58 58 59 59 60 60 61
SIZE
A (5) mm 2200 2200 2602 2602 2602 3602 3602 3602 4602
B (5) mm 920 920 1104 1104 1104 1104 1104 1104 1104
H (5) mm 1780 1780 2175 2175 2175 2175 2175 2175 2205
Operating weight (5) kg 670 710 870 880 1060 1310 1340 1410 1650
NECS-FC-NG
FREE-COOLING OFF
Cooling capacity (1) kW 44,8 52,4 63,6 69,8 90,9 107 118 135 153
Total power input (1) kW 14,1 15,5 19,5 22,5 28,3 30,9 35,8 41,1 43,8
EER 3,18 3,38 3,26 3,10 3,21 3,46 3,30 3,28 3,49
FREE-COOLING ON 100%
Cooling capacity (2) kW 44,8 54,4 63,6 69,8 90,9 107 118 135 153
Total power input (2) kW 1,50 1,50 4,20 4,20 4,20 4,20 4,20 6,30 6,30
Total Free-Cooling temperature (2) °C -1,60 -1,90 -2,20 -3 -3,80 -2,60 -3,70 -3,40 -2,80
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 87 87 90 90 91 91 92 92 93
Sound pressure (4) dB(A) 55 55 58 58 59 59 60 60 61
SIZE
A (5) mm 2200 2200 2602 2602 2602 3602 3602 3602 4602
B (5) mm 920 920 1104 1104 1104 1104 1104 1104 1104
H (5) mm 1780 1780 2175 2175 2175 2175 2175 2175 2205
Operating weight (5) kg 710 760 920 940 1130 1410 1450 1530 1780

Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

115
Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
NECS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 166 187 177 207 234 268 293 336 377
Total power input (1) kW 51,5 59,8 56,4 62,5 73,8 79,9 89,6 102 118
EER 3,23 3,12 3,14 3,31 3,17 3,35 3,27 3,31 3,19
FREE-COOLING ON 100%
Cooling capacity (2) kW 166 187 177 207 234 268 293 336 377
Total power input (2) kW 6,30 8,40 8,40 8,40 12,6 12,6 12,6 12,6 16,8
Total Free-Cooling temperature (2) °C -1,10 -1,10 1,60 -0,10 0,30 1,40 0,60 0,50 0,40
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 93 94 93 93 94 94 94 95 96
Sound pressure (4) dB(A) 61 62 61 61 62 62 62 63 64
SIZE
A (5) mm 4602 4602 4110 4110 4110 5110 5110 5110 5110
B (5) mm 1104 1104 2220 2220 2220 2220 2220 2220 2220
H (5) mm 2205 2205 2150 2150 2150 2150 2150 2430 2430
Operating weight (5) kg 1680 1740 2200 2330 2510 2880 2940 3260 3400
NECS-FC-NG
FREE-COOLING OFF
Cooling capacity (1) kW 171 192 182 212 241 275 301 345 387
Total power input (1) kW 51,5 59,8 56,4 62,5 73,8 79,9 89,6 102 118
EER 3,32 3,21 3,23 3,40 3,26 3,44 3,36 3,40 3,28
FREE-COOLING ON 100%
Cooling capacity (2) kW 171 192 182 212 241 279 301 345 387
Total power input (2) kW 6,30 8,40 8,40 8,40 12,6 12,6 12,6 12,6 16,8
Total Free-Cooling temperature (2) °C -4,10 -4,10 -1,40 -3,10 -2,70 -1,30 -2,40 -2,50 -2,60
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 93 94 93 93 94 94 94 95 96
Sound pressure (4) dB(A) 61 62 61 61 62 62 62 63 64
SIZE
A (5) mm 4602 4602 4110 4110 4110 5110 5110 5110 5110
B (5) mm 1104 1104 2220 2220 2220 2220 2220 2220 2220
H (5) mm 2205 2205 2150 2150 2150 2150 2150 2430 2430
Operating weight (5) kg 1810 1890 2510 2650 2840 3250 3320 3700 3850

Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

116
NECS-FC / SL
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
NECS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 41,5 49,8 56,9 63,8 82,4 97,9 112 122 137
Total power input (1) kW 14,3 16,1 19,1 21,8 28 32,3 35,7 41,3 45,8
EER 2,90 3,09 2,98 2,93 2,94 3,03 3,13 2,96 3
FREE-COOLING ON 100%
Cooling capacity (2) kW 41,5 49,8 56,9 63,8 82,4 97,9 112 122 137
Total power input (2) kW 0,60 1,50 1,50 1,70 1,70 2,60 2,60 2,60 3,50
Total Free-Cooling temperature (2) °C -1,20 -1,50 -1,10 -1,30 -1,30 -1,20 -0,70 -1,50 -1,60
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 77 78 78 79 80 81 81 82 83
Sound pressure (4) dB(A) 45 46 46 47 48 49 49 50 51
SIZE
A (5) mm 2200 2602 2602 2602 3602 3602 4602 4602 4602
B (5) mm 920 1104 1104 1104 1104 1104 1104 1104 1104
H (5) mm 1780 2175 2175 2175 2175 2175 2205 2205 2205
Operating weight (5) kg 680 860 920 940 1240 1350 1590 1610 1690
NECS-FC-NG
FREE-COOLING OFF
Cooling capacity (1) kW 42,6 51,2 58,4 65,6 86,5 101 115 126 141
Total power input (1) kW 14,3 16,1 19,1 21,8 28 32,3 35,7 41,3 45,8
EER 2,98 3,18 3,06 3,01 3,09 3,11 3,22 3,04 3,08
FREE-COOLING ON 100%
Cooling capacity (2) kW 42,6 51,2 58,4 65,6 86,5 101 115 126 141
Total power input (2) kW 0,60 1,50 1,50 1,70 1,70 2,60 2,60 2,60 3,40
Total Free-Cooling temperature (2) °C -4,20 -4,50 -4,10 -4,30 -4,30 -4,20 -3,70 -4,50 -4,60
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 77 78 78 79 80 81 81 82 83
Sound pressure (4) dB(A) 46 47 47 48 49 50 50 51 52
SIZE
A (5) mm 2200 2602 2602 2602 3602 3602 4602 4602 4602
B (5) mm 920 1104 1104 1104 1104 1104 1104 1104 1104
H (5) mm 1780 2175 2175 2175 2175 2175 2205 2205 2205
Operating weight (5) kg 730 910 970 990 1300 1450 1690 1730 1810

Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

117
Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
NECS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 156 179 166 193 216 243 274 313 351
Total power input (1) kW 53,3 59,2 57,2 66,2 75,2 83,5 90,3 104 120
EER 2,92 3,03 2,91 2,91 2,87 2,91 3,03 3,01 2,93
FREE-COOLING ON 100%
Cooling capacity (2) kW 156 179 166 193 216 243 274 313 351
Total power input (2) kW 3,50 4,40 3,50 5,20 5,20 5,20 5,20 5,20 6,90
Total Free-Cooling temperature (2) °C -1,70 -2,80 -1,60 -1,70 -3,30 -1,60 -2,80 -3 -2,90
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 84 85 82 83 83 84 84 85 86
Sound pressure (4) dB(A) 52 53 50 51 51 52 52 53 54
SIZE
A (5) mm 4602 4602 4110 4110 4110 5110 5110 5110 5110
B (5) mm 1277 1277 2220 2220 2220 2220 2220 2220 2220
H (5) mm 2350 2350 2150 2150 2150 2150 2150 2430 2430
Operating weight (5) kg 1920 2000 2280 2410 2580 2880 3040 3380 3520
NECS-FC-NG
FREE-COOLING OFF
Cooling capacity (1) kW 160 184 171 198 221 249 281 322 361
Total power input (1) kW 53,3 59,2 57,1 66,2 75,2 83,5 90,3 104 120
EER 3 3,11 2,99 2,99 2,94 2,99 3,12 3,09 3,01
FREE-COOLING ON 100%
Cooling capacity (2) kW 160 184 178 198 221 249 281 322 361
Total power input (2) kW 3,50 4,40 3,50 5,20 4,80 5,10 5,20 5,10 6,90
Total Free-Cooling temperature (2) °C -4,70 -5,80 -4,60 -4,70 -6,30 -4,60 -5,80 -6 -5,90
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 84 85 82 83 83 84 84 85 86
Sound pressure (4) dB(A) 53 54 50 51 51 52 52 53 54
SIZE
A (5) mm 4602 4602 4110 4110 4110 5110 5110 5110 5110
B (5) mm 1277 1277 2200 2200 2200 2200 2200 2200 2200
H (5) mm 2350 2350 2150 2150 2150 2150 2150 2430 2430
Operating weight (5) kg 2060 2150 2590 2730 2910 3250 3420 3820 3970

Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-0612 0604-1204
Switchboard side mm 800 1100
Switchboard opposite side mm 800 1100
Condensation coil side mm 1500 2000
Opposite side of cond. coil mm 800 2000

H H

A
A
B
B

118
119
Hydronic - chiller

FOCS-FC 1502÷4822
Versions
B base version
SL super-low noise version

Configurations
- base function
NG function for free-cooling without use of
glycole

Features
RANGE
Extended capacity range
ENERGY SAVING
Energy saving guaranteed by free-cooling, which exploits
the low external air temperatures; free-cooling control with
optional modulating valve
INTEGRATED HYDRONIC MODULE
It consists of 1 or 2 pumps, 2 or 4-pole motor, with high
or low head options to satisfy different applications

Main accessories
UÊEC fans with electronic DC brushless motor
UÊCompressor power factor device
Chiller, air source with free-cooling UÊElectronic expansion valve
UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
329 - 1229 kW UÊHydronic group

Unit Description
Outdoor unit for the production of chilled water with semi-hermetic screw compressors
optimized for R134a, axial-flow fans, condensing coil with copper tubes and aluminium fins,
shell and tube evaporator design by Climaveneta and thermostatic expansion valve. Base and
supporting structure and panels are of galvanized epoxy powder coated steel with increased
thickness. This air-cooled range, fitted with FREE-COOLING coils, is for use in civil and
industrial installations whenever the need for cooling continues throughout the cold months, or
when the external air temperature is lower than the temperature of the liquid returning from the
installation. During freecooling operation the fluid is cooled by means of the external air, thus
reducing the load on the compressors or even completely substituting them. The necessary
cooling capacity is therefore obtained with almost zero energy expenditure (FREECOOLING
100 % = EER 25). Further more the NG configuration complies with applications where the
use of ethylene glycol is not desired or permitted.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

120
r HFC
R-134a
SHELL & TUBES AXIAL SCREW FREE COOLING COOLING

FOCS-FC / B
Models 1502 1702 1902 1922 2022 2602 2702 2722 3602 4202 4212 4222 4822
FOCS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 329 369 417 454 502 579 636 711 858 994 1076 1126 1229
Total power input (1) kW 96,4 114 136 147 168 191 221 221 298 333 336 355 395
EER 3,41 3,24 3,07 3,09 2,99 3,03 2,88 3,22 2,88 2,98 3,20 3,17 3,11
FREE-COOLING ON 100%
Cooling capacity (2) kW 329 369 417 454 502 579 636 711 858 994 1076 1126 1229
Total power input (2) kW 9,60 9,60 21 21 21 25,2 25,2 29,4 33,6 42 50,4 50,4 50,4
Total Free-Cooling temperature (2) °C 1,70 0,70 1,80 1,10 0,10 0,60 -0,50 0,60 0 0,10 1,30 0,90 0
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 99 99 99 99 99 101 101 102 102 103 105 105 105
Sound pressure (4) dB(A) 67 67 67 67 67 69 69 69 69 70 72 72 72
SIZE
A (5) mm 4000 4000 4900 4900 4900 5800 5800 7000 7900 10000 11800 11800 11800
B (5) mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
H (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
Operating weight (5) kg 4810 4810 5310 5630 6590 7170 7190 7940 9670 11500 12530 12600 12660
FOCS-FC/NG
FREE-COOLING OFF
Cooling capacity (1) kW 338 379 428 466 516 595 653 730 881 1021 1105 1157 1262
Total power input (1) kW 104 122 136 148 169 192 222 222 299 335 338 356 397
EER 3,25 3,11 3,15 3,15 3,05 3,10 2,94 3,29 2,95 3,05 3,27 3,25 3,18
FREE-COOLING ON 100%
Cooling capacity (2) kW 338 379 428 466 516 595 653 730 881 1021 1105 1157 1262
Total power input (2) kW 16,8 16,8 21 21 21 25,2 25,2 29,4 33,6 42 50,4 50,4 50,4
Total Free-Cooling temperature (2) °C -1,30 -2,30 -1,20 -1,90 -2,90 -2,40 -3,40 -2,40 -3 -2,80 -1,70 -2,10 -3
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 99 99 99 99 99 101 101 102 102 103 105 105 105
Sound pressure (4) dB(A) 67 67 67 67 67 69 69 69 69 70 72 72 72
SIZE
A (5) mm 4000 4000 4900 4900 4900 5800 5800 7000 7900 10000 11800 11800 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
Operating weight (5) kg 5130 5130 5710 6030 6970 7630 7700 8440 10410 12130 13330 13580 13640

Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

121
FOCS-FC / SL
Models 1502 1702 1902 1922 2022 2602 2702 2722 3602 4202 4212 4222 4822
FOCS-FC
FREE-COOLING OFF
Cooling capacity (1) kW 315 348 398 435 503 548 597 683 808 936 1030 1080 1171
Total power input (1) kW 102 122 135 150 161 194 229 229 309 339 338 362 413
EER 3,09 3,25 3,35 3,30 3,12 3,22 3,01 3,38 3,01 3,16 3,05 3,38 3,24
FREE-COOLING ON 100%
Cooling capacity (2) kW 315 348 398 435 503 548 597 683 808 936 1030 1080 1171
Total power input (2) kW 9,60 9,60 12 12 14,4 14,4 14,4 16,8 19,2 24 28,8 28,8 28,8
Total Free-Cooling temperature (2) °C 0,40 -0,50 0,50 -0,30 0,20 -0,70 -1,60 -0,80 -1,20 -1,10 -0,10 -0,50 -1,40
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 92 92 92 92 94 94 94 95 95 95 97 97 97
Sound pressure (4) dB(A) 60 60 60 60 62 62 62 62 62 62 64 64 64
SIZE
A (5) mm 4000 4000 4900 4900 5800 5800 5800 7000 7900 10000 11800 11800 11800
B (5) mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
H (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
Operating weight (5) kg 4900 4900 5390 5710 7240 7260 7280 8050 9790 11660 12710 12780 12840
FOCS-FC/NG
FREE-COOLING OFF
Cooling capacity (1) kW 323 357 409 447 516 562 613 702 830 961 1058 1109 1203
Total power input (1) kW 93 103 123 151 162 195 231 230 310 341 340 364 415
EER 3,15 2,91 3,02 2,96 3,18 2,89 2,70 3,05 2,68 2,82 3,11 3,05 2,90
FREE-COOLING ON 100%
Cooling capacity (2) kW 323 357 409 447 516 562 613 702 830 961 1058 1109 1203
Total power input (2) kW 9,60 9,60 12 12 14,4 14,4 14,4 16,8 19,2 24 28,8 28,8 28,8
Total Free-Cooling temperature (2) °C -2,65 -3,51 -2,47 -3,29 -2,77 -3,68 -4,61 -3,80 -4,18 -4,12 -3,12 -3,53 -4,38
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 92 92 92 92 94 94 94 95 95 95 97 97 97
Sound pressure (4) dB(A) 60 60 60 60 62 62 62 62 62 62 64 64 64
SIZE
A (5) mm 4000 4000 4900 4900 5800 5800 5800 7000 7900 10000 11800 11800 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500
Operating weight (5) kg 5210 5210 5790 6110 7600 7720 7790 8550 10530 12290 13510 13760 13820
Note:
1 Evaporator water (in/out): 15/10°C; Condenser air (in): 30°C; Ethylene glycol: 30% (not applicable to NG configurations).
2 Evaporator water (in/out): 15/10°C; Ethylene glycol: 30 % (not applicable to NG configurations).
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1502-4822
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

122
123
Hydronic - chiller

NECS-C 0152÷1204
Versions
B base version
HT high efficiency, high outdoor temperature
version

Configurations
- base function
D partial condensing heat recovery function
R total condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment
(ODP = 0)
TOTAL VERSATILITY
The NECS-C units are available with both vertical and
horizontal air outflow. The horizontal outflow version
is particularly effective in installations where the height
of the technical compartment does not allow the
traditional vertical outflow
HIGH PERFORMANCE CENTRIFUGAL FANS
The units are fitted with statically and dynamically
balanced double-inlet centrifugal fans coupled by belt
Chiller, air source for indoor installation and pulleys. Useful static pressure up to 180 Pa.
INTEGRATED HYDRONIC MODULE
The incorporated hydronic unit already contains the
main water circuit components; it is available in various
37,1 - 325 kW configurations with one or two pumps with high or low
head
Unit Description
Indoor unit for the production of chilled water with hermetic rotary scroll compressors
dedicated to the use of R410A, centrifugal fans, braze-welded plate-type exchanger and
Main accessories
UÊSet-up for remote connectivity with ModBus/Echelon/
thermal expansion valve. External panels in pre-clad sheet steel (simil Peraluman) and base
Bacnet protocol cards
in galvanised steel with paint finish. The range includes the single-circuit two-compressor
versions and the dual circuit four-compressor versions. UÊRemote keyboard (distance to 200m and to 500m)
UÊSoft starters
UÊRubber anti-vibration mounting kit
Commands
W3000 Base / W3000SE Compact UÊHorizontal or vertical air outflow
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

124
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL COOLING

NECS-C / B
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
COOLING
Cooling capacity (1) kW 37,1 43 50,5 57 74,8 86,4 97,9 109 121
Total power input (1) kW 15,7 18,3 20,6 23,2 30,4 36,8 40,7 46,8 51,5
EER 2,67 2,64 2,72 2,69 2,65 2,60 2,64 2,53 2,54
ESEER 4,61 4,30 4,46 4,35 4,18 3,86 3,88 3,73 3,74
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
FANS
Fan air flow m3/h 15984 18000 18000 18000 20016 32004 32004 33984 33984
Max AESP (2) Pa 120 120 120 120 120 120 120 120 120
NOISE LEVELS
Sound power (3) dB(A) 82 85 85 85 87 92 92 93 93
SIZE
A (4) mm 2200 2200 2200 2200 2200 2602 2602 2602 2602
B (4) mm 920 920 920 920 920 1104 1104 1104 1104
H (4) mm 1642 1642 1642 1642 1642 1927 1927 1927 1927
Operating weight (4) kg 670 670 700 720 880 1120 1170 1210 1260

Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 138 159 152 172 195 222 244 281 312
Total power input (1) kW 58,3 67,2 62,5 73,1 83,5 89,6 102 115 133
EER 2,53 2,59 2,66 2,55 2,57 2,69 2,60 2,62 2,52
ESEER 4,17 3,94 3,86 3,72 3,61 3,97 3,77 3,88 3,74
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
FANS
Fan air flow m3/h 33984 51012 47988 51012 68004 64008 68004 68004 84996
Max AESP (2) Pa 120 120 120 120 120 120 120 120 120
NOISE LEVELS
Sound power (3) dB(A) 93 95 94 95 96 95 96 96 97
SIZE
A (4) mm 3602 3602 3602 3602 4602 4602 4602 4602 5602
B (4) mm 1104 1104 1277 1277 1277 1277 1277 1277 1277
H (4) mm 1927 1927 1900 1900 2235 2235 2235 2235 2235
Operating weight (4) kg 1450 1550 1845 1940 2310 2445 2515 2695 2885

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Useful pressure to be specified at the time of placing the order.
3 Total sound power of the fans as declared by the manufacturer referred to nominal speed of rotation and useful static head of 120 Pa on delivery side.
4 Unit in standard configuration/execution, without optional accessories

125
NECS-C / HT
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
COOLING
Cooling capacity (1) kW 39 45,5 52,7 59,4 80 91,5 103 114 130
Total power input (1) kW 14,9 17,4 20 22,4 30,6 34,6 39,8 44,1 50,8
EER 2,98 2,97 2,94 2,93 2,96 2,95 2,86 2,83 2,88
ESEER 4,83 4,48 4,51 4,42 3,93 4,01 3,81 4,03 3,78
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
FANS
Fan air flow m3/h 15984 19008 19008 19008 32004 32004 33984 33984 51012
Max AESP (2) Pa
NOISE LEVELS
Sound power (3) dB(A) 82 86 86 86 92 92 93 93 95
SIZE
A (4) mm 2200 2200 2200 2200 2602 2602 2602 3602 3602
B (4) mm 920 920 920 920 1104 1104 1104 1104 1104
H (4) mm 1642 1642 1642 1642 1927 1927 1927 1927 1927
Operating weight (4) kg 690 710 730 760 1090 1170 1230 1400 1490

Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
COOLING
Cooling capacity (1) kW 148 165 158 183 203 228 257 296 325
Total power input (1) kW 57,8 64,6 61,2 69 79,9 89,1 99,3 112 128
EER 2,98 2,80 2,85 2,96 2,81 2,80 2,86 2,88 2,74
ESEER 3,97 3,94 3,54 3,94 3,67 3,77 3,71 3,84 3,75
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
FANS
Fan air flow m3/h 51012 51012 51012 64008 68004 68004 84996 84996 84996
Max AESP (2) Pa
NOISE LEVELS
Sound power (3) dB(A) 95 95 95 95 96 96 97 97 97
SIZE
A (4) mm 3602 3602 3602 4602 4602 4602 5602 5602 5602
B (4) mm 1104 1104 1277 1277 1277 1277 1277 1277 1277
H (4) mm 1927 1927 1900 2235 2235 2235 2235 2235 2235
Operating weight (4) kg 1560 1630 1920 2320 2380 2580 2845 3055 3115

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Useful pressure to be specified at the time of placing the order.
3 Total sound power of the fans as declared by the manufacturer referred to nominal speed of rotation and useful static head of 120 Pa on delivery side.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-1204
Switchboard side mm 1000
Switchboard opposite side mm 1000
Opposite side of cond. coil mm 1000
Condensation coil side mm 2000

A
B

126
127
Hydronic - chiller

NECS-W 0152÷1204
Versions
B base version

Configurations
- base function
H function with heat pump, reversible on
hydraulic side

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta has designed the NECS-W units with a
range of integral accessories in mind for operation with
total water loss (well, water bed, etc.), dry cooler or
cooling tower so as to satisfy all service system and
installation requirements.
INTEGRATED HYDRONIC MODULE ON COOLER/
CONDENSER SIDE
The built-in hydronic module includes the main water
circuit components; it is available in various configurations
with one or two pumps with high or low head both on the
evaporator and the condenser side.
Chiller, water source INTEGRATED CONDENSATION´S CONTROL
The electronics of the units manages the most suitable
condensing control for each type of application: pressure-
controlled valve, two or three-way modulating valve and
43,4 - 371 kW inverter control for the pumps

Unit Description Main accessories


Water-cooled indoor unit for the production of chilled water with hermetic rotary Scroll UÊSet-up for remote connectivity with ModBus/Echelon/
compressors, braze-welded plate-type exchanger and thermal expansion valve. External Bacnet protocol cards
panels in pre-clad sheet steel (simil-Peraluman) and structure in galvanised steel with paint UÊCondensing control device: two or three-way
finish. The range includes the single-circuit two-compressor versions and the dual circuit four- modulating pressure-controlled valve and inverter on
compressor versions. pumps
UÊWater connections directed upwards (for 2 compressors
units only)
Commands
UÊAcoustical enclosure to reduce the noise emissions.
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
UÊRubber anti-vibration mounting kit. Spring anti-vibration
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level mounting kit (4 compressors models only)
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

128
r HFC
R-410A
PLATES SCROLL HEATING COOLING

NECS-W / B
Models 0152 0182 0202 0252 0262 0302 0352 0412 0452 0512
COOLING ONLY
Cooling capacity (1) kW 43,4 50,1 58,9 66,4 72,6 86,7 101 115 129 144
Total power input (1) kW 10,0 11,3 13,0 15,2 16,6 19,5 22,7 25,9 28,9 32,2
Condernser heating capacity (1) 52,8 60,7 71,2 80,7 88,2 105 123 139 156 174
EER 4,34 4,43 4,53 4,37 4,37 4,45 4,46 4,43 4,45 4,46
ESEER 5,80 6,00 6,00 5,70 5,60 5,70 5,80 5,70 5,80 5,80
HEATING ONLY (only -H)
Heating capacity (2) kW 50,5 58,2 68,0 77,0 85,0 101 117 132 148 165
Total power input (2) kW 12,9 14,3 16,7 19,2 21,1 24,7 28,7 32,2 36,0 40,0
COP 3,91 4,07 4,07 4,01 4,03 4,09 4,07 4,10 4,12 4,14
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 73 74 74 74 75 76 77 77 78 78
Sound pressure (4) dB(A)
SIZE
A (5) mm 1055 1055 1055 1055 1055 1222 1222 1222 1222 1222
B (5) mm 469 469 469 469 469 873 873 873 873 873
H (5) mm 1255 1255 1255 1255 1255 1496 1496 1496 1496 1496
Operating weight (5) kg 290 305 315 325 330 585 605 660 685 740

Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 165 186 174 203 228 258 288 329 371
Total power input (1) kW 36,9 41,6 38,9 45,2 51,6 58,0 64,0 74,0 83,5
Condernser heating capacity (1) 200 225 211 245 276 312 348 398 450
EER 4,47 4,48 4,47 4,48 4,42 4,45 4,50 4,44 4,44
ESEER 5,90 5,80 5,80 5,90 5,80 5,90 5,90 6,00 5,90
HEATING ONLY (only -H)
Heating capacity (2) kW 190 215 202 234 263 297 332 379 428
Total power input (2) kW 45,9 51,8 49,2 56,6 64,1 72,1 79,5 91,9 104
COP 4,14 4,14 4,11 4,13 4,10 4,12 4,17 4,13 4,12
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 79 79 86 87 88 89 90 91 91
Sound pressure (4) dB(A)
SIZE
A (5) mm 1222 1222 2227 2227 2227 2227 2227 2227 2227
B (5) mm 873 873 887 887 887 887 887 887 887
H (5) mm 1496 1496 1780 1780 1780 1780 1780 1780 1780
Operating weight (5) kg 790 830 1090 1165 1245 1290 1395 1500 1585

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-0612 0604-1204
Switchboard side mm 800 1000
Switchboard opposite side mm 600 1000
Unit’s side mm 600 1000

H H

A
B B A

129
Hydronic - chiller

FOCS-W 0401÷1902
Versions
B base version

Configurations
- base function
D partial condensing heat recovery function
H function with heat pump, reversible on
hydraulic side
R total condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
HEAT PUMP OPTION
Heat pump function water circuit side reversal

Chiller, water source Main accessories


UÊCompressor power factor device
UÊElectronic expansion valve
UÊPressostatic control valve
87,0 - 447 kW UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
Unit Description
LonTalk, Bacnet protocol board
Indoor unit for the production of chilled water with semi-hermetic screw compressors
optimized for R134a, thermostatic expansion valve, shell and tube condenser and evaporator.
Base and supporting structure and panels are of galvanized epoxy powder coated steel with
increased thickness. Flexible and reliable unit; it easily adapts itself to different thermal load
conditions thanks to the precise thermoregulation. The high performances level is achieved
thanks to the accurate sizing of all internal components.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

130
r HFC
R-134a
SHELL & TUBES SCREW HEATING COOLING

FOCS-W / B
Models 0401 0501 0551 0651 0751 0851 0951
COOLING ONLY
Cooling capacity (1) kW 87 107 130 147 165 198 221
Total power input (1) kW 19,6 24,6 28,1 32,6 37 42,8 49,6
Condernser heating capacity (1) 107 132 158 180 202 241 271
EER 4,44 4,35 4,63 4,51 4,46 4,63 4,46
ESEER 5,15 5,32 5,25 5,29 5,40 5,54 5,42
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 90,2 111 135 153 171 205 221
Total power input (2) kW 18,9 23,6 27,1 31,6 35,6 41,2 49,6
Desuperheater heating capacity (2) kW 8,50 10,6 12,1 14,1 15,9 18,5 21,4
COOLING WITH TOTAL RECOVERY (only -R)
Cooling capacity (3) kW 77,4 95,2 116 131 147 175 197
Total power input (3) kW 23,5 29,2 34,2 39,2 44 51,2 59,1
Heat recovery capacity (3) kW 99,5 123 148 168 188 202 252
HEATING ONLY (only -H)
Heating capacity (4) kW 95,7 118 142 162 181 215 243
Total power input (4) kW 23,2 28,9 33,8 38,9 43,4 50,7 58,4
COP 4,13 4,09 4,20 4,16 4,17 4,24 4,16
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 1/1
NOISE LEVELS
Sound power (5) dB(A) 91 92 94 94 94 94 94
Sound pressure (6) dB(A) * * * * * * *
SIZE
A (7) mm 2300 2500 2500 2500 2500 3200 3200
B (7) mm 1000 1000 1000 1000 1000 1500 1500
H (7) mm 1500 1500 1500 1500 1500 1200 1200
Operating weight (7) kg 800 840 1160 1180 1190 1270 1350

Models 0802 1002 1102 1302 1502 1702 1902


COOLING ONLY
Cooling capacity (1) kW 178 217 251 298 340 393 447
Total power input (1) kW 39,4 49,2 55,9 65,6 74,4 85,4 99,6
Condernser heating capacity (1) 217 266 307 364 414 478 547
EER 4,52 4,41 4,49 4,54 4,57 4,60 4,49
ESEER 5,39 5,52 5,24 5,49 5,67 5,70 5,61
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 184 217 251 298 340 393 447
Total power input (2) kW 38 49,2 55,8 65,6 74,5 85,4 99,5
Desuperheater heating capacity (2) kW 17 21,3 24,1 28,3 32,2 36,9 43
COOLING WITH TOTAL RECOVERY (only -R)
Cooling capacity (3) kW 158 194 223 265 304 348 397
Total power input (3) kW 47,1 58,7 67,9 78,6 88,6 102 118
Heat recovery capacity (3) kW 189 249 287 339 387 445 509
HEATING ONLY (only -H)
Heating capacity (4) kW 194 239 276 326 372 428 489
Total power input (4) kW 46,6 58 67,2 77,8 87,5 101 116
COP 4,16 4,12 4,11 4,19 4,25 4,23 4,18
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 94 95 97 97 97 97 97
Sound pressure (6) dB(A) * * * * * * *
SIZE
A (7) mm 3200 3200 3200 3500 3500 3500 3500
B (7) mm 1500 1500 1500 1200 1200 1200 1200
H (7) mm 1200 1200 1200 1800 1800 1800 1800
Operating weight (7) kg 1470 1490 1930 2220 2260 2320 2720
Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out): 12/7°C; Condenser water (in/out): 30/35°C; Desuperheater water (in/out): 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
7 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0401-1902
Switchboard side mm 650 H
Cooler water connections side
mm 450
(minimum)
Condenser water connections side mm 900
Condenser water fittings opposite
mm 600 B
side (minimum) A

131
Hydronic - chiller

FOCS2-W 1301÷9604
Versions
CA Class A of efficiency

CA-E Very high efficiency version: Class A


enhanced

Configurations
- base function
D partial condensing heat recovery function
H function with heat pump, reversible on
hydraulic side
R total condensing heat recovery function

Features
HIGH EFFICIENCY
The version ´CA-E´ is characterized by efficiency beyond
the ´Class A´ for Eurovent. The technological choices
adopted assure the minimization of operating costs and
therefore a quick payback time.
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
HEAT PUMP FUNCTION
High efficiency chiller, water source Heat pump function water circuit side reversal
SILENT OPERATION
Silent operation thanks to the accurate units design.
Optional integral acoustic enclosure, further reduces the
306 - 2416 kW sound level beyond the best on market

Unit Description Main accessories


Unit for indoor installation for chilled water production. Semihermetic screw compressors UÊKit HWT, High Water Temperature, to produce hot water
optimized to operate with low compression ratio and R134a; shell and tubes condenser up to 60°C
and direct expansion evaporator; electronic expansion valve. Frame in polyester-painted UÊIntegral acoustical enclosure (type base or plus)
galvanized steel. High efficiency unit: the innovative optimized compressors and the high
UÊVPF (Variable Primary Flow) system
performing heat exchangers enhance EER values up to 5,1 (CA version) and even up to
UÊSet-up for remote connectivity with ModBus/Echelon/
5,6 (CA-E version) at Eurovent standars conditions.
Bacnet protocol cards

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full
operating status display. The commands and detailed LCD display make access to the units settings easy and safe.
These resources allow to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions
for enhanced analysis of the unit operation. For multiple units systems, the regulation of the resources, via optional
proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed.
Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the
most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard
managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour
belts). The regulation features the continuous modulation of capacity, based on a dynamic dead band and referring to the
leaving water temperature. As alternative, step-wise regulation is also available, referred to the return water temperature
with selectable proportional- or proportional-integral logic. As option (VPF package), the modulation of capacity is
integrated with the modulation of the water flow, by means of inverter and dedicated resources for the hydraulic circuit.

132
r HFC
R-134a
ENERGY CLASS SHELL & TUBES SCREW HEATING COOLING

FOCS2-W / CA
Models 1301 1401 1601 1801 2101 2401 2701 3001 2802 3202 3602 4202
COOLING ONLY
Cooling capacity (1) kW 306 348 422 477 538 607 689 735 694 844 957 1071
Total power input (1) kW 60,5 68,7 83,4 94,4 106 120 136 145 137 167 189 212
Condernser heating capacity (1) - - - - - - - - - - - -
EER 5,06 5,07 5,06 5,06 5,07 5,07 5,06 5,06 5,05 5,06 5,07 5,06
ESEER
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 318 361 438 495 558 630 715 762 720 876 993 1112
Total power input (2) kW 58,4 66,3 80,5 91,1 102 116 131 140 133 161 182 204
Desuperheater heating capacity (2) kW 26,3 29,8 36,2 41 46 52 59,1 63,1 59,7 72,4 82 91,9
COOLING WITH TOTAL RECOVERY (only -R)
Cooling capacity (3) kW 276 314 376 425 483 546 603 667 625 752 853 964
Total power input (3) kW 76,8 87,3 104 118 133 150 166 183 175 209 236 265
Heat recovery capacity (3) kW 348 396 474 536 608 687 759 839 790 948 105 1214
HEATING ONLY (only -H)
Heating capacity (4) kW 348 396 474 536 608 687 759 839 790 948 1075 1214
Total power input (4) kW 76,8 87,3 104 118 133 150 166 183 175 209 236 265
COP 4,53 4,54 4,54 4,54 4,58 4,59 4,58 4,59 4,52 4,54 4,55 4,58
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 97 97 97 97 97 97 99 99 99 99 99 99
Sound pressure (6) dB(A) 75 75 75 75 75 75 77 77 77 77 77 77
SIZE
A (7) mm 3930 3930 3930 3930 3930 3930 3980 3980 4250 4750 4750 4750
B (7) mm 900 900 900 900 900 900 900 900 1150 1150 1150 1150
H (7) mm 1850 1850 1900 1950 1950 1950 1990 1990 2160 2156 2156 2226
Operating weight (7) kg * * * * * * * * * * * *

Models 4502 4802 5402 6002 6303 6603 7203 7803 8103 9003 9004 9604
COOLING ONLY
Cooling capacity (1) kW 1145 1213 1376 1467 1604 1677 1815 1977 2069 2201 2278 2416
Total power input (1) kW 226 240 272 290 317 331 359 391 409 435 451 478
Condernser heating capacity (1) - - - - - - - - - - - -
EER 5,06 5,06 5,05 5,05 5,05 5,06 5,05 5,06 5,06 5,06 5,05 5,05
ESEER
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 1188 1259 1428 1522 1664 1740 1883 2051 2146 2283 2363 2507
Total power input (2) kW 218 231 263 280 306 320 346 377 394 420 435 462
Desuperheater heating capacity (2) kW 98,2 104 118 126 138 144 156 170 178 189 196 208
COOLING WITH TOTAL RECOVERY (only -R)
Cooling capacity (3) kW 1029 1091 1205 1333
Total power input (3) kW 283 300 331 366
Heat recovery capacity (3) kW 1295 1374 1516 1676
HEATING ONLY (only -H)
Heating capacity (4) kW 1295 1374 1516 1676 1817 1898 2056 2215 2276 2515 2582 2739
Total power input (4) kW 283 300 331 366 398 415 449 484 497 548 564 599
COP 4,58 4,58 4,58 4,58 4,57 4,58 4,58 4,58 4,58 4,59 4,58 4,58
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 3/3 3/3 3/3 3/3 3/3 3/3 4/4 4/4
NOISE LEVELS
Sound power (5) dB(A) 99 99 101 101 102 102 102 102 102 102 102 102
Sound pressure (6) dB(A) 77 77 79 79 80 80 80 80 80 80 80 80
SIZE
A (7) mm 4750 4750 4850 4850 4950 4950 4950 4950 4950 4950 4650 4650
B (7) mm 1150 1150 1150 1150 1700 1700 1700 1700 1700 1700 2250 2250
H (7) mm 2226 2226 2226 2226 2150 2150 2150 2150 2150 2150 2180 2180
Operating weight (7) kg * * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out): 12/7°C; Condenser water (in/out): 30/35°C; Desuperheater water (in/out): 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
7 Unit in standard configuration/execution, without optional accessories

133
FOCS2-W / CA-E
Models 1301 1401 1601 1801 2101 2401 2802 3202 3602 4202 4802
COOLING ONLY
Cooling capacity (1) kW 321 365 442 506 574 649 729 884 1012 1147 1298
Total power input (1) kW 57,3 65,1 79,1 90,3 103 116 130 158 180 205 232
Condernser heating capacity (1) - - - - - - - - - - -
EER 5,60 5,60 5,59 5,61 5,59 5,59 5,60 5,59 5,61 5,59 5,59
ESEER 6,49 6,50 6,30 6,40 6,37 6,40 6,66 6,57 6,73 6,64 6,66
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 322 367 444 509 577 653 733 889 1017 1153 1305
Total power input (2) kW 57,2 65,0 78,9 90,1 102 116 130 158 180 205 232
Desuperheater heating capacity (2) kW 25,7 29,2 35,5 40,5 46,1 52,2 58,5 71,0 81,0 92,1 104
COOLING WITH TOTAL RECOVERY (only -R)
Cooling capacity (3) kW 289 328 395 452 657 790 904
Total power input (3) kW 73,1 83,1 99,5 114 166 199 227
Heat recovery capacity (3) kW 357 407 488 559 813 977 1118
HEATING ONLY (only -H)
Heating capacity (4) kW 357 407 488 559 638 722 813 977 1118 1275 1443
Total power input (4) kW 73,1 83,1 99,5 114 129 146 166 199 227 258 292
COP 4,89 4,89 4,91 4,92 4,94 4,94 4,89 4,91 4,92 4,94 4,94
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 97 97 97 97 97 97 99 99 99 99 99
Sound pressure (6) dB(A) 75 75 75 75 75 75 77 77 77 77 77
SIZE
A (7) mm 4300 4300 4000 4000 4000 4300 4600 4950 5220 4950 4950
B (7) mm 990 990 990 990 990 990 1240 1240 1240 1240 1375
H (7) mm 1900 1900 2000 2000 2000 2100 2195 2195 2195 2350 2430
Operating weight (7) kg * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out): 12/7°C; Condenser water (in/out): 30/35°C; Desuperheater water (in/out): 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
7 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1301-9604
Switchboard side mm 1500
Cooler water connections side (minimum) mm 900
Condenser water connections side mm 3000
Condenser water fittings opposite side (minimum) mm 1500

134
135
Hydronic - chiller

TECS2-W Vision 2.0 0251÷1954


Versions
HC High Condensing
LC Low Condensing

Configurations
- base function
H function with heat pump, reversible on
hydraulic side

Features
VERY HIGH EFFICIENCY
Very high efficiency at full and partial load, to top market
levels, thanks to adopted technological solutions: large
capacity modulation and expanded exchanger, offering
minimum running costs of the unit in real working
conditions.
DEDICATED VERSIONS
Dedicated versions for different applications: version HC,
High Condensing, for dry-cooler or heat pump systems
and version LC, Low Condensing, for cooling tower or
ground source applications.
HEAT PUMP FUNCTION
Heat pump function water circuit side reversal
EXTREMELY SILENT OPERATION
High efficiency chiller, water source Extremely silent operation in line with the best on the
market, and highly reduced vibrations
LOW INRUSH CURRENTS
Reduced breakaway starting currents thanks to the
241 - 1949 kW revolutionary centrifugal compressor

Unit Description Main accessories


Indoor unit for the production of chilled water featuring centrifugal compressors oil-free, with UÊIntegral acoustical enclosure (type base or plus)
R134a, electronic regulation valve, shell and tube condenser and shell and tube flooded
UÊVPF (Variable Primary Flow) system
evaporator. Base and supporting structure and panels are of galvanized epoxy powder
coated steel with increased thickness. Flexible and reliable unit; it easily adapts itself to UÊSeveral devices for condensation´s control
different thermal load conditions thanks to the precise thermoregulation together with the UÊLeak detector
use of inverter technology. The compressor is radically innovative: magnetic bearings and UÊSet-up for remote connectivity with ModBus/Echelon/
digital rotor speed control allow partial load efficiency levels to be reached that were hither to Bacnet protocol cards
impossible.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity by adjustment of the compressor speed. The modulation is based on PID algorithms and referring to
the leaving water temperature. This is combined with the management of the compressors status, based on a proportional
logic referred to the return temperature. As option (VPF package), the modulation of capacity is integrated with the
modulation of the water flow, by means of inverter and dedicated resources for the hydraulic circuit.

136
r HFC
R-134a
ENERGY CLASS SHELL & TUBES CENTRIFUGAL HEATING COOLING

TECS2-W Vision 2.0 / HC


Models 0251 0311 0351 0411 0512 0612 0712 0812 0913 1053 1213 1414 1614
COOLING ONLY
Cooling capacity (1) kW 241 294 359 405 497 588 716 811 881 1045 1213 1405 1618
Total power input (1) kW 46 57 69,2 78,9 94,8 114 139 156 171 203 237 269 316
Condernser heating capacity (1) - - - - - - - - - - - - -
EER 5,24 5,15 5,19 5,13 5,24 5,16 5,14 5,14 5,15 5,15 5,12 5,23 5,13
ESEER 8,70 8,83 8,84 8,95 9,08 9,16 9,04 9,21 9,13 8,96 9,12 9,16 9,20
HEATING ONLY (only -H)
Heating capacity (2) kW 287 351 439 500 592 703 877 1000 1053 1279 1496 1718 1995
Total power input (2) kW 57 70 89 101 118 140 178 203 210 261 304 346 405
COP 5,00 5,01 4,95 4,93 5,01 5,02 4,92 4,94 5,02 4,91 4,92 4,96 4,92
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 2/1 2/1 2/1 2/1 3/1 3/1 3/1 4/1 4/1
NOISE LEVELS
Sound power (3) dB(A) 91 93 92 94 94 95 94 96 96 96 97 97 98
Sound pressure (4) dB(A) 59 61 60 62 62 63 62 64 64 64 65 65 66
SIZE
A (5) mm 2990 2990 2990 2990 3490 3490 3490 3490 4990 4990 4990 5450 5450
B (5) mm 950 950 950 950 1300 1300 1300 1300 1300 1300 1300 1300 1300
H (5) mm 1900 1900 1900 1900 1800 1800 1800 1800 1800 1800 1800 1990 1990
Operating weight (5) kg - - - - - - - - - - - - -

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
5 Unit in standard configuration/execution, without optional accessories

TECS2-W Vision 2.0 / LC


Models 0511 0912 1012 1353 1453 1854 1954
COOLING ONLY
Cooling capacity (1) kW 488 879 978 1359 1461 1809 1949
Total power input (1) kW 93,2 172 186 258 280 344 373
Condernser heating capacity (1) - - - - - - -
EER 5,24 5,12 5,24 5,27 5,22 5,26 5,23
ESEER 9,37 9,19 9,45 9,43 9,41 9,52 9,42
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 2/1 2/1 3/1 3/1 4/1 4/1
NOISE LEVELS
Sound power (2) dB(A) 95 96 97 97 98 99 99
Sound pressure (3) dB(A) 63 64 65 65 66 67 67
SIZE
A (4) mm 2990 3490 3490 4990 4990 5450 5450
B (4) mm 950 1300 1300 1300 1300 1300 1300
H (4) mm 1900 1800 1800 1800 1800 1990 1990
Operating weight (4) kg - - - - - - -

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0251-0411 0512-0612 0712-1213 1414-1614
Switchboard side mm 1000 1000 1000 1000
Cooler water connections side
mm 2500 3000 4000 4500
(minimum)
Condenser water connections side mm 2500 3000 4000 4500
Raising points side mm 900 900 900 900

137
Hydronic - chiller

NECS-ME 0152÷1604
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
UNIT DESIGNED FOR COMBINATION WITH REMOTE
CONDENSER
Compact units, designed for residential- and commercial
air-conditioning systems
INTEGRAL CONTROL AND ADJUSTMENT
The condenserless unit comes complete with built-in
microprocessor control with possible connection to the
condenser.
INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main
water circuit components; it is available with single or
double pump configuration, with low or high head.

Main accessories
UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Bacnet protocol board
Condenserless chiller UÊAcoustical enclosure to reduce the noise emissions.
UÊRubber anti-vibration mounting kit

39,5 - 432 kW
Unit Description
Indoor unit for the production of chilled water that may be connected to a remote condenser
with hermetic rotary scroll compressors working with R410A, braze-welded plate-type
exchanger and thermal expansion valve. Panels and base in hot-dip galvanised sheet steel
with paint finish.

Commands
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

138
r HFC
R-410A
PLATES SCROLL COOLING

NECS-ME / B
Models 0152 0182 0202 0252 0262 0302 0352 0412 0452 0512 0552
COOLING
Cooling capacity (1) kW 39,5 45,8 53,6 60,5 67,4 80,2 92,8 105 117 131 151
Compressors power input (1) kW 12 13,5 15,7 18,1 20 23,4 26,9 30,3 33,9 37,6 43,3
Remote condenser capacity (1) kW 3,29 3,39 3,41 3,34 3,37 3,43 3,45 3,45 3,46 3,49 3,48
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (2) dB(A) 73 74 74 74 75 76 77 77 77 78 79
Sound pressure (3) dB(A) 41 42 42 42 43 44 45 45 45 46 47
SIZE
A mm 1130 1130 1130 1130 1130 1310 1310 1310 1310 1310 1310
B mm 669 669 669 669 669 893 893 893 893 893 893
H mm 1255 1255 1255 1255 1255 1496 1496 1496 1496 1496 1496
Operating weight kg 270 280 290 295 300 410 500 585 615 645 680

Models 0612 0604 0704 0804 0904 1004 1104 1204 1404 1604
COOLING
Cooling capacity (1) kW 170 161 186 207 235 263 301 339 387 432
Compressors power input (1) kW 48,9 46,9 53,7 60,6 67,9 75,2 86,5 97,8 111 124
Remote condenser capacity (1) kW 3,47 3,43 3,46 3,42 3,47 3,50 3,47 3,47 3,49 3,48
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 79 86 87 88 89 90 91 91 91 91
Sound pressure (3) dB(A) 47 54 55 56 57 58 59 59 59 59
SIZE
A mm 1310 2227 2227 2227 2227 2227 2227 2227 2227 2227
B mm 893 1020 1020 1020 1020 1020 1020 1020 1020 1020
H mm 1496 1780 1780 1780 1780 1780 1780 1780 1780 1780
Operating weight kg 755 700 950 1125 1185 1250 1330 1370 1430 1480

Note:
1 Evaporator water (in/out) = 12/7°C; Condensation temperature = 47°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Sound pressure in open field conditions on reflecting surface. Condensing coil side average value at 1 metre from the surface and at 1 m height in relation to the unit supporting base.

Minimum clearance required


0152-0612 0604-1604
Switchboard side mm 800 1000
Cooler water connections side (minimum) mm 600 1000
Unit's side mm 600 800
Switchboard opposite side mm 600 1000

H H

A
B B A

139
Hydronic - chiller

FOCS-ME 0401÷1902
Versions
B base version

Features
COMPACTNESS
Compactness in terms of overall size and weight, helping
installation and working on site
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with remote condenser
operating up to 46°C air temperature
SILENT OPERATION
Silent operation thanks to the accurate units design.
Optional integral acoustic enclosure, further reduces the
sound level beyond the best on market

Main accessories
UÊSoft start
UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Trend, Bacnet protocol board.
UÊRemote keyboard (distance to 200m and to 500m)

Condenserless chiller UÊElectronic expansion valve


UÊIntegral acoustical enclosure (type base or plus)

79,2 - 410 kW
Unit Description
Indoor unit for the production of chilled water combined with a remote condenser, with
semi-hermetic screw compressors optimized for R134a, shell and tube evaporator designed
by Climaveneta and thermostatic expansion valve. Base and supporting structure and
panels are of galvanized epoxy powder coated steel with increased thickness. Flexible and
reliable unit; it easily adapts itself to different thermal load conditions thanks to the precise
thermoregulation. The high performances level is achieved thanks to the accurate sizing of all
internal components.

Commands
W3000SE Compact
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

140
r HFC
R-134a
SHELL & TUBES SCREW COOLING

FOCS-ME / B
Models 0401 0501 0551 0651 0751 0851 0951
COOLING
Cooling capacity (1) kW 79,2 98,2 119 135 151 181 203
Compressors power input (1) kW 22,7 27,9 32,5 37,6 42,3 48,9 56,5
Remote condenser capacity (1) kW 102 126 152 173 193 230 260
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 1/1
NOISE LEVELS
Sound power (2) dB(A) 91 92 94 94 94 94 94
Sound pressure (3) dB(A)
SIZE
A mm 2024 2330 2400 2400 2400 2947 2947
B mm 880 880 880 880 880 880 880
H mm 1300 1300 1490 1490 1490 1490 1500
Operating weight kg 720 750 1040 1060 1060 1130 1150

Models 0802 1002 1102 1302 1502 1702 1902


COOLING
Cooling capacity (1) kW 162 200 230 273 312 360 410
Compressors power input (1) kW 45,6 56,0 64,6 75,3 85,0 97,7 113
Remote condenser capacity (1) kW 208 256 295 348 397 458 523
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 94 95 97 97 97 97 97
Sound pressure (3) dB(A)
SIZE
A mm 2890 2890 3016 3277 3277 3292 3362
B mm 1081 1081 1081 1081 1081 1081 1081
H mm 1430 1430 1480 1580 1580 1590 1700
Operating weight kg 1280 1290 1680 1970 1990 2010 2300
Note:
1 Evaporator water (in/out) = 12/7°C; Condensation temperature = 47°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.

Minimum clearance required


0401-1902
Switchboard side mm 1000
Cooler water connections side
mm 620
(minimum)
Compressor outlet connection side mm 500
Compressor outlet connection
mm 500
opposite side

B
A

141
Hydronic - chiller

FOCS-ME 1001÷9604
Versions
B base version

Features
COMPACTNESS
Compactness in terms of overall size and weight, helping
installation and working on site
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with remote condenser
operating up to 46°C air temperature
SILENT OPERATION
Silent operation thanks to the accurate units design.
Optional integral acoustic enclosure, further reduces the
sound level beyond the best on market

Main accessories
UÊIntegral acoustical enclosure (type base or plus)
UÊElectronic expansion valve
UÊSoft start
Condenserless chiller UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Trend, Bacnet protocol board.
UÊRemote keyboard (distance to 200m and to 500m)

219 - 2240 kW
Unit Description
Indoor unit for the production of chilled water combined with a remote condenser, with
semi-hermetic screw compressors optimized for R134a, shell and tube evaporator designed
by Climaveneta and thermostatic expansion valve. Base and supporting structure and
panels are of galvanized epoxy powder coated steel with increased thickness. Flexible and
reliable unit; it easily adapts itself to different thermal load conditions thanks to the precise
thermoregulation. The high performances level is achieved thanks to the accurate sizing of all
internal components.

Commands
W3000SE Compact
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

142
r HFC
R-134a
SHELL & TUBES SCREW COOLING

FOCS-ME / B
Models 1001 1201 1301 1351 1601 1801 2002 2402 2602
COOLING
Cooling capacity (1) kW 219 262 295 333 389 445 419 516 591
Compressors power input (1) kW 59,7 69,7 77,5 85,4 101 118 114 139 155
Remote condenser capacity (1) kW 279 332 373 418 490 563 533 655 746
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) 94 97 97 97 97 97 97 99 99
Sound pressure (3) dB(A)
SIZE
A mm 2835 3120 3120 3120 3530 3530 3730 3730 4500
B mm 900 900 900 900 900 900 1150 1150 1150
H mm 1800 1800 1800 1800 1950 1950 2000 2000 2000
Operating weight kg 1380 1870 1910 1920 2640 2650 2750 3420 3710

Models 2702 3202 3602 4202 4502 4802 5003 5203 5403
COOLING
Cooling capacity (1) kW 674 759 885 1000 1061 1120 1184 1251 1304
Compressors power input (1) kW 171 202 236 265 277 290 320 337 353
Remote condenser capacity (1) kW 845 916 1121 1265 1338 1410 1504 1588 1657
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3
NOISE LEVELS
Sound power (2) dB(A) 99 99 99 99 99 99 101 101 101
Sound pressure (3) dB(A)
SIZE
A mm 4500 4500 4500 4500 4500 4500 4425 4425 4425
B mm 1150 1150 1150 1150 1150 1150 1700 1700 1700
H mm 2000 2000 2000 2000 2000 2000 1900 1900 1900
Operating weight kg 3730 4600 5050 5220 5250 5280 6810 6840 6850

Models 5414 5904 6404 6804 7204 7804 8404 9004 9604
COOLING
Cooling capacity (1) kW 1348 1434 1548 1660 1769 1886 2001 2121 2240
Compressors power input (1) kW 342 373 406 439 472 501 530 555 580
Remote condenser capacity (1) kW 1690 1807 1954 2099 2241 2387 2531 2676 2820
COMPRESSORS
No. Compressors/No. Circuits N. 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
NOISE LEVELS
Sound power (2) dB(A) 102 102 102 102 102 102 102 102 102
Sound pressure (3) dB(A)
SIZE
A mm 4500 4500 4500 4500 4500 4500 4500 4500 4500
B mm 2250 2250 2250 2250 2250 2250 2250 2250 2250
H mm 2000 2000 2000 2000 2000 2000 2000 2000 2000
Operating weight kg 7560 8400 9980 10010 10020 10190 10350 10420 10480
Note:
1 Evaporator water (in/out) = 12/7°C; Condensation temperature = 47°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.

Minimum clearance required


1001-9604
Switchboard side mm 1000
Cooler water connections side
mm 620
(minimum)
Compressor outlet connection side mm 500
Compressor outlet connection
mm 500
opposite side

A
B

143
DR
RONIC - R
R

144
reversible
hydronic
EVERSIBLE
hydronic - reversible

145
Hydronic - reversible

NECS-N 0152÷1204
Versions
B base version
HL low noise, high efficiency, high outdoor
temperature version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta is the only company offering units with Scroll
compressors in 5 versions and 2 different configurations
designed to satisfy all service system and application
Reversible unit, air source for outdoor requirements
STANDARD SUPPLY WITH WATER FILTER ALREADY
installation INSTALLED
The water filter is already installed as standard supply
on all units, including those without hydronic kit. This
35,8 - 322 kW simplifies installation procedures, while ensuring maximum
working reliability
Unit Description INTEGRATED HYDRONIC MODULE
Outdoor unit with heat pump for the production of chilled/hot water with hermetic rotary scroll The incorporated hydronic unit already contains the
compressors dedicated to the use of R410A, axial fans, braze-welded plate-type exchanger main water circuit components; it is available in various
and thermal expansion valve. External panels in pre-clad sheet steel (simil Pereluman) and configurations with one or two pumps with high or low
base in galvanised steel with paint finish. The range includes the single-circuit two-compressor head and the buffer tank
versions and the dual circuit four-compressor versions.

Commands Main accessories


W3000 Base / W3000SE Compact UÊSet-up for remote connectivity with ModBus/Echelon/
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
Bacnet protocol cards
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and UÊRemote keyboard (distance to 200m and to 500m)
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common UÊSoft starters
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low UÊLT kit for working down to -10°C in heat pump mode
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for UÊRubber anti-vibration mounting kit. Spring anti-vibration
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the mounting kit (4 compressors models only)
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks. The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous operational
parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall energy
efficiency.

146
r HFC
R-410A
PLATES AXIAL SCROLL HEATING COOLING

NECS-N / B
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552
COOLING ONLY
Cooling capacity (1) kW 37,7 42,8 47,9 57,5 72 82,5 93,9 107 120 138
Total power input (1) kW 13,6 15,7 19,2 20,4 28 32 36 39,9 44 50,6
EER 2,77 2,73 2,49 2,82 2,57 2,58 2,61 2,68 2,73 2,73
ESEER 4,04 4,08 4,03 4 3,95 4,06 3,92 4,09 4,04 4,18
HEATING ONLY
Heating capacity (2) kW 42,9 48,1 54,2 65,2 81 93,5 105 121 136 157
Total power input (2) kW 14,2 15,6 18,1 21,2 26,1 29,8 33,8 38,1 42,4 48,6
COP 3,02 3,08 2,99 3,08 3,10 3,14 3,11 3,18 3,21 3,23
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 39,1 44,4 49,7 59,7 74,7 85,6 97,4 111 125 143
Total power input (3) kW 13,1 15,1 18,5 19,7 27,1 30,9 34,8 38,5 42,5 48,7
Desuperheater heating capacity (3) kW 11,2 13,1 16,2 16,9 23,7 27,2 30,3 33,8 37 42,7
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 84 84 84 84 85 86 86 86 87 87
Sound pressure (5) dB(A) 52 52 52 52 53 54 54 54 55 55
SIZE
A (6) mm 1695 1695 1695 2195 2195 2195 2745 2745 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1420 1420 1420 1620 1620
Operating weight (6) kg 400 410 420 500 630 690 770 850 950 1020

Models 0612 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 151 111 129 147 166 189 211 240 277 311
Total power input (1) kW 59 43,7 54 60 68,9 75,9 85,1 95,6 107 120
EER 2,56 2,54 2,39 2,45 2,41 2,49 2,48 2,51 2,58 2,58
ESEER 3,99 3,99 3,39 3,57 3,64 3,80 3,88 3,68 3,84 3,93
HEATING ONLY
Heating capacity (2) kW 173 127 145 167 185 209 234 267 306 344
Total power input (2) kW 54,6 43,6 52,7 58 64,7 72,1 79,9 92,1 104 116
COP 3,17 2,91 2,75 2,88 2,86 2,90 2,93 2,90 2,94 2,96
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 156 116 134 152 172 196 219 249 287 322
Total power input (3) kW 56,9 42,5 52,4 58,1 66,8 73,4 82,5 92,7 104 117
Desuperheater heating capacity (3) kW 50,3 35,4 40,7 46 54 60,1 68,6 74,1 84,6 96,3
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 87 91 92 92 92 92 93 94 95 95
Sound pressure (5) dB(A) 55 59 60 60 60 60 61 62 63 63
SIZE
A (6) mm 3245 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1030 1380 1570 1750 1900 2080 2270 2410 2540 2700

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

147
NECS-N / HL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 113 129 142 163 190 209 236 273 307
Total power input (1) kW 43,8 51 58,9 67,4 73,9 84,6 92,6 103 119
EER 2,58 2,53 2,41 2,42 2,57 2,47 2,55 2,63 2,57
ESEER 3,75 3,81 3,78 3,91 3,79 3,81 3,92 4,11 3,91
HEATING ONLY
Heating capacity (2) kW 128 144 159 181 211 233 261 303 340
Total power input (2) kW 44,3 49,2 53,9 60,9 71 78,7 86,4 98,7 112
COP 2,89 2,93 2,95 2,97 2,97 2,96 3,02 3,07 3,01
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 117 133 148 169 197 217 245 283 318
Total power input (3) kW 42,3 49,1 57,1 64,9 71,6 82,2 89,4 101 116
Desuperheater heating capacity (3) kW 34,7 41 48,3 55,6 59,6 69,4 76 86,4 98,1
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 86 86 86 86 88 88 88 90 91
Sound pressure (5) dB(A) 54 54 54 54 56 56 56 58 59
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1840 1980 2310 2370 2520 2800 2940
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-N / HT
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 117 134 149 172 198 219 248 287 322
Total power input (1) kW 45,5 51,3 58,4 65,7 75,3 84,9 91,5 102 118
EER 2,57 2,61 2,55 2,62 2,63 2,58 2,71 2,79 2,71
ESEER 3,42 3,53 3,64 3,77 3,57 3,60 3,82 3,98 3,80
HEATING ONLY
Heating capacity (2) kW 134 150 167 191 220 244 274 315 357
Total power input (2) kW 48,2 53 58 65,2 76,9 84,7 92,3 104 121
COP 2,78 2,83 2,88 2,93 2,86 2,88 2,97 3,02 2,95
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 121 139 155 178 205 228 257 297 334
Total power input (3) kW 44,1 49,8 56,8 63,7 73,1 82,7 88,9 99,6 115
Desuperheater heating capacity (3) kW 33 38,3 44,8 51,1 56 64,8 70,6 80,5 91,2
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 92 92 92 92 94 94 94 97 97
Sound pressure (5) dB(A) 60 60 60 60 62 62 62 64 65
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1840 1980 2310 2370 2520 2800 2940
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

148
NECS-N / LN
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552
COOLING ONLY
Cooling capacity (1) kW 35,8 41,6 48 54,6 73,2 83,5 93,9 103 119 132
Total power input (1) kW 14,2 16 19,1 21,4 27,2 31,9 36 41,5 44,6 53,4
EER 2,52 2,60 2,51 2,55 2,69 2,62 2,61 2,48 2,67 2,47
ESEER 4,09 4,16 4,03 4,02 4,08 3,96 3,94 3,93 3,99 3,97
HEATING ONLY
Heating capacity (2) kW 41,8 48,2 54,1 63,6 84,1 96,2 109 121 138 154
Total power input (2) kW 13,8 15,2 18,1 20,7 26,1 30,4 34,2 36,2 42,6 48,3
COP 3,02 3,17 2,99 3,07 3,22 3,16 3,19 3,34 3,24 3,19
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 37,1 43,1 49,8 56,7 75,9 86,7 97,4 107 123 137
Total power input (3) kW 13,8 15,5 18,4 20,6 26,3 30,9 34,8 40,2 43,1 51,6
Desuperheater heating capacity (3) kW 12,2 13,7 16,1 18,2 23,1 26,7 30,3 35,3 37,5 45,4
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 79 79 80 80 81 83 83 83 84 84
Sound pressure (5) dB(A) 47 47 48 48 49 51 51 51 52 52
SIZE
A (6) mm 1695 1695 2195 2195 2745 2745 2745 2745 3245 3245
B (6) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (6) mm 1420 1420 1420 1420 1420 1620 1620 1620 1620 1620
Operating weight (6) kg 400 420 460 500 710 770 830 880 990 1020

Models 0612 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 143 103 123 141 156 177 199 227 261 291
Total power input (1) kW 62,7 46,2 53,5 60 70,3 78,3 87,7 96,2 110 125
EER 2,28 2,23 2,30 2,35 2,22 2,26 2,27 2,36 2,37 2,32
ESEER 3,76 3,89 3,66 3,74 3,78 3,77 3,89 3,76 3,92 3,86
HEATING ONLY
Heating capacity (2) kW 169 122 138 158 176 198 225 254 290 324
Total power input (2) kW 54,2 41,5 48,9 53,7 60,7 67,8 75,5 86,1 98 110
COP 3,12 2,94 2,82 2,94 2,90 2,92 2,98 2,95 2,96 2,94
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 148 107 128 146 162 184 207 236 270 302
Total power input (3) kW 60,6 44,7 51,8 58 68,2 75,9 84,9 93,4 107 121
Desuperheater heating capacity (3) kW 53,8 39,2 43,5 49,2 58,7 65,7 74,1 79,7 92 105
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 84 85 86 86 86 86 87 88 89 89
Sound pressure (5) dB(A) 52 53 54 54 54 54 55 56 57 57
SIZE
A (6) mm 3245 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1030 1380 1570 1750 1900 2080 2270 2410 2540 2700
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

149
NECS-N / SL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 108 124 141 159 183 201 225 261 294
Total power input (1) kW 45 52,1 58,3 67,7 75,3 87,4 95,3 108 123
EER 2,40 2,38 2,42 2,35 2,43 2,30 2,36 2,41 2,38
ESEER 3,84 3,93 3,98 4,05 3,87 3,88 3,93 4,13 3,93
HEATING ONLY
Heating capacity (2) kW 125 140 158 178 205 226 253 295 330
Total power input (2) kW 42,8 47,5 52,2 59,5 68,6 76,1 83,8 96,1 110
COP 2,92 2,95 3,03 2,99 2,99 2,97 3,02 3,07 3
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 112 128 146 165 190 208 234 271 305
Total power input (3) kW 43,5 50,3 56,3 65,4 73 84,4 92,3 105 119
Desuperheater heating capacity (3) kW 37 43,3 48,9 57,3 62,7 73,3 80,6 92 104
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 82 82 82 82 83 83 83 85 86
Sound pressure (5) dB(A) 50 50 50 50 51 51 51 53 54
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1900 2050 2310 2370 2520 2800 2940

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0504-1204 0152-0612
Switchboard side mm 1100 600
Switchboard opposite side mm 1100 600
Condensation coil side mm 2000 1000

H H

A
A
B
B

150
151
Hydronic - reversible

NECS-N 0202T÷0612T
Versions
B base version
LN low noise version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS
represents the best choice for all the hydronic application
on the residential, commercial and industrial markets.
INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main
water circuit components; it is available with single or twin
in-line, for achieving both low or high head.
MAXIMUM RELIABILITY
Unit with dual-circuit refrigerant section designed to
ensure maximum efficiency at full load, ensuring continuity
without interruption of operation in the event of temporary
stop of one of the 2 circuits.
Reversible unit, air source for outdoor
installation Main accessories
UÊSet-up for remote connectivity with ModBus/Echelon/
50,3 - 169 kW Bacnet protocol cards
UÊRemote keyboard (distance to 200m and to 500m)
Unit Description UÊSoft starters
Outdoor reversible heat pump for the production of chilled/hot water with hermetic rotary UÊRubber anti-vibration mounting kit
Scroll compressors, axial-flow fans, shell and tubes heat exchanger and thermostatic UÊLCD display keyboard type W3000Compact with multi-
expansion valve. External panels in Peraluman and structure in aluminium sections. The range language user interface (refers to the shown picture)
is equipped with two compressors on two independent refrigerant circuits.

Commands
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks. The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous operational
parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall energy
efficiency.

152
SHELL & TUBES AXIAL SCROLL HEATING COOLING

NECS-N / B
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T 0552T 0612T
COOLING ONLY
Cooling capacity (1) kW 50,3 57,5 72 82,5 93,9 107 120 138 151
Total power input (1) kW 18,4 20,4 28 32 36 39,8 44 50,4 58,9
EER 2,73 2,82 2,57 2,58 2,61 2,68 2,73 2,73 2,56
ESEER 3,52 3,59 3,31 3,3 3,31 3,39 3,45 3,46 3,26
HEATING ONLY
Heating capacity (2) kW 55,1 65,2 81 93,5 105 121 136 157 173
Total power input (2) kW 18,6 21,2 26,1 29,8 33,9 37,9 42,3 48,4 54,4
COP 2,96 3,08 3,10 3,14 3,11 3,18 3,21 3,23 3,17
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 84 84 85 86 86 86 87 87 87
Sound pressure (4) dB(A) 52 52 53 54 54 54 55 55 55
SIZE
A (5) mm 2195 2195 2195 2195 2745 2745 3245 3245 3245
B (5) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (5) mm 1420 1420 1420 1420 1420 1420 1620 1620 1620
Operating weight (5) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

NECS-N / LN
Models 0202T 0252T 0302T 0352T 0412T 0452T 0512T 0552T 0612T
COOLING ONLY
Cooling capacity (1) kW 48 54,6 73,2 83,5 93,9 103 119 132 143
Total power input (1) kW 19,1 21,4 27,2 31,9 36 41,6 44,6 53,3 62,7
EER 2,52 2,56 2,69 2,62 2,61 2,48 2,67 2,47 2,28
ESEER 3,52 3,31 3,46 3,33 3,33 3,17 3,38 3,16 2,93
HEATING ONLY
Heating capacity (2) kW 54,1 63,6 84,1 96,2 109 121 137 154 170
Total power input (2) kW 18,1 20,7 26,1 30,4 34,1 37,9 42,4 48,3 54,3
COP 3,00 3,08 3,22 3,16 3,19 3,18 3,24 3,19 3,12
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 80 80 81 83 83 83 84 84 84
Sound pressure (4) dB(A) 48 48 49 51 51 51 52 52 52
SIZE
A (5) mm 2195 2195 2745 2745 2745 2745 3245 3245 3245
B (5) mm 1120 1120 1120 1120 1120 1120 1120 1120 1120
H (5) mm 1420 1420 1420 1620 1620 1620 1620 1620 1620
Operating weight (5) kg * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0202T-0612T
Switchboard side mm 600
Switchboard opposite side mm 600
Condensation coil side mm 1000

153
Hydronic - reversible

NECS-N 1314÷3218
Versions
B base version
SL super-low noise version
CA Class A of efficiency

Configurations
- base function
D partial condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS-N
represents the best choice for all the hydronic application
on the residential, commercial and industrial markets.
ELECTRONIC EXPANSION VALVE SUPPLIED
STANDARD
The use of the electronic expansion valve generates
considerable benefits, especially in cases of variable
Reversible unit, air source for outdoor demand and different external conditions. It was
introduced into these units as a result of accurate
installation design choices concerning the cooling circuit and the
optimisation of operation in various different working
339 - 898 kW conditions
CLASS A EFFICIENCY
Unit Description The full range is also available with the Class A efficiency
Outdoor heat pump for the production of chilled/hot water with hermetic rotary Scroll rating. NECS-N/CA guaranties premium levels of
compressors, ozone-friendly refrigerant R410A, axial-flow fans, shell and tubes exchanger efficiency thanks to the generous sizing of the refrigerant-
and electronic expansion valve. The range is composed by units equipped with four, six and exchange surface areas and to an accurate control of the
eight compressors in multi-circuit configuration. fans.
INTEGRATED HYDRONIC MODULE
Commands The incorporated hydronic unit already contains the
main water circuit components; it is available in various
W3000SE Compact
The W3000SE Compact controller offers advanced functions and algorithms. The keypad features an easy-to-use interface configurations with one or two pumps with high or low
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable head and the buffer tank
language setting. The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics,
beneficial in low water content systems. As alternatives the proportional- or proportional-integral regulations are also
available. The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions for
enhanced analysis of the unit operation. For multiple units systems, the regulation of the resources, via optional proprietary
devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed. Supervision can
Main accessories
be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols UÊSoft starters
as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units.
UÊSet-up for remote connectivity with ModBus, Echelon
Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a
proprietary self-adaptive logic, which features the monitoring of numerous operational parameters. This allows to reduce the LonTalk, Bacnet protocol board
number and duration of the defrost cycles, with a benefit for the overall energy efficiency. UÊRemote keyboard (distance to 200m and to 500m)
UÊLT kit for extending the operating limits in heat pump
mode down to -10°C (/SL versions) and -12°C (/CA
versions)

154
ENERGY CLASS SHELL & TUBES AXIAL SCROLL HEATING COOLING

NECS-N / B
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 340 364 396 434 478 524 546 594 637 678 728 761 792
Total power input (1) kW 114 120 139 150 160 173 180 209 213 229 240 259 279
EER 2,60 2,76 2,62 2,64 2,69 2,74 2,76 2,62 2,69 2,68 2,76 2,69 2,62
ESEER 3,80 3,88 3,79 3,88 3,78 3,89 3,91 3,77 3,78 3,83 3,92 3,88 3,78
HEATING ONLY
Heating capacity (2) kW 371 398 436 474 515 572 597 654 686 742 796 834 871
Total power input (2) kW 110 118 131 142 153 169 176 196 203 221 235 248 262
COP 3,03 3,07 3,05 3,04 3,02 3,06 3,08 3,05 3,02 3,03 3,08 3,07 3,05
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (3) dB(A) 96 96 96 96 97 97 97 98 98 98 99 99 99
Sound pressure (4) dB(A) 64 64 64 64 65 65 65 66 65 65 66 66 66
SIZE
A (5) mm 3905 3905 3905 4515 5690 5690 5690 5690 7430 7430 7430 7430 7430
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (5) kg 3170 3250 3280 4220 4610 4740 4810 4860 5950 6080 6230 6260 6300
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

NECS-N / SL
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 320 343 383 413 444 493 516 574 593 638 688 726 765
Total power input (1) kW 131 138 154 170 185 199 207 232 247 262 276 293 309
EER 2,44 2,49 2,48 2,42 2,40 2,47 2,49 2,48 2,40 2,43 2,49 2,48 2,48
ESEER 3,99 4 3,97 4,05 3,99 4,07 4,06 3,95 4 4,05 4,06 4,06 3,96
HEATING ONLY
Heating capacity (2) kW 368 390 442 474 513 564 586 663 684 736 781 838 884
Total power input (2) kW 117 125 139 152 164 180 187 209 219 235 250 264 278
COP 3,14 3,12 3,18 3,11 3,12 3,14 3,12 3,17 3,12 3,14 3,13 3,17 3,17
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (3) dB(A) 88 88 88 89 89 90 90 91 91 91 92 92 92
Sound pressure (4) dB(A) 56 56 56 57 57 57 57 58 58 58 59 59 59
SIZE
A (5) mm 4515 5080 5080 5690 5690 6865 7430 7430 7430 8605 9780 9780 9780
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (5) kg 3400 3530 3680 4720 4860 5160 5270 5500 6280 6580 6830 6990 7140

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

155
NECS-N / CA
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 352 372 417 453 504 538 559 625 667 710 745 789 833
Total power input (1) kW 121 128 143 155 173 185 192 215 228 242 256 270 287
EER 2,90 2,91 2,91 2,91 2,92 2,91 2,92 2,91 2,92 2,93 2,92 2,92 2,91
ESEER 4,12 4,20 4,07 4,19 4,08 4,18 4,17 4,09 4,09 4,14 4,18 4,17 4,09
HEATING ONLY
Heating capacity (2) kW 383 409 449 497 533 586 614 674 708 766 819 860 898
Total power input (2) kW 119 128 140 155 166 183 191 210 221 239 255 269 280
COP 3,21 3,20 3,21 3,21 3,21 3,21 3,21 3,21 3,20 3,20 3,21 3,20 3,21
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (3) dB(A) 97 97 97 97 98 98 98 99 99 99 100 100 100
Sound pressure (4) dB(A) 65 65 65 65 66 66 66 67 66 66 67 67 67
SIZE
A (5) mm 5080 5080 5080 6255 7430 7430 7430 7430 9780 9780 9780 9780 9780
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (5) kg 3490 3580 3610 4840 5120 5270 5350 5400 6610 6760 6940 6970 7000

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1314-3218
Switchboard side mm 1500
Switchboard opposite side mm 1500 H
Plant exchagers opposite side mm 1500
Plant exchagers side mm 2000

B A

156
157
Hydronic - reversible

NECS-ST-N 0504÷1204
Versions
B base version
HL low noise, high efficiency, high outdoor
temperature version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta is the only company offering units with Scroll
compressors in 5 versions and 2 different configurations
designed to satisfy all service system and application
requirements

Reversible unit, air source for outdoor SHELL AND TUBES EXCHANGER
The shell and tube exchanger allows to achieve the
installation highest flexibility on the units installation, keeping the
efficiency at the maximum level. For this reason, NECS-N
represents the best choice for all the hydronic application
103 - 322 kW on the residential, commercial and industrial markets.
INTEGRATED HYDRONIC MODULE
Unit Description The built-in hydronic module already contains the main
Outdoor reversible heat pump for the production of chilled/hot water with hermetic rotary water circuit components; it is available with single or twin
Scroll compressors, axial-flow fans, shell and tubes exchanger and thermostatic expansion in-line, for achieving both low or high head.
valve. External panels in Peraluman and structure in aluminium sections. The range is
equipped with four compressors on two circuits.

Main accessories
Commands UÊSet-up for remote connectivity with ModBus/Echelon/
W3000SE Compact Bacnet protocol cards
The W3000SE Compact controller offers advanced functions and algorithms. The keypad features an easy-to-use interface UÊRemote keyboard (distance to 200m and to 500m)
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, UÊSoft starters
beneficial in low water content systems. As alternatives the proportional- or proportional-integral regulations are also
available. The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions for
UÊLT kit for working down to -10°C in heat pump mode
enhanced analysis of the unit operation. For multiple units systems, the regulation of the resources, via optional proprietary UÊRubber anti-vibration mounting kit. Spring anti-vibration
devices, can be implemented. Energy metering, for both consumption and capacity, can also be developed. Supervision can mounting kit
be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols
as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units.
Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a
proprietary self-adaptive logic, which features the monitoring of numerous operational parameters. This allows to reduce the
number and duration of the defrost cycles, with a benefit for the overall energy efficiency.

158
r HFC
R-410A
SHELL & TUBES AXIAL SCROLL HEATING COOLING

NECS-ST-N / B
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 111 129 147 166 189 211 240 277 311
Total power input (1) kW 43,7 54 60 68,9 75,9 85,1 95,6 107 120
EER 2,54 2,39 2,45 2,41 2,49 2,48 2,51 2,58 2,58
ESEER 3,99 3,39 3,57 3,64 3,80 3,88 3,68 3,84 3,93
HEATING ONLY
Heating capacity (2) kW 127 145 167 185 209 234 267 306 344
Total power input (2) kW 43,6 52,7 58 64,7 72,1 79,9 92,1 104 116
COP 2,91 2,75 2,88 2,86 2,90 2,93 2,90 2,94 2,96
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 116 134 152 172 196 219 249 287 322
Total power input (3) kW 42,5 52,4 58,1 66,8 73,4 82,5 92,7 104 117
Desuperheater heating capacity (3) kW 35,4 40,7 46 54 60,1 68,6 74,1 84,6 96,3
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 91 92 92 92 92 93 94 95 95
Sound pressure (5) dB(A) 59 60 60 60 60 61 62 63 63
SIZE
A (6) mm 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1380 1570 1750 1900 2080 2270 2410 2540 2700
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-ST-N / HL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 113 129 142 163 190 209 236 273 307
Total power input (1) kW 43,8 51 58,9 67,4 73,9 84,6 92,6 103 119
EER 2,58 2,53 2,41 2,42 2,57 2,47 2,55 2,63 2,57
ESEER 3,75 3,81 3,78 3,91 3,79 3,81 3,92 4,11 3,91
HEATING ONLY
Heating capacity (2) kW 128 144 159 181 211 233 261 303 340
Total power input (2) kW 44,3 49,2 53,9 60,9 71 78,7 86,4 98,7 112
COP 2,89 2,93 2,95 2,97 2,97 2,96 3,02 3,07 3,01
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 117 133 148 169 197 217 245 283 318
Total power input (3) kW 42,3 49,1 57,1 64,9 71,6 82,2 89,4 101 116
Desuperheater heating capacity (3) kW 34,7 41 48,3 55,6 59,6 69,4 76 86,4 98,1
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 86 86 86 86 88 88 88 90 91
Sound pressure (5) dB(A) 54 54 54 54 56 56 56 58 59
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1840 1980 2310 2370 2520 2800 2940

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

159
NECS-ST-N / HT
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 117 134 149 172 198 219 248 287 322
Total power input (1) kW 45,5 51,3 58,4 65,7 75,3 84,9 91,5 102 118
EER 2,57 2,61 2,55 2,62 2,63 2,58 2,71 2,79 2,71
ESEER 3,42 3,53 3,64 3,77 3,57 3,60 3,82 3,98 3,80
HEATING ONLY
Heating capacity (2) kW 134 150 167 191 220 244 274 315 357
Total power input (2) kW 48,2 53 58 65,2 76,9 84,7 92,3 104 121
COP 2,78 2,83 2,88 2,93 2,86 2,88 2,97 3,02 2,95
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 121 139 155 178 205 228 257 297 334
Total power input (3) kW 44,1 49,8 56,8 63,7 73,1 82,7 88,9 99,6 115
Desuperheater heating capacity (3) kW 33 38,3 44,8 51,1 56 64,8 70,6 80,5 91,2
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 92 92 92 92 94 94 94 97 97
Sound pressure (5) dB(A) 60 60 60 60 62 62 62 64 65
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1840 1980 2310 2370 2520 2800 2940
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-ST-N / LN
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 103 123 141 156 177 199 227 261 291
Total power input (1) kW 46,2 53,5 60 70,3 78,3 87,7 96,2 110 125
EER 2,23 2,30 2,35 2,22 2,26 2,27 2,36 2,37 2,32
ESEER 3,89 3,66 3,74 3,78 3,77 3,89 3,76 3,92 3,86
HEATING ONLY
Heating capacity (2) kW 122 138 158 176 198 225 254 290 324
Total power input (2) kW 41,5 48,9 53,7 60,7 67,8 75,5 86,1 98 110
COP 2,94 2,82 2,94 2,90 2,92 2,98 2,95 2,96 2,94
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 107 128 146 162 184 207 236 270 302
Total power input (3) kW 44,7 51,8 58 68,2 75,9 84,9 93,4 107 121
Desuperheater heating capacity (3) kW 39,2 43,5 49,2 58,7 65,7 74,1 79,7 92 105
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 85 86 86 86 86 87 88 89 89
Sound pressure (5) dB(A) 53 54 54 54 54 55 56 57 57
SIZE
A (6) mm 3110 3110 3110 3110 3110 4110 4110 4110 4110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 1700 1700 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1380 1570 1750 1900 2080 2270 2410 2540 2700

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

160
NECS-ST-N / SL
Models 0504 0524 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 108 124 141 159 183 201 225 261 294
Total power input (1) kW 45 52,1 58,3 67,7 75,3 87,4 95,3 108 123
EER 2,40 2,38 2,42 2,35 2,43 2,30 2,36 2,41 2,38
ESEER 3,84 3,93 3,98 4,05 3,87 3,88 3,93 4,13 3,93
HEATING ONLY
Heating capacity (2) kW 125 140 158 178 205 226 253 295 330
Total power input (2) kW 42,8 47,5 52,2 59,5 68,6 76,1 83,8 96,1 110
COP 2,92 2,95 3,03 2,99 2,99 2,97 3,02 3,07 3
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 112 128 146 165 190 208 234 271 305
Total power input (3) kW 43,5 50,3 56,3 65,4 73 84,4 92,3 105 119
Desuperheater heating capacity (3) kW 37 43,3 48,9 57,3 62,7 73,3 80,6 92 104
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 82 82 82 82 83 83 83 85 86
Sound pressure (5) dB(A) 50 50 50 50 51 51 51 53 54
SIZE
A (6) mm 3110 3110 3110 3110 4110 4110 4110 5110 5110
B (6) mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1700 2150 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1460 1700 1900 2050 2310 2370 2520 2800 2940
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0504-1204
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

A
B

161
Hydronic - reversible

RECS 1052÷1952
Versions
B base version
LN low noise version
LT low outdoor temperature version
SL super-low noise version

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C in summer and down to -10°C in winter with
LT version
HOT WATER SUPPLY
Supply of hot water in use up to 55°C, offering maximum
versatility with respect to different plant engineering
solutions
STANDARD WATER PUMP
Standard water pump with pump unit options and
possible storage tank: 1 or 2 pumps, 2 or 4-pole motor,
for high or low head

Main accessories
Reversible unit, air source for outdoor UÊCompressor power factor device
UÊElectronic expansion valve
installation UÊVariable speed condensation control (standard on /LN,
/SL)
195 - 385 kW UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
Unit Description LonTalk, Bacnet protocol board
Outdoor unit in heat pump mode for the production of chilled/hot water with semi-hermetic
screw compressors optimized for R134a, axial-flow fans, condensing coil with copper tubes
and aluminium fins, plate heat exchanger and thermostatic expansion valve. Frame with
base in polyester-painted thick hot-galvanised sheet steel and external panels in peraluman.
Flexible and reliable unit; it easily adapts itself to different thermal load conditions thanks to the
precise thermoregulation.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation features the continuous modulation of capacity, based on a dynamic dead band and referring to the
leaving water temperature. As alternative, step-wise regulation is also available, referred to the return water temperature
with selectable proportional- or proportional-integral logic. The diagnostics includes a complete alarm management, with
the “black-box” and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the
regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and
capacity, can also be developed. Supervision can be easily developed via proprietary devices or the integration in third party
systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility
with the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

162
r HFC
R-134a
PLATES AXIAL SCREW HEATING COOLING

RECS / B
Models 1052 1152 1352 1552 1752 1952
COOLING ONLY
Cooling capacity (1) kW 195 238 276 307 359 385
Total power input (1) kW 73,9 95,6 109 113 138 154
EER 2,64 2,49 2,53 2,70 2,59 2,49
ESEER 3,43 3,13 3,25 3,49 3,31 3,34
HEATING ONLY
Heating capacity (2) kW 212 259 301 332 389 418
Total power input (2) kW 70 89,6 102 107 130 140
COP 3,03 2,89 2,94 3,08 2,97 2,97
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 96 97 97 98 98 98
Sound pressure (4) dB(A) 64 65 65 66 66 66
SIZE
A (5) mm 4610 4610 4610 5610 5610 5610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2150 2420 2430 2430 2430
Operating weight (5) kg 2910 3450 3590 3860 4100 4170
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

RECS / LN
Models 1052 1152 1352 1552 1752 1952
COOLING ONLY
Cooling capacity (1) kW 189 229 266 298 346 371
Total power input (1) kW 74,7 96,2 112 115 141 158
EER 2,53 2,38 2,37 2,59 2,45 2,34
ESEER 3,61 3,26 3,37 3,68 3,46 3,48
HEATING ONLY
Heating capacity (2) kW 205 247 289 322 374 401
Total power input (2) kW 65,9 83,2 96 101 123 132
COP 3,11 2,97 3,01 3,17 3,04 3,03
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 90 91 91 92 92 92
Sound pressure (4) dB(A) 58 59 59 60 60 60
SIZE
A (5) mm 4610 4610 4610 5610 5610 5610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2150 2420 2430 2430 2430
Operating weight (5) kg 2910 3450 3590 3860 4100 4170
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

163
RECS / LT
Models 1052 1152 1352 1552 1752 1952
COOLING ONLY
Cooling capacity (1) kW 200 248 289 313 372 399
Total power input (1) kW 74,7 88,6 103 113 133 147
EER 2,69 2,80 2,78 2,77 2,79 2,70
ESEER 3,19 3,38 3,25 3,36 3,32 3,34
HEATING ONLY
Heating capacity (2) kW 220 272 318 342 406 438
Total power input (2) kW 74,6 90,7 107 112 136 146
COP 2,95 3,00 2,96 3,04 2,98 2,99
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 97 97 97 98 99 99
Sound pressure (4) dB(A) 65 65 65 66 66 66
SIZE
A (5) mm 4610 5610 5610 5610 6610 6610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2430 2430 2430 2430 2430
Operating weight (5) kg 3010 3790 3930 3960 4650 4720

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

RECS / SL
Models 1052 1152 1352 1552 1752 1952
COOLING ONLY
Cooling capacity (1) kW 190 228 266 298 333 378
Total power input (1) kW 74,5 95,4 110 115 148 152
EER 2,55 2,39 2,40 2,57 2,24 2,48
ESEER 3,59 3,38 3,50 3,69 3,38 3,63
HEATING ONLY
Heating capacity (2) kW 206 249 294 322 363 412
Total power input (2) kW 66,5 81,9 94,8 101 119 132
COP 3,10 3,04 3,10 3,17 3,03 3,11
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 86 87 87 88 88 88
Sound pressure (4) dB(A) 54 55 55 56 56 55
SIZE
A (5) mm 4610 4610 5610 5610 5610 6610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2420 2430 2430 2430 2430
Operating weight (5) kg 3010 3550 3830 3960 4100 4720

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1052-1952
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

164
165
Hydronic - reversible

RECS 1062÷1962
Versions
B base version
LN low noise version
LT low outdoor temperature version
SL super-low noise version

Configurations
- base function
D partial condensing heat recovery function

Features
FLEXIBILITY
Flexibility in applications thanks to the many available
functions and versions
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C in summer and down to -10°C in winter with
LT version
HOT WATER SUPPLY
Supply of hot water in use up to 55°C, offering maximum
versatility with respect to different plant engineering
solutions

Reversible unit, air source for outdoor Main accessories


installation UÊRemote keyboard (distance to 200m and to 500m)
UÊCompressor power factor device

195 - 385 kW UÊElectronic expansion valve


UÊVariable speed condensation control (standard on /LN,
Unit Description /SL)
Outdoor heat pump unit for the production of chilled/hot water with semi-hermetic screw UÊSet-up for remote connectivity with ModBus, Echelon
compressors optimized for R134a, axial-flow fans, external coil with copper tubes and LonTalk, Bacnet protocol board
aluminium fines, shell and tubes heat exchangers designed by Climaveneta and thermostatic
expansion valve. Base and supporting structure and panels are galvanized epoxy powder
coated steel with increased thickness. These units are designed for two-pipes systems and
are able to produce hot or cold water according to the selected operation mode; the precise
thermoregulation guarantees an optimal response to load´s changes, in every operating
conditions.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation features the continuous modulation of capacity, based on a dynamic dead band and referring to the
leaving water temperature. As alternative, step-wise regulation is also available, referred to the return water temperature
with selectable proportional- or proportional-integral logic. The diagnostics includes a complete alarm management, with
the “black-box” and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the
regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and
capacity, can also be developed. Supervision can be easily developed via proprietary devices or the integration in third party
systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility
with the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

166
r HFC
R-134a
SHELL & TUBES AXIAL SCREW HEATING COOLING

RECS / B
Models 1062 1162 1362 1562 1762 1962
COOLING ONLY
Cooling capacity (1) kW 195 238 276 307 359 385
Total power input (1) kW 73,9 95,6 109 113 138 154
EER 2,64 2,49 2,53 2,70 2,59 2,49
ESEER 3,43 3,13 3,25 3,49 3,31 3,34
HEATING ONLY
Heating capacity (2) kW 212 259 301 332 389 418
Total power input (2) kW 70 89,6 102 107 130 140
COP 3,03 2,89 2,94 3,08 2,97 2,97
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 96 97 97 98 98 98
Sound pressure (4) dB(A) 64 65 65 66 66 66
SIZE
A (5) mm 4610 4610 4610 5610 5610 5610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2150 2420 2430 2430 2430
Operating weight (5) kg 2960 3470 3860 4140 4340 4640
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

RECS / LN
Models 1062 1162 1362 1562 1762 1962
COOLING ONLY
Cooling capacity (1) kW 189 229 266 298 346 371
Total power input (1) kW 74,8 96,3 112 115 141 158
EER 2,53 2,38 2,37 2,59 2,45 2,34
ESEER 3,61 3,26 3,37 3,68 3,46 3,48
HEATING ONLY
Heating capacity (2) kW 205 247 289 322 374 401
Total power input (2) kW 65,9 83,4 96,1 102 123 132
COP 3,11 2,97 3,01 3,17 3,04 3,03
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 90 91 91 92 92 92
Sound pressure (4) dB(A) 58 59 59 60 60 60
SIZE
A (5) mm 4610 4610 4610 5610 5610 5610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2150 2420 2430 2430 2430
Operating weight (5) kg 2960 3470 3860 4140 4340 4640

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

167
RECS / LT
Models 1062 1162 1362 1562 1762 1962
COOLING ONLY
Cooling capacity (1) kW 200 248 289 313 372 399
Total power input (1) kW 74,5 88,7 104 113 134 148
EER 2,68 2,80 2,78 2,77 2,78 2,70
ESEER 3,19 3,38 3,25 3,36 3,32 3,34
HEATING ONLY
Heating capacity (2) kW 220 272 318 342 406 438
Total power input (2) kW 74,6 90,5 108 112 136 147
COP 2,95 3,01 2,94 3,05 2,99 2,98
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 97 97 97 98 99 99
Sound pressure (4) dB(A) 65 65 65 66 66 66
SIZE
A (5) mm 4610 5610 5610 5610 6610 6610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2430 2430 2430 2430 2430
Operating weight (5) kg 3060 3840 4230 4240 4910 5210
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

RECS / SL
Models 1062 1162 1362 1562 1762 1962
COOLING ONLY
Cooling capacity (1) kW 190 228 266 298 333 378
Total power input (1) kW 74,4 95,2 111 116 149 152
EER 2,55 2,39 2,40 2,57 2,23 2,49
ESEER 3,59 3,38 3,50 3,69 3,38 3,63
HEATING ONLY
Heating capacity (2) kW 206 249 294 322 363 412
Total power input (2) kW 66,5 81,7 94,7 102 120 133
COP 3,10 3,05 3,10 3,16 3,02 3,10
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 86 87 87 88 88 88
Sound pressure (4) dB(A) 54 55 55 56 56 55
SIZE
A (5) mm 4610 4610 5610 5610 5610 6610
B (5) mm 2220 2220 2220 2220 2220 2220
H (5) mm 2150 2420 2430 2430 2430 2430
Operating weight (5) kg 3060 3570 4130 4240 4340 5210
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1062-1962
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

168
169
Hydronic - reversible

FOCS-N 2022÷4822
Versions
B base version
CA Class A of efficiency
LN-CA Low Noise, Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency

Configurations
- base function
D partial condensing heat recovery function

Features
HIGH EFFICIENCY
Unit in Class A as per Eurovent. High efficiency for low
energy consumption during the operating hours
COMPACTNESS
Reduced dimensions, for easy installation even in sites
with space´ constraints
EXTENSIVE RANGE OF OPERATION
Unit´s operation guaranteed with external air temperature
down to -10°C during winter and up to 46°C during
summer.
HOT WATER SUPPLY
Reversible unit, air source for outdoor Supply of hot water in use up to 55°C, offering maximum
versatility with respect to different plant engineering
installation solutions

441 - 1162 kW Main accessories


UÊHydronic group
Unit Description UÊVPF (Variable Primary Flow) kit: variable flow pumps with
Outdoor heat pump unit for the production of chilled/hot water with semi-hermetic screw on board regulation
compressors optimized for R134a, axial-flow fans, external coil with copper tubes and UÊElectronic expansion valve
aluminium fines, shell and tubes heat exchangers designed by Climaveneta and thermostatic UÊSet-up for remote connectivity with ModBus/Echelon/
expansion valve. Base and supporting structure and panels are galvanized epoxy powder Bacnet protocol cards
coated steel with increased thickness. These units are designed for two-pipes systems and
are able to produce hot or cold water according to the selected operation mode; the precise
thermoregulation guarantees an optimal response to load´s changes, in every operating
conditions.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation features the continuous modulation of capacity, based on a dynamic dead band and referring to the
leaving water temperature. As alternative, step-wise regulation is also available, referred to the return water temperature
with selectable proportional- or proportional-integral logic. The diagnostics includes a complete alarm management, with
the “black-box” and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the
regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and
capacity, can also be developed. Supervision can be easily developed via proprietary devices or the integration in third party
systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility
with the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

170
r HFC
R-134a
ENERGY CLASS SHELL & TUBES AXIAL SCREW HEATING COOLING

FOCS-N / B
Models 2022 2222 2422 2622 2722 3222 3622 4222 4822
COOLING ONLY
Cooling capacity (1) kW 450 494 531 572 663 791 916 1028 1146
Total power input (1) kW 163 177 187 209 229 273 299 343 389
EER 2,76 2,79 2,84 2,74 2,90 2,90 3,06 3,00 2,95
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 479 524 566 600 698 823 946 1072 1195
Total power input (2) kW 152 166 178 188 215 252 283 322 363
COP 3,15 3,16 3,18 3,19 3,25 3,27 3,34 3,33 3,29
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 99 101 101 101 101 102 102 104 104
Sound pressure (4) dB(A) 67 69 69 69 69 70 70 72 72
SIZE
A (5) mm 4900 5800 5800 5800 7000 7900 10000 10000 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (5) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

FOCS-N / CA
Models 2022 2222 2422 2622 2722 3222 3622 4222 4822
COOLING ONLY
Cooling capacity (1) kW 459 503 538 586 672 803 928 1041 1162
Total power input (1) kW 158 170 181 202 222 264 291 343 378
EER 2,91 2,96 2,97 2,90 3,03 3,04 3,19 3,03 3,07
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 470 520 553 590 683 804 923 1051 1166
Total power input (2) kW 143 156 167 177 202 238 265 309 341
COP 3,29 3,33 3,31 3,33 3,38 3,38 3,48 3,40 3,42
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 99 101 101 101 101 102 102 104 104
Sound pressure (4) dB(A) 67 69 69 69 69 70 70 72 72
SIZE
A (5) mm 4900 5800 5800 5800 7000 7900 10000 11800 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (5) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

171
FOCS-N / LN-CA
Models 2022 2222 2422 2622 2722 3222 3622 4222 4822
COOLING ONLY
Cooling capacity (1) kW 444 492 524 564 654 780 904 1013 1130
Total power input (1) kW 160 169 182 205 224 267 290 342 380
EER 2,78 2,91 2,88 2,75 2,92 2,92 3,12 2,96 2,97
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 467 520 553 586 683 804 923 1051 1166
Total power input (2) kW 143 156 167 177 202 238 265 309 341
COP 3,27 3,33 3,31 3,31 3,38 3,38 3,48 3,40 3,42
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 93 95 95 95 95 96 96 98 98
Sound pressure (4) dB(A) 61 63 63 63 63 64 64 66 66
SIZE
A (5) mm 4900 5800 5800 5800 7000 7900 10000 10000 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (5) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

FOCS-N / SL-CA
Models 2022 2222 2422 2622 2722 3222 3622 4222 4822
COOLING ONLY
Cooling capacity (1) kW 441 488 520 559 649 772 895 1004 1119
Total power input (1) kW 163 172 185 209 227 271 293 346 385
EER 2,71 2,84 2,81 2,67 2,86 2,85 3,05 2,90 2,91
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 461 514 546 578 674 794 911 1039 1151
Total power input (2) kW 142 155 166 175 200 235 262 305 338
COP 3,25 3,32 3,29 3,30 3,37 3,38 3,48 3,41 3,41
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 89 91 91 91 91 92 92 94 94
Sound pressure (4) dB(A) 57 59 59 59 59 60 60 62 62
SIZE
A (5) mm 4900 5800 5800 5800 7000 7900 10000 11800 11800
B (5) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (5) mm 2430 2430 2430 2430 2430 2430 2430 2430 2430
Operating weight (5) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


2022-4822
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

172
173
Hydronic - reversible

NECS-CN 0152÷1204
Versions
B base version

Configurations
- base function
D partial condensing heat recovery function

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
The NECS-CN units are available with both vertical and
horizontal air outflow. The horizontal outflow version is
particularly effective in installations where the height of
the technical compartment does not allow the traditional
vertical outflow
HIGH PERFORMANCE CENTRIFUGAL FANS
The units are fitted with statically and dynamically
balanced double-inlet centrifugal fans coupled by belt and
pulleys. Useful static pressure up to 180 Pa.
INTEGRATED HYDRONIC MODULE
The built-in hydronic module includes the main water
Reversible unit, air source for indoor circuit components; it is available in various configurations
with one or two pumps with high or low head.
installation
36,0 - 303 kW Main accessories
UÊSet-up for remote connectivity with ModBus/Echelon/
Unit Description Bacnet protocol cards
Indoor unit with heat pump for the production of chilled/hot water with hermetic rotary Scroll
UÊRemote keyboard (distance to 200m and to 500m)
compressors, centrifugal fans, braze-welded plate-type exchanger and thermal expansion
valve. External panels in pre-clad sheet steel (simil Pereluman) and base in galvanised steel UÊSoft starters
with paint finish. The range includes the single-circuit two-compressor versions and the dual UÊHorizontal or vertical air outflow
circuit four-compressor versions. UÊRubber anti-vibration mounting kit

Commands
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

174
r HFC
R-410A
PLATES CENTRIFUGAL SCROLL HEATING COOLING

NECS-CN / B
Models 0152 0182 0202 0252 0302 0352 0412 0452 0512
COOLING ONLY
Cooling capacity (1) kW 36,0 42,0 49,0 55,0 73,0 84,0 95,0 107 119
Total power input (1) kW 15,0 17,0 20,0 22,0 31,0 35,0 39,0 44,0 50,0
EER 2,76 2,78 2,75 2,70 2,62 2,65 2,66 2,66 2,61
ESEER 4,65 4,48 4,48 4,36 3,85 3,95 3,92 3,98 3,74
HEATING ONLY
Heating capacity (2) kW 42,0 48,0 56,0 64,0 82,0 95,0 107 122 135
Total power input (2) kW 15,0 17,0 19,0 22,0 30,0 34,0 38,0 42,0 47,0
COP 3,24 3,22 3,21 3,15 3,08 3,11 3,12 3,16 3,10
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 37,8 43,9 50,9 57,4 75,7 87,3 98,5 111 124
Total power input (3) kW 14,4 16,6 19,1 21,7 30,3 34,0 37,9 42,5 48,0
Desuperheater heating capacity (3) kW 11,9 13,3 15,7 17,9 23,2 26,4 29,8 33,6 37,4
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
FANS
Fan air flow m3/h 15012 16992 16992 16992 29988 29988 29988 32004 34992
Max AESP (4) Pa 120 120 120 120 120 120 120 120 120
NOISE LEVELS
Sound power (5) dB(A) 81 83 83 83 90 90 90 92 94
SIZE
A (6) mm 2200 2200 2200 2200 2602 2602 2602 3602 3602
B (6) mm 920 920 920 920 1104 1104 1104 1104 1104
H (6) mm 1642 1642 1642 1642 1927 1927 1927 1927 1927
Operating weight (6) kg 720 730 750 790 1080 1170 1230 1470 1490

Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 137 154 146 164 187 213 237 274 303
Total power input (1) kW 58,0 64,0 60,0 72,0 79,0 87,0 100 113 131
EER 2,60 2,61 2,64 2,47 2,59 2,64 2,57 2,64 2,50
ESEER 3,81 3,76 3,90 3,71 3,88 4,00 3,62 3,70 3,60
HEATING ONLY
Heating capacity (2) kW 153 173 165 185 208 235 261 302 336
Total power input (2) kW 55,0 62,0 58,0 66,0 74,0 83,0 94,0 108 122
COP 3,06 3,06 3,12 3,03 3,06 3,09 3,01 3,06 2,97
COOLING WITH PARTIAL RECOVERY
Cooling capacity (3) kW 142 160 152 170 194 221 246 284 315
Total power input (3) kW 56,2 62,5 58,5 69,5 76,6 84,5 96,9 109 127
Desuperheater heating capacity (3) kW 43,1 48,7 46,4 55,1 60,9 67,8 75,6 85,9 99,7
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
FANS
Fan air flow m3/h 47988 47988 45000 47988 60012 60012 68004 79992 84996
Max AESP (4) Pa 120 120 120 120 120 120 120 120 120
NOISE LEVELS
Sound power (5) dB(A) 94 94 92 94 94 94 96 96 97
SIZE
A (6) mm 3602 3602 3602 3602 4602 4602 4602 5602 5602
B (6) mm 1104 1104 1277 1277 1277 1277 1277 1277 1277
H (6) mm 1927 1927 1900 1900 2235 2235 2235 2235 2235
Operating weight (6) kg 1600 1660 1980 2055 2475 2630 2725 3145 3205
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C. Desuperheater water (in/out) = 40/45°C.
4 Useful pressure to be specified at the time of placing the order.
5 Total sound power of the fans as declared by the manufacturer referred to nominal speed of rotation and useful static head of 120 Pa on delivery side.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-1204
Switchboard side mm 1000
Switchboard opposite side mm 1000
Condensation coil side mm 2000

A
B

175
Hydronic - reversible

NECS-WN 0152÷1204
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
TOTAL VERSATILITY
Climaveneta has designed the NECS-W units with a
range of integral accessories in mind for operation with
total water loss (well, water bed, etc.), dry cooler or
cooling tower so as to satisfy all service system and
installation requirements.
INTEGRATED HYDRONIC MODULE ON COOLER/
CONDENSER SIDE
The built-in hydronic module includes the main water
circuit components; it is available in various configurations
with one or two pumps with high or low head both on the
evaporator and the condenser side.
INTEGRATED CONDENSATION´S CONTROL
The electronics of the units manages the most suitable
condensing control for each type of application: pressure-
controlled valve, two or three-way modulating valve and
inverter control for the pumps

Reversible unit, water source Main accessories


UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
UÊCondensing control device: two or three-way
43,4 - 371 kW modulating pressure-controlled valve and inverter on
pumps
Unit Description UÊWater connections directed upwards (for 2 compressors
Water-cooled indoor unit for the production of chilled/hot water with hermetic rotary Scroll units only)
compressors, braze-welded plate-type exchanger and thermal expansion valve. External UÊAcoustical enclosure to reduce the noise emissions.
panels in pre-clad sheet steel (simil-Peraluman) and structure in galvanised steel with paint UÊRubber anti-vibration mounting kit. Spring anti-vibration
finish. The range includes the single-circuit two-compressor versions and the dual circuit four- mounting kit (4 compressors models only)
compressor versions.

Commands
W3000 Base / W3000SE Compact
The controller can be chosen as: - W3000 Base: keypad and LED display - W3000SE Compact: the keypad features an
easy-to-use interface and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level
menu, with selectable language setting. The diagnostics includes a complete alarm management, with the “black-box” and
alarm logging functions for enhanced analysis of the unit operation. Compatibility with the remote keyboard managing up
to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour belts). Common
features: The regulation is based on the exclusive QuickMind algorithm, including self-adaptive control logics, beneficial in low
water content systems. As alternatives the proportional- or proportional-integral regulations are also available. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks.

176
r HFC
R-410A
PLATES SCROLL HEATING COOLING

NECS-WN / B
Models 0152 0182 0202 0252 0262 0302 0352 0412 0452 0512
COOLING ONLY
Cooling capacity (1) kW 43,4 50,1 58,9 66,4 72,6 86,7 101 115 129 144
Total power input (1) kW 10,0 11,3 13,0 15,2 16,6 19,5 22,7 25,9 28,9 32,2
Condernser heating capacity (1) 52,8 60,7 71,2 80,7 88,2 105 123 139 156 174
EER 4,34 4,43 4,53 4,37 4,37 4,45 4,46 4,43 4,45 4,46
ESEER 5,80 6,00 6,00 5,70 5,60 5,70 5,80 5,70 5,80 5,80
HEATING ONLY
Heating capacity (2) kW 50,5 58,2 68,0 77,0 85,0 101 117 132 148 165
Total power input (2) kW 12,9 14,3 16,7 19,2 21,1 24,7 28,7 32,2 36,0 40,0
COP (2) 3,91 4,07 4,07 4,01 4,03 4,09 4,07 4,10 4,12 4,14
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 73 74 74 74 75 76 77 77 78 78
Sound pressure (4) dB(A)
SIZE
A (5) mm 1055 1055 1055 1055 1055 1222 1222 1222 1222 1222
B (5) mm 649 649 649 649 649 843 843 843 843 843
H (5) mm 1255 1255 1255 1255 1255 1496 1496 1496 1496 1496
Operating weight (5) kg 290 305 315 325 330 585 605 660 685 740

Models 0552 0612 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 165 186 174 203 228 258 288 329 371
Total power input (1) kW 36,9 41,6 38,9 45,2 51,6 58,0 64,0 74,0 83,5
Condernser heating capacity (1) 200 225 211 245 276 312 348 398 450
EER 4,47 4,48 4,47 4,48 4,42 4,45 4,50 4,44 4,44
ESEER 5,90 5,80 5,80 5,90 5,80 5,90 5,90 6,00 5,90
HEATING ONLY
Heating capacity (2) kW 190 215 202 234 263 297 332 379 428
Total power input (2) kW 45,9 51,8 49,2 56,6 64,1 72,1 79,5 91,9 104
COP (2) 4,14 4,14 4,11 4,13 4,10 4,12 4,17 4,13 4,12
COMPRESSORS
No. Compressors/No. Circuits N. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 79 79 86 87 88 89 90 91 91
Sound pressure (4) dB(A)
SIZE
A (5) mm 1222 1222 2227 2227 2227 2227 2227 2227 2227
B (5) mm 873 873 877 877 877 877 877 877 877
H (5) mm 1496 1496 1780 1780 1780 1780 1780 1780 1780
Operating weight (5) kg 790 830 1090 1165 1245 1290 1395 1500 1585
Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
3 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
4 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-0612 0604-1204
Switchboard side mm 800 1000
Switchboard opposite side mm 600 1000
Unit's side mm 600 1000

H H

A
B B A

177
Hydronic - reversible

RECS-W 0802÷3202
Versions
B base version

Configurations
- base function
D partial condensing heat recovery function

Features
SILENT OPERATION
If compared to the solution of a water condensed unit
reversible on the hydronic side, these units allows a
reduction in the required technical space and, moreover,
an appreciable simplification in the plant´s design.
INTEGRATED CONDENSATION´S CONTROL
A 2 way valve is supplied as standard for the condensing
pressure control. For all the applications in which a
constant waterflow through the condenser is needed, a
3-way valve option is also available under request.
ADAPTABILITY
Adaptability at the buildings cooling request thanks to the
continuous capacity regulation, assured by sophisticated
controls logic
SILENT OPERATION
Extremely silent operation thanks to the accurate units
Reversible unit, water source design. Optional integral acoustic enclosure, reduces
more the sound level beyond the best on market

174 - 801 kW Main accessories


UÊIntegral acoustical enclosure (type base or plus)
Unit Description
Indoor heat pump unit for the production of chilled/hot water with semi-hermetic screw UÊElectronic expansion valve
compressors optimized for R134a, thermostatic expansion valve, shell and tube condenser UÊRemote keyboard
and evaporator. Base and supporting structure and panels are of galvanized epoxy UÊSet-up for remote connectivity with ModBus, Echelon
powder coated steel with increased thickness. Flexible and reliable unit; it easily adapts LonTalk, Trend, Bacnet protocol board.
itself to different thermal load conditions thanks to the precise thermoregulation. The high
performances level is achieved thanks to the accurate sizing of all internal components.

Commands
W3000SE Large
The W3000 SE Large controller offers advanced functions and algorithms. The keypad is generously sized with full operating
status display. The commands and detailed LCD display make access to the units settings easy and safe. These resources
allow to consult and intervene on the unit by means of a multi-level menu, with selectable language setting. The diagnostics
includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced analysis of the unit
operation. For multiple units systems, the regulation of the resources, via optional proprietary devices, can be implemented.
Energy metering, for both consumption and capacity, can also be developed. Supervision can be easily developed via
proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet,
Bacnet-over-IP, Echelon LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an
internal real time clock for operation scheduling (4-day profiles with 10 hour belts). The regulation features the continuous
modulation of capacity, based on a dynamic dead band and referring to the leaving water temperature. As alternative, step-
wise regulation is also available, referred to the return water temperature with selectable proportional- or proportional-integral
logic.

178
r HFC
R-134a
SHELL & TUBES SCREW HEATING COOLING

RECS-W / B
Models 0802 1002 1102 1302 1502 1702 1902 2152 2502 2602 2702 3202
COOLING ONLY
Cooling capacity (1) kW 174 213 246 292 334 379 429 499 583 631 703 800
Total power input (1) kW 39,3 49,2 55,8 65,6 75,2 88,5 98,9 109 128 137 154 176
Condernser heating capacity (1) 211 259 298 354 404 462 522 602 703 760 848 966
EER 4,43 4,33 4,41 4,46 4,44 4,28 4,34 4,57 4,57 4,61 4,56 4,55
ESEER 5,31 5,43 5,13 5,40 5,57 5,31 5,51 5,75 5,58 5,50 5,54 5,67
COOLING WITH PARTIAL RECOVERY (only -D)
Cooling capacity (2) kW 181 221 255 303 346 393 445 518 605 655 729 831
Total power input (2) kW 38 47 54 63 73 85 95 105 123 132 149 170
Desuperheater heating capacity (2) kW 17 21 24 28 32 38 43 47 55 59 67 76
HEATING ONLY
Heating capacity (3) kW 199 245 283 334 381 436 496 571 665 715 806 912
Total power input (3) kW 47,1 58,7 67,9 78,6 89,5 107 120 132 153 162 185 211
COP (3) 4,23 4,17 4,16 4,25 4,26 4,09 4,13 4,32 4,35 4,40 4,35 4,32
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 94 95 97 97 97 97 97 98 99 99 99 99
Sound pressure (5) dB(A) * * * * * * * * * * * *
SIZE
A (6) mm 3680 3680 3680 3680 3680 3680 3800 3800 3800 4800 4800 4800
B (6) mm 1170 1170 1170 1170 1170 1170 1240 1240 1240 1240 1240 1240
H (6) mm 1890 1890 1890 1890 1890 1890 1950 1950 1950 2050 2050 2050
Operating weight (6) kg 1990 2070 2490 2940 3020 3060 4080 4460 4840 5390 5490 6340

Note:
1 Evaporator water (in/out) = 12/7°C, condenser water (in/out) = 30/35°C, based on Eurovent Standard
2 Evaporator water (in/out): 12/7°C; Condenser water (in/out): 30/35°C; Desuperheater water (in/out): 40/45°C.
3 Evaporator water (in/out) = 12/7°C; Condenser water (in/out) = 40/45°C.
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Sound pressure in open field conditions on reflecting surface (directivity factor Q=2), average value on longest side, at 1 m from the outer surface and at 1 m height in relation to the unit supporting base.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0802-1702 1902-3202
Switchboard side mm 800 1500
Switchboard opposite side mm 0 0
Condensation coil side mm 0 0
Cooler water connections side
mm 500 900
(minimum)
Condenser water connections side mm 500 900
Condenser water fittings opposite
mm 500 900
side (minimum)

A
B

179
Hydronic - reversible

NECS-NR 0152÷1204
Versions
B base version
LN low noise version
SL super-low noise version

Features
TOTAL VERSATILITY
Unique proposal: unit designed to satisfy, according to
the mode of operation, requirements of cold water, hot
water for heating or hot water for domestic use
EXTENSIVE RANGE OF OPERATION
Extensive range of operation with external air temperature
up to 46°C in summer and down to -10°C in winter with
LT version
HOT WATER SUPPLY
Production of domestic hot water up to 52°C in both
summer and winter operating conditions, offering
maximum versatility with respect to different plant
engineering solutions
INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main
water circuit components; it is available with single or
twin in-line pump, for achieving both low or high head,
available for both plant and recovery circuits (up to 4
pumps).
Reversible unit, NRG line, total heat recovery,
Main accessories
air source for outdoor installation UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
36 - 311 kW UÊRemote keyboard (distance to 200m and to 500m)
UÊSoft starters
Unit Description
UÊRubber anti-vibration mounting kit
Air-cooled reversible unit with total heat recovery for the simultaneous production of chilled/
hot water with hermetic rotary Scroll compressors, with R410A, axial fans, braze-welded
plate-type exchanger and thermal expansion valve. External panels in Peraluman and base in
galvanised sheet steel with paint finish. The range includes the two-compressor and the four-
compressor versions, both with two circuits.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return water
temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and heating,
according to the selected operation mode. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with
the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

180
r HFC
R-410A
PLATES AXIAL SCROLL

NECS-NR / B
Models 0152 0182 0202 0252 0262 0302 0412 0512
COOLING ONLY
Cooling capacity (1) kW 36,6 43,2 48,5 55,8 61,2 73,3 94,8 120
Total power input (1) kW 13,3 14,5 17,9 19,9 22,8 26,2 33,6 41,7
EER 2,76 2,99 2,71 2,80 2,68 2,80 2,82 2,88
ESEER
HEATING ONLY
Heating capacity (2) kW 41,1 48,9 55,3 62,5 68,1 83,1 107 136
Total power input (2) kW 13,3 14,7 17,2 19,7 21,4 24,9 32,1 40
COP 3,10 3,33 3,22 3,17 3,18 3,34 3,34 3,40
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 37,2 43,6 50,6 57,2 64,1 76,3 97,7 124
Total power input (3) kW 12,8 14,2 16,6 18,9 21 24,5 31,9 39,6
Heat recovery capacity (3) kW 49,2 56,9 66,2 75 83,8 99,3 128 161
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 84 84 84 84 84 85 86 87
Sound pressure (5) dB(A) 52 52 52 52 52 53 54 55
SIZE
A (6) mm 2020 2020 2020 2520 2520 2520 3070 3570
B (6) mm 1300 1300 1300 1300 1300 1300 1300 1300
H (6) mm 1620 1620 1620 1620 1620 1620 1620 1620
Operating weight (6) kg 570 590 600 660 670 720 1030 1180

Models 0612 0604 0704 0804 0904 1004 1104 1204


COOLING ONLY
Cooling capacity (1) kW 151 150 166 189 211 240 277 311
Total power input (1) kW 56,6 58,9 69 75,8 85,2 95,6 107 121
EER 2,66 2,54 2,41 2,49 2,48 2,51 2,58 2,58
ESEER
HEATING ONLY
Heating capacity (2) kW 173 167 185 209 234 267 306 344
Total power input (2) kW 52,1 58 64,9 72,1 79,8 92 104 116
COP 3,31 2,88 2,86 2,90 2,93 2,90 2,94 2,96
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 160 151 173 194 220 246 281 317
Total power input (3) kW 51,3 198 226 255 288 321 368 415
Heat recovery capacity (3) kW 208 49,8 57,1 64,5 72,1 79,8 92,8 105
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 87 93 92 92 93 94 95 95
Sound pressure (5) dB(A) 55 60 60 60 61 62 63 63
SIZE
A (6) mm 3570 3110 3110 3110 4110 4110 4110 4110
B (6) mm 1300 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1290 1600 1840 2120 2320 2480 2680 2860

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

181
NECS-NR / LN
Models 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 143 157 177 199 227 261 291
Total power input (1) kW 58,8 70,2 78,4 87,8 96,5 110 125
EER 2,43 2,24 2,26 2,27 2,36 2,37 2,32
ESEER
HEATING ONLY
Heating capacity (2) kW 160 176 198 225 254 290 324
Total power input (2) kW 54 60,8 67,9 75,7 85,8 97,9 110
COP 2,95 2,89 2,92 2,98 2,95 2,96 2,94
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 151 173 194 220 246 281 317
Total power input (3) kW 198 226 255 288 321 368 415
Heat recovery capacity (3) kW 49,8 57,1 64,5 72,1 79,8 92,8 105
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 86 86 86 87 88 89 89
Sound pressure (5) dB(A) 54 54 54 55 56 57 57
SIZE
A (6) mm 3110 3110 3110 4110 4110 4110 4110
B (6) mm 2220 2220 2220 2220 2220 2220 2220
H (6) mm 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1600 1840 2120 2320 2480 2680 2860

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

182
NECS-NR / SL
Models 0152 0182 0202 0252 0262 0302 0412 0512
COOLING ONLY
Cooling capacity (1) kW 33,3 39,6 47 50,9 58,3 69,1 93,9 119
Total power input (1) kW 15 16,5 18,7 22,4 24,4 28,4 34,1 42,3
EER 2,21 2,39 2,52 2,28 2,39 2,43 2,75 2,81
ESEER
HEATING ONLY
Heating capacity (2) kW 40 47,4 55,1 60,9 70,5 80,9 109 138
Total power input (2) kW 13,1 14,6 17,2 19,7 21,5 24,8 32,2 40,1
COP 3,04 3,24 3,21 3,10 3,28 3,26 3,38 3,43
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 37,2 43,6 50,6 57,2 64,1 76,3 97,7 124
Total power input (3) kW 12,8 0 16,6 18,9 21 24,5 31,9 39,6
Heat recovery capacity (3) kW 49,2 56,9 66,2 74,9 83,8 99,3 128 161
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 78 78 79 79 79 80 82 83
Sound pressure (5) dB(A) 46 46 47 47 47 48 50 51
SIZE
A (6) mm 2020 2020 2520 2520 2520 3070 3070 3570
B (6) mm 1300 1300 1300 1300 1300 1300 1300 1300
H (6) mm 1620 1620 1620 1620 1620 1620 1620 1620
Operating weight (6) kg 570 590 660 660 700 780 1070 1230

Models 0612 0604 0704 0804 0904 1004 1104 1204


COOLING ONLY
Cooling capacity (1) kW 143 142 160 183 201 225 261 294
Total power input (1) kW 60,4 58 67,4 75,5 87,3 95,5 108 123
EER 2,37 2,45 2,37 2,43 2,30 2,36 2,41 2,38
ESEER
HEATING ONLY
Heating capacity (2) kW 169 159 178 205 226 253 295 330
Total power input (2) kW 52 52,6 59,5 68,7 76,1 83,8 96,1 110
COP 3,26 3,02 2,99 2,99 2,98 3,02 3,07 3
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 160 151 173 194 220 246 281 317
Total power input (3) kW 51,3 198 226 255 288 321 368 415
Heat recovery capacity (3) kW 208 49,8 57,1 64,5 72,1 79,8 92,8 105
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 83 82 82 83 83 83 85 86
Sound pressure (5) dB(A) 51 50 50 51 51 51 53 54
SIZE
A (6) mm 3570 3110 3110 4110 4110 4110 5110 5110
B (6) mm 1300 2220 2220 2220 2220 2220 2220 2220
H (6) mm 1620 2150 2150 2150 2150 2150 2150 2150
Operating weight (6) kg 1290 1700 1960 2350 2420 2590 2950 3100

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-1204
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

H H

A
A
B
B

183
Hydronic - reversible

NECS-NR 1314÷3218
Versions
B base version
CA Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
HOT WATER SUPPLY
Production of domestic hot water up to 55°C in both
summer and winter operating conditions, offering
maximum versatility with respect to different plant
engineering solutions.
CLASS A EFFICIENCY
The full range is also available with the Class A efficiency
rating. NECS-NR/CA and NECS-NR/SL-CA guaranty
premium levels of efficiency thanks to the generous sizing
of the refrigerant-exchange surface areas and to an
accurate control of the fans, available on both standard
and low-noise versions.
INTEGRATED HYDRONIC MODULE
The built-in hydronic module already contains the main
Reversible unit, NRG line, total heat recovery, water circuit components; it is available with single or
twin in-line pump, for achieving both low or high head,
air source for outdoor installation available for both plant and recovery circuits (up to 4
pumps).
353 - 823 kW
Unit Description Main accessories
Air-cooled reversible unit with total heat recovery for the simultaneous production of chilled/ UÊRemote keyboard (distance to 200m and to 500m)
hot water with hermetic rotary Scroll compressors, with R410A, axial fans, shell and tube heat UÊSoft starters
exchangers and electronic expansion valve. The range is composed by units equipped with UÊSet-up for remote connectivity with ModBus, Echelon
four, six and eight compressors in multi-circuit configuration. LonTalk, Bacnet protocol board
UÊLT kit for extending the operating limits in heat pump
Commands mode down to -10°C (/SL-CA versions) and -12°C (/CA
versions)
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return water
temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and heating,
according to the selected operation mode. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with
the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

184
ENERGY CLASS SHELL & TUBES AXIAL SCROLL

NECS-NR / B
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 353 378 412 452 494 546 567 617 662 704 757 791 823
Total power input (1) kW 125 131 150 163 176 189 196 225 235 250 262 281 300
EER 2,81 2,89 2,75 2,77 2,82 2,89 2,89 2,74 2,82 2,81 2,89 2,82 2,74
ESEER * * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 380 408 447 485 528 587 612 670 704 761 817 855 893
Total power input (2) kW 121 129 142 156 169 186 192 212 225 243 256 270 283
COP 3,13 3,18 3,16 3,11 3,12 3,16 3,18 3,16 3,12 3,13 3,18 3,17 3,16
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 1027 252
Heat recovery capacity (3) kW 455 485 542 590 640 700 728 814 854 912 971 240 1085
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (4) dB(A) 96 96 96 96 97 97 97 98 98 98 99 99 99
Sound pressure (5) dB(A) 64 64 64 64 65 65 65 66 65 65 66 66 66
SIZE
A (6) mm 3905 3905 3905 4515 5690 5690 5690 5690 7430 7430 7430 7430 7430
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (6) kg 3530 3620 3650 4850 5240 5370 5430 5480 6700 6830 7000 7030 7060
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

NECS-NR / CA
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 362 387 425 471 524 559 581 637 680 724 775 813 850
Total power input (1) kW 122 128 145 157 173 185 192 217 230 244 256 272 289
EER 2,96 3,03 2,94 3,01 3,04 3,03 3,03 2,94 2,95 2,96 3,03 2,99 2,94
ESEER * * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 394 420 462 507 546 603 630 693 729 788 840 882 924
Total power input (2) kW 120 127 140 155 166 183 190 210 221 2394 253 266 280
COP 3,30 3,31 3,30 3,28 3,29 3,30 3,32 3,30 3,29 3,29 3,32 3,31 3,30
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 240 252
Heat recovery capacity (3) kW 394 485 542 590 640 700 728 814 854 912 971 1027 1085
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (4) dB(A) 97 97 97 97 98 98 98 99 99 99 100 100 100
Sound pressure (5) dB(A) 65 65 65 64 65 65 65 66 66 66 67 67 67
SIZE
A (6) mm 5080 5080 5080 6255 7430 7430 7430 7430 9780 9780 9780 9780 9780
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (6) kg 3850 3950 3980 5460 5740 5890 5970 6020 7350 7500 7700 7740 7770
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

185
NECS-NR / SL-CA
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 332 357 398 429 500 512 536 596 616 663 715 754 795
Total power input (1) kW 130 137 153 169 640 198 205 230 244 260 274 290 306
EER 2,56 2,61 2,60 2,54 2,52 2,59 2,61 2,60 2,52 2,55 2,61 2,60 2,60
ESEER * * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 378 400 453 486 526 578 601 679 701 755 801 859 906
Total power input (2) kW 116 124 138 151 163 178 186 207 217 233 248 262 276
COP 3,25 3,22 3,29 3,22 3,23 3,25 3,23 3,28 3,23 3,24 3,23 3,28 3,28
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 1027 252
Heat recovery capacity (3) kW 455 485 542 590 640 700 728 814 854 912 971 240 1085
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (4) dB(A) 88 88 88 89 89 90 90 91 91 91 92 92 92
Sound pressure (5) dB(A) 56 56 56 57 57 57 57 58 58 58 59 59 59
SIZE
A (6) mm 4515 5080 5080 5690 5690 6865 7430 7430 7430 8605 9780 9780 9780
B (6) mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H (6) mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight (6) kg 3760 3900 4050 5350 5490 5780 5890 6130 7020 7330 7600 7750 7910
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1314-3218
Switchboard side mm 1500
Switchboard opposite side mm 1500
Plant exchagers opposite side mm 1500
Plant exchagers side mm 2000

B A

186
187
Hydronic - reversible

FOCS-NR 1062÷3222
Versions
CA Class A of efficiency
LN-CA Low Noise, Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency
XL-CA eXtra Low noise version, Class A of
efficiency
XL-CA-E eXtra Low noise, Class A enhanced

Features
UNIQUE PROPOSAL
Unique proposal: unit designed to satisfy, according to
the mode of operation, requirements of cold water, hot
water for heating or hot water for domestic use
EXTENSIVE RANGE OF OPERATION
Unit´s operation guaranteed with external air temperature
down to -10°C during winter and up to 46°C during
summer.
HOT WATER SUPPLY
Hot water supply up to 55°C. In winter mode the unit
manages hot water production in the plant-side heat
exchanger and in the reclaim one, with priority setted by
customer, eventually at two different set-points
VERSION ´XL-CA-E´ AVAILABLE
Exclusive Premium version. Together for the first time,
Reversible unit, NRG line, total heat recovery, the lowest noise level on the market and the maximum
efficiency in each operating mode.
air source for outdoor installation
Main accessories
200 - 826 kW UÊCompressor power factor device
UÊHydronic group
Unit Description UÊVPF (Variable Primary Flow) kit: variable flow pumps with
Outdoor heat pump unit for the production of chilled/hot water with semi-hermetic screw on board regulation
compressors optimized for R134a, axial-flow fans, external coil with copper tubes and UÊSet-up for remote connectivity with ModBus/Echelon/
aluminium fines, shell and tubes heat exchangers designed by Climaveneta and thermostatic Bacnet protocol cards
expansion valve. Base and supporting structure and panels are galvanized epoxy powder
coated steel with increased thickness. These units are designed for two-pipes systems and
are able to produce hot or cold water and even hot water on an auxiliary circuit when needed
for domestic utilities or post heating for air conditioning units.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return water
temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and heating,
according to the selected operation mode. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with
the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

188
r HFC
R-134a
SHELL & TUBES AXIAL SCREW

FOCS-NR / CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 210 248 302 329 380 425 483 525 554 624 701 826
Total power input (1) kW 72,1 84,5 102 109 129 144 156 167 176 201 222 264
EER 2,91 2,93 2,96 3,02 2,95 2,95 3,10 3,14 3,15 3,10 3,16 3,13
ESEER * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 218 258 309 339 396 434 492 541 571 615 711 826
Total power input (2) kW 67 80,7 92,2 101 122 131 149 159 169 178 207 240
COP 3,25 3,20 3,35 3,36 3,25 3,31 3,30 3,40 3,38 3,46 3,43 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Total power input kW
Sound power (4) dB(A) 97 97 97 98 99 99 99 101 101 101 101 102
Sound pressure (5) dB(A) 65 65 65 66 67 67 67 69 69 69 69 70
SIZE
A (6) mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B (6) mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H (6) mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight (6) kg * * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

FOCS-NR / LN-CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 205 241 294 322 369 414 469 513 541 604 686 800
Total power input (1) kW 70,8 84,3 103 109 130 144 163 168 177 206 226 274
EER 2,90 2,86 2,85 2,95 2,84 2,88 2,88 3,05 3,06 2,93 3,04 2,92
ESEER * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 218 258 309 339 396 434 492 541 571 615 711 826
Total power input (2) kW 67 80,7 92,2 101 122 131 149 159 169 178 207 240
COP 3,25 3,20 3,35 3,36 3,25 3,31 3,30 3,40 3,38 3,46 3,43 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 90 91 91 92 92 92 93 95 95 95 95 96
Sound pressure (5) dB(A) 58 59 59 60 60 60 61 63 63 63 63 64
SIZE
A (6) mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B (6) mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H (6) mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight (6) kg * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

189
FOCS-NR / SL-CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 200 233 283 314 356 401 464 509 537 597 680 790
Total power input (1) kW 72,7 87,2 109 113 137 149 166 170 180 210 229 281
EER 2,75 2,67 2,60 2,78 2,60 2,69 2,80 2,99 2,98 2,84 2,97 2,81
ESEER * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 211 251 301 330 385 422 486 536 564 607 703 816
Total power input (2) kW 64,8 78,4 89,9 98,4 119 127 147 157 167 176 205 238
COP 3,26 3,20 3,35 3,35 3,24 3,32 3,31 3,41 3,38 3,45 3,43 3,43
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 86 87 87 88 88 88 89 91 91 91 91 92
Sound pressure (5) dB(A) 54 55 55 56 56 56 57 59 59 59 59 60
SIZE
A (6) mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B (6) mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H (6) mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight (6) kg * * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

FOCS-NR / XL-CA
Models 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 455 501 528 584 667 772
Total power input (1) kW 167 169 180 212 230 287
EER 2,72 2,96 2,93 2,75 2,90 2,69
ESEER * * * * * *
HEATING ONLY
Heating capacity (2) kW 486 536 564 607 703 816
Total power input (2) kW 143 152 161 170 198 230
COP 3,40 3,53 3,50 3,57 3,55 3,55
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 484 521 551 631 702 832
Total power input (3) kW 137 145 153 170 193 224
Heat recovery capacity (3) kW 621 666 704 801 895 1056
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 85 87 87 87 87 88
Sound pressure (5) dB(A) 53 55 55 55 55 56
SIZE
A (6) mm 6300 7200 7200 7200 8400 9700
B (6) mm 2260 2260 2260 2260 2260 2260
H (6) mm 2350 2350 2350 2350 2350 2350
Operating weight (6) kg * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

190
FOCS-NR / XL-CA-E
Models 1062 1162 1362 1562 1762 2022 2222 2422 2622
COOLING ONLY
Cooling capacity (1) kW 204 247 293 319 366 473 510 541 611
Total power input (1) kW 66,6 76,6 99,4 105 127 153 163 169 193
EER 3,06 3,22 2,95 3,04 2,88 3,09 3,13 3,20 3,17
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 218 267 308 340 393 513 552 588 644
Total power input (2) kW 62,4 77,6 88,3 95,2 116 145 154 164 176
COP 3,49 3,44 3,49 3,57 3,39 3,54 3,58 3,59 3,66
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 484 521 551 631
Total power input (3) kW 60,6 71,9 87,1 92,5 111 137 145 153 170
Heat recovery capacity (3) kW 269 320 392 422 493 621 666 704 801
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 85 86 86 87 87 86 88 88 88
Sound pressure (5) dB(A) 53 54 54 55 55 54 56 56 56
SIZE
A (6) mm 4610 5610 5610 6610 6610 8400 9300 9300 9300
B (6) mm 2220 2220 2220 2220 2220 2260 2260 2260 2260
H (6) mm 2420 2430 2430 2430 2430 2350 2350 2350 2350
Operating weight (6) kg * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


1062-1762 2022-2622
Switchboard side mm 1100 1800
Switchboard opposite side mm 1100 1500
Condensation coil side mm 2000 2000

191
Hydronic - reversible

NECS-WNR 0152÷1604
Versions
- base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
INTEGRATED CONDENSATION´S CONTROL
A 2 way valve is supplied as standard for the condensing
pressure control. For all the applications in which a
constant waterflow through the condenser is needed, a
3-way valve option is also available under request.
ENERGY SAVING
Energy saving guaranteed by the advanced operations
logic. The best operation mode is set completely
automatically and independently by the units controller,
in order to minimize the absorbed energy whatever the
cooling and/or heating demand might be
HOT WATER SUPPLY
Production of domestic hot water up to 55°C in both
summer and winter operating conditions, offering
maximum versatility with respect to different plant
engineering solutions.

Reversible unit, NRG line, total heat recovery,


Main accessories
water source UÊRemote keyboard (distance to 200m and to 500m)
UÊWater connections directed upwards (for 2 compressors
5,7 - 491 kW units only)
UÊAcoustical enclosure to reduce the noise emissions.
Unit Description UÊSet-up for remote connectivity with ModBus, Echelon
Water source reversible unit with total heat recovery for the simultaneous production of chilled/ LonTalk, Bacnet protocol board
hot water with hermetic rotary Scroll compressors, with R410A, plate heat exchangers and
thermostatic expansion valve. The range is composed by units equipped with two and four
compressors, all with two refrigerant circuits.

Commands
W3000 large
The controller W3000 large offers the latest control and functions developed directly by Climaveneta on the basis of their
experience gained over the years with these particular units and the related plant engineering. The keypad is generously
sized with full operating status display. The controls and detailed LCD make access to machine settings easy and safe.
Temperature regulation managed on the two water circuits, with a proportional logic referred to the return water temperatures.
This allows to satisfy simultaneously the different heating- and cooling requests, with no need of mode changeover.
The diagnostics includes full management of alarms with black-box functions and alarm record for better analysis of
unit performance. Supervision is easy through Climaveneta devices or with various options for interfacing to ModBus,
Bacnet, Echelon LonTalk protocols. Compatibility with remote keyboard (management up to 10 units). Clock available with
programming of operation (standard 4 days and 10 time bands). Exclusive self-adaptive defrost logic, monitoring multiple
operational- and ambient parameters, which allows to reduce the number and duration of the defrost cycles, with a benefit
for the overall energy efficiency.

192
r HFC
R-410A
PLATES SCROLL

NECS-WNR / -
Models 0152 0182 0202 0252 0262 0302 0412 0512 0612
COOLING ONLY
Cooling capacity (1) kW 48,6 55,8 65 73,8 83,2 97,5 127 159 206
Total power input (1) kW 8,70 9,80 11,3 13,2 14,7 17,4 22,7 28,1 36,5
EER 5,59 5,69 5,75 5,59 5,66 5,60 5,59 5,64 5,63
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 52,1 59,7 69,3 79 88,9 104 135 169 219
Total power input (2) kW 12,4 13,8 16,2 18,5 20,4 23,9 31 38,4 49,9
COP 4,20 4,33 4,28 4,28 4,36 4,37 435 4,40 4,38
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 40,4 46,7 54,1 61,7 67,9 82 106 133 172
Total power input (3) kW 12,4 13,8 16,2 18,5 20,4 23,9 31 38,4 49,9
Heat recovery capacity (3) kW 52,1 59,7 69,3 79 88,9 104 135 169 219
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Total power input kW
Sound power (4) dB(A) 73 74 74 74 75 76 77 78 79
Sound pressure (5) dB(A) 42 43 43 43 44 45 46 47 48
SIZE
A (6) mm 1222 1222 1222 1222 1222 1222 1222 1222 1222
B (6) mm 893 893 893 893 893 893 893 893 893
H (6) mm 1496 1496 1496 1496 1496 1496 1496 1496 1496
Operating weight (6) kg 450 470 490 505 525 550 745 825 910

Models 0604 0704 0804 0904 1004 1104 1204 1404 1604
COOLING ONLY
Cooling capacity (1) kW 194 225 255 285 317 365 413 468 522
Total power input (1) kW 34,8 40 45,3 50,8 56,3 64,8 73 84,1 95,1
EER 5,58 5,63 5,62 5,61 5,63 5,63 5,66 5,56 5,49
ESEER * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 208 240 270 303 338 388 440 498 557
Total power input (2) kW 47,7 54,7 61,8 69,2 76,8 88,4 99,6 113 126
COP 4,36 4,38 4,37 4,38 4,40 4,39 4,41 4,41 4,42
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 163 188 212 238 266 305 346 392 438
Total power input (3) kW 47,7 54,7 61,8 69,2 76,8 88,4 99,6 113 126
Heat recovery capacity (3) kW 208 240 270 303 338 388 440 498 557
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Total power input kW
Sound power (4) dB(A) 86 87 88 89 90 91 91 91 91
Sound pressure (5) dB(A) 54 55 56 57 58 59 59 59 59
SIZE
A (6) mm 2520 2520 2520 2520 2520 2520 2520 2520 2520
B (6) mm 880 880 880 880 880 880 880 880 880
H (6) mm 1810 1810 1810 1810 1810 1810 1810 1810 1810
Operating weight (6) kg 975 1165 1365 1445 1610 1710 1810 1895 2000

Note:
1 Evaporator water (in/out) = 12/7°C; condenser water (in/out) = 14/30°C
2 Condenser water (in/out) = 40/45°C; evaporator water (in/out) = 14/7°C
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0152-0612 0604-1604
Switchboard side mm 800 1000
Switchboard opposite side mm 800 1000
Unit’s side mm 800 800

H H

A
B B A

193
Hydronic - reversible

FOCS-WNR 0802÷3202
Versions
- base version

Features
UNIQUE PROPOSAL
Unique proposal: unit designed to satisfy, according to
the mode of operation, requirements of cold water, hot
water for heating or hot water for domestic use
ENERGY SAVING
Free domestic hot water during summer season.
HOT WATER SUPPLY
Hot water supply up to 55°C. In winter mode the unit
manages hot water production in the plant-side heat
exchanger and in the reclaim one, with priority setted by
customer, eventually at two different set-points
INTEGRATED CONDENSATION´S CONTROL
A 2 way valve is supplied as standard for the condensing
pressure control. For all the applications in which a
constant waterflow through the condenser is needed, a
3-way valve option is also available under request.

Main accessories
UÊIntegral acoustical enclosure (type base or plus)

Reversible unit, NRG line, total heat recovery, UÊSeveral devices for condensation´s control
UÊElectronic expansion valve
water source UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
194 - 891 kW
Unit Description
Heat pump unit for indoor installation, designed for 2-pipes plants application for summer/
winter air conditioning. Unit complete with a section for the condensation heat reclaim: a
dedicated heat exchanger produces on request hot water for secondary uses (domestic hot
water, air treatment in AHU, ...). Semi-hermetic screw compressor, R134a, shell and tube heat
exchangers both, plant-side (primary, working as an evaporator or condenser as a function of
unit´s commutation, and secondary, working only as a condenser) and source-side. Frame in
polyester-painted galvanized steel.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return water
temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and heating,
according to the selected operation mode. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the
remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles
with 10 hour belts).

194
r HFC
R-134a
SHELL & TUBES SCREW

FOCS-WNR / -
Models 0802 1002 1102 1302 1502 1702 1902 2152 2502 2602 2702 3202 0802
COOLING ONLY
Cooling capacity (1) kW 194 240 275 326 373 435 479 554 648 703 781 891 194
Total power input (1) kW 34,3 43,2 48,5 57,2 66,1 76,5 85,7 94,5 111 121 135 153 34,3
EER 5,66 5,56 5,66 5,69 5,64 5,68 5,58 5,87 5,83 5,83 5,80 5,81 5,66
ESEER * * * * * * * * * * * * *
HEATING ONLY
Heating capacity (2) kW 205 255 291 344 393 459 514 589 686 738 831 941 205
Total power input (2) kW 45,7 57,0 65,9 76,3 86,9 103 117 128 149 158 180 205 45,7
COP 4,49 4,47 4,42 4,51 4,52 4,44 4,40 4,59 4,62 4,68 4,62 4,59 4,49
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 162 201 229 272 311 362 404 468 547 589 662 748 162
Total power input (3) kW 45,7 57,0 65,9 76,3 86,9 103 117 128 149 158 180 205 45,7
Heat recovery capacity (3) kW 205 255 291 344 393 459 514 589 686 738 831 941 205
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Total power input kW
Sound power (4) dB(A) 94 95 97 97 97 97 97 98 99 99 99 99 94
Sound pressure (5) dB(A) 76 77 79 79 79 79 78 79 80 80 80 80 76
SIZE
A (6) mm 3680 3680 3680 3680 3680 3680 3800 3800 3800 5000 5000 5000 3680
B (6) mm 1170 1170 1170 1170 1170 1170 1490 1490 1490 1490 1490 1490 1170
H (6) mm 1950 1950 1950 1950 1950 1950 1950 1950 1950 1950 1950 1950 1950
Operating weight (6) kg * * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; condenser water (in/out) = 14/30°C
2 Condenser water (in/out) = 40/45°C; evaporator water (in/out) = 14/7°C
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
5 Average sound pressure level, at 1 m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0802-3202
Switchboard side mm 800
Switchboard opposite side mm 500
Condensation coil side mm 500

195
196
197
INTEGRA

NECS-Q 0152÷1204
Versions
B base version
LN low noise version
SL super-low noise version

Features
UNIQUE PROPOSAL
Unit designed to satisfy the cold and the hot side
requirements simultaneously, for 4-pipe systems without
any particular operation mode setting
TOTAL VERSATILITY
Climaveneta is the only company to offer all-in-one units
with Scroll compressors in 3 versions designed to satisfy
all service system and application requirements
CUTTING-EDGE ELECTRONICS
The Energy Raiser units are fitted with an evolved
electronic unit that allows fully automatic management of
the best type of operation to meet the load requirements
VENTILATION CONTROL FOR LOW-TEMPERATURE
OPERATION
The standard units come fitted with pressure-operated
control of ventilation, which allows the unit to produce
cold water with an external air temperature down to
-10°C
INTEGRATED HYDRONIC MODULE
INTEGRA unit for 4-pipe systems, air source The built-in hydronic module already contains the main
water circuit components; it is available with single or
for outdoor installation twin in-line pump, for achieving both low or high head,
available for both plant and recovery circuits (up to 4
36 - 311 kW pumps).

Unit Description
Multi-purpose outdoor unit for use in 4-pipe systems for the simultaneous production of Main accessories
chilled and hot water by means of two independent hydronic circuits. These units are able UÊSet-up for remote connectivity with ModBus/Echelon/
to satisfy the demand for hot and cold water simultaneously through a system that does not Bacnet protocol cards
require seasonal switching and is therefore a valid alternative to traditional plants with chiller UÊRemote keyboard (distance to 200m and to 500m)
and boiler. This unit is equipped with hermetic rotary Scroll compressors, with R410A, axial UÊSoft starters
fans, braze-welded plate-type exchanger and thermal expansion valve. External panels in UÊRubber anti-vibration mounting kit
Peraluman and base in galvanised sheet steel with paint finish. The range includes two-
compressor and four-compressor versions, both with two independent refrigerant circuits.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return
water temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and
heating, with no need of mode setting. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with
the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

198
4 PIPE
r HFC
R-410A
PLATES AXIAL SCROLL SYSTEM

NECS-Q / B
Models 0152 0182 0202 0252 0262 0302 0412 0512
COOLING ONLY
Cooling capacity (1) kW 36,6 43,2 48,5 55,8 61,2 73,3 94,8 120
Total power input (1) kW 13,3 14,5 17,9 19,9 22,8 26,2 33,6 41,7
EER 2,76 2,99 2,71 2,80 2,68 2,80 2,82 2,88
HEATING ONLY
Heating capacity (2) kW 41,1 48,9 55,3 62,5 68,1 83,1 107 136
Total power input (2) kW 13,3 14,7 17,2 19,7 21,4 24,9 32,1 40
COP 3,10 3,33 3,22 3,17 3,18 3,34 3,34 3,40
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 37,2 43,6 50,6 57,2 64,1 76,3 97,7 124
Heat recovery capacity (3) kW 49,2 56,9 66,2 75 83,8 99,3 128 161
Total power input (3) kW 12,8 14,2 16,6 18,9 21 24,5 31,9 39,6
TER (4) - 6,75 7,08 7,04 6,99 7,04 7,17 7,08 7,20
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 84 84 84 84 84 85 86 87
Sound pressure (6) dB(A) 52 52 52 52 52 53 54 55
SIZE
A mm 2020 2020 2020 2520 2520 2520 3070 3570
B mm 1300 1300 1300 1300 1300 1300 1300 1300
H mm 1620 1620 1620 1620 1620 1620 1620 1620
Operating weight kg 570 590 600 660 670 720 1030 1180

Models 0612 0604 0704 0804 0904 1004 1104 1204


COOLING ONLY
Cooling capacity (1) kW 151 150 166 189 211 240 277 311
Total power input (1) kW 56,6 58,9 69 75,8 85,2 95,6 107 121
EER 2,66 2,54 2,41 2,49 2,48 2,51 2,58 2,58
HEATING ONLY
Heating capacity (2) kW 173 167 185 209 234 267 306 344
Total power input (2) kW 52,1 58 64,9 72,1 79,8 92 104 116
COP 3,31 2,88 2,86 2,90 2,93 2,90 2,94 2,96
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 160 151 173 194 220 246 281 317
Heat recovery capacity (3) kW 208 198 226 255 288 321 368 415
Total power input (3) kW 51,3 49,8 57,1 64,5 72,1 79,8 92,8 105
TER (4) - 7,17 7,01 6,99 6,96 7,05 7,11 6,99 6,97
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (5) dB(A) 87 92 92 92 93 94 95 95
Sound pressure (6) dB(A) 55 60 60 60 61 62 63 63
SIZE
A mm 3570 3110 3110 3110 4110 4110 4110 4110
B mm 1300 2220 2220 2220 2220 2220 2220 2220
H mm 1620 2150 2150 2150 2150 2150 2150 2150
Operating weight kg 1290 1600 1840 2120 2320 2480 2680 2860

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

199
NECS-Q / LN
Models 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 143 157 177 199 227 261 291
Total power input (1) kW 58,8 70,2 78,4 87,8 96,5 110 125
EER 2,43 2,24 2,26 2,27 2,36 2,37 2,32
HEATING ONLY
Heating capacity (2) kW 160 176 198 225 254 290 324
Total power input (2) kW 54 60,8 67,9 75,7 85,8 97,9 110
COP 2,95 2,89 2,92 2,98 2,95 2,96 2,94
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 151 173 194 220 246 281 317
Heat recovery capacity (3) kW 198 226 255 288 321 368 415
Total power input (3) kW 49,8 57,1 64,5 72,1 79,8 92,8 105
TER (4) - 7,01 6,99 6,96 7,05 7,11 6,99 6,97
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (5) dB(A) 86 86 86 87 88 89 89
Sound pressure (6) dB(A) 54 54 54 55 56 57 57
SIZE
A mm 3110 3110 3110 4110 4110 4110 4110
B mm 2220 2220 2220 2220 2220 2220 2220
H mm 2150 2150 2150 2150 2150 2150 2150
Operating weight kg 1600 1840 2120 2320 2480 2680 2860
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

200
NECS-Q / SL
Models 0152 0182 0202 0252 0262 0302 0412 0512
COOLING ONLY
Cooling capacity (1) kW 33,3 39,6 47 50,9 58,3 69,1 93,9 119
Total power input (1) kW 15 16,5 18,7 22,4 24,4 28,4 34,1 42,3
EER 2,21 2,39 2,52 2,28 2,39 2,43 2,75 2,81
HEATING ONLY
Heating capacity (2) kW 40 47,4 55,1 60,9 70,5 80,9 109 138
Total power input (2) kW 13,1 14,6 17,2 19,7 21,5 24,8 32,2 40,1
COP 3,04 3,24 3,21 3,10 3,28 3,26 3,38 3,43
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 37,2 43,6 50,6 57,2 64,1 76,3 97,7 124
Heat recovery capacity (3) kW 49,2 56,9 66,2 74,9 83,8 99,3 128 161
Total power input (3) kW 12,8 14,2 16,6 18,9 21 24,5 31,9 39,6
TER (4) - 6,75 7,08 7,04 6,99 7,04 7,17 7,08 7,20
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 78 78 79 79 79 80 82 83
Sound pressure (6) dB(A) 46 46 47 47 47 48 50 51
SIZE
A mm 2020 2020 2520 2520 2520 3070 3070 3570
B mm 130 1300 1300 1300 1300 1300 1300 1300
H mm 1620 1620 1620 1620 1620 1620 1620 1620
Operating weight kg 570 590 660 660 700 780 1070 1230

Models 0612 0604 0704 0804 0904 1004 1104 1204


COOLING ONLY
Cooling capacity (1) kW 143 142 160 183 201 225 261 294
Total power input (1) kW 60,4 58 67,4 75,5 87,3 95,5 108 123
EER 2,37 2,45 2,37 2,43 2,30 2,36 2,41 2,38
HEATING ONLY
Heating capacity (2) kW 169 159 178 205 226 253 295 330
Total power input (2) kW 52 52,6 59,5 68,7 76,1 83,8 96,1 110
COP 3,26 3,02 2,99 2,99 2,98 3,02 3,07 3
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 160 151 173 194 220 246 281 317
Heat recovery capacity (3) kW 208 198 226 255 288 321 368 415
Total power input (3) kW 51,3 49,8 57,1 64,5 72,1 79,8 92,8 105
TER (4) - 7,17 7,01 6,99 6,96 7,05 7,11 6,99 6,97
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (5) dB(A) 83 82 82 83 83 83 85 86
Sound pressure (6) dB(A) 51 50 50 51 51 51 53 54
SIZE
A mm 3570 3110 3110 4110 4110 4110 5110 5110
B mm 1300 2220 2220 2220 2220 2220 2220 2220
H mm 1620 2150 2150 2150 2150 2150 2150 2150
Operating weight kg 1290 1700 1960 2350 2420 2590 2950 3100

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


0152-1204
Switchboard side mm 1100
Switchboard opposite side mm 1100
Condensation coil side mm 2000

H H

A
A
B
B

201
INTEGRA

NECS-Q 1314÷3218
Versions
B base version
CA Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
UNIQUE PROPOSAL
Unit designed to satisfy the cold and the hot side
requirements simultaneously, for 4-pipe systems without
any particular operation mode setting
ENERGY SAVING
Energy saving guaranteed by the advanced operations
logic. The best operation mode is set completely
automatically and independently by the units controller,
in order to minimize the absorbed energy whatever the
cooling and/or heating demand might be
CLASS A EFFICIENCY
The full range is also available with the Class A efficiency
rating. NECS-Q/CA and NECS-Q/SL-CA guaranty
premium levels of efficiency thanks to the generous sizing
INTEGRA unit for 4-pipe systems, air source of the refrigerant-exchange surface areas and to an
accurate control of the fans, available on both standard
for outdoor installation and low-noise versions.
INTEGRATED HYDRONIC MODULE
353 - 823 kW The built-in hydronic module already contains the main
water circuit components; it is available with single or twin
Unit Description in-line pump, for achieving low or high head, available
Multi-purpose outdoor unit for use in 4-pipe systems for the simultaneous production of for both hot and cold water distribution systems (up to 4
chilled and hot water by means of two independent hydronic circuits. These units are able pumps).
to satisfy the demand for hot and cold water simultaneously through a system that does not
require seasonal switching and is therefore a valid alternative to traditional plants with chiller
and boiler. This unit is equipped with hermetic rotary Scroll compressors, with R410A, axial Main accessories
fans, shell and tube heat exchangers and electronic expansion valve. The range is composed UÊRemote keyboard (distance to 200m and to 500m)
by units equipped with four, six and eight compressors in multi-circuit configuration. UÊSoft starters
UÊSet-up for remote connectivity with ModBus, Echelon
LonTalk, Bacnet protocol board
UÊLT kit for extending the operating limits in heat pump
Commands mode down to -10°C (/SL-CA versions) and -12°C (/CA
W3000SE Large versions)
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return
water temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and
heating, with no need of mode setting. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with
the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features the monitoring of numerous
operational parameters. This allows to reduce the number and duration of the defrost cycles, with a benefit for the overall
energy efficiency.

202
4 PIPE

ENERGY CLASS SHELL & TUBES AXIAL SCROLL SYSTEM

NECS-Q / B
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 353 378 412 452 494 546 567 617 662 704 757 791 823
Total power input (1) kW 125 131 150 163 176 189 196 225 235 250 262 281 300
EER 2,81 2,89 2,75 2,77 2,82 2,89 2,89 2,74 2,82 2,81 2,89 2,82 2,74
HEATING ONLY
Heating capacity (2) kW 380 408 447 485 528 587 612 670 704 761 817 855 893
Total power input (2) kW 121 129 142 156 169 186 192 212 225 243 256 270 283
COP 3,13 3,18 3,16 3,11 3,12 3,16 3,18 3,16 3,12 3,13 3,18 3,17 3,16
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Heat recovery capacity (3) kW 455 485 542 590 640 700 728 814 854 912 971 240 1085
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 1027 252
TER (4) - 7,57 7,65 7,66 7,55 7,60 7,65 7,63 7,67 7,61 7,62 7,62 1,01 7,67
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (5) dB(A) 96 96 96 96 97 97 97 98 98 98 99 99 99
Sound pressure (6) dB(A) 64 64 64 64 65 65 65 66 65 65 66 66 66
SIZE
A mm 3905 3905 3905 4515 5690 5690 5690 5690 7430 7430 7430 7430 7430
B mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight kg 3530 3620 3650 4850 5240 5370 5430 5480 6700 6830 7000 7030 7060
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

NECS-Q / CA
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 362 387 425 471 524 559 581 637 680 724 775 813 850
Total power input (1) kW 122 128 145 157 173 185 192 217 230 244 256 272 289
EER 2,96 3,03 2,94 3,01 3,04 3,03 3,03 2,94 2,95 2,96 3,03 2,99 2,94
HEATING ONLY
Heating capacity (2) kW 394 420 462 507 546 603 630 693 729 788 840 882 924
Total power input (2) kW 120 127 140 155 166 183 190 210 221 2394 253 266 280
COP 3,30 3,31 3,30 3,28 3,29 3,30 3,32 3,30 3,29 3,29 3,32 3,31 3,30
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Heat recovery capacity (3) kW 394 485 542 590 640 700 728 814 854 912 971 1027 1085
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 240 252
TER (4) - 7,00 7,65 7,66 7,55 7,60 7,65 7,63 7,67 7,61 7,62 7,62 7,62 7,67
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (5) dB(A) 97 97 97 97 98 98 98 99 99 99 100 100 100
Sound pressure (6) dB(A) 65 65 65 64 65 65 65 66 66 66 67 67 67
SIZE
A mm 5080 5080 5080 6255 7430 7430 7430 7430 9780 9780 9780 9780 9780
B mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight kg 3850 3950 3980 5460 5740 5890 5970 6020 7350 7500 7700 7740 7770
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

203
NECS-Q / SL-CA
Models 1314 1414 1614 1716 1816 2016 2116 2416 2418 2618 2818 3018 3218
COOLING ONLY
Cooling capacity (1) kW 332 357 398 429 500 512 536 596 616 663 715 754 795
Total power input (1) kW 130 137 153 169 640 198 205 230 244 260 274 290 306
EER 2,56 2,61 2,60 2,54 2,52 2,59 2,61 2,60 2,52 2,55 2,61 2,60 2,60
HEATING ONLY
Heating capacity (2) kW 378 400 453 486 526 578 601 679 701 755 801 859 906
Total power input (2) kW 116 124 138 151 163 178 186 207 217 233 248 262 276
COP 3,25 3,22 3,29 3,22 3,23 3,25 3,23 3,28 3,23 3,24 3,23 3,28 3,28
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 355 379 423 460 500 547 569 636 667 711 758 802 848
Heat recovery capacity (3) kW 455 485 542 590 640 700 728 814 854 912 971 240 1085
Total power input (3) kW 107 113 126 139 150 163 170 189 200 213 227 1027 252
TER (4) - 7,57 7,65 7,66 7,55 7,60 7,65 7,63 7,67 7,61 7,62 7,62 1,01 7,67
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 6/3 6/3 6/3 6/3 6/3 8/4 8/4 8/4 8/4 8/4
NOISE LEVELS
Sound power (5) dB(A) 88 88 88 89 89 90 90 91 91 91 92 92 92
Sound pressure (6) dB(A) 56 56 56 57 57 57 57 58 58 58 59 59 59
SIZE
A mm 4515 5080 5080 5690 5690 6865 7430 7430 7430 8605 9780 9780 9780
B mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
H mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
Operating weight kg 3760 3900 4050 5350 5490 5780 5890 6130 7020 7330 7600 7750 7910

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


1314-3218
Switchboard side mm 1500
Switchboard opposite side mm 1500
Plant exchagers opposite side mm 1500
Plant exchagers side mm 2000

B A

204
205
INTEGRA

ERACS2-Q 1062÷3222
Versions
CA Class A of efficiency
LN-CA Low Noise, Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency
XL-CA eXtra Low noise version, Class A of
efficiency
XL-CA-E eXtra Low noise, Class A enhanced

Features
UNIQUE PROPOSAL
Unit designed to satisfy the cold and the hot side
requirements simultaneously, for 4-pipe systems without
any particular operation mode setting
ENERGY SAVING
Energy saving guaranteed by the advanced operations
logic. The best operation mode is set completely
automatically and independently by the units controller,
in order to minimize the absorbed energy whatever the
cooling and/or heating demand might be
EXTENSIVE RANGE OF OPERATION
Unit´s operation guaranteed with external air temperature
down to -10°C during winter and up to 46°C during
summer.
VERSION ´XL-CA-E´ AVAILABLE
INTEGRA unit for 4-pipe systems, air source Exclusive Premium version. Together for the first time,
the lowest noise level on the market and the maximum
for outdoor installation efficiency in each operating mode.
HOT WATER SUPPLY
200 - 826 kW Supply of hot water in use up to 55°C, offering maximum
versatility with respect to different plant engineering
Unit Description solutions
Multi-purpose outdoor unit for use in 4-pipe systems for the simultaneous production of
chilled and hot water by means of two independent hydronic circuits. These units are able Main accessories
to satisfy the demand for hot and cold water simultaneously through a system that does not UÊHydronic group
require seasonal switching and is therefore a valid alternative to traditional plants with chiller UÊVPF (Variable Primary Flow) kit: variable flow pumps with
and boiler. Each circuit works with a semi-hermetic screw compressor using R134a, two shell on board regulation
and tubes heat exchangers shared by both circuits, a cold heat exchanger on plants side that UÊElectronic expansion valve
acts as an evaporator in the production of cold water, a heat exchanger on plants side that
UÊSet-up for remote connectivity with ModBus/Echelon/
works as a condenser in the production of hot water, and a source side coil heat exchanger
Bacnet protocol cards
that works as either condenser or evaporator as required by the loads.

Commands
W3000 large
The controller W3000 large offers the latest control and functions specially developed for these units. The keypad is
generously sized with full operating status display. The controls and detailed LCD make access to machine settings easy and
safe. These resources permit to diirectly act on the unit settings through a multilevel menu, available in several languages.
The diagnostics includes full management of alarms with black-box functions and alarm record for better analysis of unit
performance. For multi-units plants a special device to coordinate and manage all the resources is available as an option;
energy metering device is even possible as an option. Supervision is easy through Climaveneta devices or with various
options for interfacing to ModBus, Bacnet, Echelon LonTalk protocols. Compatibility with remote keyboard (management up
to 10 units). Clock available with programming of operation (standard 4 days and 10 time bands). Temperature regulation
managed on the two water circuits, with a proportional logic referred to the return water temperatures. This allows to satisfy
simultaneously the different heating- and cooling requests, with no need of mode changeover. Exclusive self-adaptive defrost
logic, monitoring multiple operational- and ambient parameters, which allows to reduce the number and duration of the
defrost cycles, with a benefit for the overall energy efficiency.

206
4 PIPE
r HFC
R-134a
SHELL & TUBES AXIAL SCREW SYSTEM

ERACS2-Q / CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 210 248 302 329 380 425 483 525 554 624 701 826
Total power input (1) kW 72,1 84,5 102 109 129 144 156 167 176 201 222 264
EER 2,91 2,93 2,96 3,02 2,95 2,95 3,10 3,14 3,15 3,10 3,16 3,13
HEATING ONLY
Heating capacity (2) kW 218 258 309 339 396 434 492 541 571 615 711 826
Total power input (2) kW 67 80,7 92,2 101 122 131 149 159 169 178 207 240
COP 3,25 3,20 3,35 3,36 3,25 3,31 3,30 3,40 3,38 3,46 3,43 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
TER (4) - 7,89 7,90 8,00 8,12 7,87 8,01 8,07 8,19 8,20 8,42 8,27 8,43
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 97 97 97 98 99 99 99 101 101 101 101 102
Sound pressure (6) dB(A) 65 65 65 66 67 67 67 69 69 69 69 70
SIZE
A mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight kg * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

ERACS2-Q / LN-CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 205 241 294 322 369 414 469 513 541 604 686 800
Total power input (1) kW 70,8 84,3 103 109 130 144 163 168 177 206 226 274
EER 2,90 2,86 2,85 2,95 2,84 2,88 2,88 3,05 3,06 2,93 3,04 2,92
HEATING ONLY
Heating capacity (2) kW 218 258 309 339 396 434 492 541 571 615 711 826
Total power input (2) kW 67 80,7 92,2 101 122 131 149 159 169 178 207 240
COP 3,25 3,20 3,35 3,36 3,25 3,31 3,30 3,40 3,38 3,46 3,43 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
TER (4) - 7,89 7,90 8,00 8,12 7,87 8,01 8,07 8,19 8,20 8,42 8,27 8,43
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 90 91 91 92 92 92 93 95 95 95 95 96
Sound pressure (6) dB(A) 58 59 59 60 60 60 61 63 63 63 63 64
SIZE
A mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight kg * * * * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

207
ERACS2-Q / SL-CA
Models 1062 1162 1362 1562 1762 1962 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 200 233 283 314 356 401 464 509 537 597 680 790
Total power input (1) kW 72,7 87,2 109 113 137 149 166 170 180 210 229 281
EER 2,75 2,67 2,60 2,78 2,60 2,69 2,80 2,99 2,98 2,84 2,97 2,81
HEATING ONLY
Heating capacity (2) kW 211 251 301 330 385 422 486 536 564 607 703 816
Total power input (2) kW 64,8 78,4 89,9 98,4 119 127 147 157 167 176 205 238
COP 3,26 3,20 3,35 3,35 3,24 3,32 3,31 3,41 3,38 3,45 3,43 3,43
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 428 484 521 551 631 702 832
Heat recovery capacity (3) kW 269 320 392 422 493 549 621 666 704 801 895 1056
Total power input (3) kW 60,6 71,9 87,1 92,5 111 122 137 145 153 170 193 224
TER (4) - 7,89 7,90 8,00 8,12 7,87 8,01 8,07 8,19 8,20 8,42 8,27 8,43
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 86 87 87 88 88 88 89 91 91 91 91 92
Sound pressure (6) dB(A) 54 55 55 56 56 56 57 59 59 59 59 60
SIZE
A mm 4610 4610 5610 5610 6610 6610 6300 7200 7200 7200 8400 9700
B mm 2220 2220 2220 2220 2220 2220 2260 2260 2260 2260 2260 2260
H mm 2150 2420 2430 2430 2430 2430 2350 2350 2350 2350 2350 2350
Operating weight kg * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

ERACS2-Q / XL-CA
Models 2022 2222 2422 2622 2722 3222
COOLING ONLY
Cooling capacity (1) kW 455 501 528 584 667 772
Total power input (1) kW 167 169 180 212 230 287
EER 2,72 2,96 2,93 2,75 2,90 2,69
HEATING ONLY
Heating capacity (2) kW 486 536 564 607 703 816
Total power input (2) kW 143 152 161 170 198 230
COP 3,40 3,53 3,50 3,57 3,55 3,55
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 484 521 551 631 702 832
Heat recovery capacity (3) kW 621 666 704 801 895 1056
Total power input (3) kW 137 145 153 170 193 224
TER (4) - 8,07 8,19 8,20 8,42 8,27 8,43
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 85 87 87 87 87 88
Sound pressure (6) dB(A) 53 55 55 55 55 56
SIZE
A mm 6300 7200 7200 7200 8400 9700
B mm 2260 2260 2260 2260 2260 2260
H mm 2350 2350 2350 2350 2350 2350
Operating weight kg * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

208
ERACS2-Q / XL-CA-E
Models 1062 1162 1362 1562 1762 2022 2222 2422 2622
COOLING ONLY
Cooling capacity (1) kW 204 247 293 319 366 473 510 541 611
Total power input (1) kW 66,6 76,6 99,4 105 127 153 163 169 193
EER 3,06 3,22 2,95 3,04 2,88 3,09 3,13 3,20 3,17
HEATING ONLY
Heating capacity (2) kW 218 267 308 340 393 513 552 588 644
Total power input (2) kW 62,4 77,6 88,3 95,2 116 145 154 164 176
COP 3,49 3,44 3,49 3,57 3,39 3,54 3,58 3,59 3,66
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 209 248 305 329 381 484 521 551 631
Heat recovery capacity (3) kW 269 320 392 422 493 621 666 704 801
Total power input (3) kW 60,6 71,9 87,1 92,5 111 137 145 153 170
TER (4) - 7,89 7,90 8,00 8,12 7,87 8,07 8,19 8,20 8,42
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) 85 86 86 87 87 86 88 88 88
Sound pressure (6) dB(A) 53 54 54 55 55 54 56 56 56
SIZE
A mm 4610 5610 5610 6610 6610 8400 9300 9300 9300
B mm 2220 2220 2220 2220 2220 2260 2260 2260 2260
H mm 2420 2430 2430 2430 2430 2350 2350 2350 2350
Operating weight kg * * * * * * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


1062-1762 2022-2622
Switchboard side mm 1100 1800
Switchboard opposite side mm 1100 1500
Condensation coil side mm 2000 2000

209
INTEGRA

i-FX-Q 0502÷0802
Versions
CA Class A of efficiency
LN-CA Low Noise, Class A of efficiency
SL-CA Super Low noise version, Class A of
efficiency

Features
UNIQUE PROPOSAL - PATENT PENDING
The exclusive regulation´s logic of the INTEGRA units,
the only able to satisfy cold and hot building loads
simultaneously, and the use of inverter motors ensure the
highest energy saving for complex plants, as the 4-pipes
system are
VERY HIGH EFFICIENCY AT PARTIAL LOAD
Very high efficiency at partial load thanks to the inverter
technology applied on screw compressors. Therefore,
operating costs are reduced to a minimum
TRUE SILENCE
Silence optimized for the most frequent operational
conditions, thanks to the accurate structures design, to
the use of EC fans (DC brushless) and to the adoption of
variable-speed driven compressors
EXTENSIVE RANGE OF OPERATION
Unit´s operation guaranteed with external air temperature
down to -10°C during winter and up to 46°C during
INTEGRA unit for 4-pipe systems, air source summer.
HARMONY BETWEEN UNIT AND PLANT
for outdoor installation Low inrush current and cos(phi) higher than 0.9, permit
an easy electrical installation which is not stressed
479 - 811 kW during start-up and with no need of extra devices for
power factor correction. The use of inverter allows the
unit partialize down to 15%, with consequent lower
Unit Description
fluctuations of leaving water temperature
Multi-purpose outdoor unit for use in 4-pipe systems for the simultaneous production of
chilled and hot water by means of two independent hydronic circuits. These units are able
to satisfy the demand for hot and cold water simultaneously through a system that does not Main accessories
require seasonal switching and is therefore a valid alternative to traditional plants with chiller UÊHydronic group
and boiler. Each circuit works with an inverter driven semi-hermetic screw compressor using UÊVPF (Variable Primary Flow) kit: variable flow pumps with
R134a, two shell and tubes heat exchangers shared by both circuits, a cold heat exchanger on board regulation
and a hot one on plants side, and a source side coil heat exchanger that works as either UÊSet-up for remote connectivity with ModBus/Echelon/
condenser or evaporator as required by the loads. The revolutionary units design, patent Bacnet protocol cards
pending, and the use of inverter motors on compressors, fans and, on request, on pumps,
ensures un umbeatable efficiency, specially at part load.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface and a
complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable language
setting. The regulation operates on both water circuits and features the continuous modulation of capacity by adjustment
of the compressor speed. The modulation is based on PID algorithms and referring to the leaving water temperature. This
is combined with the management of the compressors status, with two selectable logics (proportional referred to the return
temperature or dead band referred to the leaving temperature). This allows to satisfy simultaneously and accurately the
different requests of both cooling and heating, with no need of mode setting. The diagnostics includes a complete alarm
management, with the “black-box” and alarm logging functions for enhanced analysis of the unit operation. For multiple
units systems, the regulation of the resources, via optional proprietary devices, can be implemented. Energy metering, for
both consumption and capacity, can also be developed. Supervision can be easily developed via proprietary devices or the
integration in third party systems by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features
the monitoring of numerous operational parameters. This allows to reduce the number and duration of the defrost cycles,
with a benefit for the overall energy efficiency.

210
4 PIPE
r HFC
R-134a
SHELL & TUBES EC FAN SCREW SYSTEM

i-FX-Q / CA
Models 0502 0602 0702 0802
COOLING ONLY
Cooling capacity (1) kW 498 617 711 811
Total power input (1) kW 164 210 245 273
EER 3,04 2,94 2,90 2,97
HEATING ONLY
Heating capacity (2) kW 528 654 758 856
Total power input (2) kW 155 194 224 249
COP 3,41 3,37 3,38 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 485 613 715 814
Heat recovery capacity (3) kW 624 787 917 1040
Total power input (3) kW 147 185 215 240
TER (4) - 7,54 7,57 7,59 7,72
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) * * * *
Sound pressure (6) dB(A) * * * *
SIZE
A mm 7800 9000 9000 9900
B mm 2260 2260 2260 2260
H mm 2430 2430 2430 2430
Operating weight kg * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

i-FX-Q / LN-CA
Models 0502 0602 0702 0802
COOLING ONLY
Cooling capacity (1) kW 484 599 690 787
Total power input (1) kW 159 206 243 271
EER 3,04 2,91 2,84 2,90
HEATING ONLY
Heating capacity (2) kW 528 654 758 856
Total power input (2) kW 155 194 224 249
COP 3,41 3,37 3,38 3,44
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 485 613 715 814
Heat recovery capacity (3) kW 624 787 917 1040
Total power input (3) kW 147 185 215 240
TER (4) - 7,54 7,57 7,59 7,72
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) * * * *
Sound pressure (6) dB(A) * * * *
SIZE
A mm 7800 9000 9000 9900
B mm 2260 2260 2260 2260
H mm 2430 2430 2430 2430
Operating weight kg * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

211
i-FX-Q / SL-CA
Models 0502 0602 0702 0802
COOLING ONLY
Cooling capacity (1) kW 479 592 681 777
Total power input (1) kW 158 207 245 273
EER 3,03 2,86 2,78 2,85
HEATING ONLY
Heating capacity (2) kW 523 649 750 847
Total power input (2) kW 152 191 220 244
COP 3,44 3,40 3,41 3,47
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 485 613 715 814
Heat recovery capacity (3) kW 624 787 917 1040
Total power input (3) kW 147 185 215 240
TER (4) - 7,54 7,57 7,59 7,72
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (5) dB(A) * * * *
Sound pressure (6) dB(A) * * * *
SIZE
A mm 7800 9000 9000 9900
B mm 2260 2260 2260 2260
H mm 2430 2430 2430 2430
Operating weight kg * * * *

Note:
1 Evaporator water (in/out) = 12/7°C; Condenser air (in) = 35°C.
2 Condenser water (in/out) = 40/45°C; evaporator air (in) = 7°C - r.h. 87%.
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


0502-0802
Switchboard side mm 1800
Switchboard opposite side mm 1500
Condensation coil side mm 2000

212
213
INTEGRA

NECS-WQ 0152÷1604
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0)
INTEGRATED CONDENSATION´S CONTROL
A 2 way valve is supplied as standard for the condensing
pressure control. For all the applications in which a
constant waterflow through the condenser is needed, a
3-way valve option is also available under request.
ENERGY SAVING
Energy saving guaranteed by the advanced operations
logic. The best operation mode is set completely
automatically and independently by the units controller,
in order to minimize the absorbed energy whatever the
cooling and/or heating demand might be
HOT WATER SUPPLY
Production of hot water up to 54°C to meet the most
demanding application needs.

Main accessories
INTEGRA unit for 4-pipe systems, water UÊRemote keyboard (distance to 200m and to 500m)
UÊSet-up for remote connectivity with ModBus, Echelon
source LonTalk, Bacnet protocol board
UÊAcoustical enclosure to reduce the noise emissions.
45,7 - 491 kW UÊWater connections directed upwards (for 2 compressors
units only)
Unit Description
Multi-purpose indoor unit for use in 4-pipe systems for the simultaneous production of chilled
and hot water by means of two independent water circuits. These units are able to satisfy
the demand for hot and cold water simultaneously through a system that does not require
seasonal switching. Water-source unit equipped with hermetic rotary Scroll compressors, with
R410A, plate heat exchangers and thermostatic expansion valve. The range is composed by
units equipped with two and four compressors, all with two independent refrigerant circuits.

Commands
W3000 large
The controller W3000 large offers the latest control and functions developed directly by Climaveneta on the basis of their
experience gained over the years with these particular units and the related plant engineering. The keypad is generously
sized with full operating status display. The controls and detailed LCD make access to machine settings easy and safe.
Temperature regulation managed on the two water circuits, with a proportional logic referred to the return water temperatures.
This allows to satisfy simultaneously the different heating- and cooling requests, with no need of mode changeover.
The diagnostics includes full management of alarms with black-box functions and alarm record for better analysis of
unit performance. Supervision is easy through Climaveneta devices or with various options for interfacing to ModBus,
Bacnet, Echelon LonTalk protocols. Compatibility with remote keyboard (management up to 10 units). Clock available with
programming of operation (standard 4 days and 10 time bands). Exclusive self-adaptive defrost logic, monitoring multiple
operational- and ambient parameters, which allows to reduce the number and duration of the defrost cycles, with a benefit
for the overall energy efficiency.

214
4 PIPE
r HFC
R-410A
PLATES SCROLL SYSTEM

NECS-WQ / B
Models 0152 0182 0202 0252 0262 0302 0412 0512 0612
COOLING ONLY
Cooling capacity (1) kW 48,6 55,8 65 73,8 83,2 97,5 127 159 206
Total power input (1) kW 8,70 9,80 11,3 13,2 14,7 17,4 22,7 28,1 36,5
EER 5,59 5,69 5,75 5,59 5,66 5,60 5,59 5,64 5,63
HEATING ONLY
Heating capacity (2) kW 52,1 59,7 69,3 79 88,9 104 135 169 219
Total power input (2) kW 12,4 13,8 16,2 18,5 20,4 23,9 31 38,4 49,9
COP 4,20 4,33 4,28 4,28 4,36 4,37 435 4,40 4,38
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 40,4 46,7 54,1 61,7 67,9 82 106 133 172
Heat recovery capacity (3) kW 52,1 59,7 69,3 79 88,9 104 135 169 219
Total power input (3) kW 12,4 13,8 16,2 18,5 20,4 23,9 31 38,4 49,9
TER (4) - 7,46 7,71 7,62 7,61 7,69 7,78 7,77 7,86 7,84
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Total power input kW
Sound power (5) dB(A) 73 74 74 74 75 76 77 78 79
Sound pressure (6) dB(A) 42 43 43 43 44 45 46 47 48
SIZE
A (7) mm 1222 1222 1222 1222 1222 1222 1222 1222 1222
B (7) mm 893 893 893 893 893 893 893 893 893
H (7) mm 1496 1496 1496 1496 1496 1496 1496 1496 1496
Operating weight (7) kg 450 470 490 505 525 550 745 825 910

Models 0604 0704 0804 0904 1004 1104 1204 1404 1604
COOLING ONLY
Cooling capacity (1) kW 194 225 255 285 317 365 413 468 522
Total power input (1) kW 34,8 40 45,3 50,8 56,3 64,8 73 84,1 95,1
EER 5,58 5,63 5,62 5,61 5,63 5,63 5,66 5,56 5,49
HEATING ONLY
Heating capacity (2) kW 208 240 270 303 338 388 440 498 557
Total power input (2) kW 47,7 54,7 61,8 69,2 76,8 88,4 99,6 113 126
COP 4,36 4,38 4,37 4,38 4,40 4,39 4,41 4,41 4,42
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 163 188 212 238 266 305 346 392 438
Heat recovery capacity (3) kW 208 240 270 303 338 388 440 498 557
Total power input (3) kW 47,7 54,7 61,8 69,2 76,8 88,4 99,6 113 126
TER (4) - 7,78 7,82 7,80 7,82 7,86 7,84 7,89 7,88 7,90
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Total power input kW
Sound power (5) dB(A) 86 87 88 89 90 91 91 91 91
Sound pressure (6) dB(A) 54 55 56 57 58 59 59 59 59
SIZE
A (7) mm 2520 2520 2520 2520 2520 2520 2520 2520 2520
B (7) mm 880 880 880 880 880 880 880 880 880
H (7) mm 1810 1810 1810 1810 1810 1810 1810 1810 1810
Operating weight (7) kg 975 1165 1365 1445 1610 1710 1810 1895 2000
Note:
1 Evaporator water (in/out) = 12/7°C; condenser water (in/out) = 14/30°C
2 Condenser water (in/out) = 40/45°C; evaporator water (in/out) = 14/7°C
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 1 m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
7 Unit in standard configuration/execution, without optional accessories
Minimum clearance required
0152-0612 0604-1604
Switchboard side mm 800 1000
Switchboard opposite side mm 800 1000
Condensation coil side mm 800 800

H H

A
B B A

215
INTEGRA

ERACS2-WQ 0802÷3202
Versions
- base version

Features
UNIQUE PROPOSAL
Unit designed to satisfy the cold and the hot side
requirements simultaneously, for 4-pipe systems without
any particular operation mode setting
ENERGY SAVING
Energy saving guaranteed by the advanced operations
logic. The best operation mode is set completely
automatically and independently by the units controller,
in order to minimize the absorbed energy whatever the
cooling and/or heating demand might be
EXTENSIVE RANGE OF OPERATION
Supply of hot water in use up to 55°C, offering maximum
versatility with respect to different plant engineering
solutions
INTEGRATED CONDENSATION´S CONTROL
A 2 way valve is supplied as standard for the condensing
pressure control. For all the applications in which a
constant waterflow through the condenser is needed, a
3-way valve option is also available under request.

INTEGRA unit for 4-pipe systems, water Main accessories


UÊIntegral acoustical enclosure (type base or plus)
source UÊSeveral devices for condensation´s control
UÊElectronic expansion valve
194 - 891 kW UÊSet-up for remote connectivity with ModBus/Echelon/
Bacnet protocol cards
Unit Description
Multi-purpose indoor unit for use in 4-pipe systems for the simultaneous production of
chilled and hot water by means of two independent water circuits. These units are able to
satisfy the demand for hot and cold water simultaneously through a system that does not
require seasonal switching. Each circuit works with a semi-hermetic screw compressor using
R134a, and three tube nest heat exchangers, a cold exchanger on the user side shared by
both circuits that acts as an evaporator in the production of cold water, a heat exchanger on
the user side that words as a condenser in the production of hot water, and a source side
exchanger that works as either condenser or evaporator as required by the loads.

Commands
W3000SE Large
The W3000SE Large controller offers advanced functions and algorithms. The keypad features an easy-to-use interface
and a complete LCD display, allowing to consult and intervene on the unit by means of a multi-level menu, with selectable
language setting. The regulation operates on both water circuits featuring the step-wise regulation referred to the return
water temperature with proportional logic. This allows to satisfy simultaneously the different requests of both cooling and
heating, with no need of mode setting. The diagnostics includes a complete alarm management, with the “black-box”
and alarm logging functions for enhanced analysis of the unit operation. For multiple units systems, the regulation of the
resources, via optional proprietary devices, can be implemented. Energy metering, for both consumption and capacity, can
also be developed. Supervision can be easily developed via proprietary devices or the integration in third party systems
by means of the most common protocols as ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks. Compatibility with the
remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day profiles
with 10 hour belts).

216
4 PIPE
r HFC
R-134a
SHELL & TUBES SCREW SYSTEM

ERACS2-WQ / -
Models 0802 1002 1102 1302 1502 1702 1902 2152 2502 2602 2702 3202
COOLING ONLY
Cooling capacity (1) kW 194 240 275 326 373 435 479 554 648 703 781 891
Total power input (1) kW 34,3 43,2 48,5 57,2 66,1 76,5 85,7 94,5 111 121 135 153
EER 5,66 5,56 5,66 5,69 5,64 5,68 5,58 5,87 5,83 5,83 5,80 5,81
HEATING ONLY
Heating capacity (2) kW 205 255 291 344 393 459 514 589 686 738 831 941
Total power input (2) kW 45,7 57 65,9 76,3 86,9 103 117 128 149 158 180 205
COP 4,49 4,47 4,42 4,51 4,52 4,44 4,40 4,59 4,62 4,68 4,62 4,59
COOLING WITH TOTAL RECOVERY
Cooling capacity (3) kW 162 201 229 272 311 362 404 468 547 589 662 748
Heat recovery capacity (3) kW 205 255 291 344 393 459 514 589 686 738 831 941
Total power input (3) kW 45,7 57 65,9 76,3 86,9 103 117 128 149 158 180 205
TER (4) - 8,03 8,00 7,89 8,07 8,10 7,97 7,85 8,26 8,28 8,40 8,29 8,24
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Total power input kW
Sound power (5) dB(A) 94 95 97 97 97 97 97 98 99 99 99 99
Sound pressure (6) dB(A) 76 77 79 79 79 79 78 79 80 80 80 80
SIZE
A (7) mm 3680 3680 3680 3680 3680 3680 3800 3800 3800 5000 5000 5000
B (7) mm 1170 1170 1170 1170 1170 1170 1490 1490 1490 1490 1490 1490
H (7) mm 1950 1950 1950 1950 1950 1950 1950 1950 1950 2050 2050 2050
Operating weight (7) kg * * * * * * * * * * * *
Note:
1 Evaporator water (in/out) = 12/7°C; condenser water (in/out) = 14/30°C
2 Condenser water (in/out) = 40/45°C; evaporator water (in/out) = 14/7°C
3 Evaporator water (in/out) = 12/7°C; Recovery unit water (in/out) = 40/45°C
4 TER := Total Efficiency Ratio = (Cooling capacity + Heating capacity) / (Total power input)
5 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
6 Average sound pressure level, at 1 m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
7 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0802-3202
Switchboard side mm 800
Switchboard opposite side mm 500
Condensation coil side mm 500

217
RONIC
N TEEER
218
RMINALS hydronic terminals

terminals
hydronic

219
Hydronic terminals

a-LIFE 120÷840
Versions
DFI built-in version, front air intake
DFU version with cabinet, front air intake
DLI built-in version, bottom air intake
DLU version with cabinet, bottom air intake

Features
Low noise centrifugal fan, with double intake and forward
blade;
Four pipe system: 3+2 and 4+1 (number of rows for main
+ additional coil);
6-speed autotransformer;
Air filter on all models;
Cabinet in galvanised steel with prevarnished finish for
maximum resistance to rust;
Automatically closing flap to cover and protect electric
controls from dripping water (in conformity with directive
60335-2-40);

Main accessories
UÊHot water coil kit 1 row and 2 rows
UÊKit RS485 - interface for Building Management System
UÊKit control board to manage 0-10V or 3 points
modulating valve unit
Fan-coil for professional applications, with UÊMain coil valve unit ON/OFF, 0-10 V, 3 points 2-way or
3-way
cabinet or built-in version UÊAdditional coil valve unit ON/OFF, PWM, 0-10 V, 3 points
3-way or 2-way
UÊKit LIFE BOX
1,45 - 11,9 kW UÊStraight and angular (90°) plenum kits for air inlet
Unit Description UÊStraight and angular (90°) plenum kits for air outlet
a-LIFE fan-coil has been specifically developed to adapt to every ambient thanks to UÊPlenum kit with round air ducts for plenum kit
its modern and minimal design, which is a result of the full experience and know-how UÊElectric heaters
Climaveneta has in this range of products.

Commands
NS plug-in/NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PS plug-in/PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MT plug-in/MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
AT plug-in/ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.

220
CONTROLLER FAN COIL CENTRIFUGAL 4 PIPES 2 PIPES

a-LIFE / DLU
Models 120 130 140 220 230 240 320 330 340 420 430
Air flow rate
Speed 1 m3/h 430 410 390 500 480 450 510 485 460 830 815
Speed 2 m3/h 390 360 340 430 410 380 440 415 390 700 680
Speed 3 m3/h 330 315 290 365 350 320 375 355 330 580 565
Speed 4 m3/h 290 270 250 310 300 270 320 305 280 480 470
Speed 5 m3/h 220 200 180 240 225 210 250 230 220 330 315
Speed 6 m3/h 180 175 160 210 200 180 220 205 190 280 270
Total output cooling capacity (1)
Speed 1 (1) kW 1,45 1,91 2,32 2,13 2,67 3,20 2,76 3,22 3,68 3,77 4,69
Speed 2 (1) kW 1,37 1,75 2,10 1,93 2,37 2,81 2,49 2,86 3,23 3,39 4,14
Speed 3 (1) kW 1,24 1,59 1,87 1,72 2,10 2,46 2,23 2,53 2,79 3 3,62
Speed 4 (1) kW 1,14 1,42 1,67 1,53 1,85 2,13 1,99 2,24 2,42 2,64 3,16
Speed 5 (1) kW 0,96 1,11 1,27 1,26 1,42 1,71 1,65 1,77 1,97 2,02 2,31
Speed 6 (1) kW 0,84 0,97 1,16 1,13 1,23 1,48 1,49 1,59 1,64 1,79 2,03
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,36 1,63 1,77 1,89 2,17 2,41 2,26 2,47 2,68 3,25 3,77
Speed 2 (1) kW 1,27 1,47 1,58 1,68 1,91 2,09 2,01 2,17 2,34 2,86 3,27
Speed 3 (1) kW 1,13 1,32 1,39 1,48 1,67 1,82 1,77 1,90 2,01 2,48 2,82
Speed 4 (1) kW 1,03 1,16 1,23 1,30 1,46 1,56 1,56 1,67 1,73 2,15 2,42
Speed 5 (1) kW 0,83 0,89 0,93 1,04 1,11 1,24 1,27 1,30 1,40 1,59 1,72
Speed 6 (1) kW 0,71 0,78 0,84 0,93 0,97 1,07 1,14 1,17 1,18 1,39 1,50
Max Water flow (1) l/h 250 330 400 370 460 550 470 550 630 650 800
Max Pressure drop (1) kPa 12 5 10 6 5 8 11 7 5 19 14
Total output heating capacity (2)
Speed 1 (2) kW 3,25 4,46 5,01 4,77 5,79 6,28 5,40 6,36 6,76 7,68 9,58
Speed 2 (2) kW 3,04 4,04 4,49 4,28 5,12 5,44 4,84 5,60 5,85 6,81 8,33
Speed 3 (2) kW 2,72 3,66 3,94 3,79 4,51 4,70 4,28 4,92 5,05 5,94 7,19
Speed 4 (2) kW 2,49 3,25 3,49 3,36 3,98 4,05 3,79 4,33 4,36 5,16 6,20
Speed 5 (2) kW 2,05 2,56 2,64 2,76 3,13 3,24 3,11 3,39 3,50 3,88 4,45
Speed 6 (2) kW 1,77 2,30 2,38 2,49 2,83 2,82 2,81 3,07 3,05 3,41 3,90
Max Water flow (2) l/h 350 390 440 420 510 550 470 560 590 670 840
Max Pressure drop (2) kPa 10 5 8 5 4 7 9 6 5 16 12
Total output heating capacity (3)
Speed 1 (3) kW 1,98 2,71 3,04 2,91 3,52 3,80 3,29 3,86 4,09 4,69 5,83
Speed 2 (3) kW 1,86 2,46 2,72 2,61 3,11 3,30 2,94 3,40 3,54 4,15 5,06
Speed 3 (3) kW 1,66 2,22 2,39 2,31 2,74 2,84 2,60 2,98 3,05 3,62 4,37
Speed 4 (3) kW 1,52 1,97 2,11 2,04 2,41 2,45 2,30 2,62 2,63 3,14 3,76
Speed 5 (3) kW 1,25 1,55 1,60 1,68 1,90 1,96 1,89 2,05 2,09 2,36 2,69
Speed 6 (3) kW 1,08 1,39 1,44 1,51 1,72 1,70 1,71 1,85 1,80 2,07 2,36
Water flow Max (3) l/h 350 470 530 510 610 660 570 670 710 820 1020
Pressure drop Max (3) kPa 11 5 8 5 5 7 10 6 5 17 13
Output supplementary coil (2)
Speed 1 (2) kW 1,48 1,48 - 2,12 2,12 - 2,48 2,48 - 3,48 3,48
Speed 2 (2) kW 1,37 1,37 - 1,92 1,92 - 2,24 2,24 - 3,13 3,13
Speed 3 (2) kW 1,26 1,26 - 1,74 1,74 - 2,02 2,02 - 2,78 2,78
Speed 4 (2) kW 1,15 1,15 - 1,57 1,57 - 1,82 1,82 - 2,46 2,46
Speed 5 (2) kW 0,95 0,95 - 1,30 1,30 - 1,50 1,50 - 1,92 1,92
Speed 6 (2) kW 0,87 0,87 - 1,20 1,20 - 1,39 1,39 - 1,72 1,72
Water flow Max (2) l/h 130 130 - 190 190 - 220 220 - 310 310
Pressure drop Max (2) kPa 2 2 - 4 4 - 7 7 - 13 13
Sound pressure level (4)
Speed 1 (4) dB(A) 46 46 47 48 48 49 48 48 49 51 51
Speed 2 (4) dB(A) 41 41 42 44 44 45 44 44 45 47 47
Speed 3 (4) dB(A) 38 38 39 40 40 41 40 40 41 43 43
Speed 4 (4) dB(A) 35 35 36 37 37 38 37 37 38 41 41
Speed 5 (4) dB(A) 30 30 31 30 30 31 31 31 32 33 33
Speed 6 (4) dB(A) 28 28 29 29 29 30 29 29 30 30 30
Water content l 0,50 0,70 0,70 0,70 1 1 1 1,40 1,40 1 1,40
Fan 1C 1C 1C 1C 1C 1C 1C 1C 1C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 66 66 66 77 77 77 93 93 93 130 130
Max absorbed current A 0,29 0,29 0,29 0,30 0,30 0,30 0,41 0,41 0,41 0,57 0,57
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 732 732 732 922 922 922 1112 1112 1112 1112 1112
H (mm) 541 541 541 541 541 541 541 541 541 541 541
P (mm) 233 233 233 233 233 233 233 233 233 233 233
Weight kg 18 18 18 22 22 22 26 26 26 28 28

221
Models 440 520 530 540 620 630 640 720 730 740
Air flow rate
Speed 1 m3/h 790 950 915 880 940 925 900 1360 1310 1260
Speed 2 m3/h 660 815 780 750 810 790 770 1150 1090 1070
Speed 3 m3/h 454 710 680 655 710 685 670 970 920 880
Speed 4 m3/h 455 610 585 560 600 590 560 790 740 700
Speed 5 m3/h 300 460 440 420 460 445 440 640 590 570
Speed 6 m3/h 260 400 390 380 410 400 390 480 440 430
Total output cooling capacity (1)
Speed 1 (1) kW 5,57 4,66 5,75 6,54 5,18 6,92 7,47 6,59 8,94 9,64
Speed 2 (1) kW 4,87 4,21 5,13 5,80 4,68 6,16 6,57 5,92 7,81 8,54
Speed 3 (1) kW 4,22 3,84 4,65 5,26 4,26 5,53 5,84 5,29 6,89 7,30
Speed 4 (1) kW 3,65 3,45 4,15 4,63 3,77 4,88 5,08 4,60 5,87 6,02
Speed 5 (1) kW 2,56 2,81 3,36 3,66 3,09 3,90 4,14 3,96 4,88 5,13
Speed 6 (1) kW 2,28 2,52 3,05 3,38 2,83 3,58 3,71 3,20 3,87 4,03
Sensible output cooling capacity (1)
Speed 1 (1) kW 4,20 3,95 4,50 4,86 4,23 5,13 5,40 5,61 6,81 7,12
Speed 2 (1) kW 3,62 3,51 3,96 4,27 3,76 4,52 4,72 4,94 5,86 6,24
Speed 3 (1) kW 3,10 3,15 3,54 3,84 3,38 4,03 4,17 4,33 5,11 5,28
Speed 4 (1) kW 2,66 2,79 3,12 3,35 2,95 3,53 3,59 3,68 4,30 4,31
Speed 5 (1) kW 1,84 2,22 2,48 2,61 2,37 2,78 2,82 3,11 3,53 3,63
Speed 6 (1) kW 1,63 1,97 2,24 2,40 2,15 2,54 2,50 2,45 2,75 2,82
Max Water flow (1) l/h 960 800 990 1120 890 1190 1280 1130 1530 1650
Max Pressure drop (1) kPa 11 11 22 18 16 18 14 24 27 23
Total output heating capacity (2)
Speed 1 (2) kW 10,7 9,92 11,2 12,3 10,8 13,1 13,5 13,7 17,4 18
Speed 2 (2) kW 9,18 8,86 9,88 10,7 9,61 11,4 11,8 12,2 15 15,7
Speed 3 (2) kW 7,81 7,98 8,85 9,56 8,68 10,1 10,4 10,7 13 13,3
Speed 4 (2) kW 6,69 7,11 7,83 8,34 7,61 8,88 8,85 9,16 10,8 10,8
Speed 5 (2) kW 4,63 5,70 6,18 6,47 6,15 6,91 7,09 7,78 8,88 8,99
Speed 6 (2) kW 4,07 5,09 5,58 5,91 5,59 6,28 6,33 6,18 6,84 6,94
Max Water flow (2) l/h 930 870 980 1080 950 1150 1190 1210 1530 1580
Max Pressure drop (2) kPa 10 10 19 15 14 11 12 21 22 19
Total output heating capacity (3)
Speed 1 (3) kW 6,46 6,04 6,81 7,44 6,67 7,93 8,25 8,37 10,6 11
Speed 2 (3) kW 5,57 5,39 6 6,50 5,93 6,93 7,19 7,40 9,10 9,55
Speed 3 (3) kW 4,73 4,86 5,37 5,79 5,33 6,12 6,35 6,52 7,89 8,05
Speed 4 (3) kW 4,05 4,32 4,75 5,05 4,73 5,37 5,33 5,57 6,55 6,57
Speed 5 (3) kW 2,80 3,46 3,75 3,91 3,77 4,18 4,19 4,73 5,37 5,42
Speed 6 (3) kW 2,46 3,09 3,38 3,57 3,36 3,79 3,72 3,75 4,13 4,10
Water flow Max (3) l/h 1130 1050 1190 1300 1160 1380 1440 1460 1850 1920
Pressure drop Max (3) kPa 10 10 20 16 14 16 12 22 24 21
Output supplementary coil (2)
Speed 1 (2) kW - 4,11 4,11 - 4,52 4,52 - 5,62 5,62 -
Speed 2 (2) kW - 3,71 3,71 - 4,09 4,09 - 5,02 5,02 -
Speed 3 (2) kW - 3,40 3,40 - 3,72 3,72 - 4,51 4,51 -
Speed 4 (2) kW - 3,09 3,09 - 3,37 3,37 - 3,92 3,92 -
Speed 5 (2) kW - 2,55 2,55 - 2,78 2,78 - 3,37 3,37 -
Speed 6 (2) kW - 2,35 2,35 - 2,59 2,59 - 2,76 2,76 -
Water flow Max (2) l/h - 360 360 - 400 400 - 490 490 -
Pressure drop Max (2) kPa - 20 20 - 24 24 - 35 35 -
Sound pressure level (4)
Speed 1 (4) dB(A) 52 51 51 52 52 52 53 54 54 55
Speed 2 (4) dB(A) 48 47 47 48 48 48 49 49 49 50
Speed 3 (4) dB(A) 44 44 44 45 45 45 46 46 46 47
Speed 4 (4) dB(A) 42 40 40 42 41 41 42 41 41 42
Speed 5 (4) dB(A) 34 33 33 34 35 35 36 36 36 37
Speed 6 (4) dB(A) 31 30 30 31 33 33 34 33 33 34
Water content l 1 1,20 1,80 1,40 1,50 2,20 2,20 1,50 2,20 2,20
Fan 2C 2C 2C 2C 2C 2C 2C 3C 3C 3C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 130 150 150 150 165 165 165 245 245 245
Max absorbed current A 0,57 0,60 0,60 0,60 0,73 0,73 0,73 1,10 1,10 1,10
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 1112 1302 1302 1302 1492 1492 1492 1492 1492 1492
H (mm) 541 541 541 541 541 541 541 541 541 541
P (mm) 233 233 233 233 233 233 233 233 233 233
Weight kg 28 32 32 32 38 38 38 43 43 43
Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

222
a-LIFE / DFU
Models 120 130 140 220 230 240 320 330 340 420 430
Air flow rate
Speed 1 m3/h 430 410 390 500 480 450 510 485 460 830 815
Speed 2 m3/h 390 360 340 430 410 380 440 415 390 700 680
Speed 3 m3/h 330 315 290 365 350 320 375 355 330 580 565
Speed 4 m3/h 290 270 250 310 300 270 320 305 280 480 470
Speed 5 m3/h 220 200 180 240 225 210 250 230 220 330 315
Speed 6 m3/h 180 175 160 210 200 180 220 205 190 280 270
Total output cooling capacity (1)
Speed 1 (1) kW 1,45 1,91 2,32 2,13 2,67 3,20 2,76 3,22 3,68 3,77 4,69
Speed 2 (1) kW 1,37 1,75 2,10 1,93 2,37 2,81 2,49 2,86 3,23 3,39 4,14
Speed 3 (1) kW 1,24 1,59 1,87 1,72 2,10 2,46 2,23 2,53 2,79 3 3,62
Speed 4 (1) kW 1,14 1,42 1,67 1,53 1,85 2,13 1,99 2,24 2,42 2,64 3,16
Speed 5 (1) kW 0,96 1,11 1,27 1,26 1,42 1,71 1,65 1,77 1,97 2,02 2,31
Speed 6 (1) kW 0,84 0,97 1,16 1,13 1,23 1,48 1,49 1,59 1,64 1,79 2,03
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,36 1,63 1,77 1,89 2,17 2,41 2,26 2,47 2,68 3,25 3,77
Speed 2 (1) kW 1,27 1,47 1,58 1,68 1,91 2,09 2,01 2,17 2,34 2,86 3,27
Speed 3 (1) kW 1,13 1,32 1,39 1,48 1,67 1,82 1,77 1,90 2,01 2,48 2,82
Speed 4 (1) kW 1,03 1,16 1,23 1,30 1,46 1,56 1,56 1,67 1,73 2,15 2,42
Speed 5 (1) kW 0,83 0,89 0,93 1,04 1,11 1,24 1,27 1,30 1,40 1,59 1,72
Speed 6 (1) kW 0,71 0,78 0,84 0,93 0,97 1,07 1,14 1,17 1,18 1,39 1,50
Max Water flow (1) l/h 250 330 400 370 460 550 470 550 630 650 800
Max Pressure drop (1) kPa 12 5 10 6 5 8 11 7 5 19 14
Total output heating capacity (2)
Speed 1 (2) kW 3,25 4,46 5,01 4,77 5,79 6,28 5,40 6,36 6,76 7,68 9,58
Speed 2 (2) kW 3,04 4,04 4,49 4,28 5,12 5,44 4,84 5,60 5,85 6,81 8,33
Speed 3 (2) kW 2,72 3,66 3,94 3,79 4,51 4,70 4,28 4,92 5,05 5,94 7,19
Speed 4 (2) kW 2,49 3,25 3,49 3,36 3,98 4,05 3,79 4,33 4,36 5,16 6,20
Speed 5 (2) kW 2,05 2,56 2,64 2,76 3,13 3,24 3,11 3,39 3,50 3,88 4,45
Speed 6 (2) kW 1,77 2,30 2,38 2,49 2,83 2,82 2,81 3,07 3,05 3,41 3,90
Max Water flow (2) l/h 350 390 440 420 510 550 470 560 590 670 840
Max Pressure drop (2) kPa 10 5 8 5 4 7 9 6 5 16 12
Total output heating capacity (3)
Speed 1 (3) kW 1,98 2,71 3,04 2,91 3,52 3,80 3,29 3,86 4,09 4,69 5,83
Speed 2 (3) kW 1,86 2,46 2,72 2,61 3,11 3,30 2,94 3,40 3,54 4,15 5,06
Speed 3 (3) kW 1,66 2,22 2,39 2,31 2,74 2,84 2,60 2,98 3,05 3,62 4,37
Speed 4 (3) kW 1,52 1,97 2,11 2,04 2,41 2,45 2,30 2,62 2,63 3,14 3,76
Speed 5 (3) kW 1,25 1,55 1,60 1,68 1,90 1,96 1,89 2,05 2,09 2,36 2,69
Speed 6 (3) kW 1,08 1,39 1,44 1,51 1,72 1,70 1,71 1,85 1,80 2,07 2,36
Water flow Max (3) l/h 350 470 530 510 610 660 570 670 710 820 1020
Pressure drop Max (3) kPa 11 5 8 5 5 7 10 6 5 17 13
Output supplementary coil (2)
Speed 1 (2) kW 1,48 1,48 - 2,12 2,12 - 2,48 2,48 - 3,48 3,48
Speed 2 (2) kW 1,37 1,37 - 1,92 1,92 - 2,24 2,24 - 3,13 3,13
Speed 3 (2) kW 1,26 1,26 - 1,74 1,74 - 2,02 2,02 - 2,78 2,78
Speed 4 (2) kW 1,15 1,15 - 1,57 1,57 - 1,82 1,82 - 2,46 2,46
Speed 5 (2) kW 0,95 0,95 - 1,30 1,30 - 1,50 1,50 - 1,92 1,92
Speed 6 (2) kW 0,87 0,87 - 1,20 1,20 - 1,39 1,39 - 1,72 1,72
Water flow Max (2) l/h 130 130 - 190 190 - 220 220 - 310 310
Pressure drop Max (2) kPa 2 2 - 4 4 - 7 7 - 13 13
Sound pressure level (4)
Speed 1 (4) dB(A) 46 46 47 48 48 49 48 48 49 51 51
Speed 2 (4) dB(A) 41 41 42 44 44 45 44 44 45 47 47
Speed 3 (4) dB(A) 38 38 39 40 40 41 40 40 41 43 43
Speed 4 (4) dB(A) 35 35 36 37 37 38 37 37 38 41 41
Speed 5 (4) dB(A) 30 30 31 30 30 31 31 31 32 33 33
Speed 6 (4) dB(A) 28 28 29 29 29 30 29 29 30 30 30
Water content l 0,50 0,70 0,70 0,70 1 1 1 1,40 1,40 1 1,40
Fan 1C 1C 1C 1C 1C 1C 1C 1C 1C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 66 66 66 77 77 77 93 93 93 130 130
Max absorbed current A 0,29 0,29 0,29 0,30 0,30 0,30 0,41 0,41 0,41 0,57 0,57
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 732 732 732 922 922 922 1112 1112 1112 1112 1112
H (mm) 541 541 541 541 541 541 541 541 541 541 541
P (5) (mm) 245 245 245 245 245 245 245 245 245 245 245
Weight kg 18 18 18 22 22 22 26 26 26 28 28

223
Models 440 520 530 540 620 630 640 720 730 740
Air flow rate
Speed 1 m3/h 790 950 915 880 940 925 900 1360 1310 1260
Speed 2 m3/h 660 815 780 750 810 790 770 1150 1090 1070
Speed 3 m3/h 454 710 680 655 710 685 670 970 920 880
Speed 4 m3/h 455 610 585 560 600 590 560 790 740 700
Speed 5 m3/h 300 460 440 420 460 445 440 640 590 570
Speed 6 m3/h 260 400 390 380 410 400 390 480 440 430
Total output cooling capacity (1)
Speed 1 (1) kW 5,57 4,66 5,75 6,54 5,18 6,92 7,47 6,59 8,94 9,64
Speed 2 (1) kW 4,87 4,21 5,13 5,80 4,68 6,16 6,57 5,92 7,81 8,54
Speed 3 (1) kW 4,22 3,84 4,65 5,26 4,26 5,53 5,84 5,29 6,89 7,30
Speed 4 (1) kW 3,65 3,45 4,15 4,63 3,77 4,88 5,08 4,60 5,87 6,02
Speed 5 (1) kW 2,56 2,81 3,36 3,66 3,09 3,90 4,14 3,96 4,88 5,13
Speed 6 (1) kW 2,28 2,52 3,05 3,38 2,83 3,58 3,71 3,20 3,87 4,03
Sensible output cooling capacity (1)
Speed 1 (1) kW 4,20 3,95 4,50 4,86 4,23 5,13 5,40 5,61 6,81 7,12
Speed 2 (1) kW 3,62 3,51 3,96 4,27 3,76 4,52 4,72 4,94 5,86 6,24
Speed 3 (1) kW 3,10 3,15 3,54 3,84 3,38 4,03 4,17 4,33 5,11 5,28
Speed 4 (1) kW 2,66 2,79 3,12 3,35 2,95 3,53 3,59 3,68 4,30 4,31
Speed 5 (1) kW 1,84 2,22 2,48 2,61 2,37 2,78 2,82 3,11 3,53 3,63
Speed 6 (1) kW 1,63 1,97 2,24 2,40 2,15 2,54 2,50 2,45 2,75 2,82
Max Water flow (1) l/h 960 800 990 1120 890 1190 1280 1130 1530 1650
Max Pressure drop (1) kPa 11 11 22 18 16 18 14 24 27 23
Total output heating capacity (2)
Speed 1 (2) kW 10,7 9,92 11,2 12,3 10,8 13,1 13,5 13,7 17,4 18
Speed 2 (2) kW 9,18 8,86 9,88 10,7 9,61 11,4 11,8 12,2 15 15,7
Speed 3 (2) kW 7,81 7,98 8,85 9,56 8,68 10,1 10,4 10,7 13 13,3
Speed 4 (2) kW 6,69 7,11 7,83 8,34 7,61 8,88 8,85 9,16 10,8 10,8
Speed 5 (2) kW 4,63 5,70 6,18 6,47 6,15 6,91 7,09 7,78 8,88 8,99
Speed 6 (2) kW 4,07 5,09 5,58 5,91 5,59 6,28 6,33 6,18 6,84 6,94
Max Water flow (2) l/h 930 870 980 1080 950 1150 1190 1210 1530 1580
Max Pressure drop (2) kPa 10 10 19 15 14 11 12 21 22 19
Total output heating capacity (3)
Speed 1 (3) kW 6,46 6,04 6,81 7,44 6,67 7,93 8,25 8,37 10,6 11
Speed 2 (3) kW 5,57 5,39 6 6,50 5,93 6,93 7,19 7,40 9,10 9,55
Speed 3 (3) kW 4,73 4,86 5,37 5,79 5,33 6,12 6,35 6,52 7,89 8,05
Speed 4 (3) kW 4,05 4,32 4,75 5,05 4,73 5,37 5,33 5,57 6,55 6,57
Speed 5 (3) kW 2,80 3,46 3,75 3,91 3,77 4,18 4,19 4,73 5,37 5,42
Speed 6 (3) kW 2,46 3,09 3,38 3,57 3,36 3,79 3,72 3,75 4,13 4,10
Water flow Max (3) l/h 1130 1050 1190 1300 1160 1380 1440 1460 1850 1920
Pressure drop Max (3) kPa 10 10 20 16 14 16 12 22 24 21
Output supplementary coil (2)
Speed 1 (2) kW - 4,11 4,11 - 4,52 4,52 - 5,62 5,62 -
Speed 2 (2) kW - 3,71 3,71 - 4,09 4,09 - 5,02 5,02 -
Speed 3 (2) kW - 3,40 3,40 - 3,72 3,72 - 4,51 4,51 -
Speed 4 (2) kW - 3,09 3,09 - 3,37 3,37 - 3,92 3,92 -
Speed 5 (2) kW - 2,55 2,55 - 2,78 2,78 - 3,37 3,37 -
Speed 6 (2) kW - 2,35 2,35 - 2,59 2,59 - 2,76 2,76 -
Water flow Max (2) l/h - 360 360 - 400 400 - 490 490 -
Pressure drop Max (2) kPa - 20 20 - 24 24 - 35 35 -
Sound pressure level (4)
Speed 1 (4) dB(A) 52 51 51 52 52 52 53 54 54 55
Speed 2 (4) dB(A) 48 47 47 48 48 48 49 49 49 50
Speed 3 (4) dB(A) 44 44 44 45 45 45 46 46 46 47
Speed 4 (4) dB(A) 42 40 40 42 41 41 42 41 41 42
Speed 5 (4) dB(A) 34 33 33 34 35 35 36 36 36 37
Speed 6 (4) dB(A) 31 30 30 31 33 33 34 33 33 34
Water content l 1 1,20 1,80 1,40 1,50 2,20 2,20 1,50 2,20 2,20
Fan 2C 2C 2C 2C 2C 2C 2C 3C 3C 3C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 130 150 150 150 165 165 165 245 245 245
Max absorbed current A 0,57 0,60 0,60 0,60 0,73 0,73 0,73 1,10 1,10 1,10
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 1112 1302 1302 1302 1492 1492 1492 1492 1492 1492
H (mm) 541 541 541 541 541 541 541 541 541 541
P (5) (mm) 245 245 245 245 245 245 245 245 245 245
Weight kg 28 32 32 32 38 38 38 43 43 43

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground
5 Size related to the air inlet grille

224
a-LIFE / DLI
Models 120 130 140 220 230 240 320 330 340 420 430 440
Air flow rate
Speed 1 m3/h 430 410 390 500 480 450 510 485 460 830 815 790
Speed 2 m3/h 390 360 340 430 410 380 440 415 390 700 680 660
Speed 3 m3/h 330 315 290 365 350 320 375 355 330 580 565 454
Speed 4 m3/h 290 270 250 310 300 270 320 305 280 480 470 455
Speed 5 m3/h 220 200 180 240 225 210 250 230 220 330 315 300
Speed 6 m3/h 180 175 160 210 200 180 220 205 190 280 270 260
Total output cooling capacity (1)
Speed 1 (1) kW 1,45 1,91 2,32 2,13 2,67 3,20 2,76 3,22 3,68 3,77 4,69 5,57
Speed 2 (1) kW 1,37 1,75 2,10 1,93 2,37 2,81 2,49 2,86 3,23 3,39 4,14 4,87
Speed 3 (1) kW 1,24 1,59 1,87 1,72 2,10 2,46 2,23 2,53 2,79 3 3,62 4,22
Speed 4 (1) kW 1,14 1,42 1,67 1,53 1,85 2,13 1,99 2,24 2,42 2,64 3,16 3,65
Speed 5 (1) kW 0,96 1,11 1,27 1,26 1,42 1,71 1,65 1,77 1,97 2,02 2,31 2,56
Speed 6 (1) kW 0,84 0,97 1,16 1,13 1,23 1,48 1,49 1,59 1,64 1,79 2,03 2,28
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,36 1,63 1,77 1,89 2,17 2,41 2,26 2,47 2,68 3,25 3,77 4,20
Speed 2 (1) kW 1,27 1,47 1,58 1,68 1,91 2,09 2,01 2,17 2,34 2,86 3,27 3,62
Speed 3 (1) kW 1,13 1,32 1,39 1,48 1,67 1,82 1,77 1,90 2,01 2,48 2,82 3,10
Speed 4 (1) kW 1,03 1,16 1,23 1,30 1,46 1,56 1,56 1,67 1,73 2,15 2,42 2,66
Speed 5 (1) kW 0,83 0,89 0,93 1,04 1,11 1,24 1,27 1,30 1,40 1,59 1,72 1,84
Speed 6 (1) kW 0,71 0,78 0,84 0,93 0,97 1,07 1,14 1,17 1,18 1,39 1,50 1,63
Max Water flow (1) l/h 250 330 400 370 460 550 470 550 630 650 800 960
Max Pressure drop (1) kPa 12 5 10 6 5 8 11 7 5 19 14 11
Total output heating capacity (2)
Speed 1 (2) kW 3,25 4,46 5,01 4,77 5,79 6,28 5,40 6,36 6,76 7,68 9,58 10,7
Speed 2 (2) kW 3,04 4,04 4,49 4,28 5,12 5,44 4,84 5,60 5,85 6,81 8,33 9,18
Speed 3 (2) kW 2,72 3,66 3,94 3,79 4,51 4,70 4,28 4,92 5,05 5,94 7,19 7,81
Speed 4 (2) kW 2,49 3,25 3,49 3,36 3,98 4,05 3,79 4,33 4,36 5,16 6,20 6,69
Speed 5 (2) kW 2,05 2,56 2,64 2,76 3,13 3,24 3,11 3,39 3,50 3,88 4,45 4,63
Speed 6 (2) kW 1,77 2,30 2,38 2,49 2,83 2,82 2,81 3,07 3,05 3,41 3,90 4,07
Max Water flow (2) l/h 350 390 440 420 510 550 470 560 590 670 840 930
Max Pressure drop (2) kPa 10 5 8 5 4 7 9 6 5 16 12 10
Total output heating capacity (3)
Speed 1 (3) kW 1,98 2,71 3,04 2,91 3,52 3,80 3,29 3,86 4,09 4,69 5,83 6,46
Speed 2 (3) kW 1,86 2,46 2,72 2,61 3,11 3,30 2,94 3,40 3,54 4,15 5,06 5,57
Speed 3 (3) kW 1,66 2,22 2,39 2,31 2,74 2,84 2,60 2,98 3,05 3,62 4,37 4,73
Speed 4 (3) kW 1,52 1,97 2,11 2,04 2,41 2,45 2,30 2,62 2,63 3,14 3,76 4,05
Speed 5 (3) kW 1,25 1,55 1,60 1,68 1,90 1,96 1,89 2,05 2,09 2,36 2,69 2,80
Speed 6 (3) kW 1,08 1,39 1,44 1,51 1,72 1,70 1,71 1,85 1,80 2,07 2,36 2,46
Water flow Max (3) l/h 350 470 530 510 610 660 570 670 710 820 1020 1130
Pressure drop Max (3) kPa 11 5 8 5 5 7 10 6 5 17 13 10
Output supplementary coil (2)
Speed 1 (2) kW 1,48 1,48 - 2,12 2,12 - 2,48 2,48 - 3,48 3,48 -
Speed 2 (2) kW 1,37 1,37 - 1,92 1,92 - 2,24 2,24 - 3,13 3,13 -
Speed 3 (2) kW 1,26 1,26 - 1,74 1,74 - 2,02 2,02 - 2,78 2,78 -
Speed 4 (2) kW 1,15 1,15 - 1,57 1,57 - 1,82 1,82 - 2,46 2,46 -
Speed 5 (2) kW 0,95 0,95 - 1,30 1,30 - 1,50 1,50 - 1,92 1,92 -
Speed 6 (2) kW 0,87 0,87 - 1,20 1,20 - 1,39 1,39 - 1,72 1,72 -
Water flow Max (2) l/h 130 130 - 190 190 - 220 220 - 310 310 -
Pressure drop Max (2) kPa 2 2 - 4 4 - 7 7 - 13 13 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 46 47 48 48 49 48 48 49 51 51 52
Speed 2 (4) dB(A) 41 41 42 44 44 45 44 44 45 47 47 48
Speed 3 (4) dB(A) 38 38 39 40 40 41 40 40 41 43 43 44
Speed 4 (4) dB(A) 35 35 36 37 37 38 37 37 38 41 41 42
Speed 5 (4) dB(A) 30 30 31 30 30 31 31 31 32 33 33 34
Speed 6 (4) dB(A) 28 28 29 29 29 30 29 29 30 30 30 31
Water content l 0,50 0,70 0,70 0,70 1 1 1 1,40 1,40 1 1,40 1
Fan 1C 1C 1C 1C 1C 1C 1C 1C 1C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 66 66 66 77 77 77 93 93 93 130 130 130
Max absorbed current A 0,29 0,29 0,29 0,30 0,30 0,30 0,41 0,41 0,41 0,57 0,57 0,57
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 411 411 411 601 601 601 791 791 791 791 791 791
H (mm) 495 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225 225
Weight kg 12 12 14 15 15 17 18 18 20 20 20 22

225
Models 520 530 540 620 630 640 720 730 740 830 840
Air flow rate
Speed 1 m3/h 950 915 880 940 925 900 1360 1310 1260 1620 1580
Speed 2 m3/h 815 780 750 810 790 770 1150 1090 1070 1380 1340
Speed 3 m3/h 710 680 655 710 685 670 970 920 880 1165 1120
Speed 4 m3/h 610 585 560 600 590 560 790 740 700 930 880
Speed 5 m3/h 460 440 420 460 445 440 640 590 570 720 690
Speed 6 m3/h 400 390 380 410 400 390 480 440 430 520 480
Total output cooling capacity (1)
Speed 1 (1) kW 4,66 5,75 6,54 5,18 6,92 7,47 6,59 8,94 9,64 10,2 11,9
Speed 2 (1) kW 4,21 5,13 5,80 4,68 6,16 6,57 5,92 7,81 8,54 9,11 10,5
Speed 3 (1) kW 3,84 4,65 5,26 4,26 5,53 5,84 5,29 6,89 7,30 8,05 9,16
Speed 4 (1) kW 3,45 4,15 4,63 3,77 4,88 5,08 4,60 5,87 6,02 6,80 7,50
Speed 5 (1) kW 2,81 3,36 3,66 3,09 3,90 4,14 3,96 4,88 5,13 5,59 6,17
Speed 6 (1) kW 2,52 3,05 3,38 2,83 3,58 3,71 3,20 3,87 4,03 4,29 4,52
Sensible output cooling capacity (1)
Speed 1 (1) kW 3,95 4,50 4,86 4,23 5,13 5,40 5,61 6,81 7,12 7,97 8,82
Speed 2 (1) kW 3,51 3,96 4,27 3,76 4,52 4,72 4,94 5,86 6,24 7,01 7,71
Speed 3 (1) kW 3,15 3,54 3,84 3,38 4,03 4,17 4,33 5,11 5,28 6,11 6,65
Speed 4 (1) kW 2,79 3,12 3,35 2,95 3,53 3,59 3,68 4,30 4,31 5,07 5,38
Speed 5 (1) kW 2,22 2,48 2,61 2,37 2,78 2,82 3,11 3,53 3,63 4,11 4,37
Speed 6 (1) kW 1,97 2,24 2,40 2,15 2,54 2,50 2,45 2,75 2,82 3,11 3,07
Max Water flow (1) l/h 800 990 1120 890 1190 1280 1130 1530 1650 1750 2040
Max Pressure drop (1) kPa 11 22 18 16 18 14 24 27 23 24 22
Total output heating capacity (2)
Speed 1 (2) kW 9,92 11,2 12,3 10,8 13,1 13,5 13,7 17,4 18 20,3 22,4
Speed 2 (2) kW 8,86 9,88 10,7 9,61 11,4 11,8 12,2 15 15,7 17,9 19,5
Speed 3 (2) kW 7,98 8,85 9,56 8,68 10,1 10,4 10,7 13 13,3 15,6 16,7
Speed 4 (2) kW 7,11 7,83 8,34 7,61 8,88 8,85 9,16 10,8 10,8 13 13,5
Speed 5 (2) kW 5,70 6,18 6,47 6,15 6,91 7,09 7,78 8,88 8,99 10,4 10,9
Speed 6 (2) kW 5,09 5,58 5,91 5,59 6,28 6,33 6,18 6,84 6,94 7,85 7,78
Max Water flow (2) l/h 870 980 1080 950 1150 1190 1210 1530 1580 1780 1970
Max Pressure drop (2) kPa 10 19 15 14 11 12 21 22 19 20 19
Total output heating capacity (3)
Speed 1 (3) kW 6,04 6,81 7,44 6,67 7,93 8,25 8,37 10,6 11 12,4 13,7
Speed 2 (3) kW 5,39 6 6,50 5,93 6,93 7,19 7,40 9,10 9,55 10,9 11,9
Speed 3 (3) kW 4,86 5,37 5,79 5,33 6,12 6,35 6,52 7,89 8,05 9,47 10,2
Speed 4 (3) kW 4,32 4,75 5,05 4,73 5,37 5,33 5,57 6,55 6,57 7,85 8,21
Speed 5 (3) kW 3,46 3,75 3,91 3,77 4,18 4,19 4,73 5,37 5,42 6,31 6,57
Speed 6 (3) kW 3,09 3,38 3,57 3,36 3,79 3,72 3,75 4,13 4,10 4,75 4,57
Water flow Max (3) l/h 1050 1190 1300 1160 1380 1440 1460 1850 1920 2160 2380
Pressure drop Max (3) kPa 10 20 16 14 16 12 22 24 21 22 20
Output supplementary coil (2)
Speed 1 (2) kW 4,11 4,11 - 4,52 4,52 - 5,62 5,62 - 6,70 -
Speed 2 (2) kW 3,71 3,71 - 4,09 4,09 - 5,02 5,02 - 6,07 -
Speed 3 (2) kW 3,40 3,40 - 3,72 3,72 - 4,51 4,51 - 5,46 -
Speed 4 (2) kW 3,09 3,09 - 3,37 3,37 - 3,92 3,92 - 4,73 -
Speed 5 (2) kW 2,55 2,55 - 2,78 2,78 - 3,37 3,37 - 4 -
Speed 6 (2) kW 2,35 2,35 - 2,59 2,59 - 2,76 2,76 - 3,21 -
Water flow Max (2) l/h 360 360 - 400 400 - 490 490 - 590 -
Pressure drop Max (2) kPa 20 20 - 24 24 - 35 35 - 10 -
Sound pressure level (4)
Speed 1 (4) dB(A) 51 51 52 52 52 53 54 54 55 57 58
Speed 2 (4) dB(A) 47 47 48 48 48 49 49 49 50 53 54
Speed 3 (4) dB(A) 44 44 45 45 45 46 46 46 47 49 50
Speed 4 (4) dB(A) 40 40 42 41 41 42 41 41 42 43 44
Speed 5 (4) dB(A) 33 33 34 35 35 36 36 36 37 38 39
Speed 6 (4) dB(A) 30 30 31 33 33 34 33 33 34 31 32
Water content l 1,20 1,80 1,40 1,50 2,20 2,20 1,50 2,20 2,20 1,70 2,60
Fan 2C 2C 2C 2C 2C 2C 3C 3C 3C 4C 4C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 150 150 150 165 165 165 245 245 245 272 272
Max absorbed current A 0,60 0,60 0,60 0,73 0,73 0,73 1,10 1,10 1,10 1,03 1,03
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 981 981 981 1171 1171 1171 1171 1171 1171 1361 1361
H (mm) 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225
Weight kg 23 23 25 27 27 29 31 31 33 38 38

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

226
a-LIFE / DFI
Models 120 130 140 220 230 240 320 330 340 420 430 440
Air flow rate
Speed 1 m3/h 430 410 390 500 480 450 510 485 460 830 815 790
Speed 2 m3/h 390 360 340 430 410 380 440 415 390 700 680 660
Speed 3 m3/h 330 315 290 365 350 320 375 355 330 580 565 454
Speed 4 m3/h 290 270 250 310 300 270 320 305 280 480 470 455
Speed 5 m3/h 220 200 180 240 225 210 250 230 220 330 315 300
Speed 6 m3/h 180 175 160 210 200 180 220 205 190 280 270 260
Total output cooling capacity (1)
Speed 1 (1) kW 1,45 1,91 2,32 2,13 2,67 3,20 2,76 3,22 3,68 3,77 4,69 5,57
Speed 2 (1) kW 1,37 1,75 2,10 1,93 2,37 2,81 2,49 2,86 3,23 3,39 4,14 4,87
Speed 3 (1) kW 1,24 1,59 1,87 1,72 2,10 2,46 2,23 2,53 2,79 3 3,62 4,22
Speed 4 (1) kW 1,14 1,42 1,67 1,53 1,85 2,13 1,99 2,24 2,42 2,64 3,16 3,65
Speed 5 (1) kW 0,96 1,11 1,27 1,26 1,42 1,71 1,65 1,77 1,97 2,02 2,31 2,56
Speed 6 (1) kW 0,84 0,97 1,16 1,13 1,23 1,48 1,49 1,59 1,64 1,79 2,03 2,28
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,36 1,63 1,77 1,89 2,17 2,41 2,26 2,47 2,68 3,25 3,77 4,20
Speed 2 (1) kW 1,27 1,47 1,58 1,68 1,91 2,09 2,01 2,17 2,34 2,86 3,27 3,62
Speed 3 (1) kW 1,13 1,32 1,39 1,48 1,67 1,82 1,77 1,90 2,01 2,48 2,82 3,10
Speed 4 (1) kW 1,03 1,16 1,23 1,30 1,46 1,56 1,56 1,67 1,73 2,15 2,42 2,66
Speed 5 (1) kW 0,83 0,89 0,93 1,04 1,11 1,24 1,27 1,30 1,40 1,59 1,72 1,84
Speed 6 (1) kW 0,71 0,78 0,84 0,93 0,97 1,07 1,14 1,17 1,18 1,39 1,50 1,63
Max Water flow (1) l/h 250 330 400 370 460 550 470 550 630 650 800 960
Max Pressure drop (1) kPa 12 5 10 6 5 8 11 7 5 19 14 11
Total output heating capacity (2)
Speed 1 (2) kW 3,25 4,46 5,01 4,77 5,79 6,28 5,40 6,36 6,76 7,68 9,58 10,7
Speed 2 (2) kW 3,04 4,04 4,49 4,28 5,12 5,44 4,84 5,60 5,85 6,81 8,33 9,18
Speed 3 (2) kW 2,72 3,66 3,94 3,79 4,51 4,70 4,28 4,92 5,05 5,94 7,19 7,81
Speed 4 (2) kW 2,49 3,25 3,49 3,36 3,98 4,05 3,79 4,33 4,36 5,16 6,20 6,69
Speed 5 (2) kW 2,05 2,56 2,64 2,76 3,13 3,24 3,11 3,39 3,50 3,88 4,45 4,63
Speed 6 (2) kW 1,77 2,30 2,38 2,49 2,83 2,82 2,81 3,07 3,05 3,41 3,90 4,07
Max Water flow (2) l/h 350 390 440 420 510 550 470 560 590 670 840 930
Max Pressure drop (2) kPa 10 5 8 5 4 7 9 6 5 16 12 10
Total output heating capacity (3)
Speed 1 (3) kW 1,98 2,71 3,04 2,91 3,52 3,80 3,29 3,86 4,09 4,69 5,83 6,46
Speed 2 (3) kW 1,86 2,46 2,72 2,61 3,11 3,30 2,94 3,40 3,54 4,15 5,06 5,57
Speed 3 (3) kW 1,66 2,22 2,39 2,31 2,74 2,84 2,60 2,98 3,05 3,62 4,37 4,73
Speed 4 (3) kW 1,52 1,97 2,11 2,04 2,41 2,45 2,30 2,62 2,63 3,14 3,76 4,05
Speed 5 (3) kW 1,25 1,55 1,60 1,68 1,90 1,96 1,89 2,05 2,09 2,36 2,69 2,80
Speed 6 (3) kW 1,08 1,39 1,44 1,51 1,72 1,70 1,71 1,85 1,80 2,07 2,36 2,46
Water flow Max (3) l/h 350 470 530 510 610 660 570 670 710 820 1020 1130
Pressure drop Max (3) kPa 11 5 8 5 5 7 10 6 5 17 13 10
Output supplementary coil (2)
Speed 1 (2) kW 1,48 1,48 - 2,12 2,12 - 2,48 2,48 - 3,48 3,48 -
Speed 2 (2) kW 1,37 1,37 - 1,92 1,92 - 2,24 2,24 - 3,13 3,13 -
Speed 3 (2) kW 1,26 1,26 - 1,74 1,74 - 2,02 2,02 - 2,78 2,78 -
Speed 4 (2) kW 1,15 1,15 - 1,57 1,57 - 1,82 1,82 - 2,46 2,46 -
Speed 5 (2) kW 0,95 0,95 - 1,30 1,30 - 1,50 1,50 - 1,92 1,92 -
Speed 6 (2) kW 0,87 0,87 - 1,20 1,20 - 1,39 1,39 - 1,72 1,72 -
Water flow Max (2) l/h 130 130 - 190 190 - 220 220 - 310 310 -
Pressure drop Max (2) kPa 2 2 - 4 4 - 7 7 - 13 13 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 46 47 48 48 49 48 48 49 51 51 52
Speed 2 (4) dB(A) 41 41 42 44 44 45 44 44 45 47 47 48
Speed 3 (4) dB(A) 38 38 39 40 40 41 40 40 41 43 43 44
Speed 4 (4) dB(A) 35 35 36 37 37 38 37 37 38 41 41 42
Speed 5 (4) dB(A) 30 30 31 30 30 31 31 31 32 33 33 34
Speed 6 (4) dB(A) 28 28 29 29 29 30 29 29 30 30 30 31
Water content l 0,50 0,70 0,70 0,70 1 1 1 1,40 1,40 1 1,40 1
Fan 1C 1C 1C 1C 1C 1C 1C 1C 1C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 66 66 66 77 77 77 93 93 93 130 130 130
Max absorbed current A 0,29 0,29 0,29 0,30 0,30 0,30 0,41 0,41 0,41 0,57 0,57 0,57
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 411 411 411 601 601 601 791 791 791 791 791 791
H (mm) 495 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225 225
Weight kg 12 12 14 15 15 17 18 18 20 20 20 22

227
Models 520 530 540 620 630 640 720 730 740 830 840
Air flow rate
Speed 1 m3/h 950 915 880 940 925 900 1360 1310 1260 1620 1580
Speed 2 m3/h 815 780 750 810 790 770 1150 1090 1070 1380 1340
Speed 3 m3/h 710 680 655 710 685 670 970 920 880 1165 1120
Speed 4 m3/h 610 585 560 600 590 560 790 740 700 930 880
Speed 5 m3/h 460 440 420 460 445 440 640 590 570 720 690
Speed 6 m3/h 400 390 380 410 400 390 480 440 430 520 480
Total output cooling capacity (1)
Speed 1 (1) kW 4,66 5,75 6,54 5,18 6,92 7,47 6,59 8,94 9,64 10,2 11,9
Speed 2 (1) kW 4,21 5,13 5,80 4,68 6,16 6,57 5,92 7,81 8,54 9,11 10,5
Speed 3 (1) kW 3,84 4,65 5,26 4,26 5,53 5,84 5,29 6,89 7,30 8,05 9,16
Speed 4 (1) kW 3,45 4,15 4,63 3,77 4,88 5,08 4,60 5,87 6,02 6,80 7,50
Speed 5 (1) kW 2,81 3,36 3,66 3,09 3,90 4,14 3,96 4,88 5,13 5,59 6,17
Speed 6 (1) kW 2,52 3,05 3,38 2,83 3,58 3,71 3,20 3,87 4,03 4,29 4,52
Sensible output cooling capacity (1)
Speed 1 (1) kW 3,95 4,50 4,86 4,23 5,13 5,40 5,61 6,81 7,12 7,97 8,82
Speed 2 (1) kW 3,51 3,96 4,27 3,76 4,52 4,72 4,94 5,86 6,24 7,01 7,71
Speed 3 (1) kW 3,15 3,54 3,84 3,38 4,03 4,17 4,33 5,11 5,28 6,11 6,65
Speed 4 (1) kW 2,79 3,12 3,35 2,95 3,53 3,59 3,68 4,30 4,31 5,07 5,38
Speed 5 (1) kW 2,22 2,48 2,61 2,37 2,78 2,82 3,11 3,53 3,63 4,11 4,37
Speed 6 (1) kW 1,97 2,24 2,40 2,15 2,54 2,50 2,45 2,75 2,82 3,11 3,07
Max Water flow (1) l/h 800 990 1120 890 1190 1280 1130 1530 1650 1750 2040
Max Pressure drop (1) kPa 11 22 18 16 18 14 24 27 23 24 22
Total output heating capacity (2)
Speed 1 (2) kW 9,92 11,2 12,3 10,8 13,1 13,5 13,7 17,4 18 20,3 22,4
Speed 2 (2) kW 8,86 9,88 10,7 9,61 11,4 11,8 12,2 15 15,7 17,9 19,5
Speed 3 (2) kW 7,98 8,85 9,56 8,68 10,1 10,4 10,7 13 13,3 15,6 16,7
Speed 4 (2) kW 7,11 7,83 8,34 7,61 8,88 8,85 9,16 10,8 10,8 13 13,5
Speed 5 (2) kW 5,70 6,18 6,47 6,15 6,91 7,09 7,78 8,88 8,99 10,4 10,9
Speed 6 (2) kW 5,09 5,58 5,91 5,59 6,28 6,33 6,18 6,84 6,94 7,85 7,78
Max Water flow (2) l/h 870 980 1080 950 1150 1190 1210 1530 1580 1780 1970
Max Pressure drop (2) kPa 10 19 15 14 11 12 21 22 19 20 19
Total output heating capacity (3)
Speed 1 (3) kW 6,04 6,81 7,44 6,67 7,93 8,25 8,37 10,6 11 12,4 13,7
Speed 2 (3) kW 5,39 6 6,50 5,93 6,93 7,19 7,40 9,10 9,55 10,9 11,9
Speed 3 (3) kW 4,86 5,37 5,79 5,33 6,12 6,35 6,52 7,89 8,05 9,47 10,2
Speed 4 (3) kW 4,32 4,75 5,05 4,73 5,37 5,33 5,57 6,55 6,57 7,85 8,21
Speed 5 (3) kW 3,46 3,75 3,91 3,77 4,18 4,19 4,73 5,37 5,42 6,31 6,57
Speed 6 (3) kW 3,09 3,38 3,57 3,36 3,79 3,72 3,75 4,13 4,10 4,75 4,57
Water flow Max (3) l/h 1050 1190 1300 1160 1380 1440 1460 1850 1920 2160 2380
Pressure drop Max (3) kPa 10 20 16 14 16 12 22 24 21 22 20
Output supplementary coil (2)
Speed 1 (2) kW 4,11 4,11 - 4,52 4,52 - 5,62 5,62 - 6,70 -
Speed 2 (2) kW 3,71 3,71 - 4,09 4,09 - 5,02 5,02 - 6,07 -
Speed 3 (2) kW 3,40 3,40 - 3,72 3,72 - 4,51 4,51 - 5,46 -
Speed 4 (2) kW 3,09 3,09 - 3,37 3,37 - 3,92 3,92 - 4,73 -
Speed 5 (2) kW 2,55 2,55 - 2,78 2,78 - 3,37 3,37 - 4 -
Speed 6 (2) kW 2,35 2,35 - 2,59 2,59 - 2,76 2,76 - 3,21 -
Water flow Max (2) l/h 360 360 - 400 400 - 490 490 - 590 -
Pressure drop Max (2) kPa 20 20 - 24 24 - 35 35 - 10 -
Sound pressure level (4)
Speed 1 (4) dB(A) 51 51 52 52 52 53 54 54 55 57 58
Speed 2 (4) dB(A) 47 47 48 48 48 49 49 49 50 53 54
Speed 3 (4) dB(A) 44 44 45 45 45 46 46 46 47 49 50
Speed 4 (4) dB(A) 40 40 42 41 41 42 41 41 42 43 44
Speed 5 (4) dB(A) 33 33 34 35 35 36 36 36 37 38 39
Speed 6 (4) dB(A) 30 30 31 33 33 34 33 33 34 31 32
Water content l 1,20 1,80 1,40 1,50 2,20 2,20 1,50 2,20 2,20 1,70 2,60
Fan 2C 2C 2C 2C 2C 2C 3C 3C 3C 4C 4C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 150 150 150 165 165 165 245 245 245 272 272
Max absorbed current A 0,60 0,60 0,60 0,73 0,73 0,73 1,10 1,10 1,10 1,03 1,03
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 981 981 981 1171 1171 1171 1171 1171 1171 1361 1361
H (mm) 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225
Weight kg 23 23 25 27 27 29 31 31 33 38 38

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

228
Dimension

H
H

L L
P P

229
Hydronic terminals

a-LIFE HP 230÷840
Versions
DFI built-in version, front air intake
DLI built-in version, bottom air intake

Features
Four pipe system: 3+2 and 4+1 (number of rows for main
+ additional coil);
High pressure centrifugal fan unit for ducted system;
6-speed autotransformer;
Air filter on all models;
Structure in hot galvanised steel for maximum resistance
to rust;

Main accessories
UÊHot water coil kit 1 row and 2 rows
UÊKit RS485 - interface for Building Management System
UÊKit control board to manage 0-10V or 3 points
modulating valve unit
UÊMain coil valve unit ON/OFF, 0-10 V, 3 points 2-way or
3-way
UÊAdditional coil valve unit ON/OFF, PWM, 0-10 V, 3 points
3-way or 2-way
UÊStraight and angular (90°) plenum kits for air inlet
UÊStraight and angular (90°) plenum kits for air outlet
High head fan-coil for professional application UÊPlenum kit with round air ducts for plenum kit
UÊElectric heaters
built-in version
2,83 - 10,9 kW
Unit Description
a-LIFE HP are professional high-head fan coils by Climaveneta. The enhanced motor and the
built-in version make these units ideal for ducted systems in tertiary and commercial sectors.

Commands
NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.

230
CONTROLLER DUCT FAN COIL CENTRIFUGAL 4 PIPES 2 PIPES

a-LIFE HP / DLI
Models 230 240 430 440 530 540 730 740 830 840
Air flow rate
Speed 1 m3/h 520 520 600 600 930 930 960 960 1330 1330
Speed 2 m3/h 490 490 540 540 800 800 890 890 1260 1260
Speed 3 m3/h 460 460 470 470 670 670 810 810 1130 1130
Speed 4 m3/h 415 415 405 405 520 520 695 695 940 940
Speed 5 m3/h 320 320 290 290 380 380 540 540 720 720
Speed 6 m3/h 275 275 250 250 280 280 380 380 520 520
Effective static pressure Speed
Pa 40 40 40 40 40 40 40 40 40 40
1 - Max
Total output cooling capacity (1)
Speed 1 (1) kW 2,83 3,57 4,04 4,69 5,58 6,54 7,36 8,15 9,95 10,9
Speed 2 (1) kW 2,71 3,41 3,74 4,35 5,02 5,90 6,97 7,66 9,56 10,5
Speed 3 (1) kW 2,59 3,25 3,37 3,91 4,41 5,15 6,47 7,09 8,83 9,60
Speed 4 (1) kW 2,39 3 3,01 3,46 3,64 4,19 5,77 6,23 7,68 8,25
Speed 5 (1) kW 1,95 2,46 2,31 2,59 2,87 3,26 4,67 5,11 6,27 6,63
Speed 6 (1) kW 1,72 2,17 2,04 2,29 2,25 2,50 3,54 3,75 4,81 5,06
Sensible output cooling capacity (1)
Speed 1 (1) kW 2,32 2,72 3,13 3,45 4,39 4,90 5,45 5,90 7,53 7,94
Speed 2 (1) kW 2,21 2,59 2,87 3,19 3,90 4,38 5,14 5,52 7,21 7,62
Speed 3 (1) kW 2,10 2,45 2,56 2,84 3,37 3,78 4,74 5,09 6,60 6,94
Speed 4 (1) kW 1,93 2,24 2,26 2,50 2,73 3,04 4,20 4,44 5,66 5,91
Speed 5 (1) kW 1,54 1,82 1,70 1,85 2,11 2,32 3,36 3,46 4,55 4,69
Speed 6 (1) kW 1,35 1,59 1,49 1,63 1,63 1,76 2,43 2,43 3,33 3,33
Max Water flow (1) l/h 480 610 690 810 960 1120 1260 1400 1710 1870
Max Pressure drop (1) kPa 5 10 11 9 23 17 20 16 21 19
Total output heating capacity (2)
Speed 1 (2) kW 6,16 7,07 7,85 8,72 11,4 12,8 13,8 14,3 18,6 19,4
Speed 2 (2) kW 5,88 6,73 7,26 7,98 10,1 11,3 12,9 13,4 17,8 18,5
Speed 3 (2) kW 5,60 6,39 6,54 7,08 8,75 9,74 11,9 12,3 16,3 16,8
Speed 4 (2) kW 5,17 5,86 5,82 6,22 7,11 7,82 10,4 10,8 14 14,3
Speed 5 (2) kW 4,19 4,70 4,43 4,63 5,46 5,91 8,37 8,56 11,1 11,3
Speed 6 (2) kW 3,70 4,11 3,90 4,04 4,19 4,48 6,11 6,16 8,39 8,38
Max Water flow (2) l/h 540 620 770 770 1000 1130 1210 1260 1630 1700
Max Pressure drop (2) kPa 4 9 10 8 20 16 18 13 18 16
Total output heating capacity (3)
Speed 1 (3) kW 3,75 4,29 4,76 5,34 6,90 7,86 8,58 9,14 11,3 12
Speed 2 (3) kW 3,58 4,08 4,38 4,88 6,12 6,93 8,04 8,48 10,8 11,4
Speed 3 (3) kW 3,41 3,87 3,91 4,33 5,31 5,96 7,42 7,72 9,86 10,4
Speed 4 (3) kW 3,14 3,55 3,46 3,80 4,31 4,78 6,50 6,62 8,46 8,83
Speed 5 (3) kW 2,55 2,84 2,61 2,76 3,30 3,61 5,14 5,14 6,74 6,86
Speed 6 (3) kW 2,25 2,49 2,29 2,37 2,53 2,67 3,62 3,62 4,95 4,95
Water flow Max (3) l/h 650 750 830 930 1200 1370 1500 1600 1970 2090
Pressure drop Max (3) kPa 4 10 10 9 21 17 18 15 19 18
Output supplementary coil (2)
Speed 1 (2) kW 2,23 - 3,34 - 4,42 - 5,45 - 7,68 -
Speed 2 (2) kW 2,15 - 3,13 - 4,02 - 5,19 - 7,43 -
Speed 3 (2) kW 2,07 - 2,86 - 3,59 - 4,88 - 6,93 -
Speed 4 (2) kW 1,94 - 2,59 - 3,04 - 4,42 - 6,16 -
Speed 5 (2) kW 1,64 - 2,07 - 2,46 - 3,74 - 5,17 -
Speed 6 (2) kW 1,48 - 1,87 - 1,99 - 2,94 - 4,15 -
Water flow Max (2) l/h 200 - 290 - 390 - 480 - 670 -
Pressure drop Max (2) kPa 4 - 13 - 20 - 35 - 10 -
Sound pressure level (4)
Speed 1 (4) dB(A) 48 49 51 52 51 52 54 55 57 58
Speed 2 (4) dB(A) 44 45 47 48 47 48 49 50 53 54
Speed 3 (4) dB(A) 40 41 44 45 44 45 45 46 49 50
Speed 4 (4) dB(A) 37 38 42 43 40 41 42 43 43 44
Speed 5 (4) dB(A) 31 32 33 34 33 34 36 37 38 39
Speed 6 (4) dB(A) 30 31 31 32 30 31 34 35 31 32
Water content l 1 1,30 1,40 19 1,80 2,40 2,20 2,90 2,60 3,50
Fan 1C 1C 2C 2C 2C 2C 2C 2C 3C 3C
Water IN connection inch 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F
Max absorbed power W 140 140 120 120 210 210 240 240 270 270
Max absorbed current A 0,64 0,64 0,58 0,58 0,95 0,95 1,10 1,10 1,20 1,20
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 601 601 791 791 981 981 1171 1171 1361 1361
H (mm) 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225
Weight kg 18 18 21 21 27 27 29 29 40 40

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

231
a-LIFE HP / DFI
Models 230 240 430 440 530 540 730 740 830 840
Air flow rate
Speed 1 m3/h 520 520 600 600 930 930 960 960 1330 1330
Speed 2 m3/h 490 490 540 540 800 800 890 890 1260 1260
Speed 3 m3/h 460 460 470 470 670 670 810 810 1130 1130
Speed 4 m3/h 415 415 405 405 520 520 695 695 940 940
Speed 5 m3/h 320 320 290 290 380 380 540 540 720 720
Speed 6 m3/h 275 275 250 250 280 280 380 380 520 520
Effective static pressure Speed
Pa 40 40 40 40 40 40 40 40 40 40
1 - Max
Total output cooling capacity (1)
Speed 1 (1) kW 2,83 3,57 4,04 4,69 5,58 6,54 7,36 8,15 9,95 10,9
Speed 2 (1) kW 2,71 3,41 3,74 4,35 5,02 5,90 6,97 7,66 9,56 10,5
Speed 3 (1) kW 2,59 3,25 3,37 3,91 4,41 5,15 6,47 7,09 8,83 9,60
Speed 4 (1) kW 2,39 3 3,01 3,46 3,64 4,19 5,77 6,23 7,68 8,25
Speed 5 (1) kW 1,95 2,46 2,31 2,59 2,87 3,26 4,67 5,11 6,27 6,63
Speed 6 (1) kW 1,72 2,17 2,04 2,29 2,25 2,50 3,54 3,75 4,81 5,06
Sensible output cooling capacity (1)
Speed 1 (1) kW 2,32 2,72 3,13 3,45 4,39 4,90 5,45 5,90 7,53 7,94
Speed 2 (1) kW 2,21 2,59 2,87 3,19 3,90 4,38 5,14 5,52 7,21 7,62
Speed 3 (1) kW 2,10 2,45 2,56 2,84 3,37 3,78 4,74 5,09 6,60 6,94
Speed 4 (1) kW 1,93 2,24 2,26 2,50 2,73 3,04 4,20 4,44 5,66 5,91
Speed 5 (1) kW 1,54 1,82 1,70 1,85 2,11 2,32 3,36 3,46 4,55 4,69
Speed 6 (1) kW 1,35 1,59 1,49 1,63 1,63 1,76 2,43 2,43 3,33 3,33
Max Water flow (1) l/h 480 610 690 810 960 1120 1260 1400 1710 1870
Max Pressure drop (1) kPa 5 10 11 9 23 17 20 16 21 19
Total output heating capacity (2)
Speed 1 (2) kW 6,16 7,07 7,85 8,72 11,4 12,8 13,8 14,3 18,6 19,4
Speed 2 (2) kW 5,88 6,73 7,26 7,98 10,1 11,3 12,9 13,4 17,8 18,5
Speed 3 (2) kW 5,60 6,39 6,54 7,08 8,75 9,74 11,9 12,3 16,3 16,8
Speed 4 (2) kW 5,17 5,86 5,82 6,22 7,11 7,82 10,4 10,8 14 14,3
Speed 5 (2) kW 4,19 4,70 4,43 4,63 5,46 5,91 8,37 8,56 11,1 11,3
Speed 6 (2) kW 3,70 4,11 3,90 4,04 4,19 4,48 6,11 6,16 8,39 8,38
Max Water flow (2) l/h 540 620 770 770 1000 1130 1210 1260 1630 1700
Max Pressure drop (2) kPa 4 9 10 8 20 16 18 13 18 16
Total output heating capacity (3)
Speed 1 (3) kW 3,75 4,29 4,76 5,34 6,90 7,86 8,58 9,14 11,3 12
Speed 2 (3) kW 3,58 4,08 4,38 4,88 6,12 6,93 8,04 8,48 10,8 11,4
Speed 3 (3) kW 3,41 3,87 3,91 4,33 5,31 5,96 7,42 7,72 9,86 10,4
Speed 4 (3) kW 3,14 3,55 3,46 3,80 4,31 4,78 6,50 6,62 8,46 8,83
Speed 5 (3) kW 2,55 2,84 2,61 2,76 3,30 3,61 5,14 5,14 6,74 6,86
Speed 6 (3) kW 2,25 2,49 2,29 2,37 2,53 2,67 3,62 3,62 4,95 4,95
Water flow Max (3) l/h 650 750 830 930 1200 1370 1500 1600 1970 2090
Pressure drop Max (3) kPa 4 10 10 9 21 17 18 15 19 18
Output supplementary coil (2)
Speed 1 (2) kW 2,23 - 3,34 - 4,42 - 5,45 - 7,68 -
Speed 2 (2) kW 2,15 - 3,13 - 4,02 - 5,19 - 7,43 -
Speed 3 (2) kW 2,07 - 2,86 - 3,59 - 4,88 - 6,93 -
Speed 4 (2) kW 1,94 - 2,59 - 3,04 - 4,42 - 6,16 -
Speed 5 (2) kW 1,64 - 2,07 - 2,46 - 3,74 - 5,17 -
Speed 6 (2) kW 1,48 - 1,87 - 1,99 - 2,94 - 4,15 -
Water flow Max (2) l/h 200 - 290 - 390 - 480 - 670 -
Pressure drop Max (2) kPa 4 - 13 - 20 - 35 - 10 -
Sound pressure level (4)
Speed 1 (4) dB(A) 48 49 51 52 51 52 54 55 57 58
Speed 2 (4) dB(A) 44 45 47 48 47 48 49 50 53 54
Speed 3 (4) dB(A) 40 41 44 45 44 45 45 46 49 50
Speed 4 (4) dB(A) 37 38 42 43 40 41 42 43 43 44
Speed 5 (4) dB(A) 31 32 33 34 33 34 36 37 38 39
Speed 6 (4) dB(A) 30 31 31 32 30 31 34 35 31 32
Water content l 1 1,30 1,40 19 1,80 2,40 2,20 2,90 2,60 3,50
Fan 1C 1C 2C 2C 2C 2C 2C 2C 3C 3C
Water IN connection inch 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F 1/2” G F
Max absorbed power W 140 140 120 120 210 210 240 240 270 270
Max absorbed current A 0,64 0,64 0,58 0,58 0,95 0,95 1,10 1,10 1,20 1,20
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
Built-in
L (mm) 601 601 791 791 981 981 1171 1171 1361 1361
H (mm) 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225
Weight kg 18 18 21 21 27 27 29 29 40 40

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

232
Dimension

L
P

233
Hydronic terminals

i-LIFE 130÷640
Versions
DFI built-in version, front air intake
DFU version with cabinet, front air intake
DLI built-in version, bottom air intake
DLU version with cabinet, bottom air intake

Features
Brushless motor with permanent magnets electronic
switches;
Modulating centrifugal fan with fine regulation of the air
flow;
Four pipe system: 3+2 and 4+1 (number of rows for main
+ additional coil);
Cabinet in galvanised steel with prevarnished finish for
maximum resistance to rust;
Air filter on all models;
Automatically closing flap to cover and protect electric
controls from dripping water (in conformity with directive
60335-2-40);

Main accessories
UÊHot water coil kit 1 row and 2 rows
UÊKit RS485 - interface for Building Management System
UÊKit control board to manage 0-10V or 3 points
modulating valve unit
Fan-coil with high efficiency brushless motor, UÊMain coil valve unit ON/OFF, 0-10 V, 3 points 2-way or
3-way
continuous air flow modulation, universal UÊAdditional coil valve unit ON/OFF, PWM, 0-10 V, 3 points
3-way or 2-way
installation UÊKit LIFE BOX

1,91 - 7,47 kW
Unit Description
NEW i-LIFE fan-coil is powered by modulating speed centrifugal fan. This new generation of
fan-coil guarantees air flow regulation from 0% to 100% and energy consumption is reduced
by more than 50% respect traditional unit. Furthermore new commands are available to
manage all functions offered by this range of terminal units.

Commands
EK plug-in control /EKW wall mounted control
User interface for selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature
set. Control of main coil valve unit (summer/winter - 2 pipes installation) and additional coil (winter - 4 pipes installation).
Management of traditional ON/OFF valve unit or modulating valve unit 0-10V or 3 points (supply 230 VAC or 24V) . Air and
water temperature probe. Multifunction digital input configurable by user. Configuration dip switch. Modbus protocol for
installation in Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-
Slave system up to 8 LIFE fan coil units. Easy control installation thanks to 2 wires connection.
iK control with LCD screen
Interface with LCD screen with user-friendly icons. Control kit for universal installation: wall-mounted as well as plug-in.
Selection of functioning mode (OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), temperature set. Control iK
could function manually or with weekly timer regulation configurable by the customer. Control of main coil valve unit (summer/
winter - 2 pipes) and additional coil (winter - 4 pipes). Management of traditional ON/OFF valve unit or modulating valve unit
0-10V or 3 points (supply 230 VAC or 24V) . Parameters configurable directly by user. Modbus protocol for installation in
Building Management System (e.g. Idrorelax system by Climaveneta). Installation and management of Master-Slave system
up to 8 LIFE fan coil units. Easy control installation thanks to 2 wires connection.

234
CONTROLLER FAN COIL CENTRIFUGAL 4 PIPES 2 PIPES

i-LIFE / DLU
Models 130 140 230 240 330 340 430 440 530 540 630 640
Air flow rate
Speed 1 m3/h 410 390 480 450 485 460 815 790 915 880 925 900
Speed 2 m3/h 360 340 410 380 415 390 680 660 780 750 790 770
Speed 3 m3/h 315 290 350 320 355 330 565 545 680 655 685 670
Speed 4 m3/h 270 250 300 270 305 280 470 455 585 560 590 560
Speed 5 m3/h 200 180 225 210 230 220 315 300 440 420 445 440
Speed 6 m3/h 105 95 120 110 130 120 200 190 310 295 320 305
Total output cooling capacity (1)
Speed 1 (1) kW 1,91 2,32 2,67 3,20 3,22 3,68 4,69 5,57 5,75 6,54 6,92 7,47
Speed 2 (1) kW 1,75 2,10 2,37 2,81 2,86 3,23 4,14 4,87 5,13 5,80 6,16 6,57
Speed 3 (1) kW 1,59 1,87 2,10 2,46 2,53 2,79 3,62 4,22 4,65 5,26 5,53 5,84
Speed 4 (1) kW 1,42 1,67 1,85 2,13 2,24 2,42 3,16 3,65 4,15 4,63 4,88 5,08
Speed 5 (1) kW 1,11 1,27 1,42 1,71 1,77 1,97 2,31 2,56 3,36 3,66 3,90 4,14
Speed 6 (1) kW 0,70 0,75 0,88 1,00 1,06 1,16 1,56 1,64 2,53 2,72 2,95 2,95
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,63 1,77 2,17 2,41 2,47 2,68 3,77 4,20 4,50 4,86 5,13 5,40
Speed 2 (1) kW 1,47 1,58 1,91 2,09 2,17 2,34 3,27 3,62 3,96 4,27 4,52 4,72
Speed 3 (1) kW 1,32 1,39 1,67 1,82 1,90 2,01 2,82 3,10 3,54 3,84 4,03 4,17
Speed 4 (1) kW 1,16 1,23 1,46 1,56 1,67 1,73 2,42 2,66 3,12 3,35 3,53 3,59
Speed 5 (1) kW 0,89 0,93 1,11 1,24 1,30 1,40 1,72 1,84 2,48 2,61 2,78 2,82
Speed 6 (1) kW 0,53 0,54 0,66 0,70 0,77 0,77 1,15 1,18 1,84 1,91 2,07 1,95
Max Water flow (1) l/h 330 400 460 550 550 630 800 960 990 1120 1190 1280
Max Pressure drop (1) kPa 5 10 5 8 7 5 14 11 22 18 18 14
Total output heating capacity (2)
Speed 1 (2) kW 4,46 5,01 5,79 6,28 6,36 6,76 9,58 10,7 11,2 12,3 13,1 13,5
Speed 2 (2) kW 4,04 4,49 5,12 5,44 5,60 5,85 8,33 9,18 9,88 10,7 11,4 11,8
Speed 3 (2) kW 3,66 3,94 4,51 4,70 4,92 5,05 7,19 7,81 8,85 9,56 10,1 10,4
Speed 4 (2) kW 3,25 3,49 3,98 4,05 4,33 4,36 6,20 6,69 7,83 8,34 8,88 8,85
Speed 5 (2) kW 2,56 2,64 3,13 3,24 3,39 3,50 4,45 4,63 6,18 6,47 6,91 7,09
Speed 6 (2) kW 1,50 1,49 1,81 1,78 2,04 1,94 3,00 3,05 4,58 4,70 5,12 4,44
Max Water flow (2) l/h 390 440 510 550 560 590 840 930 980 1080 1150 1190
Max Pressure drop (2) kPa 5 8 4 7 6 5 12 10 19 15 11 12
Total output heating capacity (3)
Speed 1 (3) kW 2,71 3,04 3,52 3,80 3,86 4,09 5,83 6,46 6,81 7,44 7,93 8,25
Speed 2 (3) kW 2,46 2,72 3,11 3,30 3,40 3,54 5,06 5,57 6 6,50 6,93 7,19
Speed 3 (3) kW 2,22 2,39 2,74 2,84 2,98 3,05 4,37 4,73 5,37 5,79 6,12 6,35
Speed 4 (3) kW 1,97 2,11 2,41 2,45 2,62 2,63 3,76 4,05 4,75 5,05 5,37 5,33
Speed 5 (3) kW 1,55 1,60 1,90 1,96 2,05 2,09 2,69 2,80 3,75 3,91 4,18 4,19
Speed 6 (3) kW 0,91 0,90 1,10 1,05 1,23 1,14 1,82 1,80 2,77 2,81 3,05 2,90
Water flow Max (3) l/h 470 530 610 660 670 710 1020 1130 1190 1300 1380 1440
Pressure drop Max (3) kPa 5 8 5 7 6 5 13 10 20 16 16 12
Output supplementary coil (2)
Speed 1 (2) kW 1,48 - 2,12 - 2,48 - 3,48 - 4,11 - 4,52 -
Speed 2 (2) kW 1,37 - 1,92 - 2,24 - 3,13 - 3,71 - 4,09 -
Speed 3 (2) kW 1,26 - 1,74 - 2,02 - 2,78 - 3,40 - 3,72 -
Speed 4 (2) kW 1,15 - 1,57 - 1,82 - 2,46 - 3,09 - 3,37 -
Speed 5 (2) kW 0,95 - 1,30 - 1,50 - 1,92 - 2,55 - 2,78 -
Speed 6 (2) kW 0,62 - 0,84 - 1,00 - 1,36 - 2,01 - 2,21 -
Water flow Max (2) l/h 130 - 190 - 220 - 310 - 360 - 400 -
Pressure drop Max (2) kPa 2 - 4 - 7 - 13 - 20 - 24 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 47 48 49 48 49 51 52 51 52 52 53
Speed 2 (4) dB(A) 41 42 44 45 44 45 47 48 47 48 48 49
Speed 3 (4) dB(A) 38 39 40 41 40 41 43 44 44 45 45 46
Speed 4 (4) dB(A) 35 36 37 38 37 38 41 42 40 42 41 42
Speed 5 (4) dB(A) 30 31 30 31 31 32 33 34 33 34 35 36
Speed 6 (4) dB(A) 22 22 23 23 24 24 25 25 26 26 26 26
Water content l 0,70 0,70 1 1 1,40 1,40 1,40 1 1,80 1,40 2,20 2,20
Fan 1C 1C 1C 1C 1C 1C 2C 2C 2C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 33 33 34 34 37 37 59 59 72 72 74 74
Min absorbed power W 4 4 4 4 4 4 7 7 7 7 7 7
Max absorbed current A 0,29 0,29 0,29 0,29 0,31 0,31 0,49 0,49 0,57 0,57 0,58 0,58
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 732 732 922 922 1112 1112 1112 1112 1302 1302 1492 1492
H (mm) 541 541 541 541 541 541 541 541 541 541 541 541
P (mm) 233 233 233 233 233 233 233 233 233 233 233 233
Weight kg 18 18 22 22 26 26 28 28 32 32 38 38
Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

235
i-LIFE / DFU
Models 130 140 230 240 330 340 430 440 530 540 630 640
Air flow rate
Speed 1 m3/h 410 390 480 450 485 460 815 790 915 880 925 900
Speed 2 m3/h 360 340 410 380 415 390 680 660 780 750 790 770
Speed 3 m3/h 315 290 350 320 355 330 565 545 680 655 685 670
Speed 4 m3/h 270 250 300 270 305 280 470 455 585 560 590 560
Speed 5 m3/h 200 180 225 210 230 220 315 300 440 420 445 440
Speed 6 m3/h 105 95 120 110 130 120 200 190 310 295 320 305
Total output cooling capacity (1)
Speed 1 (1) kW 1,91 2,32 2,67 3,20 3,22 3,68 4,69 5,57 5,75 6,54 6,92 7,47
Speed 2 (1) kW 1,75 2,10 2,37 2,81 2,86 3,23 4,14 4,87 5,13 5,80 6,16 6,57
Speed 3 (1) kW 1,59 1,87 2,10 2,46 2,53 2,79 3,62 4,22 4,65 5,26 5,53 5,84
Speed 4 (1) kW 1,42 1,67 1,85 2,13 2,24 2,42 3,16 3,65 4,15 4,63 4,88 5,08
Speed 5 (1) kW 1,11 1,27 1,42 1,71 1,77 1,97 2,31 2,56 3,36 3,66 3,90 4,14
Speed 6 (1) kW 0,70 0,75 0,88 1,00 1,06 1,16 1,56 1,64 2,53 2,72 2,95 2,95
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,63 1,77 2,17 2,41 2,47 2,68 3,77 4,20 4,50 4,86 5,13 5,40
Speed 2 (1) kW 1,47 1,58 1,91 2,09 2,17 2,34 3,27 3,62 3,96 4,27 4,52 4,72
Speed 3 (1) kW 1,32 1,39 1,67 1,82 1,90 2,01 2,82 3,10 3,54 3,84 4,03 4,17
Speed 4 (1) kW 1,16 1,23 1,46 1,56 1,67 1,73 2,42 2,66 3,12 3,35 3,53 3,59
Speed 5 (1) kW 0,89 0,93 1,11 1,24 1,30 1,40 1,72 1,84 2,48 2,61 2,78 2,82
Speed 6 (1) kW 0,53 0,54 0,66 0,70 0,77 0,77 1,15 1,18 1,84 1,91 2,07 1,95
Max Water flow (1) l/h 330 400 460 550 550 630 800 960 990 1120 1190 1280
Max Pressure drop (1) kPa 5 10 5 8 7 5 14 11 22 18 18 14
Total output heating capacity (2)
Speed 1 (2) kW 4,46 5,01 5,79 6,28 6,36 6,76 9,58 10,7 11,2 12,3 13,1 13,5
Speed 2 (2) kW 4,04 4,49 5,12 5,44 5,60 5,85 8,33 9,18 9,88 10,7 11,4 11,8
Speed 3 (2) kW 3,66 3,94 4,51 4,70 4,92 5,05 7,19 7,81 8,85 9,56 10,1 10,4
Speed 4 (2) kW 3,25 3,49 3,98 4,05 4,33 4,36 6,20 6,69 7,83 8,34 8,88 8,85
Speed 5 (2) kW 2,56 2,64 3,13 3,24 3,39 3,50 4,45 4,63 6,18 6,47 6,91 7,09
Speed 6 (2) kW 1,50 1,49 1,81 1,78 2,04 1,94 3,00 3,05 4,58 4,70 5,12 4,44
Max Water flow (2) l/h 390 440 510 550 560 590 840 930 980 1080 1150 1190
Max Pressure drop (2) kPa 5 8 4 7 6 5 12 10 19 15 11 12
Total output heating capacity (3)
Speed 1 (3) kW 2,71 3,04 3,52 3,80 3,86 4,09 5,83 6,46 6,81 7,44 7,93 8,25
Speed 2 (3) kW 2,46 2,72 3,11 3,30 3,40 3,54 5,06 5,57 6 6,50 6,93 7,19
Speed 3 (3) kW 2,22 2,39 2,74 2,84 2,98 3,05 4,37 4,73 5,37 5,79 6,12 6,35
Speed 4 (3) kW 1,97 2,11 2,41 2,45 2,62 2,63 3,76 4,05 4,75 5,05 5,37 5,33
Speed 5 (3) kW 1,55 1,60 1,90 1,96 2,05 2,09 2,69 2,80 3,75 3,91 4,18 4,19
Speed 6 (3) kW 0,91 0,90 1,10 1,05 1,23 1,14 1,82 1,80 2,77 2,81 3,05 2,90
Water flow Max (3) l/h 470 530 610 660 670 710 1020 1130 1190 1300 1380 1440
Pressure drop Max (3) kPa 5 8 5 7 6 5 13 10 20 16 16 12
Output supplementary coil (2)
Speed 1 (2) kW 1,48 - 2,12 - 2,48 - 3,48 - 4,11 - 4,52 -
Speed 2 (2) kW 1,37 - 1,92 - 2,24 - 3,13 - 3,71 - 4,09 -
Speed 3 (2) kW 1,26 - 1,74 - 2,02 - 2,78 - 3,40 - 3,72 -
Speed 4 (2) kW 1,15 - 1,57 - 1,82 - 2,46 - 3,09 - 3,37 -
Speed 5 (2) kW 0,95 - 1,30 - 1,50 - 1,92 - 2,55 - 2,78 -
Speed 6 (2) kW 0,62 - 0,84 - 1,00 - 1,36 - 2,01 - 2,21 -
Water flow Max (2) l/h 130 - 190 - 220 - 310 - 360 - 400 -
Pressure drop Max (2) kPa 2 - 4 - 7 - 13 - 20 - 24 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 47 48 49 48 49 51 52 51 52 52 53
Speed 2 (4) dB(A) 41 42 44 45 44 45 47 48 47 48 48 49
Speed 3 (4) dB(A) 38 39 40 41 40 41 43 44 44 45 45 46
Speed 4 (4) dB(A) 35 36 37 38 37 38 41 42 40 42 41 42
Speed 5 (4) dB(A) 30 31 30 31 31 32 33 34 33 34 35 36
Speed 6 (4) dB(A) 22 22 23 23 24 24 25 25 26 26 26 26
Water content l 0,70 0,70 1 1 1,40 1,40 1,40 1 1,80 1,40 2,20 2,20
Fan 1C 1C 1C 1C 1C 1C 2C 2C 2C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 33 33 34 34 37 37 59 59 72 72 74 74
Min absorbed power W 4 4 4 4 4 4 7 7 7 7 7 7
Max absorbed current A 0,29 0,29 0,29 0,29 0,31 0,31 0,49 0,49 0,57 0,57 0,58 0,58
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 732 732 922 922 1112 1112 1112 1112 1302 1302 1492 1492
H (mm) 541 541 541 541 541 541 541 541 541 541 541 541
P (mm) 245 245 245 245 245 245 245 245 245 245 245 245
Weight kg 18 18 22 22 26 26 28 28 32 32 38 38
Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

236
i-LIFE / DLI
Models 130 140 230 240 330 340 430 440 530 540 630 640
Air flow rate
Speed 1 m3/h 410 390 480 450 485 460 815 790 915 880 925 900
Speed 2 m3/h 360 340 410 380 415 390 680 660 780 750 790 770
Speed 3 m3/h 315 290 350 320 355 330 565 545 680 655 685 670
Speed 4 m3/h 270 250 300 270 305 280 470 455 585 560 590 560
Speed 5 m3/h 200 180 225 210 230 220 315 300 440 420 445 440
Speed 6 m3/h 105 95 120 110 130 120 200 190 310 295 320 305
Total output cooling capacity (1)
Speed 1 (1) kW 1,91 2,32 2,67 3,20 3,22 3,68 4,69 5,57 5,75 6,54 6,92 7,47
Speed 2 (1) kW 1,75 2,10 2,37 2,81 2,86 3,23 4,14 4,87 5,13 5,80 6,16 6,57
Speed 3 (1) kW 1,59 1,87 2,10 2,46 2,53 2,79 3,62 4,22 4,65 5,26 5,53 5,84
Speed 4 (1) kW 1,42 1,67 1,85 2,13 2,24 2,42 3,16 3,65 4,15 4,63 4,88 5,08
Speed 5 (1) kW 1,11 1,27 1,42 1,71 1,77 1,97 2,31 2,56 3,36 3,66 3,90 4,14
Speed 6 (1) kW 0,70 0,75 0,88 1,00 1,06 1,16 1,56 1,64 2,53 2,72 2,95 2,95
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,63 1,77 2,17 2,41 2,47 2,68 3,77 4,20 4,50 4,86 5,13 5,40
Speed 2 (1) kW 1,47 1,58 1,91 2,09 2,17 2,34 3,27 3,62 3,96 4,27 4,52 4,72
Speed 3 (1) kW 1,32 1,39 1,67 1,82 1,90 2,01 2,82 3,10 3,54 3,84 4,03 4,17
Speed 4 (1) kW 1,16 1,23 1,46 1,56 1,67 1,73 2,42 2,66 3,12 3,35 3,53 3,59
Speed 5 (1) kW 0,89 0,93 1,11 1,24 1,30 1,40 1,72 1,84 2,48 2,61 2,78 2,82
Speed 6 (1) kW 0,53 0,54 0,66 0,70 0,77 0,77 1,15 1,18 1,84 1,91 2,07 1,95
Max Water flow (1) l/h 330 400 460 550 550 630 800 960 990 1120 1190 1280
Max Pressure drop (1) kPa 5 10 5 8 7 5 14 11 22 18 18 14
Total output heating capacity (2)
Speed 1 (2) kW 4,46 5,01 5,79 6,28 6,36 6,76 9,58 10,7 11,2 12,3 13,1 13,5
Speed 2 (2) kW 4,04 4,49 5,12 5,44 5,60 5,85 8,33 9,18 9,88 10,7 11,4 11,8
Speed 3 (2) kW 3,66 3,94 4,51 4,70 4,92 5,05 7,19 7,81 8,85 9,56 10,1 10,4
Speed 4 (2) kW 3,25 3,49 3,98 4,05 4,33 4,36 6,20 6,69 7,83 8,34 8,88 8,85
Speed 5 (2) kW 2,56 2,64 3,13 3,24 3,39 3,50 4,45 4,63 6,18 6,47 6,91 7,09
Speed 6 (2) kW 1,50 1,49 1,81 1,78 2,04 1,94 3,00 3,05 4,58 4,70 5,12 4,44
Max Water flow (2) l/h 390 440 510 550 560 590 840 930 980 1080 1150 1190
Max Pressure drop (2) kPa 5 8 4 7 6 5 12 10 19 15 11 12
Total output heating capacity (3)
Speed 1 (3) kW 2,71 3,04 3,52 3,80 3,86 4,09 5,83 6,46 6,81 7,44 7,93 8,25
Speed 2 (3) kW 2,46 2,72 3,11 3,30 3,40 3,54 5,06 5,57 6 6,50 6,93 7,19
Speed 3 (3) kW 2,22 2,39 2,74 2,84 2,98 3,05 4,37 4,73 5,37 5,79 6,12 6,35
Speed 4 (3) kW 1,97 2,11 2,41 2,45 2,62 2,63 3,76 4,05 4,75 5,05 5,37 5,33
Speed 5 (3) kW 1,55 1,60 1,90 1,96 2,05 2,09 2,69 2,80 3,75 3,91 4,18 4,19
Speed 6 (3) kW 0,91 0,90 1,10 1,05 1,23 1,14 1,82 1,80 2,77 2,81 3,05 2,90
Water flow Max (3) l/h 470 530 610 660 670 710 1020 1130 1190 1300 1380 1440
Pressure drop Max (3) kPa 5 8 5 7 6 5 13 10 20 16 16 12
Output supplementary coil (2)
Speed 1 (2) kW 1,48 - 2,12 - 2,48 - 3,48 - 4,11 - 4,52 -
Speed 2 (2) kW 1,37 - 1,92 - 2,24 - 3,13 - 3,71 - 4,09 -
Speed 3 (2) kW 1,26 - 1,74 - 2,02 - 2,78 - 3,40 - 3,72 -
Speed 4 (2) kW 1,15 - 1,57 - 1,82 - 2,46 - 3,09 - 3,37 -
Speed 5 (2) kW 0,95 - 1,30 - 1,50 - 1,92 - 2,55 - 2,78 -
Speed 6 (2) kW 0,62 - 0,84 - 1,00 - 1,36 - 2,01 - 2,21 -
Water flow Max (2) l/h 130 - 190 - 220 - 310 - 360 - 400 -
Pressure drop Max (2) kPa 2 - 4 - 7 - 13 - 20 - 24 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 47 48 49 48 49 51 52 51 52 52 53
Speed 2 (4) dB(A) 41 42 44 45 44 45 47 48 47 48 48 49
Speed 3 (4) dB(A) 38 39 40 41 40 41 43 44 44 45 45 46
Speed 4 (4) dB(A) 35 36 37 38 37 38 41 42 40 42 41 42
Speed 5 (4) dB(A) 30 31 30 31 31 32 33 34 33 34 35 36
Speed 6 (4) dB(A) 22 22 23 23 24 24 25 25 26 26 26 26
Water content l 0,70 0,70 1 1 1,40 1,40 1,40 1 1,80 1,40 2,20 2,20
Fan 1C 1C 1C 1C 1C 1C 2C 2C 2C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 33 33 34 34 37 37 59 59 72 72 74 74
Min absorbed power W 4 4 4 4 4 4 7 7 7 7 7 7
Max absorbed current A 0,29 0,29 0,29 0,29 0,31 0,31 0,49 0,49 0,57 0,57 0,58 0,58
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 411 411 601 601 791 791 791 791 981 981 1171 1171
H (mm) 495 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225 225
Weight kg 12 14 15 17 18 20 20 22 23 25 27 29
Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

237
i-LIFE / DFI
Models 130 140 230 240 330 340 430 440 530 540 630 640
Air flow rate
Speed 1 m3/h 410 390 480 450 485 460 815 790 915 880 925 900
Speed 2 m3/h 360 340 410 380 415 390 680 660 780 750 790 770
Speed 3 m3/h 315 290 350 320 355 330 565 545 680 655 685 670
Speed 4 m3/h 270 250 300 270 305 280 470 455 585 560 590 560
Speed 5 m3/h 200 180 225 210 230 220 315 300 440 420 445 440
Speed 6 m3/h 105 95 120 110 130 120 200 190 310 295 320 305
Total output cooling capacity (1)
Speed 1 (1) kW 1,91 2,32 2,67 3,20 3,22 3,68 4,69 5,57 5,75 6,54 6,92 7,47
Speed 2 (1) kW 1,75 2,10 2,37 2,81 2,86 3,23 4,14 4,87 5,13 5,80 6,16 6,57
Speed 3 (1) kW 1,59 1,87 2,10 2,46 2,53 2,79 3,62 4,22 4,65 5,26 5,53 5,84
Speed 4 (1) kW 1,42 1,67 1,85 2,13 2,24 2,42 3,16 3,65 4,15 4,63 4,88 5,08
Speed 5 (1) kW 1,11 1,27 1,42 1,71 1,77 1,97 2,31 2,56 3,36 3,66 3,90 4,14
Speed 6 (1) kW 0,70 0,75 0,88 1,00 1,06 1,16 1,56 1,64 2,53 2,72 2,95 2,95
Sensible output cooling capacity (1)
Speed 1 (1) kW 1,63 1,77 2,17 2,41 2,47 2,68 3,77 4,20 4,50 4,86 5,13 5,40
Speed 2 (1) kW 1,47 1,58 1,91 2,09 2,17 2,34 3,27 3,62 3,96 4,27 4,52 4,72
Speed 3 (1) kW 1,32 1,39 1,67 1,82 1,90 2,01 2,82 3,10 3,54 3,84 4,03 4,17
Speed 4 (1) kW 1,16 1,23 1,46 1,56 1,67 1,73 2,42 2,66 3,12 3,35 3,53 3,59
Speed 5 (1) kW 0,89 0,93 1,11 1,24 1,30 1,40 1,72 1,84 2,48 2,61 2,78 2,82
Speed 6 (1) kW 0,53 0,54 0,66 0,70 0,77 0,77 1,15 1,18 1,84 1,91 2,07 1,95
Max Water flow (1) l/h 330 400 460 550 550 630 800 960 990 1120 1190 1280
Max Pressure drop (1) kPa 5 10 5 8 7 5 14 11 22 18 18 14
Total output heating capacity (2)
Speed 1 (2) kW 4,46 5,01 5,79 6,28 6,36 6,76 9,58 10,7 11,2 12,3 13,1 13,5
Speed 2 (2) kW 4,04 4,49 5,12 5,44 5,60 5,85 8,33 9,18 9,88 10,7 11,4 11,8
Speed 3 (2) kW 3,66 3,94 4,51 4,70 4,92 5,05 7,19 7,81 8,85 9,56 10,1 10,4
Speed 4 (2) kW 3,25 3,49 3,98 4,05 4,33 4,36 6,20 6,69 7,83 8,34 8,88 8,85
Speed 5 (2) kW 2,56 2,64 3,13 3,24 3,39 3,50 4,45 4,63 6,18 6,47 6,91 7,09
Speed 6 (2) kW 1,50 1,49 1,81 1,78 2,04 1,94 3,00 3,05 4,58 4,70 5,12 4,44
Max Water flow (2) l/h 390 440 510 550 560 590 840 930 980 1080 1150 1190
Max Pressure drop (2) kPa 5 8 4 7 6 5 12 10 19 15 11 12
Total output heating capacity (3)
Speed 1 (3) kW 2,71 3,04 3,52 3,80 3,86 4,09 5,83 6,46 6,81 7,44 7,93 8,25
Speed 2 (3) kW 2,46 2,72 3,11 3,30 3,40 3,54 5,06 5,57 6 6,50 6,93 7,19
Speed 3 (3) kW 2,22 2,39 2,74 2,84 2,98 3,05 4,37 4,73 5,37 5,79 6,12 6,35
Speed 4 (3) kW 1,97 2,11 2,41 2,45 2,62 2,63 3,76 4,05 4,75 5,05 5,37 5,33
Speed 5 (3) kW 1,55 1,60 1,90 1,96 2,05 2,09 2,69 2,80 3,75 3,91 4,18 4,19
Speed 6 (3) kW 0,91 0,90 1,10 1,05 1,23 1,14 1,82 1,80 2,77 2,81 3,05 2,90
Water flow Max (3) l/h 470 530 610 660 670 710 1020 1130 1190 1300 1380 1440
Pressure drop Max (3) kPa 5 8 5 7 6 5 13 10 20 16 16 12
Output supplementary coil (2)
Speed 1 (2) kW 1,48 - 2,12 - 2,48 - 3,48 - 4,11 - 4,52 -
Speed 2 (2) kW 1,37 - 1,92 - 2,24 - 3,13 - 3,71 - 4,09 -
Speed 3 (2) kW 1,26 - 1,74 - 2,02 - 2,78 - 3,40 - 3,72 -
Speed 4 (2) kW 1,15 - 1,57 - 1,82 - 2,46 - 3,09 - 3,37 -
Speed 5 (2) kW 0,95 - 1,30 - 1,50 - 1,92 - 2,55 - 2,78 -
Speed 6 (2) kW 0,62 - 0,84 - 1,00 - 1,36 - 2,01 - 2,21 -
Water flow Max (2) l/h 130 - 190 - 220 - 310 - 360 - 400 -
Pressure drop Max (2) kPa 2 - 4 - 7 - 13 - 20 - 24 -
Sound pressure level (4)
Speed 1 (4) dB(A) 46 47 48 49 48 49 51 52 51 52 52 53
Speed 2 (4) dB(A) 41 42 44 45 44 45 47 48 47 48 48 49
Speed 3 (4) dB(A) 38 39 40 41 40 41 43 44 44 45 45 46
Speed 4 (4) dB(A) 35 36 37 38 37 38 41 42 40 42 41 42
Speed 5 (4) dB(A) 30 31 30 31 31 32 33 34 33 34 35 36
Speed 6 (4) dB(A) 22 22 23 23 24 24 25 25 26 26 26 26
Water content l 0,70 0,70 1 1 1,40 1,40 1,40 1 1,80 1,40 2,20 2,20
Fan 1C 1C 1C 1C 1C 1C 2C 2C 2C 2C 2C 2C
Water IN connection inch 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F 1/2”G F
Water OUT connection inch
Max absorbed power W 33 33 34 34 37 37 59 59 72 72 74 74
Min absorbed power W 4 4 4 4 4 4 7 7 7 7 7 7
Max absorbed current A 0,29 0,29 0,29 0,29 0,31 0,31 0,49 0,49 0,57 0,57 0,58 0,58
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
With Cabinet
L (mm) 411 411 601 601 791 791 791 791 981 981 1171 1171
H (mm) 495 495 495 495 495 495 495 495 495 495 495 495
P (mm) 225 225 225 225 225 225 225 225 225 225 225 225
Weight kg 12 14 15 17 18 20 20 22 23 25 27 29

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Sound pressure in semianechoic room at 1 m from fan front and 1 m from the ground

238
Dimension

H
H

L L
P P

239
Hydronic terminals

NFT 102÷703
Versions
I version without cabinet
U version with cabinet

Features
Plastic air intake and outlet grille;
Very low noise fan unit;
6-speed autotransformer;
Air filter on all models;
Cabinet in galvanised steel for maximum resistance to
rust;
Automatically closing flap to cover and protect electric
controls from dripping water (in conformity with directive
60335-2-40);
Lockable control covers;
Plug-in controls fixing bracket;

Main accessories
UÊPair of decorative and structural feet
UÊAir intake grille kit with version cover
UÊIR reciver for CE comand with remote control
UÊInterface SPB Kit
UÊRear panel for vertical housing
Residential fan-coils with cabinet or UÊHorizontal and vertical fan coil auxiliary tray
UÊHose kit
built-in version UÊIn-line delivery plenum kit
UÊFront air intake plenum for built-in version
0,86 - 4,25 kW UÊManual external air intake lock kit
Unit Description UÊMain coil valve unit ON/OFF, PWM
NFT belongs to residential fan coil range by Climaveneta. This compact fan coil UÊAdditional coil valve unit ON/OFF, PWM
incorporates a tangential low noise fan. They are designed for residential market and
small tertiary installation. Wall-mounted LIFE controls: NSW, PSW, MTW, ATW could be
connected. NFT participates to EUROVENT certification programme.

Commands
NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.
CE Plug-in
Control for plug-in installation on fan coil. Off/summer/winter/auto selector switch. Three speed/auto selector switch.
Thermostat with set point regulation. Air and water probe. ON/OFF valve unit control (summer/winter for 2 pipes installation),
ON/OFF second valve unit control (winter for 4 pipes installation).
PCE wall-mounted
Off/summer/winter/auto selector switch. Room temperature control. Room temperature sensor. Coil temperature sensor.
Three speed air flow control + Auto. Automatic summer/winter switching. Automatic ON/OFF valve control.

240
CONTROLLER FAN COIL TANGENZIALE 4 PIPES 2 PIPES

NFT / U
Models 102 202 302 402 502 603
Air flow rate
Max speed m3/h 310 310 410 410 590 610
Med speed m3/h 250 250 330 330 450 470
Min speed m3/h 175 175 250 250 300 320
Total output cooling capacity (1)
Max speed (1) kW 0,86 1,51 2,02 2,51 3,4 4,25
Med speed (1) kW 0,62 1,18 1,7 2 2,75 3,5
Min speed (1) kW 0,49 0,85 1,35 1,63 1,95 2,4
Sensible output cooling capacity (1)
Max speed (1) kW 0,8 1,22 1,67 1,97 2,65 3,32
Med speed (1) kW 0,56 0,92 1,36 1,52 2,05 2,65
Min speed (1) kW 0,4 0,67 1,05 1,23 1,4 1,75
Max Water flow (1) l/h 147 259 346 430 580 730
Max Pressure drop (1) kPa 10,6 9 24,5 27,1 28 25,6
Total output heating capacity (2)
Max speed (2) kW 2,3 3,5 4,6 5,7 7 9,5
Med speed (2) kW 1,9 3 3,8 4,5 5,8 7,2
Min speed (2) kW 1,42 2,2 3 3,6 4,5 5,5
Max Water flow (2) l/h 200 307 404 499 614 830
Max Pressure drop (2) kPa 3 3 9 13 16 14
Total output heating capacity (3)
Max speed (3) kW 1,25 1,95 2,6 2,86 4,2 5,26
Med speed (3) kW 0,97 1,6 2,3 2,35 3,3 4,23
Min speed (3) kW 0,8 1,3 1,8 1,94 2,5 2,91
Water flow Max (3) l/h 147 259 346 430 580 730
Pressure drop Max (3) kPa 10,4 8,2 22,9 24,9 27 17
Output supplementary coil (2)
Max speed (2) kW 2,1 2,1 2,7 2,9 3,3 3,8
Water flow Max (2) l/h 180 180 240 250 310 330
Pressure drop Max (2) kPa 3 3 9 10 11 13
Sound pressure level (4)
Max speed (4) dB(A) 37 41 41 41 48 48
Med speed (4) dB(A) 30 34 33 37 36 45
Min speed (4) dB(A) 30 25 23 24 33 29
Sound power (5)
Max speed (5) dB(A) 48 52 52 52 59 59
Med speed (5) dB(A) 41 45 44 48 47 56
Min speed (5) dB(A) 41 36 34 35 44 40
Fan
Water IN connection inch 1/2” G F
Water OUT connection inch 1/2” G F
Max absorbed power W 48 50 58 58 68 68
Max absorbed current A 0,23 0,24 0,25 0,25 0,35 0,35
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
With Cabinet
L (mm) 720 720 910 910 1100 1100
H (mm) 535 535 535 535 535 535
P (mm) 200 200 200 200 200 200
Weight kg 18 19 22 23 25 27

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Noise level measured at 1 m in open field conditions
5 Sound power on the basis of measurements made in compliance with Eurovent 8/2

241
NFT / I
Models 102 202 302 402 502 603
Air flow rate
Max speed m3/h 310 310 410 410 590 610
Med speed m3/h 250 250 330 330 450 470
Min speed m3/h 175 175 250 250 300 320
Total output cooling capacity (1)
Max speed (1) kW 0,86 1,51 2,02 2,51 3,4 4,25
Med speed (1) kW 0,62 1,18 1,7 2 2,75 3,5
Min speed (1) kW 0,49 0,85 1,35 1,63 1,95 2,4
Sensible output cooling capacity (1)
Max speed (1) kW 0,8 1,22 1,67 1,97 2,65 3,32
Med speed (1) kW 0,56 0,92 1,36 1,52 2,05 2,65
Min speed (1) kW 0,4 0,67 1,05 1,23 1,4 1,75
Max Water flow (1) l/h 147 259 346 430 580 730
Max Pressure drop (1) kPa 10,6 9 24,5 27,1 28 25,6
Total output heating capacity (2)
Max speed (2) kW 2,3 3,5 4,6 5,7 7 9,5
Med speed (2) kW 1,9 3 3,8 4,5 5,8 7,2
Min speed (2) kW 1,42 2,2 3 3,6 4,5 5,5
Max Water flow (2) l/h 200 307 404 499 614 830
Max Pressure drop (2) kPa 3 3 9 13 16 14
Total output heating capacity (3)
Max speed (3) kW 1,25 1,95 2,6 2,86 4,2 5,26
Med speed (3) kW 0,97 1,6 2,3 2,35 3,3 4,23
Min speed (3) kW 0,8 1,3 1,8 1,94 2,5 2,91
Water flow Max (3) l/h 147 259 346 430 580 730
Pressure drop Max (3) kPa 10,4 8,2 22,9 24,9 27 17
Output supplementary coil (2)
Max speed (2) kW 2,1 2,1 2,7 2,9 3,3 3,8
Water flow Max (2) l/h 180 180 240 250 310 330
Pressure drop Max (2) kPa 3 3 9 10 11 13
Sound pressure level (4)
Max speed (4) dB(A) 37 41 41 41 48 48
Med speed (4) dB(A) 30 34 33 37 36 45
Min speed (4) dB(A) 30 25 23 24 33 29
Sound power (5)
Max speed (5) dB(A) 48 52 52 52 59 59
Med speed (5) dB(A) 41 45 44 48 47 56
Min speed (5) dB(A) 41 36 34 35 44 40
Fan
Water IN connection inch 1/2” G F
Water OUT connection inch 1/2” G F
Max absorbed power W 48 50 58 58 68 68
Max absorbed current A 0,23 0,24 0,25 0,25 0,35 0,35
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
Built-in
L (mm) 545 545 735 735 925 925
H (mm) 503 503 503 503 503 503
P (mm) 195 195 195 195 195 195
Weight kg 13 14 15 16 18 20

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
4 Noise level measured at 1 m in open field conditions
5 Sound power on the basis of measurements made in compliance with Eurovent 8/2

Dimension

H
H

P P
L L

242
243
Hydronic terminals

MHD 30÷60
Versions
- base version

Features
Fan coil in ABS with high mechanical characteristics and
resistance to ageing;
Adjustable air flow direction;
Arrangement for right-left condensate drain pipe;
Removable panel;
Management of all functions by remote control

Main accessories
UÊFrame kit
UÊSolenoid valve 2 ways 1/2”
UÊSolenoid valve kit 3 ways, 4 fits 1/2” with frame
UÊCondensate drain pump

Hydronic hi-wall fan-coil

2,15 - 4,7 kW
Unit Description
MHD belongs to hi-wall fan-coils of Climaveneta. The compactness of this model and its
exclusive elegance soften the visual impact and make it ideal for residential and small tertiary
installations.

Commands
Remote control
Set-point regulation. Selection of functioning mode (cool, heat, dehumidify, fan), fan speed (Max, Med, Min, AUTO). Main
available function: Swing, Sleep, Timer. User-sfriendly compact remote control with fine aethetics.

244
CONTROLLER WALL TANGENZIALE 2 PIPES

MHD / -
Models 30 40 50 60
Air flow rate
Max speed m3/h 436 632 780 920
Med speed m3/h 376 522 691 810
Min speed m3/h 334 403 570 697
Total output cooling capacity (1)
Max speed (1) kW 2,15 2,80 4 4,70
Med speed (1) kW 1,85 2 3,40 3,90
Min speed (1) kW 1,65 1,75 3,10 3,35
Sensible output cooling capacity (1)
Max speed (1) kW 1,82 2,48 3,40 3,60
Med speed (1) kW 1,60 1,75 2,90 3,30
Min speed (1) kW 1,45 1,55 2,60 2,85
Max Water flow (1) l/h
Max Pressure drop (1) kPa 10 16 37 46
Total output heating capacity (2)
Max speed (2) kW 2,70 3,60 4,90 5,80
Med speed (2) kW 2,30 2,55 4,20 4,85
Min speed (2) kW 1,98 2,20 3,80 4,15
Water flow Max (2) l/h
Pressure drop Max (2) kPa 9 15 35 4
Sound power (3) dB(A)
Max speed (3) dB(A) 45 52 55 60
Med speed (3) dB(A) 42 42 52 56
Min speed (3) dB(A) 38 39 48 53
Water IN connection mm 12 12 12 12
Water OUT connection mm 12 12 12 12
Max absorbed power W 24 28 40 50
Max absorbed current A
Electrical power supply V-Ph~Hz 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSION
L mm 845 845 940 940
H mm 270 270 298 298
P mm 180 180 200 200
Weight kg 10 10 13 13

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
3 Sound power on the basis of measurements made in compliance with Eurovent 8/2

Dimension

L P

245
Hydronic terminals

HWD 602÷1104
Versions
- base version
E electronic regulation version with remote
control

Features
Unit coils guarantee high efficiency thermal exchange with
low pressure drop. Finned unit coils are made of copper
tubes and high exchange surface area aluminium fins.
Coils are always tested for leaks with dried air at 30 bar;
Electrical power and control switchboard complete
with electronic air flow regulator and terminal blocks for
connection to power supply and remote control;
Internal insulation in closed cell expanded polyethylene
with suitable thick to limit heat loss and noise emission;
The fan unit high pressure are fitted with balanced
impellers to guarantee minimum noise levels;
Structure and base plate in hot-dip galvanised steel for
maximum resistance to rust;
Extra modules available as accessories to the standard
unit;
Remote control to manage main unit functions to provide
a total enviroment comfort. Full Auto function;
Arrangement for electronic control of two on/off or
modulating valve unit in the water circuit;

Ducted type terminal Main accessories


UÊInterface SPB Kit
UÊHot water coil kit
4,8 - 15,1 kW UÊAir purifier module with actived carbon filter
UÊHeating element module
Unit Description UÊHumidifier module
HWD are Climaveneta ducted hydronic terminal units. The fan units at available working
UÊDelivery and intake plenum
pressures, through internal insulation, ensure excellent acoustic comfort levels. The
compactness and ease of installation make HWD a suitable hydronic terminal unit for any type UÊDelivery plenum for round ducts
of setting. UÊTwo way intake plenum with air lock
UÊCondensate drain pump
Commands
NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.
PCE wall-mounted
Off/summer/winter/auto selector switch. Room temperature control. Room temperature sensor. Coil temperature sensor.
Three speed air flow control + Auto. Automatic summer/winter switching. Automatic ON/OFF valve control.

250
CONTROLLER DUCT CENTRIFUGAL 4 PIPES 2 PIPES

HWD / -
Models 602 703 803 904 1003 1104
Air flow rate
Max speed m3/h 1300 1300 1600 1600 2200 2500
Med speed m3/h 1171 1171 1357 1357 1985 2243
Min speed m3/h 1021 1021 1057 1057 1585 1771
Useful head (basic unit with filter) Pa 60 60 60 60 60 60
Total output cooling capacity (1)
Max speed (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Med speed (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Min speed (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible output cooling capacity (1)
Max speed (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Med speed (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Min speed (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max Pressure drop (1) kPa 12 8 14 13 24 23
Total output heating capacity (2)
Max speed (2) kW 6,61 8,48 10,5 12,1 14,8 18,7
Med speed (2) kW 6,19 7,88 9,34 10,7 13,7 17,3
Min speed (2) kW 5,65 7,13 7,75 8,73 11,6 14,3
Pressure drop Max (2) kPa 10 7 12 11 21 20
Output supplementary coil (3)
Max speed (3) kW 9,10 9,10 11,8 11,8 16,7 18,0
Pressure drop Max (3) kPa 9 9 14 14 13 15
Sound power (4)
Max speed (4) dB(A) 68 68 72 72 78 80
Med speed (4) dB(A) 65 65 69 69 76 77
Min speed (4) dB(A) 62 62 63 63 70 72
Hydraulic connections main coil inch 1/2” 1/2” 3/4” 3/4” 1” 1”
Hydraulic connections
inch 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
supplementary coil
Max absorbed power W 370 370 440 440 900 900
Max absorbed current A 1,30 1,30 1,55 1,55 3,50 3,50
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
Built-in
L (mm) 900 900 1050 1050 1250 1250
H (mm) 295 295 295 295 315 315
P (mm) 695 695 695 695 750 750
Weight kg 41 43 50 52 63 63

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
4 Sound power on the basis of measurements made in compliance with Eurovent 8/12

251
HWD / E
Models 602 703 803 904 1003 1104
Air flow rate
Max speed m3/h 1300 1300 1600 1600 2200 2500
Med speed m3/h 1171 1171 1357 1357 1985 2243
Min speed m3/h 1021 1021 1057 1057 1585 1771
Useful head (basic unit with filter) Pa 60 60 60 60 60 60
Total output cooling capacity (1)
Max speed (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Med speed (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Min speed (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible output cooling capacity (1)
Max speed (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Med speed (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Min speed (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max Pressure drop (1) kPa 12 8 14 13 24 23
Total output heating capacity (2)
Max speed (2) kW 6,61 8,48 10,5 12,1 14,8 18,7
Med speed (2) kW 6,19 7,88 9,34 10,7 13,7 17,3
Min speed (2) kW 5,65 7,13 7,75 8,73 11,6 14,3
Pressure drop Max (2) kPa 10 7 12 11 21 20
Output supplementary coil (3)
Max speed (3) kW 9,10 9,10 11,8 11,8 16,7 18,0
Pressure drop Max (3) kPa 9 9 14 14 13 15
Sound power (4)
Max speed (4) dB(A) 68 68 72 72 78 80
Med speed (4) dB(A) 65 65 69 69 76 77
Min speed (4) dB(A) 62 62 63 63 70 72
Hydraulic connections main coil inch 1/2” 1/2” 3/4” 3/4” 1” 1”
Hydraulic connections
inch 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
supplementary coil
Max absorbed power W 370 370 440 440 900 900
Max absorbed current A 1,30 1,30 1,55 1,55 3,50 3,50
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
Built-in
L (mm) 900 900 1050 1050 1250 1250
H (mm) 295 295 295 295 315 315
P (mm) 695 695 695 695 750 750
Weight kg 41 43 50 52 63 63

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 50°C, with identical flow rate that in the cooling mode
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
4 Sound power on the basis of measurements made in compliance with Eurovent 8/12

Dimension

252
253
Hydronic terminals

HWD-HP 0071÷0121
Versions
- base version

Features
Unit coils guarantee high efficiency thermal exchange with
low pressure drop. Finned unit coils are made of copper
tubes and high exchange surface area aluminium fins.
Coils are always tested for leaks with dried air at 30 bar;
The electrical power and control switchboard includes
electronic air flow regulator and terminal blocks for
connection to power supply and remote control;
Internal insulation in closed cell expanded polyethylene
with suitable thick to limit heat loss and noise emission;
The fan unit high pressure are fitted with balanced
impellers to guarantee minimum noise levels;
Cabinet in galvanised steel for maximum resistance to
rust;
Extra modules available as accessories to the standard
unit;

Main accessories
UÊInterface SPB Kit
UÊHot water coil kit
UÊHeating element module

High head ducted type terminal UÊDelivery and intake plenum


UÊIntake grill
UÊTwo way intake plenum with air lock
UÊCeiling brackets
16,8 - 29,8 kW UÊAuxiliary condensate collecting tray

Unit Description
HWD HP belongs to ducted type fan-coils high head of Climaveneta. The possibility of vertical
or horizontal installation, airflow adjustment and attractive external panelling guarantees an
ease installation and make the unit adaptable to any type of surroundings.

Commands
NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.
PCE wall-mounted
Off/summer/winter/auto selector switch. Room temperature control. Room temperature sensor. Coil temperature sensor.
Three speed air flow control + Auto. Automatic summer/winter switching. Automatic ON/OFF valve control.

254
CONTROLLER DUCT CENTRIFUGAL 4 PIPES 2 PIPES

HWD-HP / -
Models 0071 0091 0101 0121
Total output cooling capacity (1) kW 16,8 20 23,4 29,8
Sensitive output cooling capacity (1) kW 12,3 14,4 17,3 21,7
Total output heating capacity (2) kW 16,3 19,6 23 29,5
Heating capacity standard coil (3) kW 34,6 40 47,8 60,4
Output supplementary coil (3) kW 25 25 36 39
Pressure drop main coil (1) kPa 24 22 14 12
Pressure drop additional coil (3) kPa 14 14 19 22
Absorbed power kW 0,68 0,68 1,75 2,24
Absorbed current at nominal
A 2,9 2,9 7,9 9,5
conditions
Nominal air flow m3/h 3200 3200 4400 5000
Useful head (basic unit with filter) Pa 105 93 250 141
Hydraulic connections main coil inch 1”1/4 1”1/4 1”1/2 1”1/2
Hydraulic connections
inch 3/4” 3/4” 1 1
supplementary coil
Sound pressure level (4) dB(A) 60 60 66 69
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
DIMENSION
L mm 1300 1300 1500 1500
H mm 510 510 625 625
P mm 1119 1119 1349 1349
Weight kg 121 124 145 149

Note:
1 Operation in cooling mode: room temperature 27°C d.b./19°C w.b., chilled water at inlet 7°C and at outlet 12°C
2 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 45°C and at outlet 40°C
3 Operation in heating mode: room temperature 20°C d.b., hot water at inlet 70°C and at outlet 60°C
4 Noise level measured at 1 m in open field conditions

Dimension
L
P

255
Hydronic terminals

HRD 0021÷0151
Versions
- base version

Features
Removable aluzink plate side panels;
Panels insulated and soundproofed with polyethylene/
polyester with average thickness of 10 mm (mod. HRD
0021-0051) and 20 mm for the other models;
High efficiency aluminium plate static type heat recovery
units, with airflow separated by special seals;
UE3 efficiency air filters, which may be easily removed
from any side of the unit (bottom, side, top) for periodic
cleaning;
Fan casings on vibration-isolation mountings;
Double inlet centrifugal fans for fresh air intake and used
air extraction, which may be removed from any side of the
unit for periodic maintenance;
Multi speed directly coupled electric motor;
A terminal block with a relay board is fitted on the unit to
aid electrical connections and fan control;
Stainless steel condensate collecting tray, with
condensate drain directed downwards;

Main accessories
UÊInterface SPB Kit
Heat recuperator unit UÊHot water coil kit
UÊCool water coil kit
UÊHeating element kit

290 - 4000 m3/h


Unit Description
HRD heat recuperator units for residential and commercial application allow maximum room
comfort and energy saving. In modern systems is becoming necessary to create forced
ventilation, which involves air conditioned expelling; thereby consuming more energy and
consequenting increasing costs. HRD heat recuperators have obviated such as problems
using an aluminium static recovery unit that saves more than 50% energy, otherwise be lost
with expelled stale air. HRD can be integrated in traditional systems with fan coils, chillers
and radiators and may operate both in summer and winter. These units are recommended
for suspended ceiling installation and may be suitably ducted to allow the fresh air intake and
distribution.

Commands
NSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Setting for minimum temperature thermostat.
PSW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/
OFF second valve unit control (winter for 4 pipes installation). Remote water temperature probe.
MTW wall mounted
Fan speed slider, mode slider (OFF/summer/winter). Thermostat with set point regulation. ON/OFF valve unit control (summer/
winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes installation). Room temperature probe.
Remote water temperature probe.
ATW wall mounted
Mode button (OFF/summer/winter/AUTO), fan speed button (Max/Med/Min/AUTO). Thermostat with set point regulation.
ON/OFF valve unit control (summer/winter for 2 pipes installation), ON/OFF second valve unit control (winter for 4 pipes
installation). Control of traditional or PWM modulating valve units. Room temperature probe and water temperature probe.
Digital input configurable as: window contact, economy, heating or cooling remote changeover, periodic ventilation.
Configuration dip switch. TTL serial port with Modbus protocol for installation in Building Management System.
PCE wall-mounted
Off/summer/winter/auto selector switch. Room temperature control. Room temperature sensor. Coil temperature sensor.
Three speed air flow control + Auto. Automatic summer/winter switching. Automatic ON/OFF valve control.

256
CONTROLLER PLATE CENTRIFUGAL

HRD / -
Models 0021 0031 0051 0071 0091 0101 0121 0151
Max air flow m3/h 290 600 1000 1400 1900 2500 3200 4000
Sound level Max (1) dB(A) 54 56 54 59,5 58 57,5 60,5 62
Axle power available W 2x45 2x90 2x147 2x350 2x350 2x350 2x550 2x750
Poles N° 4 2 4 4 4 4 4 4
Max absorption A 1,3 1,8 3,0 5,8 6,2 6,0 11,4 6,2
N° fan speeds N° 2 1 3 3 3 3 3 2
Efficiency % 52,3 54,6 53,4 52,1 51,8 57,6 56,0 55,6
Recuperated thermal power kW 1 3 5 6 8 12 15 19
Renewal air temperature °C 8,10 8,70 8,30 8,00 7,90 9,40 9,00 8,90
Efficiency G3 G3 G3 G3 G3 G3 G3 G3
Frontal air speed m/s 1,7 3,6 2,9 4,1 4,5 3,8 4,3 4,3
Protection grade IP 20 54 44 55 44 55 20 55
Isolation grade B F F F F F F F
ESP Pa 40 80 90 140 120 110 170 170
Electrical power supply internal unit V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz
DIMENSION
L mm 990 990 1150 1350 1450 1700 1700 1700
H mm 270 270 385 410 470 490 530 630
P mm 750 750 860 900 900 1230 1230 1230
Net weight kg 39 41 68 91 99 140 155 179

Note:
1 Sound pressure measured at 1 m in open field conditions

Dimension

L P

257
H
HP
258
PAC
259
HPAC

HPAC
HPAC

i-AX 18÷90
Versions
STD base version with fan speed regulation
for i-BRE
MOD version with condensing fan speed regulation
LT low outdoor temperature version with
condensing fan speed regulation

Features

Unit for installing inside or outside the room to be air-


conditioned.
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material
to limit noise levels.
The reliability and functionality of the compressor and all
the other parts are guaranteed by partners who are world
leaders in their sector.

NEW EC INVERTER fans with electronic commutation in


order to maximize the energy saving and reducing the
noise emissions.
Condensing control for maximum low noise (optional).
Standard G2/G4 filtering section, F6-F8 optional, to CEN-
Close control unit, direct expansion air EN 779 with average degree of separation 90.1%
ASHRAE. The filter is self-extinguishing.
cooled with INVERTER compressor The microprocessor controls the compressor activation
times with FIFO logic, thereby regulating the cooling
7 - 100 kW capacity; it also controls the operating alarms with the
possibility of interfacing to supervisor and remote-
servicing systems.
Unit Description Switchboard to IEC 204-1/EN60204-1
Ductable close control units air-conditioners with capacity ranging from 7 to 100 Refrigerant circuit consisting in the standard version of a
kW for vertical installation and cooling only, with optional heating by means of electronic expansion valve, liquid solenoid valve, high/low
heating elements and hot water, optional humidifer and dehumidifier for precise pressure switch, sight glass liquid indicator drier filter and
temperature and humidity control. Particularly suitable for air conditioning oil separator in order to guarantee the right lubrification of
technological, servers and IT rooms and all technological applications in general. the compressor at the low speed.
The INVERTER compressor allows the cooling capacity modulation according to Capillary Pre and After sales service.
the real internal load, particularly efficient at the partial loads and optimizing the
power absorbed and eliminating the start current. Units fitted with electronic
expansion valve and EC INVERTER fans, upflow or downflow.
Main accessories
Commands • Remote user terminal
EVOLUTION • Electric heating coil
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm, • Water heating coil
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management, • Humidifier
Automatic rotation, Serious alarms, Operating contemporaneousness • Vibration isolation frame with rubber mountings
• Air distribution plenum
• Sound absorber plenum for air outlet
• Interface electronic board

260
Inverter i-AX
Models 18 29 50 70 90
Frame F2 F3 F4 F5 F6
Power supply V/Ph/Hz 400/3N/50 400/3N/50 400/3N/50 400/3N/50 400/3N/50
Refrigerant R410A R410A R410A R410A R410A
N° compressors 1 1 1 2 2
PERFORMANCES
High Speed
Total cooling capacity (1) kW 16,60 28,07 53,14 68,40 84,68
Sensible cooling capacity (1) kW 16,60 28,07 50,30 67,30 84,68
SHR (1) 1,00 1,00 0,95 0,98 1,00
Total compressors absorbed power kW 4,09 7,14 13,92 16,47 21,03
EER 3,65 3,24 3,12 3,25 3,12
Low speed
Total cooling capacity (1) kW 6,27 10,62 23,68 22,06 22,70
Sensible cooling capacity (1) kW 6,27 10,62 23,68 22,06 22,70
SHR (1) 1,00 1,00 1,00 1,00 1,00
Total compressors absorbed power kW 1,24 1,96 4,85 4,82 4,83
Booster (not continuative functioning)
Total cooling capacity (1) kW 20,42 34,77 56,52 85,31 93,47
Sensible cooling capacity (1) kW 18,44 31,10 51,30 74,60 89,77
SHR (1) 0,90 0,89 0,91 0,87 0,96
Total compressors absorbed power kW 5,66 8,00 15,24 22,49 24,49
VENTILATION
Nominal air flow volume mc/h 4900 8000 13500 19000 25000
Fan absorbed power kW 0,47 1,51 3,13 4,57 6,1
Sound pressure level (2) dB(A) 53 60 64 67 67
HUMIDIFIER
Capacity kg/h 5 5 5 8 8
Absorbed power kW 3,75 3,75 3,75 6 6
ELECTRICAL HEATERS
Steps 3 3 3 3 3
Absorbed power kW 8 9 15 18 18
DIMENSIONS
L mm 1000 1000 1550 2100 2650
P mm 500 790 790 790 790
H mm 1980 1980 1980 1980 1980

NOTE
(1) Indoor conditions: 24°C-50% Condensing temp. 45°C - ESP 20Pa
(2) Measured at 1,5 m height, 2 m in front of the unit in free field

P L

261
HPAC

i-AW 18÷90
Versions
STD base version with fan speed regulation
for i-BDC

MOD_A version with condensing fan speed regulation

MOD_B version with condensing pressostatic regulation

Features

Unit for installing inside or outside the room to be air-


conditioned.
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material
to limit noise levels.
The reliability and functionality of the compressor and all
the other parts are guaranteed by partners who are world
leaders in their sector.

NEW EC INVERTER fans with electronic commutation in


order to maximize the energy saving and reducing the
noise emissions.
Condensing control for maximum low noise (optional).
Standard G2/G4 filtering section, F6-F8 optional, to CEN-
Close control unit, direct expansion EN 779 with average degree of separation 90.1%
ASHRAE. The filter is self-extinguishing.
water cooled with INVERTER The microprocessor controls the compressor activation
times with FIFO logic, thereby regulating the cooling
compressor 7 - 100 kW capacity; it also controls the operating alarms with the
possibility of interfacing to supervisor and remote-
Unit Description servicing systems.
Ductable close control units air-conditioners with capacity ranging from 7 to 100 Switchboard to IEC 204-1/EN60204-1
kW for vertical installation and cooling only, with optional heating by means of Refrigerant circuit consisting in the standard version of a
heating elements and hot water, optional humidifer and dehumidifier for precise electronic expansion valve, liquid solenoid valve, high/low
temperature and humidity control. Particularly suitable for air conditioning pressure switch, sight glass liquid indicator drier filter and
technological, servers and IT rooms and all technological applications in general. oil separator in order to guarantee the right lubrification of
The INVERTER compressor allows the cooling capacity modulation according to the compressor at the low speed.
the real internal load, particularly efficient at the partial loads and optimizing the Capillary Pre and After sales service.
power absorbed and eliminating the start current. Units fitted with electronic
expansion valve and EC INVERTER fans, upflow or downflow.

Main accessories
Commands • Remote user terminal
EVOLUTION • Electric heating coil
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm,
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management, • Water heating coil
Automatic rotation, Serious alarms, Operating contemporaneousness • Humidifier
• Vibration isolation frame with rubber mountings
• Air distribution plenum
• Sound absorber plenum for air outlet
• Special filter plenum for air outlet
• Interface electronic board

262
Inverter i-AW
Models 18 29 50 70 90
Frame F2 F3 F4 F5 F6
Power supply V/Ph/Hz 400/3N/50 400/3N/50 400/3N/50 400/3N/50 400/3N/50
Refrigerant R410A R410A R410A R410A R410A
N° compressors 1 1 1 2 2
PERFORMANCES
High Speed
Total cooling capacity (1) kW 17,35 29,32 55,00 72,25 91,52
Sensible cooling capacity (1) kW 17,04 28,60 50,80 69,48 89,80
SHR (1) 0,98 0,98 0,92 0,96 0,98
Total compressors absorbed power kW 3,68 6,38 13,02 14,47 19,64
EER 4,18 3,71 3,40 3,80 3,56
Low speed
Total cooling capacity (1) kW 7,27 12,33 25,67 23,61 25,36
Sensible cooling capacity (1) kW 7,27 12,33 25,67 23,61 25,36
SHR (1) 1,00 1,00 1,00 1,00 1,00
Total compressors absorbed power kW 0,96 1,43 3,83 3,99 3,92
Booster (not continuative functioning)
Total cooling capacity (1) kW 21,69 35,30 58,07 88,03 100,09
Sensible cooling capacity (1) kW 18,96 31,10 52,00 75,90 93,10
SHR (1) 0,87 0,88 0,90 0,86 0,93
Total compressors absorbed power kW 4,97 7,83 14,46 21,00 23,64
VENTILATION
Nominal air flow volume mc/h 4900 8000 13500 19000 25000
Fan absorbed power kW 0,47 1,51 3,13 4,57 6,1
Sound pressure level (2) dB(A) 53 60 64 67 67
HUMIDIFIER
Capacity kg/h 5 5 5 8 8
Absorbed power kW 3,75 3,75 3,75 6 6
ELECTRICAL HEATERS
Steps 3 3 3 3 3
Absorbed power kW 8 9 15 18 18
DIMENSIONS
L mm 1000 1000 1550 2100 2650
P mm 500 790 790 790 790
H mm 1980 1980 1980 1980 1980

NOTE
(1) Indoor conditions :24°C-50% Water 30- 35°C - ESP 20Pa
(2) Measured at 1,5 m height, 2 m in front of the unit in free field

P L

263
HPAC

AX 07÷90
Versions
STD base version
LT low outdoor temperature version with condensing
fan speed regulation
MOD version with condensing fan speed regulation

Features
Unit for installing inside or outside the room to be
air-conditioned.
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint finish.
The panels are lined with sound-insulating material to limit
noise levels.
The reliability and functionality of the compressor and all
the other parts are guaranteed by partners who are world
leaders in their sector.
Double-inlet centrifugal fan per standard installed, directly
coupled and suspended on vibration-isolation mountings.
The fans are of the forward-bladed type for maximum
efficiency and low noise. Available as option, EC INVERTER
fans with electronic commutation, Backward Curved Fan type
to minimize energy consumption and noise emission.
Condensing control for maximum low noise (optional).
Close control unit, air cooled, direct Standard G2/G4 filtering section, F6-F8 optional, to
CEN-EN 779 with average degree of separation 90.1%
expansion ASHRAE. The filter is self-extinguishing.
The microprocessor controls the compressor activation
7 - 90 kW times with FIFO logic, thereby regulating the cooling capacity;
it also controls the operating alarms with the possibility of
interfacing to supervisor and remote-servicing systems.
Unit Description Switchboard to IEC 204-1/EN60204-1
Ductable close control air-conditioners with capacities ranging from 7 to 90 kW for Refrigerant circuit consisting in the standard version of a
vertical installation and cooling only, with optional heating by means of heating thermostatic valve with external equalization (electronic
element or hot water, optional humidifier and dehumidifier for precise temperature expansion valve avaible as option), liquid solenoid valve,
and humidity control. Particularly suitable for air-conditioning technological, server high/low pressure switch, sight glass liquid indicator and
and CED rooms and all technological applications in general. Units fitted with drier filter.
centrifugal fans with upward airflow from the top or from the bottom. Capillary Pre and After sales service.
External air condenser. Power supply 400V/3+N/50Hz (all models).
Main accessories
Commands • Remote user terminal
EVOLUTION • Electric heating coil
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm, • Water heating coil
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management, • Humidifier
Automatic rotation, Serious alarms, Operating contemporaneousness • Vibration isolation frame with rubber mountings
• Air distribution plenum
• Sound absorber plenum for air outlet
• Interface electronic board
• Electronic Thermostatic valve

264
ACCURATE AX / STD

Models 07 10 15 18 20 26 29 39
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 7,20 9,60 16,3 19,1 23,3 28,9 31,8 41
Sensible cooling capacity (1) kW 7,20 9,20 16,3 18,2 23,3 28,8 29,9 41
SHR 1 0,96 1 0,95 1 1 0,94 1
COMPRESSORS
Quantity n° 1 1 1 1 1 1 1 1
Power absorbed kW 1,69 2,20 3,64 4,31 4,93 6 6,93 7,86
N° Circuits n° 1 1 1 1 1 1 1 1
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
FANS
Fan air flow m3/h 2500 2500 4900 4900 6500 8000 8000 13500
N° Centrifugal fans n° 1 1 2 2 1 1 1 2
N° EC Inverter fans n° 1 1 2 2 1 1 1 2
Centrifugal fans power abs. kW 0,49 0,49 1 1 1,66 2,02 2,02 3,61
EC Inverter fans power abs. kW 0,27 0,27 0,53 0,53 0,89 1,69 1,69 3,51
ESP std. Pa 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 50 50 53 53 56 60 60 64
AIR FILTER
Degree filtration G2 G2 G2 G2 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 3 3 5 5 5 5 5 5
Power absorbed kW 2,25 2,25 3,75 3,75 3,75 3,75 3,75 3,75
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3
Power absorbed kW 4 4 8 8 9 9 9 15
DIMENSION
L mm 600 600 1000 1000 1000 1000 1000 1550
P mm 500 500 500 500 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BRE STD/LT/LN 014m 014m 022m 027m 027m 044m 044m 051m

Models 30 40 50 55 60 70 80 90
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 33,4 46,2 52,3 60,3 68,1 73,2 87,8 95,4
Sensible cooling capacity (1) kW 33,4 46,2 49,9 60,3 68,1 70,1 87,8 91,8
SHR 1 1 0,95 1 1 0,96 1 0,96
COMPRESSORS
Quantity n° 2 2 2 2 2 2 2 2
Power absorbed kW 7,26 9,85 12 12 13,9 15,7 17,7 21,3
N° Circuits n° 2 2 2 2 2 2 2 2
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
FANS
Fan air flow m3/h 10500 13500 13500 19000 19000 19000 25000 25000
N° Centrifugal fans n° 2 2 2 2 2 2 - -
N° EC Inverter fans n° 2 2 2 3 3 3 4 4
Centrifugal fans power abs. kW 2,89 3,61 3,61 6,55 6,55 6,55 - -
EC Inverter fans power abs. kW 2,09 3,51 3,51 5,11 5,11 5,11 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 59 64 64 67 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 8 8 8 8 8
Power absorbed kW 3,75 3,75 3,75 6 6 6 6 6
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3
Power absorbed kW 15 15 15 18 18 18 18 18
DIMENSION
L mm 1550 1550 1550 2100 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BRE STD/LT/LN 054b 054b 065b 065b 076b 100b 100b 116b

NOTE
(1) Indoor air: 24°C/50% r.h.; Condensing temp.: 45°C
(2) Measured at 1,5 m high and 2 m front unit, in open field conditions

265
HPAC

AW 07÷90
Versions
STD base version
MOD_A version with condensing fan speed regulation
MOD_B version with condensing pressostatic regulation

Features
Unit for installing inside or outside the room to be
air-conditioned.
Maximum resistance to rust thanks to galvanised sheet metal
structures and panels with powder-coated paint finish.
The panels are lined with sound-insulating material to limit noise
levels. The reliability and functionality of the compressor and all
the other parts are guaranteed by partners who are world
leaders in their sector.
Double-inlet centrifugal fan per standard installed, directly
coupled and suspended on vibration-isolation mountings.
The fans are of the forward-bladed type for maximum efficiency
and low noise. Available as option, EC INVERTER fans with
electronic commutation, Backward Curved Fan type to
minimize energy consumption and noise emission.
Condensing control for maximum low noise (optional).
Standard G2/G4 filtering section, F6-F8 optional, to
Close control unit, water cooled direct CEN-EN 779 with average degree of separation 90.1%
ASHRAE. The filter is self-extinguishing.
expansion The microprocessor controls the compressor activation times
with FIFO logic, thereby regulating the cooling capacity; it also
07 - 90 kW controls the operating alarms with the possibility of interfacing
to supervisor and remote-servicing systems.
Refrigerant circuit consisting in the standard version of a
Unit Description thermostatic valve with external equalization (electronic
Ducted close-control air-conditioners with capacities ranging from 7 to 90 kW for expansion valve avaible as option), liquid solenoid valve,
vertical installation and cooling only, with optional reheating by means of heating high/low pressure switch, sight glass liquid indicator and
element or hot water, optional humidifier and dehumidifier for precise temperature drier filter.
and humidity control. Particularly suitable for air-conditioning technological, server Switchboard to IEC 204-1/EN60204-1
and CED rooms and all technological applications in general. Units fitted with Capillary Pre and After sales service.
centrifugal fans with upward airflow from the top and from the bottom and
incorporated water-cooled condenser. External Dry Cooler.
Power supply 400V/3+N/50Hz (for all units). Main accessories
• Remote user terminal
Commands • Electric heating coil
EVOLUTION • Water heating coil
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm, • Humidifier
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management, • Vibration isolation frame with rubber mountings
Automatic rotation, Serious alarms, Operating contemporaneousness • Air distribution plenum
• Sound absorber plenum for air outlet
• Interface electronic board
• Electronic Thermostatic valve

266
ACCURATE AW / STD

Models 07 10 15 18 20 26 29 39
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 7,50 9,80 16,9 19,8 24,5 29,2 33 43
Sensible cooling capacity (1) kW 7,50 9,30 16,9 18,3 23,8 28,3 29,9 43
SHR 1 0,95 1 0,92 0,97 0,97 0,91 1
COMPRESSORS
Quantity n° 1 1 1 1 1 1 1 1
Power absorbed kW 1,47 1,91 3,26 3,93 4,28 5,38 6,24 6,91
N° Circuits n° 1 1 1 1 1 1 1 1
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
FANS
Fan air flow m3/h 2500 2500 4900 4900 6500 8000 8000 13500
N° Centrifugal fans n° 1 1 2 2 1 1 1 2
N° EC Inverter fans n° 1 1 2 2 1 1 1 2
Centrifugal fans power abs. kW 0,49 0,49 1 1 1,66 2,02 2,02 3,61
EC Inverter fans power abs. kW 0,27 0,27 0,53 0,53 0,89 1,69 1,69 3,51
ESP std. Pa 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 50 50 53 53 56 60 60 64
AIR FILTER
Degree filtration G2 G2 G2 G2 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 3 3 5 5 5 5 5 5
Power absorbed kW 2,25 2,25 3,75 3,75 3,75 3,75 3,75 3,75
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3
Power absorbed kW 4 4 8 8 9 9 9 15
PLATE CONDENSER
Water flow rate (1) l/h 1520 2050 3390 4020 4820 5930 6730 8360
Pressure drop (1) kPa 8 14 57 23 30 27 24 30
DIMENSION
L mm 600 600 1000 1000 1000 1000 1000 1550
P mm 500 500 500 500 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BDC STD/LT/LN 013m 013m 030m 030m 030m 039m 039m 052m

Models 30 40 50 55 60 70 80 90
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 34,8 48,5 54,5 62,6 70,8 77,4 90,6 99,3
Sensible cooling capacity (1) kW 34,8 48,4 49,9 62,6 69,1 71,1 90 92,8
SHR 1 1 0,92 1 0,98 0,92 0,99 0,93
COMPRESSORS
Quantity n° 2 2 2 2 2 2 2 2
Power absorbed kW 6,42 8,53 10,8 10,8 12,4 13,5 15,9 19,2
N° Circuits n° 2 2 2 2 2 2 2 2
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
FANS
Fan air flow m3/h 10500 13500 13500 19000 19000 19000 25000 25000
N° Centrifugal fans n° 2 2 2 2 2 2 - -
N° EC Inverter fans n° 2 2 2 3 3 3 4 4
Centrifugal fans power abs. kW 2,89 3,61 3,61 6,55 6,55 6,55 - -
EC Inverter fans power abs. kW 2,09 3,51 3,51 5,11 5,11 5,11 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 59 64 64 67 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 8 8 8 8 8
Power absorbed kW 3,75 3,75 3,75 6 6 6 6 6
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3
Power absorbed kW 15 15 15 18 18 18 18 18
PLATE CONDENSER
Water flow rate (1) l/h 3460x2 4780x2 5715x2 6155x2 6975x2 7705x2 17850 20160
Pressure drop (1) kPa 21 30 33 30 26 31 39
DIMENSION
L mm 1550 1550 1550 2100 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BDC STD/LT/LN 039m 052m 062m 078m 078m 092m 103m 123m
NOTE
(1) Indoor air: 24°C/50% r.h.; Water: 30°-35°C
(2) Measured at 1,5 m high and 2 m front unit, in open field conditions

267
HPAC

AD 20÷90
Versions
STD base version
LT low outdoor temperature version with
condensing fan speed regulation
MOD version with condensing fan speed regulation

Features
Unit for installing inside or outside the room to be
air-conditioned
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material.
The reliability of all the components is guaranteed by
partners who are world leaders in their sector.
NEW EC INVERTER fans with electronic commutation in
order to maximize the energy saving and reducing the
noise emissions.
Standard G4 filtering section, F6-F8 optional, under
CEN-EN 779 rule with the separation degree 90,1%
ASHRAE. The filter is autoestinguishing type.
The microprocessor controls all the main functions of the
air conditioners; it also controls the operating alarms
with the possibility of interfacing to supervisor and
Close control unit dual fluid, air cooled remoteservicing systems.
Electrical box under IEC 204-1/EN60204-1 rules.
direct expansion Capillary Pre and After sales service.

20 - 100 kW Main accessories


• Remote user terminal
• Electric heating coil
Unit Description • Water heating coil
Ductable close control units air-conditioners with capacity ranging from 20 to 100 • Humidifier
kW for vertical installation and cooling only, with optional heating by means of • Vibration isolation frame with rubber mountings
heating elements and hot water, optional humidifer and dehumidifier for precise • Air distribution plenum
temperature and humidity control. Particularly suitable for air conditioning • Sound absorber plenum for air outlet
technological, servers and IT rooms and all technological applications in general. • Interface electronic board
Units fittend with EC INVERTER fans, upflow or downflow. • Electronic Thermostatic valve

DUAL FLUID unit has to be connected to an external chiller for PRIMARY circuit.
The direct expansion circuit, secondary or BACK-UP circuit, is air cooled and has
to be connected with a remote condenser.

Commands
EVOLUTION
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm,
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management,
Automatic rotation, Serious alarms, Operating contemporaneousness

268
ACCURATE AD/STD

Models 20 26 29 39 30 40 50 60 70 80 90
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES (DX)
Total cooling capacity (1) kW 23,7 29,4 32,7 42,2 36,7 47,6 55,1 62,1 75,5 86,3 98,8
Sensible cooling capacity (1) kW 21,8 27,9 30,2 42,2 36,2 47 50,7 62,1 71 86,1 91
SHR 0,92 0,95 0,92 1 0,99 0,99 0,92 1 0,94 1 0,92
COMPRESSORS
Quantity n° 1 1 1 1 2 2 2 2 2 2 2
Power abs. kW 4,93 6,01 6,75 7,87 7,15 9,87 11,7 12 15,4 17,7 21,4
N° Circuits n° 1 1 1 1 2 2 2 2 2 2 2
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
COOLING PERFORMANCES (CW)
Total cooling capacity (2) kW 23,8 28,1 29,5 20 41 50 51,4 65 67,6 91 91
Sensible cooling capacity (2) kW 21,8 26,4 27,6 46,3 37 46,3 47,5 62,2 64,5 85 85
SHR 0,92 0,94 0,94 0,93 0,90 0,93 0,92 0,96 0,95 0,93 0,93
Water flow rate (2) l/h 3890 4590 4590 8170 6710 8170 8170 10630 10630 14870 14870
Total pressure drop water side kPa 26 35 35 46 30 46 46 26 26 53 53
VENTILATION
Air flow mc/h 6000 7500 8000 13000 10000 13000 13500 18000 19000 24000 24000
N° EC Inverter fans n° 1 1 1 2 2 2 2 3 3 4 4
EC Inverter fans power abs. kW 0,89 1,60 1,80 3,40 2,09 3,40 3,65 4,50 5,20 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20 20 20 20
Sound pressure level (3) dB(A) 56 60 60 64 59 64 64 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 5 5 5 5 8 8 8 8
Power abs. kW 3,75 3,75 3,75 3,75 3,75 3,75 3,75 6 6 6 6
ELECTRICAL HEATERS
Steps 3 3 3 3 3 3 3 3 3 3 3
Power abs. kW 9 9 9 15 15 15 15 18 18 18 18
DIMENSION
L mm 1000 1000 1000 1550 1550 1550 1550 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BRE STD/LT/LN 027m 044m 044m 051m 054b 054b 065b 076b 100b 100b 116b

NOTE
(1) Indoor air: 24°C/50% r.h.; Condensing temp.: 45°C
(2) Indoor air: 24°C/50% r.h.; Water (in/out): 7/12°C
(3) Measured at 1,5 m high and 2 m front unit, in open field conditions

P L

269
HPAC

AT 20÷90
Versions
STD base version
MOD_A version with condensing fan speed regulation
MOD_B version with condensing pressostatic regulation

Features
Unit for installing inside or outside the room to be
air-conditioned
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material.
The reliability of all the components is guaranteed by
partners who are world leaders in their sector.
NEW EC INVERTER fans with electronic commutation
in order to maximize the energy saving and reducing the
noise emissions.
Standard G4 filtering section, F6-F8 optional, under
CEN-EN 779 rule with the separation degree 90,1%
ASHRAE. The filter is autoestinguishing type.
The microprocessor controls all the main functions of the
air conditioners; it also controls the operating alarms
with the possibility of interfacing to supervisor and
Close control unit dual fluid, water cooled remoteservicing systems.
Electrical box under IEC 204-1/EN60204-1 rules.
direct expansion Capillary Pre and After sales service.

20-100kW Main accessories


• Remote user terminal
Unit Description • Electric heating coil
Ductable close control units air-conditioners with capacity ranging from 20 to 100 • Water heating coil
kW for vertical installation and cooling only, with optional heating by means of • Humidifier
heating elements and hot water, optional humidifer and dehumidifier for precise • Air distribution plenum
temperature and humidity control. Particularly suitable for air conditioning • Sound absorber plenum for air outlet
technological, servers and IT rooms and all technological applications in general. • Interface electronic board
Units fittend with EC INVERTER fans, upflow or downflow. • Electronic Thermostatic valve

DUAL FLUID unit has to be connected to an external chiller for PRIMARY circuit.
The direct expansion circuit, secondary or BACK-UP circuit, is water cooled and
has to be connected with a remote dry cooler or to city water net.

Commands
EVOLUTION
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm,
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management,
Automatic rotation, Serious alarms, Operating contemporaneousness

270
ACCURATE AT/STD

Models 20 26 29 39 30 40 50 60 70 80 90
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES (DX)
Total cooling capacity (1) kW 24,9 30,6 32,3 47,3 47,3 50 54,5 70,3 76,6 91,8 102
Sensible cooling capacity (1) kW 22,8 28,3 30 46,9 46,9 47,9 50,7 66,8 71,1 88,2 92,2
SHR 0,92 0,92 0,93 0,99 0,99 0,96 0,93 0,95 0,93 0,96 0,90
COMPRESSORS
Quantity n° 1 1 1 1 2 2 2 2 2 2 2
Power abs. kW 4,30 5,40 6,11 6,94 6,44 8,61 10,6 12,3 13,3 16 19,3
N° Circuits n° 1 1 1 1 2 2 2 2 2 2 2
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
COOLING PERFORMANCES (CW)
Total cooling capacity (2) kW 23,8 28,1 29,5 50 41 50 51,4 65 67,6 91 91
Sensible cooling capacity (2) kW 21,8 26,4 27,6 46,3 37 46,3 47,5 62,2 64,5 85 85
SHR 0,92 0,94 0,94 0,93 0,90 0,93 0,92 0,96 0,95 0,93 0,93
Water flow rate (2) l/h 3890 4590 4590 8170 6710 8170 8170 10630 10630 14870 14870
Total pressure drop water side (2) kPa 26 35 35 46 30 46 46 26 26 53 53
VENTILATION
Air flow mc/h 6000 7500 8000 13000 10000 13000 13500 18000 19000 24000 24000
N° EC Inverter fans n° 1 1 1 2 2 2 2 3 3 4 4
EC Inverter fans power abs. kW 0,89 1,60 1,80 3,40 2,09 3,40 3,65 4,50 5,20 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20 20 20 20
Sound pressure level (3) dB(A) 56 60 60 64 59 64 64 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 5 5 5 5 8 8 8 8
Power abs. kW 3,75 3,75 3,75 3,75 3,75 3,75 3,75 6 6 6 6
ELECTRICAL HEATERS
Steps 3 3 3 3 3 3 3 3 3 3 3
Power abs. kW 9 9 9 15 15 15 15 18 18 18 18
PLATE CONDENSER
Water flow rate (1) l/h 4780 6190 7204 9650 3720x2 4805x2 6156x2 7370x2 8340x2 19160 21340
Pressure drop (1) kPa 22 35 32 36 26 22 33 36 32 32 40
Water content l 2,50 2,50 3 3,80 2x1,6 2x2,5 2x2,5 2x3 2x3,8 8,53 8,53
DIMENSION
L mm 1000 1000 1000 1550 1550 1550 1550 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BDC STD/LT/LN 030m 039m 039m 052m 039m 052m 062m 078m 092m 103m 123m

NOTE
(1) Indoor air: 24°C/50% r.h.; Water: 30°-35°C
(2) Indoor air: 24°C/50% r.h.; Water (in/out): 7/12°C
(3) Measured at 1,5 m high and 2m front unit, in open field conditions H

P L

271
HPAC

AF 20÷90
Versions
STD base version
MOD_A version with condensing fan speed regulation

Features
Unit for installing inside or outside the room to be
air-conditioned
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material.
The reliability of all the components is guaranteed by
partners who are world leaders in their sector.
NEW EC INVERTER fans with electronic commutation
in order to maximize the energy saving and reducing the
noise emissions.
Standard G4 filtering section, F6-F8 optional, under
CEN-EN 779 rule with the separation degree 90,1%
ASHRAE. The filter is autoestinguishing type.
The microprocessor controls all the main functions of the
air conditioners; it also controls the operating alarms
with the possibility of interfacing to supervisor and
Close control unit free-cooling source, remoteservicing systems.
Electrical box under IEC 204-1/EN60204-1 rules.
water cooled direct expansion Capillary Pre and After sales service.

20 - 100 kW Main accessories


• Remote user terminal
• Electric heating coil
Unit Description • Water heating coil
Ductable close control units air-conditioners with capacity ranging from 20 to 100 • Humidifier
kW for vertical installation and cooling only, with optional heating by means of • Vibration isolation frame with rubber mountings
heating elements and hot water, optional humidifer and dehumidifier for precise • Air distribution plenum
temperature and humidity control. Particularly suitable for air conditioning • Sound absorber plenum for air outlet
technological, servers and IT rooms and all technological applications in general. • Interface electronic board
Units fittend with EC INVERTER fans, upflow or downflow. • Electronic Thermostatic valve

FREE-COOLING unit water cooled has to be connected with a remote dry cooler
or an external chiller.

Commands
EVOLUTION
Semi-graphic display 132 x 64 pixel, Programmable software, Record storage of 100 alarms, General alarm,
Automatic reset after blackout, Compressor FIFO management, Integral LAN system, Standby management,
Automatic rotation, Serious alarms, Operating contemporaneousness

272
ACCURATE AF/STD

Models 20 26 29 39 30 40 50 60 70 80 90
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES (DX)
Total cooling capacity (1) kW 24,9 30,6 32,3 47,3 38,1 50 54,5 70,3 76,6 91,8 102
Sensible cooling capacity (1) kW 22,8 28,3 30 46,9 36,7 47,9 50,7 66,8 71,1 88,2 92,2
SHR 0,92 0,92 0,93 0,99 0,96 0,96 0,93 0,95 0,93 0,96 0,90
COMPRESSORS
Quantity n° 1 1 1 1 2 2 2 2 2 2 2
Power abs. kW 4,40 5,40 6,11 8 6,44 8,61 10,6 12,3 13,3 16 19,3
N° Circuits n° 1 1 1 1 2 2 2 2 2 2 2
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A R410A
COOLING PERFORMANCES (FC)
Total cooling capacity (2) kW 20 24 25,1 40,8 33,6 41,5 43,8 56,6 58,1 76,7 78,3
Sensible cooling capacity (2) kW 20 24 25,1 40,8 33,6 41,5 43,8 56,6 58,1 76,7 78,3
SHR 1 1 1 1 1 1 1 1 1 1 1
Water flow rate l/h 4900 6330 7002 8430 7380 9810 11954 14360 16133 18120 20830
Total water pressure drop kPa 60 97 69 89 64 84 95 85 91 80 99
PLATE CONDENSER
Water content l 11,8 11,8 11,8 17,9 17 19,1 19,1 25,2 26,8 32,5 32,5
VENTILATION
Air flow mc/h 6000 7500 8000 13000 10000 13000 13500 18000 19000 24000 24000
N° EC Inverter fans n° 1 1 1 2 2 2 2 3 3 4 4
EC Inverter fans power abs. kW 0,89 1,60 1,80 3,40 2,09 3,40 3,65 4,50 5,20 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20 20 20 20
Sound pressure level (3) dB(A) 56 60 60 64 59 64 64 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 5 5 5 5 8 8 8 8
Power abs. kW 3,75 3,75 3,75 3,75 3,75 3,75 3,75 6 6 6 6
ELECTRICAL HEATERS
Steps 3 3 3 3 3 3 3 3 3 3 3
Power abs. kW 9 9 9 15 15 15 15 18 18 18 18
DIMENSION
L mm 1000 1000 1000 1550 1550 1550 1550 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980 1980
COUPLING EXTERNAL UNIT
BDC STD/LT/LN 030m 039m 039m 052m 039m 052m 062m 078m 092m 103m 123m

NOTE
(1) Indoor air: 24°C/50% r.h.; Water: 30°-35°C
(2) Indoor air: 24°C/50% r.h.; Water IN: 10°C and water flow of DX mode
(3) Measured at 1,5 m high and 2m front unit, in open field conditions H

P L

273
HPAC

AC 007÷221
Versions
STD base version
HT for High Density application

Features
Unit for installing inside or outside the room to be
air-conditioned.
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating
material to limit noise levels.
The reliability and functionality of the all parts are
guaranteed by partners who are world leaders in their
sector.
Double-inlet centrifugal fan per standard installed,
directly coupled and suspended on vibration-isolation
mountings. The fans are of the forward-bladed type for
maximum efficiency and low noise. Available as option,
EC INVERTER fans with electronic commutation,
Backward Curved Fan type to minimize energy
consumption and noise emission.
Standard G2/G4 filtering section, F6-F8 optional, to
CEN-EN 779 with average degree of separation 90.1%
ASHRAE. The filter is self-extinguishing.
The microprocessor controls the mains functions of the
Close control unit chilled water conditioning unit, it also controls the operating alarms
with the possibility of interfacing to supervisor and
8 - 225 kW remote-servicing systems.
Switchboard to IEC 204-1/EN60204-1
Capillary Pre and After sales service.

Unit Description Main accessories


Ductable close control air-conditioners with capacities ranging from 8 to 225 kW • Remote user terminal
for vertical installation and cooling only, with optional heating by means of heating • Electric heating coil
element or hot water, optional humidifier and dehumidifier for precise temperature • Water heating coil
and humidity control.Particularly suitable for air-conditioning technological, server • Humidifier
and CED rooms and all technological applications in general. Units fitted with • Vibration isolation frame with rubber mountings
centrifugal fans with upward airflow from the top or from the bottom. These units • Air distribution plenum
are provided with 3way valve and servomotor. Unit has to be connected with an • Sound absorber plenum for air outlet
external chiller. • Interface electronic board

Commands
EVOLUTION
Semi-graphic display 132 x 64 pixel Programmable software, Record storage of 100 alarms, General alarm
Automatic reset after blackout, Integral LAN system Standby management, Automatic rotation, Serious alarms,
Operating contemporaneousness

274
ACCURATE AC/STD

Models 07 09 14 19 25 30 34 41 50
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 8,50 10,1 15,7 20,4 28,4 33,8 37,4 48,5 57,7
Sensible cooling capacity (1) kW 8,50 9,50 15,7 19 28,4 30,9 37,4 48,5 52,8
SHR 1 0,94 1 0,93 1 0,91 1 1 0,92
Water flow rate (1) l/h 1390 1660 2570 3330 4640 5520 6110 7930 9430
Total unit pressure drop (1) kPa 33 36 39 60 57 65 46 69 71
N° water circuits n° 1 1 1 1 1 1 1 1 1
FANS
Fan air flow m3/h 2500 2500 4900 4900 8000 8000 13500 13500 13500
N° Centrifugal fans n° 1 1 2 2 1 1 2 2 2
N° EC Inverter fans n° 1 1 2 2 1 1 2 2 2
Centrifugal fans power abs. kW 0,49 0,49 1 1 2,02 2,02 3,61 3,61 3,61
EC Inverter fans power abs. kW 0,27 0,27 0,53 0,53 1,69 1,69 3,51 3,51 3,51
ESP std. Pa 20 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 50 50 53 53 60 60 64 64 64
AIR FILTER
Degree filtration G2 G2 G2 G2 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 3 3 5 5 5 5 5 5 5
Power absorbed kW 2,25 2,25 3,75 3,75 3,75 3,75 3,75 3,75 3,75
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3 3
Power absorbed kW 4 4 8 8 9 9 15 15 15
DIMENSION
L mm 600 600 1000 1000 1000 1000 1550 1550 1550
P mm 500 500 500 500 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980 1980

Models 060 070 080 090 131 151 171 191 221
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 69 82,6 88,7 104 131 155 178 197 225
Sensible cooling capacity (1) kW 69 73,7 88,7 97 106 127 136 156 168
SHR 1 0,89 1 0,93 0,81 0,82 0,77 0,79 0,75
Water flow rate (1) l/h 11280 13500 14500 17050 21650 25530 29290 32350 36610
Total unit pressure drop (1) kPa 71 73 69 74 122 88 105 147 135
N° water circuits n° 1 1 1 1 1 1 1 1 1
FANS
Fan air flow m3/h 19000 19000 25000 25000 25000 30000 30000 36000 36000
N° Centrifugal fans n° 2 2 3 3 3 - - - -
N° EC Inverter fans n° 3 3 4 4 4 3 3 3 3
Centrifugal fans power abs. kW 6,55 6,55 9,42 9,42 9,42 - - - -
EC Inverter fans power abs. kW 5,11 5,11 6,82 6,82 6,82 4,9 4,9 6,7 6,7
ESP std. Pa 20 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 67 67 67 67 67 69 69 70 70
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 8 8 8 8 8 10 10 15 15
Power absorbed kW 6 6 6 6 6 7,50 7,5 11,3 11,3
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3 3
Power absorbed kW 18 18 18 18 18 24 24 24 24
DIMENSION
L mm 2100 2100 2650 2650 2650 2650 2650 3200 3200
P mm 790 790 790 790 790 890 890 890 890
H mm 1980 1980 1980 1980 1980 2180 2180 2180 2180

NOTE
(1) Indoor air: 24°C/50% r.h.; Water (in/out): 7/12°C
(5) Measured at 1,5 m high and 2m front unit, in open field conditions

275
ACCURATE AC/HT

Models 025 030 034 041 050 060 070 080 090
Electrical power supply V-Ph~Hz 400/3+N/50
COOLING PERFORMANCES
Total cooling capacity (1) kW 30,8 37,1 44,5 52,2 63,2 73,3 87,4 97,4 108
Sensible cooling capacity (1) kW 30,8 37,1 44,5 52,2 63,2 73,3 87,4 97,4 108
SHR 1 1 1 1 1 1 1 1 1
Water flow rate (1) l/h 5320 6410 7654 9020 10920 12670 15100 16830 18660
Total unit pressure drop (1) kPa 50 64 51 51 76 41 46 75 80
N° water circuits n° 1 1 1 1 1 1 1 1 1
FANS
Fan air flow m3/h 8000 8000 13500 13500 13500 19000 19000 25000 25000
N° Centrifugal fans n° 1 1 2 2 2 2 2 3 3
N° EC Inverter fans n° 1 1 2 2 2 3 3 4 4
Centrifugal fans power abs. kW 2,02 2,02 3,61 3,61 3,61 6,55 6,55 9,42 9,42
EC Inverter fans power abs. kW 1,69 1,69 3,51 3,51 3,51 5,11 5,11 6,82 6,82
ESP std. Pa 20 20 20 20 20 20 20 20 20
Sound pressure level (2) dB(A) 60 60 64 64 64 67 67 67 67
AIR FILTER
Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4
HUMIDIFIER
Capacity kg/h 5 5 5 5 5 8 8 8 8
Power absorbed kW 3,75 3,75 3,75 3,75 3,75 6 6 6 6
ELECTRICAL HEATERS
Steps n° 3 3 3 3 3 3 3 3 3
Power absorbed kW 9 9 15 15 15 18 18 18 18
DIMENSION
L mm 1000 1000 1550 1550 1550 2100 2100 2650 2650
P mm 790 790 790 790 790 790 790 790 790
H mm 1980 1980 1980 1980 1980 1980 1980 1980 1980

NOTE
(1) Indoor air: 33°C/40% r.h.; Water (in/out): 15/20°C
(5) Measured at 1,5 m high and 2m front unit, in open field condition

P L

276
277
HPAC

AB 020÷140
Versions
STD base version

Features
Unit for installing inside or outside the room to be
air-conditioned
Maximum resistance to rust thanks to galvanised sheet
metal structures and panels with powder-coated paint
finish. The panels are lined with sound-insulating material.
The reliability and functionality of the all parts are
guaranteed by partners who are world leaders in their
sector.
NEW EC INVERTER fans with electronic commutation
in order to maximize the energy saving and reducing the
noise emissions.
Standard G4 filtering section, F6-F8 optional, under
CEN-EN 779 rule with the separation degree 90,1%
ASHRAE. The filter is autoestinguishing type.
The microprocessor controls the mains functions of the
conditioning unit, it also controls the operating alarms
with the possibility of interfacing to supervisor and
remote-servicing systems.
Electrical box under IEC 204-1/EN60204-1 rules.
Capillary Pre and After sales service.
DUAL COIL close control unit, chilled
water type Main accessories
• Remote user terminal
20 - 145 kW •

Electric heating coil
Water heating coil
• Humidifier
• Vibration isolation frame with rubber mountings
Unit Description
• Air distribution plenum
Ductable close control units air-conditioners with capacity ranging from 20 to 145
• Sound absorber plenum for air outlet
kW for vertical installation and cooling only, with optional heating by means of
• Interface electronic board
heating elements and hot water, optional humidifer and dehumidifier for precise
temperature and humidity control. Particularly suitable for air conditioning
technological, servers and IT rooms and all technological applications in general.
Units fittend with EC INVERTER fans, upflow or downflow. These units are provided
with two indipendent chilled water circuits, each one with 3way valve and
servomotor. Units has to be connected to 2 complete independent circuit each one
in back-up to the other one.

Commands
EVOLUTION
Semi-graphic display 132 x 64 pixel Programmable software, Record storage of 100 alarms, General alarm
Automatic reset after blackout, Integral LAN system Standby management, Automatic rotation, Serious alarms,
Operating contemporaneousness

278
ACCURATE AB/STD

Models 020 025 030 040 045 055 060 075 105 120 130 140

Electrical power supply V-Ph~Hz 400/3+N/50

COOLING PERFORMANCES x each circuit

Total cooling capacity (1) kW 22,5 29 41,2 50,5 54,2 66,4 76,6 94,3 105 125 131 148

Sensible cooling capacity (1) kW 22,5 27,7 41,2 47,5 54,2 64,5 76,6 89,9 102 112 128 137

SHR 1,00 0,96 1,00 0,94 1,00 0,97 1,00 0,95 0,98 0,90 0,98 0,92

Water flow rate (1) l/h 3670 4840 6740 8420 8860 11060 12520 15710 17420 20780 21880 24070

Total unit pressure drop (1) kPa 51 72 42 45 38 53 43 52 95 73 55 66

FANS

Fan air flow m3/h 8000 8000 13500 13500 19000 19000 26000 26000 30000 30000 36000 36000

N° EC Inverter fans n° 1 1 2 2 3 3 4 4 3 3 3 3

EC Inverter fans power abs. kW 1,69 1,69 3,51 3,51 5,11 5,11 6,82 6,82 4,9 4,9 6,7 6,7
ESP std. Pa 20 20 20 20 20 20 20 20 20 20 20 20

Sound pressure level (2) dB(A) 60 60 64 64 67 67 67 67 69 69 70 70

AIR FILTER

Degree filtration G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4 G4

HUMIDIFIER

Capacity kg/h 5 5 5 5 8 8 8 8 10 10 15 15

Power absorbed kW 3,75 3,75 3,75 3,75 6 6 6 6 7,50 7,50 11,3 11,3

ELECTRICAL HEATERS

Steps n° 3 3 3 3 3 3 3 3 3 3 3 3

Power absorbed kW 9 9 15 15 18 18 18 18 24 24 24 24

DIMENSION

L mm 1000 1000 1550 1550 2100 2100 2650 2650 2650 2650 3200 3200

P mm 790 790 790 790 790 790 790 790 890 890 890 890

H mm 1980 1980 1980 1980 1980 1980 1980 1980 2180 2180 2180 2180

NOTE
(1) Indoor air: 24°C/50% r.h.; Water (in/out): 7/12°C
(2) Measured at 1,5 m high and 2m front unit, in open field conditions

P L

279
HPAC

BRE 014m÷116b
Versions
STD base version
LN low noise version
LT low outdoor temperature version

Features

ELECTRIC FANS of an axial type, statically and


dynamically balanced on two levels, with blades in an
inoxidable material and external rotor motor suitable for
adjusting the speed, all mounted on a metal supporting
grid in conformity with safety regulations. The motors are
to VDE 0530-12.84. The protection rating is IP54 to
DIN40050.

CONDENSING COIL: the combination of innovative


corrugated fins with the use of smooth pipes on the
exchanger ensures excellent heat transfer with a
minimum amount of fluid. The heat exchangers consist
of aluminium fins and copper pipes.

REFRIGERANT CIRCUIT CONNECTIONS are


arranged along one side of the unite and are to be
welded for safe connection that prevents any fluid leak.

Remote condenser with axial fans


Main accessories
• Legs kit for vertical air flow installation
Unit Description • Epoxy coated (for fins only)
Remote condensers with axial-type fan(s) for outdoor installation. Installation may • Cataphoresys coil treatment
be vertical with a horizontal air outflow or, using special brackets, horizontal with an • Copper-Copper coil
upward air outflow. The very low noise, adjustable-speed fans are excellent for use
in both technological and civil applications. BRC-BRE units operate with a single-
phase 230/1/50 power supply totally independent and separate from the indoor
unit ACCURATE. These condensing units are therefore also suited for use without
being directly connected to indoor units. BRC-BRE units are not provided with
integrated fans speed regulator per standard. However, CLIMAVENETA can provide
such fans speed regulator as OPTIONAL, by installing it directly inside the indoor
unit ACCURATE.

280
BRE / STD
Models 014m 022m 027m 044m 051m 054b 065b 076b 100b 116b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 13,4 21,7 26,6 43,5 50,4 53,3 65,1 76,2 100 116
Total power input kW 0,27 0,60 0,60 1,20 1,20 1,20 1,80 1,80 2,40 3
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 72 85 102 137 153 167 191 213 302 339
VENTILATION
Air flow m3/h 5000 8200 7200 16400 15200 14400 24600 22800 28800 38000
Sound pressure level (2) dB(A) 40 46 46 49 49 49 51 51 52 53
DIMENSION (3)
L mm 1240 1360 1360 2360 2360 2360 3360 3360 4360 5360
P mm 494 580 580 580 580 580 580 580 580 580
H mm 764 1070 1070 1070 1070 1070 1070 1070 1070 1070
NOTE
(1) Ext. air 35°C; 6T = 13°K
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BRE / LN
Models 014m 022m 027m 044m 051m 054b 065b 076b 100b 116b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 14,1 20 28,2 42,3 50 55,3 73,1 75,5 99,1 118
Total power input kW 0,33 0,26 0,66 0,99 0,99 0,99 1,32 1,32 1,65 2,52
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 85 125 137 191 213 235 276 302 339 397
VENTILATION
Air flow m3/h 6000 6500 12000 18000 16500 16000 22000 20300 27050 28560
Sound pressure level (2) dB(A) 37 35 39 41 41 41 42 42 43 43
DIMENSION (3)
L mm 1360 2120 2360 3360 3360 3360 4360 4360 5360 5560
P mm 580 494 580 580 580 580 580 580 580 615
H mm 1070 764 1070 1070 1070 1070 1070 1070 1070 1070
NOTE
(1) Ext. air 35°C; 6T = 13°K
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BRE / LT
Models 014m 022m 027m 044m 051m 054b 065b 076b 100b 116b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 13,4 21,7 26,6 43,5 50,4 53,3 65,1 76,2 100 116
Total power input kW 0,27 0,60 0,60 1,20 1,20 1,20 1,80 1,80 2,40 3
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 72 85 102 137 153 167 191 213 302 339
VENTILATION
Air flow m3/h 5000 8200 7200 16400 15200 14400 24600 22800 28800 38000
Sound pressure level (2) dB(A) 40 46 46 49 49 49 51 51 52 53
DIMENSION (3)
L mm 1240 1360 1360 2360 2360 2360 3360 3360 4360 5360
P mm 494 580 580 580 580 580 580 580 580 580
H mm 764 1070 1070 1070 1070 1070 1070 1070 1070 1070
NOTE
(1) Ext. air 35°C; 6T = 13°K
(2) Sound pressure measured at 10 m in open field conditions L
(3) Without legs kit configuration; horizontal air flow
H

281
HPAC

BRC 014m÷120b
Versions
STD base version
LN low noise version
LT low outdoor temperature version

Features

HOUSING: designed to allowed easy access to internal


components, is made from prepainted galvanized sheet
steel, and it:
• offers hight corrosion strenght and impact resistence;
• is resistant at low temperatures;
• is non toxic;
• does not produce polluting debris;
• is completely covered in a protective plastic film.

ELECTRIC FANS of an axial type, statically and


dynamically balanced on two levels, with blades in an
inoxidable material and external rotor motor suitable for
adjusting the speed, all mounted on a metal supporting
grid in conformity with safety regulations. The motors are
to VDE 0530-12.84. The protection rating is IP54 to
DIN40050.

CONDENSING COIL: the combination of innovative


corrugated fins with the use of smooth pipes on the
Remote condenser with axial fans exchanger ensures excellent heat transfer with a
minimum amount of fluid. The heat exchangers consist
of aluminium fins and copper pipes.
Unit Description
Remote condensers with axial-type fan(s) for outdoor installation. Installation may REFRIGERANT CIRCUIT CONNECTIONS are
be vertical with a horizontal air outflow or, using special brackets, horizontal with an arranged along one side of the unite and are to be
upward air outflow. The very low noise, adjustable-speed fans are excellent for use welded for safe connection that prevents any fluid leak.
in both technological and civil applications. BRC-BRE units operate with a single- ISOLATING SWITCH, contained in an electric box with
phase 230/1/50 power supply totally independent and separate from the indoor protection rating IP54, with switch control accessible
unit ACCURATE. These condensing units are therefore also suited for use without from the outside and connecting terminals.
being directly connected to indoor units. BRC-BRE units are not provided with
integrated fans speed regulator per standard. However, CLIMAVENETA can provide
such fans speed regulator as OPTIONAL, by installing it directly inside the indoor
unit ACCURATE. Main accessories
• Legs kit for vertical air flow installation
• Epoxy coated (for fins only)
• Cataphoresys coil treatment
• Copper-Copper coil

282
BRC / STD
Models 014m 025m 032m 051b 052m 077b 088b 093b 102b 120b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 14 26 32 52 52 77 90 93 102 120
Total power input kW 0,28 0,60 0,60 1,20 1,20 1,80 1,80 1,80 2,40 2,40
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 45 90 110 167 167 239 253 293 320 337
VENTILATION
Air flow m3/h 4410 8780 7870 17560 17560 26340 25230 23610 35120 33640
Sound pressure level (2) dB(A) 41 48 48 51 51 53 53 53 54 54
DIMENSION (3)
L mm 1175 1325 1325 2425 2425 3525 3525 3525 4625 4625
P mm 510 630 630 630 630 630 630 630 630 630
H mm 872 1168 1168 1168 1168 1168 1168 1168 1168 1168
NOTE
(1) Ext. air 35°C; 6T = 15°K
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BRC / LN
Models 014m 025m 032m 051b 052m 077b 088b 093b 102b 120b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 13 22 42 48 48 72 76 85 95 101
Total power input kW 0,13 0,33 0,66 0,66 0,66 0,99 0,99 1,32 1,32 1,32
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 50 90 110 177 177 253 293 320 337 391
VENTILATION
Air flow m3/h 2930 6410 12820 12160 12160 18240 17340 25640 24320 23400
Sound pressure level (2) dB(A) 33 38 41 41 41 43 43 44 44 44
DIMENSION (3)
L mm 1175 1325 2425 2425 2425 3525 3525 4625 4625 4625
P mm 510 630 630 630 630 630 630 630 630 630
H mm 872 1168 1168 1168 1168 1168 1168 1168 1168 1168
NOTE
(1) Ext. air 35°C; 6T = 15°K
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BRC / LT
Models 014m 025m 032m 051b 052m 077b 088b 093b 102b 120b
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 14 26 32 52 52 77 90 93 102 120
Total power input kW 0,28 0,60 0,60 1,20 1,20 1,80 1,80 1,80 2,40 2,40
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 45 90 110 167 167 239 253 293 320 337
VENTILATION
Air flow m3/h 4410 8780 7870 17560 17560 26340 25230 23610 35120 33640
Sound pressure level (2) dB(A) 41 48 48 51 51 53 53 53 54 54
DIMENSION (3)
L mm 1175 1325 1325 2425 2425 3525 3525 3525 4625 4625
P mm 510 630 630 630 630 630 630 630 630 630
H mm 872 1168 1168 1168 1168 1168 1168 1168 1168 1168
NOTE
(1) Ext. air 35°C; 6T = 15°K
(2) Sound pressure measured at 10 m in open field conditions L
(3) Without legs kit configuration; horizontal air flow
H

283
HPAC

ARCC M1D÷M4F_B
Versions
STD base version

Features

CONDENSING COIL with high efficiency made by


innovative corrugated fins and copper pipes with
grooved internal surface.
FANS with double-inlet, with vibration-isolation
mountings, with protection rating IP44 and insulation
class F.

Main accessories
• Legs kit for vertical air flow installation
• Copper-Copper coil

Remote condenser with centrifugal fans


Unit Description
Condensing unit with centrifugal fan with very low noise level are excellent for use in
both technological and civil applications, designed for ductable installation with max
ESP 150Pa. The possibility to remove the side panel made easier the cleaning
operation and the air flow configuration. The ARCC units operate with a
230V/1/50Hz and 400V/3+N/50Hz power supply totally independent and separate
from the indoor unit ACCURATE. These units are therefore also suited for use
without being directly connected to indoor units.

284
ARCC / STD
Models M1D M2B M2C M2D M3C M3D M2E
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 14 18 22 28 33 42 55
Total power input kW 0,525 1,1 1,05 1,50 1,575 1,575 2,76
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 400/3+N/50
Net weight kg 87 83 121 135 162 183 188
VENTILATION
Air flow (2) m3/h 3230 4560 7040 6460 10560 9690 13120
Sound pressure level (3) dB(A) 35 38 37 37 39 39 46
DIMENSION (4)
L mm 760 1020 1360 1360 1960 1960 2060
P mm 950 800 845 845 845 845 845
H mm 845 520 950 950 950 950 950

Models M3D_B M2E_B M3G_B M3E_B M3F_B M4E_B M4F_B


NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 42 55 66 82,5 87 110 116
Total power input kW 1,575 2,76 4,14 4,14 4,14 5,52 5,52
Electrical power supply V-Ph~Hz 230/1/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50
Net weight kg 183 188 216 266 293 344 378
VENTILATION
Air flow (2) m3/h 9690 13120 17490 19680 18570 26240 24760
Sound pressure level (3) dB(A) 39 46 48 48 48 49 49
DIMENSION (4)
L mm 1960 2060 1960 3010 3010 3960 3960
P mm 845 845 845 845 845 845 845
H mm 950 950 950 950 950 950 950

NOTE
(1) Ext. Air 35°C; 6T =15°K
(2) ESP=100Pa
(3) Sound pressure measured at 10 m in open field conditions
(4) Without legs kit configuration; horizontal air flow
H

L
P

285
HPAC

BDC 013m÷123m
Versions
STD base version
LN low noise version
LT low outdoor temperature version

Features

HOUSING: designed to allowed easy access to internal


components, is made from prepainted galvanized sheet
steel, and it:
• offers hight corrosion strenght and impact resistence;
• is resistant at low temperatures;
• is non toxic;
• does not produce polluting debris;
• is completely covered in a protective plastic film.

ELECTRIC FANS of an axial type, statically and


dynamically balanced on two levels, with blades in an
inoxidable material and external rotor motor suitable for
adjusting the speed, all mounted on a metal supporting
grid in conformity with safety regulations. The motors are
to VDE 0530-12.84. The protection rating is IP54 to
DIN40050.

HEAT EXCHANGER: the combination of innovative


corrugated fins with the use of smooth pipes on the
Dry Cooler exchanger ensures excellent heat transfer with a
minimum amount of fluid. The heat exchangers consist
of aluminium fins and copper pipes.
Unit Description
Dry Cooler with axial-type fan(s) for outdoor installation. Installation may be vertical HYDRAULICS CIRCUIT CONNECTIONS are arranged
with a horizontal air outflow or, using special brackets, horizontal with an upward air along one side of the unite and are to be welded for safe
outflow. The very low noise, adjustable-speed fans are excellent for use in both connection that prevents any fluid leak.
technological and civil applications. BDC units operate with a single-phase
230/1/50 power supply totally independent and separate from the indoor unit ISOLATING SWITCH, contained in an electric box with
ACCURATE. These units are therefore also suited for use without being directly protection rating IP54, with switch control accessible
connected to indoor units. BDC units are not provided with integrated fans speed from the outside and connecting terminals.
regulator per standard. However, CLIMAVENETA can provide such fans speed
regulator as OPTIONAL, by installing it directly inside the indoor unit ACCURATE.

Main accessories
• Legs kit for vertical air flow installation
• Epoxy coated (for fins only)
• Cataphoresys coil treatment
• Copper-Copper coil

286
BDC / STD
Models 013m 030m 039m 052m 062m 078m 092m 103m 123m
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 17 33 40,5 61 68 83 98,5 121 135
Total power input kW 0,60 1,20 1,20 1,80 1,80 2,40 3,60 3,60 3,60
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 90 167 177 253 293 337 490 519 601
VENTILATION
Air flow m3/h 8780 17560 16820 25230 23610 33640 52680 50460 47220
Sound pressure level (2) dB(A) 48 51 51 53 53 54 56 56 56
DIMENSION (3)
L mm 1325 2425 2425 3525 3525 4625 3658 3658 3658
P mm 630 630 630 630 630 630 760 760 760
H mm 1168 1168 1168 1168 1168 1168 2286 2286 2286
NOTE
(1) Water temp.: 35/30°C; Ext. Temp.: 24°C
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BDC / LN
Models 013m 030m 039m 052m 062m 078m 092m 103m 123m
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 14 32 40,5 54 65,5 82 96 107 129
Total power input kW 0,33 0,66 0,99 1,32 1,32 1,65 1,98 2,64 2,64
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 90 177 239 320 337 363 519 640 675
VENTILATION
Air flow m3/h 6410 12160 19230 25640 24320 30400 36480 51280 48640
Sound pressure level (2) dB(A) 38 41 43 44 44 45 46 47 47
DIMENSION (3)
L mm 1325 2425 3525 4625 4625 5725 3658 4758 4758
P mm 630 630 630 630 630 630 760 760 760
H mm 1168 1168 1168 1168 1168 1168 2286 2286 2286
NOTE
(1) Water temp.: 35/30°C; Ext. Temp.: 24°C
(2) Sound pressure measured at 10 m in open field conditions
(3) Without legs kit configuration; horizontal air flow

BDC / LT
Models 013m 030m 039m 052m 062m 078m 092m 103m 123m
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 17 33 40,5 61 68 83 98,5 121 135
Total power input kW 0,601,20 1,20 1,80 1,80 2,40 3,60 3,60 3,60
Electrical power supply V-Ph~Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Net weight kg 90 167 177 253 293 337 490 519 601
VENTILATION
Air flow m3/h 8780 17560 16820 25230 23610 33640 52680 50460 47220
Sound pressure level (2) dB(A) 48 51 51 53 53 54 56 56 56
DIMENSION (3)
L mm 1325 2425 2425 3525 3525 4625 3658 3658 3658
P mm 630 630 630 630 630 630 760 760 760
H mm 1168 1168 1168 1168 1168 1168 2286 2286 2286
NOTE
(1) Water temp.: 35/30°C; Ext. Temp.: 24°C
(2) Sound pressure measured at 10 m in open field conditions L
(3) Without legs kit configuration; horizontal air flow
H

287
ACKA
A
ACK
KA
A
288
AGED packaged

packaged

289
Packaged

WORK 0101÷0602
Versions
B base version

Configurations
B base function
AX function with exhaust air axial fan
CE function with return air centrifugal fan

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
COMFORT
The wide working field and the accurate design of the unit
ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
Reversible rooftop unit, for medium crowding
applications Main accessories
UÊHigh efficiency filters: electronic or rigid pocket F7
37,4 - 198 kW UÊEnthalpy free-cooling
UÊCO2 control sensor for air quality
Unit Description
UÊHot gas post heating
Unit for outdoor installation, reversible and direct expansion for the air conditioning, with scroll
compressors running on R410A, prepainted panelling with internal thermic insulating and UÊRemote keyboard (distance to 200m and to 500m)
soundproofing material, top frame made with Alloy, basement made from hot-galvanised, UÊSet-up for remote connectivity with ModBus/Echelon
centrifugal supply fan section, free-cooling, Exhaust Air thermodynamic effect. Efficiency, protocol cards
Plug&Play approach, an intuitive and comprehensive electronic controller are the leading
features of this unit. It is designed to obtain extreme compactness, simplified on-site
installations and maintainance and a reduction in their associated costs. All the same, it is
guaranteed the best air treatment quality, thanks to the R-410A refrigerant use, the Exhaust
Air thermodynamic effect and the optional high efficiency filters.

Commands
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features
the monitoring of numerous operational parameters. This allows to reduce the number and duration of the defrost cycles,
with a benefit for the overall energy efficiency.

290
r HFC
R-410A
THERMODYNAMIC CENTRIFUGAL AXIAL SCROLL FREE COOLING HEATING COOLING

WORK / B
Models 0101 0121 0152 0182 0202 0252 0302 0352 0402 0452 0502 0552 0602
COOLING ONLY
Cooling capacity (1) kW 37,4 45,9 53,2 60,3 70,4 86,4 100 115 132 143 166 182 198
Sensible cooling capacity (1) kW 27,9 33,5 38,3 44,2 51,2 63,3 72,3 84,3 97 105 122 132 144
Compressor power input (1) kW 7,70 10,5 13,1 16,1 17,5 23,3 27,2 32 35,3 40,6 44,7 49,5 54,7
HEATING ONLY
Heating capacity (2) kW 35,7 44,4 50,3 56,9 66 83,8 91,4 108 127 138 156 175 194
Compressors power input (2) kW 7 9,20 10,2 12,4 13,5 18,1 19,3 23,8 28,2 31,7 32,1 37,5 42,4
OUTLET FANS
Supply air flow rate m3/h 6000 8000 9000 10000 11500 15000 17000 20000 23000 25500 29500 30500 33000
Useful static head (3) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,57 2,49 3,18 3,97 2,96 5,46 5,68 7,90 6,90 8,31 10,9 11,8 14,2
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (4) dB(A) 82 83 86 87 87 87 88 89 90 91 91 91 92
SIZE
A (5) mm 2175 2175 2175 2175 3145 3145 3145 3145 4600 4600 4600 4600 4600
B (5) mm 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
H (5) mm 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410
Operating weight (5) kg 1050 1060 1110 1130 1530 1550 1600 1660 2360 2370 2380 2440 2470

Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 26°C 52% R.H. / Mix 30%
2 Heating: Outdoor 7°C 87% R.H. / Indoor 20°C 50% R.H. / Mix 30%
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0101-0602
Switchboard side mm 1500
Condensation coil side mm 2000

291
Packaged

WORK-T 0101÷0602
Versions
B base version

Configurations
B base function
AX function with exhaust air axial fan
CE function with return air centrifugal fan

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
COMFORT
The wide working field and the accurate design of the unit
ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
Cooling only rooftop unit, for medium
crowding applications Main accessories
UÊEnthalpy free-cooling
34,7 - 200 kW UÊCO2 control sensor for air quality
UÊHot gas post heating
Unit Description UÊSet-up for remote connectivity with ModBus/Echelon
Unit for outdoor installation, cooling-only and direct expansion for the air conditioning, with protocol cards
scroll compressors running on R410A, prepainted panelling with internal thermic insulating
UÊRemote keyboard (distance to 200m and to 500m)
and soundproofing material, top frame made with Alloy, basement made from hot-galvanised,
centrifugal supply fan section, free-cooling, Exhaust Air thermodynamic effect. Efficiency, UÊHigh efficiency filters: electronic or rigid pocket F7
Plug&Play approach, an intuitive and comprehensive electronic controller are the leading
features of this unit. It is designed to obtain extreme compactness, simplified on-site
installations and maintainance and a reduction in their associated costs. All the same, it is
guaranteed the best air treatment quality, thanks to the R-410A refrigerant use, the exhaust air
thermodynamic effect and the optional high efficiency filters.

Commands
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts).

292
r HFC
R-410A
THERMODYNAMIC CENTRIFUGAL AXIAL SCROLL FREE COOLING COOLING

WORK-T / B
Models 0101 0121 0152 0182 0202 0252 0302 0352 0402 0452 0502 0552 0602
COOLING ONLY
Cooling capacity (1) kW 34,7 43,1 51,7 60,5 70,6 86,6 100 115 133 143 167 182 200
Sensible cooling capacity (1) kW 25,9 32,9 37,4 44,2 51,2 63,3 72,3 84,3 96,2 105 122 132 145
Compressor power input (1) kW 9 11,8 13,8 16 17,4 23,2 27 31,9 35,1 40,4 44,5 49,3 53,9
OUTLET FANS
Supply air flow rate m3/h 6000 8000 9000 10000 11500 15000 17000 20000 23000 25500 29500 30500 33000
Available static pressure (2) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,57 2,49 3,18 3,97 1,48 2,73 2,84 3,95 2,30 2,77 3,63 3,94 4,73
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
NOISE LEVELS
Sound power (3) dB(A) 82 83 86 87 87 87 88 89 90 91 91 91 92
SIZE
A (4) mm 1175 1175 1175 1175 3145 3145 3145 3145 4600 4600 4600 4600 4600
B (4) mm 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250 2250
H (4) mm 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410 2410
Operating weight (4) kg 1050 1060 1110 1130 1530 1550 1600 1660 2360 2370 2380 2440 2470
Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 26°C 52% R.H. / Mix 30%
2 ESP for standard configuration (optional accessories not included/calculated)
3 Sound power on the basis of measurements made in compliance with ISO 3744.
4 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0101-0602
Switchboard side mm 1500
Condensation coil side mm 2000

293
Packaged

WHISPER 0102÷0604
Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
HIGH ENERGY EFFICIENCY
The use of the R410A gas conjoined to the elevated
thermodynamic recovery degree of the energy contained
in the exhaust air guarantee a high efficiency during the
operation.
PLUG-FAN VENTILATION
The plug-fan supply and return fan section matchs the
high efficacy ventilation with a quicker and easier electric
and aerolics installation of the unit.
SAFE USE
The wide working field and the accurate design of the unit
ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
in the more onerous thermohygrometric conditions.

High efficiency reversible rooftop unit, for Main accessories


UÊHot gas post heating
medium crowding applications UÊCO2 control sensor for air quality
UÊHigh efficiency filters: electronic or rigid pocket F7
35,7 - 197 kW UÊEnthalpy free-cooling
UÊSet-up for remote connectivity with ModBus/Echelon
Unit Description protocol cards
Autonomous rooftop unit, air/air reversible, for the thermohygrometric treatment, the filtration
UÊRemote keyboard (distance to 200m and to 500m)
and the air change in wide areas. Both winter and summer operating conditions, double
refrigerant circuit, scroll compressors with refrigerant R410A. Direct expansion finned external
exchangers with thermodynamic effect on the exhaust air. Air treatment section with plug-
fans and direct expansion finned internal exchangers. Management of air treatment section
according to the requested heating or cooling capacity by the Vair function.

Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. Defrosting is based on a self-adaptive propriety logic with
monitoring of many operating and environmental parameters. The specific VAir function is used to deliver air according to
the flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

294
r HFC
R-410A
THERMODYNAMIC PLUG FAN AXIAL SCROLL FREE COOLING HEATING COOLING

WHISPER / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404 0454 0504 0604
COOLING ONLY
Cooling capacity (1) kW 35,7 45 52,3 60,7 73,1 94,5 103 122 125 139 153 182 197
Sensible cooling capacity (1) kW 27,2 34,5 38,3 46,4 55,7 69,5 75,5 93,5 92,1 102 117 132 145
Compressor power input (1) kW 8,70 11,9 13,6 16,5 17,2 22,3 26,4 31,9 33,7 37,4 41,1 44,7 53
HEATING ONLY
Heating capacity (2) kW 31,9 42,9 49,6 57,5 64,9 87,3 94,7 113 115 130 140 172 186
Compressors power input (2) kW 6,70 9,20 10,1 12,1 12,8 16,5 19,2 21,8 22,7 25,3 31,1 34,5 40,7
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Useful static head (3) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,34 1,72 1,96 2,78 2,36 3,20 4,04 4,44 4,44 5,44 5,28 6,10 7,70
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Available static pressure (3) Pa 150 150 150 150 150 150 150 150 150 150 150 150 150
Power Input kW 1,30 1,24 1,16 1,66 1,58 1,68 2,06 2,02 2,02 2,46 3 3,54 4,48
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 88 89 90 91 94 95 95 96 95 97 97 97 98
SIZE
A mm 4350 4350 4350 4350 4500 4500 4500 5295 5295 5295 6500 6500 6500
B mm 1700 1700 1700 1700 2250 2250 2250 2250 2250 2250 2250 2250 2250
H mm 1630 1630 1630 1630 2390 2390 2390 2390 2390 2390 2390 2390 2390
Operating weight kg 1290 1320 1380 1400 2170 2230 2280 2750 2860 2880 3360 3450 3500

Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 27°C 47% R.H. / Mix 30%
2 Heating: Outdoor 7°C 87% R.H. / Indoor 20°C 50% R.H. / Mix 30%
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


0102-0604
Switchboard side mm 1500
Condensation coil side mm 2000

295
Packaged

WHISPER-T 0102÷0604
Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
HIGH ENERGY EFFICIENCY
The use of the R410A gas conjoined to the elevated
thermodynamic recovery degree of the energy contained
in the exhaust air guarantee a high efficiency during the
operation.
PLUG-FAN VENTILATION
The plug-fan supply and return fan section matchs the
high efficacy ventilation with a quicker and easier electric
and aerolics installation of the unit.
SAFE USE
The wide working field and the accurate design of the unit
ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
in the more onerous thermohygrometric conditions.

High efficiency cooling only rooftop unit, for Main accessories


UÊHot gas post heating
medium crowding applications UÊCO2 control sensor for air quality
UÊHigh efficiency filters: electronic or rigid pocket F7
35,8 - 197 kW UÊEnthalpy free-cooling
UÊHeating resource: hot water coil, electrical heater, burner
Unit Description methane gas
Autonomous rooftop unit, air/air cooling-only, for the thermohygrometric treatment, the UÊSet-up for remote connectivity with ModBus/Echelon
filtration and the air change in wide areas. Both winter and summer operating conditions, protocol cards
double refrigerant circuit, scroll compressors with refrigerant R410A. Direct expansion finned
UÊRemote keyboard (distance to 200m and to 500m)
external exchangers with thermodynamic effect on the exhaust air. Air treatment section with
plug-fans and direct expansion finned internal exchangers. Management of air treatment
section according to the requested heating or cooling capacity by the Vair function.

Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. The specific VAir function is used to deliver air according to the
flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

296
r HFC
R-410A
THERMODYNAMIC PLUG FAN AXIAL SCROLL FREE COOLING COOLING

WHISPER-T / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404 0454 0504 0604
COOLING ONLY
Cooling capacity (1) kW 35,8 44,6 52,2 60,6 71,9 94,8 103 123 126 139 154 182 197
Sensible cooling capacity (1) kW 27,6 33,7 38,3 45,7 55,7 69 77,3 92,1 92,8 101 116 131 144
Compressor power input (1) kW 8,60 12,2 13,6 16,6 17,4 22,2 26,3 31,3 33,1 37,4 40,7 44,4 52,7
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23000 27000 29000 32000
Available static pressure (2) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input (3) kW 1,34 1,72 1,96 2,78 2,36 3,20 4,04 4,44 4,44 5,44 5,28 6,10 7,70
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Useful static head (2) Pa 150 150 150 150 150 150 150 150 150 150 150 150 150
Power Input kW 1,30 1,24 1,16 1,66 1,58 1,68 2,06 2,02 2,02 2,46 3 3,54 4,48
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 88 89 90 91 94 95 95 96 95 97 97 97 98
SIZE
A mm 4350 4350 4350 4350 4500 4500 4500 5295 5295 5295 6500 6500 6500
B mm 1700 1700 1700 1700 2250 2250 2250 2250 2250 2250 2250 2250 2250
H mm 1630 1630 1630 1630 2390 2390 2390 2390 2390 2390 2390 2390 2390
Operating weight kg 1290 1320 1380 1400 2170 2230 2280 2750 2860 2880 3360 3450 3500
Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 27°C 47% R.H. / Mix 30%
2 ESP for standard configuration (optional accessories not included/calculated)
3 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


0102-0604
Switchboard side mm 1500
Condensation coil side mm 2000

297
Packaged

i-WHISPER ENTHALPY 0182÷0753


Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
THERMOHYGROMETRIC MANAGEMENT ON THE
SUPPLY AIRFLOW
The thermohygrometric management on the supply
airflow is the best way to maintain the requested indoor
temperature and relative humidity, even for high fresh
airflow rate.
EXTREME ADAPTABILITY TO THE REQUESTED LOAD
The cooling/heating capacity provided is perfectly
adapted to the load of the room to be served, thanks to
the advantages of Inverter technology for compressors.
This ensures excellent conditions of well-being.
WIDE RANGE OF AIRFLOW MIX/PRECISION ON
INDOOR CONDITIONS
This unit is perfect for air conditioning of a wide range of
architectural construction types (fresh airflow up to 80%)
in which indoor air conditions are the most important
thing, moreover precise regulation on supply and indoor
High efficiency reversible rooftop unit, with conditions is requested.
ROTARY-TYPE ENTHALPY RECOVERY
enthalpy recovery for medium crowding The exclusive rotary-type enthalpy recovery allows to get
high running capacity guarantying a lower introduction of
applications moisture in the summer operation of the unit.

87,0 - 338 kW
Unit Description Main accessories
Autonomous rooftop unit, air/air reversible, for the thermohygrometric treatment, the filtration UÊCO2 control sensor for air quality
and the air change in wide areas. Both winter and summer operating conditions, double UÊHigh efficiency filters: electronic or rigid pocket F7
refrigerant circuit, scroll compressors with variable speed and refrigerant R410A. Direct
UÊSet-up for remote connectivity with ModBus/Echelon
expansion finned external exchangers with thermodynamic effect on the exhaust air, axial fans
protocol cards
and condensation control device. Enthalpic Freecooling. Post-heating gas coil. Air treatment
UÊRemote keyboard (distance to 200m and to 500m)
section with plug-fans and direct expansion finned internal exchangers. Enthalpic rotary heat
recovery. Management of air treatment section according to the requested heating or cooling
capacity by the Vair function.

Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical days
and 10 time bands. The heat adjustment feature offers sophistcated capacity management wth proportional compressor
modulation that can be based on the temperature of the delivery air. This allows accurate temperature adjustment and
maximum comfort, partly thanks to the special integration with post-heating. Functions include adjustment of available
resources, ambient humidity and enthalpic free-cooling. Defrosting is based on a self-adaptive propriety logic with monitoring
of many operating and environmental parameters. The specific VAir function is used to deliver air according to the flow
of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans. The
function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

298
r HFC
R-410A
THERMODYNAMIC ROTARY PLUG FAN SCROLL FREE COOLING HEATING COOLING

i-WHISPER ENTHALPY / B
Models 0182 0202 0262 0302 0352 0402 0553 0653 0753
COOLING ONLY
Cooling capacity + Recovery (1) kW 87 113 134 150 166 200 242 294 338
Compressor power input (1) kW 19 20 26 27 34 40 55 63 73
HEATING ONLY
Heating capacity + Recovery (2) kW 86 104 124 136 159 190 248 293 335
Compressors power input (2) kW 16 18 21 23 28 34 45 54 61
OUTLET FANS
Supply air flow rate m3/h 7200 9000 11000 12500 13500 16500 20000 24000 30000
Useful static head (3) Pa 810 780 705 785 765 790 805 830 840
Power Input kW 3,50 3,60 5,30 6 6,30 8,50 10,8 12,6 16,1
SUCTION FANS/BLOWERS
Nominal air flow m3/h 7200 9000 11000 12500 13500 16500 20000 24000 30000
Available static pressure (3) Pa 600 600 530 600 600 600 600 600 600
Power Input kW 2,70 3 3,50 4,60 5 7,50 7,10 9,50 12,3
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 3/2 3/2 3/2
NOISE LEVELS
Sound power (4) dB(A) 92 94 94 94 95 96 97 97 98
SIZE
A mm 4350 4500 4500 4500 4500 5300 6500 6500 6500
B mm 1700 2250 2250 2250 2250 2250 2250 2250 2250
H mm 1630 2390 2390 2390 2390 2390 2390 2390 2390
Operating weight kg * * * * * * * * *
Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 26°C 50% R.H. / Mix 80%
2 Heating: Outdoor 7°C 87% R.H. / Indoor 20°C 50% R.H. / Mix 80%
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


0182-0753
Switchboard side mm 1500
Condensation coil side mm 2000

299
Packaged

WHISPER ENTHALPY 0102÷0604


Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
HIGH ENERGY EFFICIENCY
The use of the R410A gas conjoined to the elevated
thermodynamic recovery degree of the energy contained
in the exhaust air guarantee a high efficiency during the
operation.
ROTARY-TYPE ENTHALPY RECOVERY
The exclusive rotary recovery allows sensible and latent
energy from the exhaust airflow both in winter and
summer conditions. The latent recovery, in particular,
is important in dehumidification in summer and
humidification in winter for indoor, with very high efficiency
values.
PLUG-FAN VENTILATION
The plug-fan supply and return fan section matchs the
high efficacy ventilation with a quicker and easier electric
and aerolics installation of the unit.
High efficiency reversible rooftop unit, with SAFE USE
The wide working field and the accurate design of the unit
enthalpy recovery for medium crowding ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
applications in the more onerous thermohygrometric conditions.

47,4 - 243 kW Main accessories


Unit Description UÊHot gas post heating
Autonomous rooftop unit, air/air reversible, for the thermohygrometric treatment, the filtration UÊCO2 control sensor for air quality
and the air change in wide areas. Both winter and summer operating conditions, double
UÊHigh efficiency filters: electronic or rigid pocket F7
refrigerant circuit, scroll compressors with refrigerant R410A. Direct expansion finned external
exchangers with thermodynamic effect on the exhaust air. Air treatment section with plug-fans UÊEnthalpy free-cooling
and direct expansion finned internal exchangers. Enthalpic rotary heat recovery. Management UÊSet-up for remote connectivity with ModBus/Echelon
of air treatment section according to the requested heating or cooling capacity by the Vair protocol cards
function. UÊRemote keyboard (distance to 200m and to 500m)

Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. Defrosting is based on a self-adaptive propriety logic with
monitoring of many operating and environmental parameters. The specific VAir function is used to deliver air according to
the flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

300
r HFC
R-410A
THERMODYNAMIC ROTARY PLUG FAN AXIAL SCROLL FREE COOLING HEATING COOLING

WHISPER ENTHALPY / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404 0454 0504 0604
COOLING ONLY
Cooling capacity + Recovery (1) kW 47,4 58,3 66,6 77,5 96,7 122 133 157 160 176 195 225 243
Sensible cooling capacity +
kW 31,3 38 43,6 52,2 64,2 79,1 87,6 105 107 118 133 149 163
Recovery (1)
Compressor power input (1) kW 8,60 11,7 13,4 16,2 16,9 21,9 26 31,4 33 36,9 40,5 44 52,2
HEATING ONLY
Heating capacity + Recovery (2) kW 40,8 53,3 60,7 70,7 83,2 108 118 140 143 159 173 207 224
Compressors power input (2) kW 7,20 9,90 10,8 12,8 13,7 17,6 20,6 23,2 24,2 26,9 33,2 36,8 43,2
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Useful static head (3) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,50 1,96 2,24 3,18 2,74 3,68 4,66 5,22 5,22 6,38 7,84 9,06 11,3
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Available static pressure (3) Pa 150 150 150 150 150 150 150 150 150 150 150 150 150
Power Input kW 1,04 1,62 1,92 2,82 2 2,68 3,98 3,66 3,66 4,50 4,42 5,16 6,82
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 88 89 90 91 94 95 95 96 95 97 97 97 98
SIZE
A mm 4350 4350 4350 4350 4500 4500 4500 5295 5295 5295 6500 6500 6500
B mm 1700 1700 1700 1700 2250 2250 2250 2250 2250 2250 2250 2250 2250
H mm 1630 1630 1630 1630 2390 2390 2390 2390 2390 2390 2390 2390 2390
Operating weight kg 1430 1460 1520 1540 2430 2480 2540 3000 3110 3130 3620 3710 3760

Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 27°C 47% R.H. / Mix 30%
2 Heating: Outdoor 7°C 87% R.H. / Indoor 20°C 50% R.H. / Mix 30%
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


0102-0604
Switchboard side mm 1500
Condensation coil side mm 2000

301
Packaged

WHISPER ENTHALPY-T 0102÷0604


Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
HIGH ENERGY EFFICIENCY
The use of the R410A gas conjoined to the elevated
thermodynamic recovery degree of the energy contained
in the exhaust air guarantee a high efficiency during the
operation.
ROTARY-TYPE ENTHALPY RECOVERY
The exclusive rotary recovery allows sensible and latent
energy from the exhaust airflow both in winter and
summer conditions. The latent recovery, in particular,
is important in dehumidification in summer and
humidification in winter for indoor, with very high efficiency
values.
PLUG-FAN VENTILATION
The plug-fan supply and return fan section matchs the
high efficacy ventilation with a quicker and easier electric
and aerolics installation of the unit.
High efficiency cooling only rooftop unit, SAFE USE
The wide working field and the accurate design of the unit
with enthalpy recovery for medium crowding ensure optimum capacities and guaranty comfort, with a
continuous and constant bringing in of thermal load also
applications in the more onerous thermohygrometric conditions.

47,4 - 243 kW Main accessories


Unit Description UÊHot gas post heating
Autonomous rooftop unit, air/air cooling-only, for the thermohygrometric treatment, the UÊCO2 control sensor for air quality
filtration and the air change in wide areas. Both winter and summer operating conditions,
UÊHigh efficiency filters: electronic or rigid pocket F7
double refrigerant circuit, scroll compressors with refrigerant R410A. Direct expansion finned
external exchangers with thermodynamic effect on the exhaust air. Air treatment section with UÊEnthalpy free-cooling
plug-fans and direct expansion finned internal exchangers. Enthalpic rotary heat recovery. UÊHeating resource: hot water coil, electrical heater, burner
Management of air treatment section according to the requested heating or cooling capacity methane gas
by the Vair function. UÊSet-up for remote connectivity with ModBus/Echelon
protocol cards
UÊRemote keyboard (distance to 200m and to 500m)
Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. The specific VAir function is used to deliver air according to the
flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

302
r HFC
R-410A
THERMODYNAMIC ROTARY PLUG FAN AXIAL SCROLL FREE COOLING COOLING

WHISPER ENTHALPY-T / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404 0454 0504 0604
COOLING ONLY
Cooling capacity + Recovery (1) kW 47,4 58,4 66,5 77,5 96,9 122 133 158 161 176 196 225 243
Sensible cooling capacity +
kW 31,3 38 43,6 52,2 64,2 79,1 87 104 107 118 133 149 163
Recovery (1)
Compressor power input (1) kW 8,50 11,7 13,3 16,3 16,8 21,8 25,9 30,9 32,5 36,8 40,1 43,8 52
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Useful static head (2) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,50 1,96 2,24 3,18 2,74 3,68 4,66 5,22 5,22 6,38 7,84 9,06 11,3
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500 27000 29000 32000
Available static pressure (2) Pa 150 150 150 150 150 150 150 150 150 150 150 150 150
Power Input kW 1,04 1,62 1,92 2,82 2 2,68 3,98 3,66 3,66 4,50 4,42 5,16 6,82
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 88 89 90 91 94 95 95 96 95 97 97 97 98
SIZE
A mm 4350 4350 4350 4350 4500 4500 4500 5295 5295 5295 6500 6500 6500
B mm 1700 1700 1700 1700 2250 2250 2250 2250 2250 2250 2250 2250 2250
H mm 1630 1630 1630 1630 2390 2390 2390 2390 2390 2390 2390 2390 2390
Operating weight kg 1430 1460 1520 1540 2430 2480 2540 3000 3110 3130 3620 3710 3760
Note:
1 Cooling: Outdoor 35°C 50% R.H. / Indoor 27°C 47% R.H. / Mix 30%
2 ESP for standard configuration (optional accessories not included/calculated)
3 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


0102-0604
Switchboard side mm 1500
Condensation coil side mm 2000

303
Packaged

WHISPER HALL 110÷400


Versions
B base version

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
HIGH ENERGY EFFICIENCY
The use of the R410A gas conjoined to the elevated
thermodynamic recovery degree of the energy contained
in the exhaust air guarantee a high efficiency during the
operation.
ROTARY-TYPE ENTHALPY RECOVERY
The exclusive rotary recovery allows sensible and latent
energy from the exhaust airflow both in winter and
summer conditions. The latent recovery, in particular,
is important in dehumidification in summer and
humidification in winter for indoor, with very high efficiency
values.
PLUG-FAN VENTILATION
The plug-fan supply and return fan section matchs the
high efficacy ventilation with a quicker and easier electric
and aerolics installation of the unit.
High efficiency reversible rooftop unit, COMFORT
The wide working field, the air quality probe, the
with enthalpy recovery for high crowding predisposition for the remote supervising and the
accurate planning of the unit ensure optimum capacities
applications and comfort warrantee, with a continuous and constant
bringing in of thermal load also in the more onerous
45,9 - 146 kW thermohygrometric and crowding conditions.

Unit Description Main accessories


Autonomous rooftop unit, air/air reversible, for the thermohygrometric treatment, the filtration UÊHot gas post heating
and the air change in wide areas. Both winter and summer operating conditions, double UÊHigh efficiency filters: electronic or rigid pocket F7
refrigerant circuit, scroll compressors with refrigerant R410A. Direct expansion finned external
UÊEnthalpy free-cooling
exchangers with thermodynamic effect on the exhaust air. Air treatment section with plug-fans
and direct expansion finned internal exchangers. Air quality control with CO2 probe. Enthalpic UÊSet-up for remote connectivity with Echelon protocol
rotary heat recovery. Management of air treatment section according to the requested heating cards
or cooling capacity by the Vair function. UÊRemote keyboard (distance to 200m and to 500m)

Commands
AIR3000SE
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. Defrosting is based on a self-adaptive propriety logic with
monitoring of many operating and environmental parameters. The specific VAir function is used to deliver air according to
the flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

304
r HFC
R-410A
THERMODYNAMIC ROTARY PLUG FAN AXIAL SCROLL FREE COOLING HEATING COOLING

WHISPER HALL / B
Models 110 140 180 200 260 300 360 400
COOLING ONLY
Cooling capacity + Recovery (1) kW 45,9 55,7 63,7 72 98,3 115 128 146
Sensible cooling capacity +
kW 25,1 31,1 36,8 41,6 55,7 65,1 73,7 83,2
Recovery (1)
Compressor power input (1) kW 7,60 10,9 12,4 15 14,9 20,4 24,1 29
HEATING ONLY
Heating capacity + Recovery (2) kW 53,1 65,4 75,5 84,4 115 137 154 171
Compressors power input (2) kW 7,10 8,80 9,70 11,7 12,4 16,8 19,4 21,5
OUTLET FANS
Supply air flow rate m3/h 4300 5400 6800 7800 10000 11700 14000 15000
Useful static head (3) Pa 260 260 260 260 260 260 260 260
Power Input kW 1,28 1,72 2,42 3,08 3,08 4,02 5,64 6,42
SUCTION FANS/BLOWERS
Nominal air flow m3/h 4300 5400 6800 7800 10000 11700 14000 15000
Available static pressure (3) Pa 150 150 150 150 150 150 150 150
Power Input kW 1,22 1,30 1,48 1,72 1,58 1,96 3,04 2,96
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 88 89 90 91 94 94 94 95
SIZE
A mm 4350 4350 4350 4350 4500 4500 4500 5295
B mm 1700 1700 1700 1700 2250 2250 2250 2250
H mm 1630 1630 1630 1630 2390 2390 2390 2390
Operating weight kg 1430 1460 1520 1540 2430 2480 2540 3000

Note:
1 Cooling: Outdoor 32°C 50% R.H. / Indoor 26°C 50% R.H. / Mix 75%
2 Heating: Outdoor -5°C 85% R.H. / Indoor 20°C 50% R.H. / Mix 75%
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.

Minimum clearance required


110-400
Switchboard side mm 1500
Condensation coil side mm 2000

305
Packaged

WISDOM 0101÷1204
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
FLEXIBILITY
Climaveneta offers units with innumerable choices for the
supply and return airflows directions.

Main accessories
Reversible rooftop unit, for medium crowding UÊSet-up for remote connectivity with ModBus/Echelon
protocol cards
applications UÊHot gas post heating
UÊCO2 control sensor for air quality
34,5 - 355 kW UÊHigh efficiency filters: electronic or rigid pocket F7
UÊEnthalpy free-cooling
Unit Description
Unit for outdoor installation, reversible and direct expansion for the air conditioning, with UÊRemote keyboard (distance to 200m and to 500m)
scroll compressors running on R410A, sandwich panel with thickness of 42mm, aluminium
frame, base made in pre-painted galvanized steel profiles and centrifugal fan section. The unit
in standard execution can treat recirculating-only air; other available executions (optionals)
are MIX (return air and fresh air mix), FCS (Standard Free-Cooling with supply fans) or FCC
(Centrifugal Free-Cooling with supply and return fans).

Commands
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features
the monitoring of numerous operational parameters. This allows to reduce the number and duration of the defrost cycles,
with a benefit for the overall energy efficiency.

306
r HFC
R-410A
CENTRIFUGAL AXIAL SCROLL FREE COOLING HEATING COOLING

WISDOM / B
Models 0101 0121 0151 0102 0122 0152 0182 0202 0252 0302 0352
COOLING ONLY
Cooling capacity (1) kW 34,5 41,2 48,5 33,8 41,4 49,3 55 65,9 85,7 92,9 109
Sensible cooling capacity (1) kW 26,8 30,9 36,6 26,5 31 37,9 42,5 50,6 65,6 71,1 80,9
Compressor power input (1) kW 8,30 11,6 12,6 8,30 12,6 13 14,6 17,4 23 26,8 29,1
HEATING ONLY
Heating capacity (2) kW 33,2 43,2 47,6 32,2 44,1 48,7 53,1 63,4 83,8 90,9 109
Compressors power input (2) kW 7 9,90 10,5 6,80 10,6 10,7 11,4 14,1 18,3 21 24
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8500 6500 7800 8600 10500 13000 15500 17500 21000
Available static pressure (3) Pa 220 219 330 220 219 315 261 208 202 269 271
Power Input kW 1,10 1,50 2,20 1,10 1,50 2,20 3 2,20 3 4,40 6
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 78 78 78 78 78 78 78 84 84 84 87
Sound pressure (5) dB(A) 63 63 63 63 63 63 63 68 68 68 71
SIZE
A (6) mm 2900 2900 2900 2900 2900 2900 2900 3400 3400 3400 3400
B (6) mm 1780 1780 1780 1780 1780 1780 1780 2330 2330 2330 2330
H (6) mm 1640 1640 1640 1640 1640 1640 1640 1790 1790 1790 1790
Operating weight (6) kg 870 910 950 870 910 980 1010 1210 1290 1350 1450

Models 0364 0404 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 113 128 153 168 189 213 258 278 316 335 355
Sensible cooling capacity (1) kW 86 96,8 116 125 142 159 196 211 238 245 253
Compressor power input (1) kW 27,9 35,4 39,9 44,8 52,5 61,2 68,5 78,4 84,8 93 105
HEATING ONLY
Heating capacity (2) kW 110 126 148 170 185 213 256 279 313 343 378
Compressors power input (2) kW 23 28,6 32,3 38,3 41,7 52,3 57,6 65,4 70,2 78,8 91,4
OUTLET FANS
Supply air flow rate m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (3) Pa 271 303 215 261 333 235 255 400 290 290 290
Power Input kW 6 8 6 8 11 12 16 22 30 30 30
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 87 87 93 93 93 * * * * * *
Sound pressure (5) dB(A) 71 71 76 76 76 * * * * * *
SIZE
A (6) mm 3900 3900 3900 3900 3900 6580 6580 6580 6580 6580 6580
B (6) mm 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330
H (6) mm 1820 1820 2380 2380 2380 2350 2350 2350 2350 2350 2350
Operating weight (6) kg 1560 1650 1890 2080 2230 3530 3790 3790 3910 4150 4160

Note:
1 Cooling: Outdoor 34°C 50% R.H. Indoor 27°C 47% R.H.
2 Heating: Outdoor 7°C 87% R.H. / Indoor 20°C 50% R.H.
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.
5 Sound pressure in open field conditions on reflecting surface. Condensing coil side average value at 1 metre from the surface and at 1 m height in relation to the unit supporting base.
6 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0101-1204
Switchboard side mm 1500
Switchboard opposite side mm 0
Condensation coil side mm 2000

307
Packaged

WISDOM-T 0101÷1204
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
FLEXIBILITY
Climaveneta offers units with innumerable choices for the
supply and return airflows directions.

Main accessories
Cooling only rooftop unit, for medium UÊHot gas post heating
UÊCO2 control sensor for air quality
crowding applications UÊHigh efficiency filters: electronic or rigid pocket F7
UÊEnthalpy free-cooling
34,7 - 357 kW UÊHeating resource: hot water coil, electrical heater, burner
methane gas
Unit Description UÊSet-up for remote connectivity with ModBus/Echelon
Unit for outdoor installation, cooling-only and direct expansion for the air conditioning, with
protocol cards
scroll compressors running on R410A, sandwich panel with thickness of 42mm, aluminium
UÊRemote keyboard (distance to 200m and to 500m)
frame, base made in pre-painted galvanized steel profiles and centrifugal fan section. The unit
in standard execution can treat recirculating-only air; other available executions (optionals)
are MIX (return air and fresh air mix), FCS (Standard Free-Cooling with supply fans) or FCC
(Centrifugal Free-Cooling with supply and return fans).

Commands
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts).

308
r HFC
R-410A
CENTRIFUGAL AXIAL SCROLL FREE COOLING COOLING

WISDOM-T / B
Models 0101 0121 0151 0102 0122 0152 0182 0202 0252 0302 0352
COOLING ONLY
Cooling capacity (1) kW 34,7 - 48,8 34,1 41,8 47,8 55,3 66,4 83,2 93,8 109
Sensible cooling capacity (1) kW 26,9 - 36,7 26,7 31,1 37,4 42,6 50,9 64,8 71,3 80,9
Compressor power input (1) kW 8,11 - 12,4 8,11 12,3 13,8 14,3 17,1 24,4 26,2 29,1
OUTLET FANS
Supply air flow rate m3/h 6500 - 8500 6500 7800 8600 10500 13000 15500 17500 21000
Available static pressure (2) Pa 220 - 330 220 219 315 261 208 202 269 271
Power Input kW 1,10 - 2,20 1,10 1,50 2,20 3,00 2,20 3,00 4,40 6,00
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 - 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 78,0 - 78,0 78,0 78,0 78,0 78,0 84,0 84,0 84,0 87,0
Sound pressure (4) dB(A) 63,0 - 63,0 63,0 63,0 63,0 63,0 68,0 68,0 68,0 71,0
SIZE
A (5) mm 2900 - 2900 2900 2900 2900 2900 3400 3400 3400 3400
B (5) mm 1780 - 1780 1780 1780 1780 1780 2330 2330 2330 2330
H (5) mm 1640 - 1640 1640 1640 1640 1640 1790 1790 1790 1790
Operating weight (5) kg 870 - 950 870 910 980 1010 1210 1290 1350 1450

Models 0364 0404 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 110 129 154 170 191 215 260 280 318 337 357
Sensible cooling capacity (1) kW 85,3 97,1 116 126 142 159 197 211 239 246 253
Compressor power input (1) kW 29,7 34,7 39,2 44,1 51,5 60,1 67,5 77,0 83,6 91,9 104
OUTLET FANS
Supply air flow rate m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (2) Pa 271 303 215 261 333 235 255 400 290 290 290
Power Input kW 6,00 8,00 6,00 8,00 11,0 12,0 16,0 22,0 30,0 30,0 30,0
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 87,0 87,0 93,0 93,0 93,0 * * * * * *
Sound pressure (4) dB(A) 71,0 71,0 76,0 76,0 76,0 * * * * * *
SIZE
A (5) mm 3900 3900 3900 3900 3900 6580 6580 6580 6580 6580 6580
B (5) mm 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330 2330
H (5) mm 1820 1820 2380 2380 2380 2350 2350 2350 2350 2350 2350
Operating weight (5) kg 1560 1650 1890 2080 2230 3530 3790 3790 3910 4150 4160

Note:
1 Cooling: Outdoor 34°C 50% R.H. Indoor 27°C 47% R.H.
2 ESP for standard configuration (optional accessories not included/calculated)
3 Sound power on the basis of measurements made in compliance with ISO 3744.
4 Sound pressure in open field conditions on reflecting surface. Condensing coil side average value at 1 metre from the surface and at 1 m height in relation to the unit supporting base.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0101 0121-1204
Switchboard side mm 1500 2000
Condensation coil side mm 2000 2000

309
Packaged

WISDOM-R 0101÷1204
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
STATIC RECOVERY WITH CROSS FLOWS
The air/air cross flow exchangery allows a constant and
efficient exhaust airflow energy recovery. The excellent
efficiency values (more than 50%) in winter conditions and
no power consumption (there are no moving parts) give a
concrete energy and economic saving.
COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
Reversible rooftop unit, with heat recovery for FLEXIBILITY
Climaveneta offers units with innumerable choices for the
medium crowding applications supply and return airflows directions.

43,0 - 422 kW Main accessories


Unit Description UÊHot gas post heating
Unit for outdoor installation, reversible and direct expansion for the air conditioning, with scroll UÊCO2 control sensor for air quality
compressors running on R410A, sandwich panel with thickness of 42mm, aluminium frame, UÊHigh efficiency filters: electronic or rigid pocket F7
base made in pre-painted galvanized steel profiles and centrifugal fan section. The standard
UÊEnthalpy free-cooling
execution is FCC (Centrifugal Free-Cooling with supply and return fans).
UÊSet-up for remote connectivity with ModBus/Echelon
protocol cards
Commands UÊRemote keyboard (distance to 200m and to 500m)
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts). The defrost adopts a proprietary self-adaptive logic, which features
the monitoring of numerous operational parameters. This allows to reduce the number and duration of the defrost cycles,
with a benefit for the overall energy efficiency.

310
r HFC
R-410A
PLATE CENTRIFUGAL AXIAL SCROLL FREE COOLING HEATING COOLING

WISDOM-R / B
Models 0101 0121 0151 0102 0122 0152 0182 0202 0252 0302 0352
COOLING ONLY
Cooling capacity + Recovery (1) kW 43 51,5 59,7 42,6 51,8 61 68,4 83,2 107 115 135
Sensible cooling capacity +
kW 29 34 39,5 28,8 34 41 47,4 56,4 71,6 79,5 90,9
Recovery (1)
Compressor power input (1) kW 8,40 11,9 12,9 8,49 13 13,3 15 17,8 23,6 27,6 29,9
HEATING ONLY
Heating capacity + Recovery (2) kW 41,7 53,2 58,2 40,9 54 59,6 66 80,1 103 113 132
Compressors power input (2) kW 6,81 9,59 10,1 6,61 10,2 10,3 10,8 13,6 17,5 19,8 22,7
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8500 6500 7800 8600 10500 13000 15500 17500 21000
Available static pressure (3) Pa 264 314 230 264 314 210 365 240 275 330 350
Power Input kW 1,50 2,20 2,20 1,50 2,20 2,20 4 3 4,40 6 8
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8500 6500 7800 8600 10500 13000 15500 17500 21000
Useful static head (3) Pa 194 223 194 194 223 188 235 159 150 200 150
Power Input kW 1,10 1,50 1,50 1,10 1,50 1,50 2,20 2,20 3 4,40 6
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (4) dB(A) 79 79 79 79 79 79 79 85 85 85 88
Sound pressure (5) dB(A) 63 63 63 63 63 63 63 68 68 68 71
SIZE
A mm 5250 5250 5250 5250 5250 5250 5250 6450 6450 6450 6450
B mm 1780 1780 1780 1780 1780 1780 1780 2330 2330 2330 2330
H mm 1640 1640 1640 1640 1640 1640 1640 1790 1790 1790 1790
Operating weight kg 1500 1540 1580 1500 1540 1610 1650 2190 2270 2330 2450

Models 0364 0404 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity + Recovery (1) kW 139 157 188 206 230 263 313 341 380 402 422
Sensible cooling capacity +
kW 95,7 108 125 138 156 196 235 262 282 290 297
Recovery (1)
Compressor power input (1) kW 28,4 36,3 40,8 45,9 54,2 63,1 70,4 81,5 87,5 95,2 108
HEATING ONLY
Heating capacity + Recovery (2) kW 134 152 179 203 222 262 310 337 372 404 437
Compressors power input (2) kW 21,8 26,8 30,7 36,3 39,3 48,6 53,6 59,6 65 72,9 84,4
OUTLET FANS
Supply air flow rate m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (3) Pa 350 440 240 370 460 290 365 200 370 370 370
Power Input kW 8 11 8 11 15 12 16 22 30 30 30
SUCTION FANS/BLOWERS
Nominal air flow m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Useful static head (3) Pa 150 150 125 189 258 295 380 200 450 450 450
Power Input kW 6 8 6 8 11 12 16 22 30 30 30
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 88 88 94 94 94 * * * * * *
Sound pressure (5) dB(A) 71 71 76 76 76 * * * * * *
SIZE
A mm 6950 6950 6950 6950 6950 11080 11080 11080 11080 11080 11080
B mm 2330 2330 2340 2340 2340 2330 2330 2330 2330 2330 2330
H mm 1820 1820 2380 2380 2380 2350 2350 2350 2350 2350 2350
Operating weight kg 2550 2640 3240 3350 3490 5470 5730 5730 5870 6090 6100

Note:
1 Cooling: External 35°C 50% r.h. / Internal 27°C 47% r.h. / Mix 50 %
2 Heating: External 7°C 87% r.h. / Internal 20°C 50% r.h. / Mix 50 %
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.
5 Sound pressure in open field conditions on reflecting surface. Condensing coil side average value at 1 metre from the surface and at 1 m height in relation to the unit supporting base.

Minimum clearance required


0101-0302 0352-1204
Switchboard side mm 1500 0
Condensation coil side mm 2000 0

311
Packaged

WISDOM-T-R 0101÷1204
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
STATIC RECOVERY WITH CROSS FLOWS
The air/air cross flow exchangery allows a constant and
efficient exhaust airflow energy recovery. The excellent
efficiency values (more than 50%) in winter conditions and
no power consumption (there are no moving parts) give a
concrete energy and economic saving.
COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
Cooling only rooftop unit, with heat recovery FLEXIBILITY
Climaveneta offers units with innumerable choices for the
for medium crowding applications supply and return airflows directions.

43,5 - 425 kW Main accessories


Unit Description UÊHot gas post heating
Unit for outdoor installation, reversible and direct expansion for the air conditioning, with scroll UÊCO2 control sensor for air quality
compressors running on R410A, sandwich panel with thickness of 42mm, aluminium frame, UÊHigh efficiency filters: electronic or rigid pocket F7
base made in pre-painted galvanized steel profiles and centrifugal fan section. The standard
UÊEnthalpy free-cooling
execution is FCC (Centrifugal Free-Cooling with supply and return fans).
UÊHeating resource: hot water coil, electrical heater, burner
methane gas
Commands UÊSet-up for remote connectivity with ModBus/Echelon
AIR3000 protocol cards
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status UÊRemote keyboard (distance to 200m and to 500m)
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts).

312
r HFC
R-410A
PLATE CENTRIFUGAL AXIAL SCROLL FREE COOLING COOLING

WISDOM-T-R / B
Models 0101 0121 0151 0102 0122 0152 0182 0202 0252 0302 0352
COOLING ONLY
Cooling capacity + Recovery (1) kW 43,5 52 60,1 42,9 52,5 59,3 69,1 83,6 103 117 135
Sensible cooling capacity +
kW 29,1 34,1 39,7 28,9 34,3 40,5 47,6 56,6 70,5 79,9 90,9
Recovery (1)
Compressor power input (1) kW 8,30 11,6 12,7 8,30 12,6 14 14,7 17,4 25,2 27,1 29,9
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8500 6500 7800 8600 10500 13000 15500 17500 21000
Available static pressure (2) Pa 264 314 230 264 314 210 365 240 275 330 350
Power Input kW 1,50 2,20 2,20 1,50 2,20 2,20 4 3 4,40 6 8
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8500 6500 7800 8600 10500 13000 15500 17500 21000
Useful static head (2) Pa 194 223 194 194 223 188 235 159 150 200 150
Power Input kW 1,10 1,50 1,50 1,10 1,50 1,50 2,20 2,20 3 4,40 6
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (3) dB(A) 79 79 79 79 79 79 79 85 85 85 88
Sound pressure (4) dB(A) 63 63 63 63 63 63 63 68 68 68 71
SIZE
A mm 5250 5250 5250 5250 5250 5250 5250 6450 6450 6450 6450
B mm 1780 1780 1780 1780 1780 1780 1780 2330 2330 2330 2330
H mm 1640 1640 1640 1640 1640 1640 1640 1790 1790 1790 1790
Operating weight kg 1500 1540 1580 1500 1540 1610 1650 2190 2270 2330 2450

Models 0364 0404 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity + Recovery (1) kW 135 158 189 208 233 265 315 340 382 404 425
Sensible cooling capacity +
kW 94,9 109 125 139 156 196 236 254 283 291 296
Recovery (1)
Compressor power input (1) kW 30,6 35,5 40,1 45,1 53,1 61,7 69,2 79,3 85,8 93,9 106
OUTLET FANS
Supply air flow rate m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (2) Pa 350 440 240 370 460 290 365 200 370 370 370
Power Input kW 8 11 8 11 15 12 16 22 30 30 30
SUCTION FANS/BLOWERS
Nominal air flow m3/h 21000 23500 27000 29000 32000 45000 50000 54000 56000 56000 56000
Useful static head (2) Pa 150 150 125 189 258 295 380 200 450 450 450
Power Input kW 6 8 6 8 11 12 16 22 30 30 30
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (3) dB(A) 88 88 94 94 94 * * * * * *
Sound pressure (4) dB(A) 71 71 76 76 76 * * * * * *
SIZE
A mm 6950 6950 6950 6950 6950 11080 11080 11080 11080 11080 11080
B mm 2330 2330 2340 2340 2340 2330 2330 2330 2330 2330 2330
H mm 1820 1820 2380 2380 2380 2350 2350 2350 2350 2350 2350
Operating weight kg 2550 2640 3240 3350 3490 5470 5730 5730 5870 6090 6100
Note:
1 Cooling: External 35°C 50% r.h. / Internal 27°C 47% r.h. / Mix 50 %
2 ESP for standard configuration (optional accessories not included/calculated)
3 Sound power on the basis of measurements made in compliance with ISO 3744.
4 Sound pressure in open field conditions on reflecting surface. Condensing coil side average value at 1 metre from the surface and at 1 m height in relation to the unit supporting base.

Minimum clearance required


0101-1204
Switchboard side mm 1500
Condensation coil side mm 2000

313
Packaged

WET-RMT 0015÷0101
Versions
B base version

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
FUCNTIONALITY
The constructional simplicity ensures high reliability of use
the minimum acoustic impact, also thanks to the special
care given to insulation and aerodynamic profiles of the air
supply area.
EFFICIENCY
The use of the top quality parts ensures maximum
operating efficiency in all situations of plant design
requirement.
COMPACTNESS
Units with reduced height making them especially suitable
for installation in suspended ceilings and for ducted
supply and return.
INSTALLATION AND SERVICING
The installation is simply for the reduced dimensions and
the limited weight, while the servicing is made easier
because all parts can be reached by removing just one
WET line unit for water loop systems, indoor panel.

installation Main accessories


UÊManual on/off valves
7,2 - 34,4 kW UÊTwo way motorized ON/OFF valve
UÊPressure-solenoid valve
Unit Description
Unit for indoor installation (in ceiling mounted or inserted behind a suspended ceiling), UÊAmbient air sensor
reversible and direct expansion for the air conditioning, with scroll compressors running on
R410A. Panels and frame in hot-dip galvanised sheet steel, electric centrifugal supply fan.
Hydraulic and electrical connections are simple thanks to the compact size and reduced
weight of the units; maintenance is simple as all the components can be reached by removing
just one panel.

Commands
S3
The S3 controller features ease of use and nice design. The regulation is reliable thanks to the algorithms developed and to
the availability of a multi-level menu with differentiated access modes. The controller includes the control board, mounted
in the unit, the user interface with keypad and LCD display, with 4 lines, to be placed in the room (supplied separately and
mandatory) and a remote air probe for air duct. The user interface allows the language selection (Italian, English, German).
The diagnostics includes a complete alarm management, with the “black-box” and alarm logging functions for enhanced
analysis of the unit operation. Availability of an internal real time clock for operation scheduling (4-day profiles with 10 hour
belts). This allows to define operating status and modes. As standard, serial connectivity via ModBus protocol is featured,
allowing the supervision by proprietary devices or the integration in third party systems. Supervision can be also implemented
via optional protocols (Bacnet or Echelon LonWorks).

314
r HFC
R-410A
CENTRIFUGAL SCROLL HEATING COOLING

WET-RMT / B
Models 0015 0021 0031 0041 0061 0065 0071 0081 0091 0101
COOLING ONLY
Cooling capacity (1) kW 7,20 9 11,7 14,3 17,3 9 23,3 25,5 29,3 34,4
Sensible cooling capacity (1) kW 5,83 7,29 9,48 11,6 14 16,4 18,9 20,7 23,7 27,9
Compressors power input (1) kW 1,60 1,90 2,40 3 3,60 4,20 4,80 5,30 5,90 6,90
HEATING ONLY
Heating capacity (2) kW 7 8,80 11,2 13,8 16,5 19,4 22,2 24,4 27,9 32,6
Compressors power input (2) kW 1,80 2,10 2,70 3,30 3,90 4,50 5,10 5,60 6,30 7,40
PLATE EXCHANGER
Water flow m3/h 1,26 1,56 2,02 2,48 3 3,50 4,03 4,42 5,05 5,93
INTERNAL FANS
Airflow rate m3/h 1300 1600 2300 2700 3100 3600 4200 4600 5200 6100
Available static pressure (3) Pa 100 100 100 100 120 120 120 120 120 120
Power Input kW 0,24 0,24 0,50 0,50 0,50 0,50 0,74 0,73 0,74 0,74
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1
NOISE LEVELS
Sound power (4) dB(A) 67 69 71 72 73 74 74 76 77 78
SIZE
A mm 900 900 955 955 1092 1092 1135 1135 1455 1455
B mm 705 705 972 972 1069 1069 1114 1114 1135 1135
H mm 450 450 500 500 573 573 663 663 732 732
Operating weight kg. 103 111 123 155 245 - 255 - 293 310
Note:
1 Cooling: Indoor air 27°C 47% R.H. / Water loop temperature IN 29°C OUT 35°C
2 Heating: Indoor air 20°C 50% R.H. / Water loop temperature OUT 15°C
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power measured in standard operating conditions without air ducts.

Minimum clearance required


0015-0101
Switchboard side mm 0
Raising points side mm 0

A B

315
Packaged

WET ENTHALPY 0102÷0604


Versions
B base version

Configurations
PC function for constant water flow system
PV function for variable water flow system
PP function for disposable water system

Features
VARIABLE AIRFLOW FOR AIR TREATMENT SECTION
The specific VAir function is used to deliver air according
to the flow of hot-cold air and many other operating
parameters. This offers significant reductions in the power
input of the fans.
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
ROTARY-TYPE ENTHALPY RECOVERY
The exclusive rotary recovery allows sensible and latent
energy from the exhaust airflow both in winter and
summer conditions. The latent recovery, in particular,
is important in dehumidification in summer and
humidification in winter for indoor, with very high efficiency
High efficiency WET line unit for water loop values.
PLUG-FAN VENTILATION
systems, with enthalpy recovery, outdoor The plug-fan supply and return fan section joins the high
efficacy ventilation with a quicker and easier electric and
installation aerolics installation of the unit.
SAFE USE
50,6 - 262 kW The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
Unit Description This means a lower accidental risk to contaminate
Autonomous rooftop unit, water/air reversible, for the thermohygrometric treatment, the the indoor environment and moreover allowing the
filtration and the air change in wide areas. Both winter and summer operating conditions, thermostatic valve adjustment while the unit is on.
double refrigerant circuit, scroll compressors with refrigerant R410A. Air treatment section
with plug-fans and direct expansion finned internal exchangers. Enthalpic rotary heat recovery. Main accessories
Management of air treatment section according to the requested heating or cooling capacity UÊEnthalpy free-cooling
by the Vair function.
UÊCO2 control sensor for air quality
UÊHot gas post heating
Commands UÊSet-up for remote connectivity with ModBus/Echelon
AIR3000SE protocol cards
The AIR3000SE controller offers advanced functions and algorithms. The keypad features functional controls and a complete
LCD display that allows assessment and intervention on the unit by means of a multi-level menu with selectable user´s UÊRemote keyboard (distance to 200m and to 500m)
language. The presence of the programmable timer allows the creation of an operating profile containing up to 4 typical
days and 10 time bands. The proportional step heat adjustment is based on the return temperature; proportional-integral
UÊHigh efficiency filters: electronic or rigid pocket F7
adjustment can also be set. Functions include adjustment of available resources, ambient humidity, thermal or enthalpic
(optional) free-cooling and delivery temperature limitation. The specific VAir function is used to deliver air according to the
flow of hot-cold air and many other operating parameters. This offers significant reductions in the power input of the fans.
The function can be selected from a parameter, it operates within settable flow values and is compatible with the adjusted
rotation speed, adjusted flow and adjusted pressure ventilation methods. It also guarantees any differences required between
return and delivery airflows. The diagnostics comprises a complete alarm management system, including black box (via
PC) functions and an alarm log (via display or also PC) for optimised analysis of unit performance. Supervision can be easily
developed via proprietary devices or the integration in third party systems by means of the most common protocols as
ModBus, Bacnet, Bacnet-over-IP, Echelon LonWorks protocols. Compatibility with the remote keyboard managing up to 10
units.

316
ROTARY PLUG FAN SCROLL FREE COOLING HEATING COOLING

WET ENTHALPY / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404 0454 0504 0604
COOLING ONLY
Cooling capacity + Recovery (1) kW 50,6 62,5 71,7 83,8 103 130 143 171 175 193 211 241 262
Sensible cooling capacity +
kW 32,4 39,8 45 53,9 64,6 80,7 90,5 109 110 121 138 153 168
Recovery (1)
Compressor power input (1) kW 6,90 9,20 10,8 12,9 13,9 18,1 20,5 24,4 26,1 28 32 36 41,2
HEATING ONLY
Heating capacity + Recovery (2) kW 50,7 64,8 74 86,7 102 131 146 174 178 199 219 251 279
Compressors power input (2) kW 7,90 11,6 12,4 14,8 15,9 19,9 22,9 25,8 28 31,7 39,9 41,2 49,2
PLATE EXCHANGER
Water flow m3/h 6,30 8,03 9,40 11 12,8 16,6 18,4 22,2 23 25,4 27,8 32,3 35,6
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23000 27000 29000 32000
Available static pressure (3) Pa 250 250 250 250 250 250 250 250 250 250 250 250 250
Power Input kW 1,50 1,96 2,24 3,18 2,74 3,68 4,66 5,22 5,22 6,38 7,84 9,06 11,3
SUCTION FANS/BLOWERS
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23000 27000 29000 32000
Useful static head (3) Pa 150 150 150 150 150 150 150 150 150 150 150 150 150
Power Input kW 1,04 1,62 1,92 2,82 2 2,68 3,98 3,66 3,66 4,50 4,42 5,16 6,82
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power (4) dB(A) 88 89 90 91 94 94 94 95 95 96 97 97 98
SIZE
A mm 3760 3760 3760 3760 4035 4035 4035 4830 4830 4830 5200 5200 5200
B mm 1780 1780 1780 1780 2330 2330 2330 2330 2330 2330 2330 2330 2330
H mm 1490 1490 1490 1490 2240 2240 2240 2240 2240 2240 2240 2240 2240
Operating weight kg 1430 1460 1520 1540 2430 2480 2540 3000 3110 3130 3620 3710 3760
Note:
1 Cooling: Outdoor air 35°C 50% R.H. / Indoor air 27°C 47% R.H. / Mix 30% / Water loop temperature IN 29°C OUT 35°C
2 Heating: Outdoor air 7°C 87% R.H. / Indoor air 20°C 50% R.H. / Mix 30% / Water loop temperature OUT 10°C
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power measured in standard operating conditions without air ducts.

Minimum clearance required


0102-0604
Switchboard side mm 1500
Raising points side mm 2000

317
Packaged

WET-RTF 0102÷1204
Versions
B base version

Configurations
PC function for constant water flow system
PV function for variable water flow system
PP function for disposable water system

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment
(ODP=0).

COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
SAFE USE
The refrigerant piping and the regulation devices are put
in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
WET line unit for water loop systems, outdoor the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
installation FLEXIBILITY
Climaveneta offers units with innumerable choices for the
37,2 - 396 kW supply and return airflows directions.

Unit Description
Unit for indoor installation, reversible and direct expansion for the air conditioning, with scroll Main accessories
compressors running on R410A, sandwich panel with thickness of 42mm, aluminium frame, UÊHot gas post heating
base made in pre-painted galvanized steel profiles and centrifugal fan section. The unit in UÊCO2 control sensor for air quality
standard version, STD, can treat recirculating-only air; other available executions (optionals)
UÊHigh efficiency filters: electronic or rigid pocket F7
are MIX (return air and fresh air mix), FCS (Standard Free-Cooling with supply fans) or FCC
(Centrifugal Free-Cooling with supply and return fans). UÊEnthalpy free-cooling
UÊSet-up for remote connectivity with ModBus/Echelon
protocol cards
Commands UÊRemote keyboard (distance to 200m and to 500m)
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
operation scheduling (4-day profiles with 10 hour belts).

318
r HFC
R-410A
CENTRIFUGAL SCROLL FREE COOLING HEATING COOLING

WET-RTF / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404
COOLING ONLY
Cooling capacity (1) kW 37,2 46,5 54,6 62,3 73,8 96,3 106 121 125 144
Sensible cooling capacity (1) kW 27,9 32,6 39,6 45 53 69,3 75,7 84,5 90,2 102
Compressor power input (1) kW 6,85 9,24 10,7 11,3 13,8 18,3 20,4 21,6 22,6 27,5
HEATING ONLY
Heating capacity (2) kW 42,6 55,2 64,2 71,9 84,5 113 126 144 146 173
Compressors power input (2) kW 7,87 11,9 12,2 13,1 16,1 21,1 24,9 25,9 26,3 33,5
CONDENSER
Water flow rate mc/h 6,32 7,99 9,36 10,6 12,6 16,4 18,1 20,4 21,1 24,5
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500
Available static pressure (3) Pa 220 219 315 261 208 202 269 271 271 303
Power Input kW 1,10 1,50 2,20 3 2,20 3 4,40 6 6 8
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2
NOISE LEVELS (4)
Sound power dB(A) 78 76 76 76 82 82 82 87 87 87
SIZE
A (5) mm 2200 2200 2200 2200 2470 2470 2470 2470 2470 2470
B (5) mm 1780 1780 1780 1780 2330 2330 2330 2330 2330 2330
H (5) mm 1490 1490 1490 1490 1640 1640 1640 1640 1640 1640
Operating weight (5) kg 710 780 790 810 1030 1080 1110 1250 1340 1350

Models 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity (1) kW 170 187 215 243 288 314 352 375 396
Sensible cooling capacity (1) kW 102 131 150 172 207 224 250 258 266
Compressor power input (1) kW 32,1 36,4 40,4 48,2 55,6 61,7 67,4 74,5 82,8
HEATING ONLY
Heating capacity (2) kW 199 225 252 283 333 368 410 442 488
Compressors power input (2) kW 37,2 44,4 48,7 61,5 66,4 76,9 82,8 92,4 109
CONDENSER
Water flow rate mc/h 28,9 32 36,6 41,8 49,2 53,8 60,1 64,4 68,7
OUTLET FANS
Supply air flow rate m3/h 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (3) Pa 215 261 333 235 255 400 290 290 290
Power Input kW 6 8 11 12 16 22 30 30 30
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS (4)
Sound power dB(A) 92 92 92 * * * * * *
SIZE
A (5) mm 2470 2470 2470 5000 5000 5000 5000 5000 5000
B (5) mm 2330 2330 2330 2330 2330 2330 2330 2330 2330
H (5) mm 2240 2240 2240 2240 2240 2240 2240 2240 2240
Operating weight (5) kg 1570 1630 1750 2770 3000 3200 3250 3300 3350
Note:
1 Cooling: Indoor air 27°C 47% R.H. / Water loop temperature IN 29°C OUT 35°C
2 Heating: Indoor air 20°C 50% R.H. / Water loop temperature OUT 10°C
3 ESP for standard configuration (optional accessories not included/calculated)
4 Sound power on the basis of measurements made in compliance with ISO 3744.
5 Unit in standard configuration/execution, without optional accessories

Minimum clearance required


0102-1204
Switchboard side mm 1500
Raising points side mm 2000

319
Packaged

WET-RTF-R 0102÷1204
Versions
B base version

Configurations
PC function for constant water flow system
PV function for variable water flow system
PP function for disposable water system

Features
REFRIGERANT GAS R410A
The use of R410A has resulted in units offering better
energy efficiency in full respect for the environment (ODP
= 0).
STATIC RECOVERY WITH CROSS FLOWS
The air/air cross flow exchangery allows a constant and
efficient exhaust airflow energy recovery. The excellent
efficiency values (more than 50%) in winter conditions and
no power consumption (there are no moving parts) give a
concrete energy and economic saving.
COMFORT
The wide working field and the accurate designed of the
unit ensure optimum capacities and guaranty comfort,
with a continuous and constant bringing in of thermal load
also in the more onerous thermohygrometric conditions.
WET line unit for water loop systems, with heat SAFE USE
The refrigerant piping and the regulation devices are put
recovery, outdoor installation in suitable space, splitted from the air treatment section.
This means a lower accidental risk to contaminate
44,8 - 468 kW the indoor environment and moreover allowing the
thermostatic valve adjustment while the unit is on.
Unit Description FLEXIBILITY
Unit for outdoor installation, reversible and direct expansion for the air conditioning, with scroll Climaveneta offers units with innumerable choices for the
compressors running on R410A, sandwich panel with thickness of 42mm, aluminium frame, supply and return airflows directions.
base made in pre-painted galvanized steel profiles and centrifugal fan section. The standard
execution is FCC (Centrifugal Free-Cooling with supply and return fans).
Main accessories
UÊHot gas post heating
Commands
UÊCO2 control sensor for air quality
AIR3000
The controller AIR3000 offers advanced functions and algorithms. The keypad is generously sized with full operating status UÊHigh efficiency filters: electronic or rigid pocket F7
display. The controls and detailed LCD make access to unit settings easy and safe. Temperature regulation is based on
step-wise proportional logic referring to the return air temperature. The diagnostics includes full management of alarms with UÊEnthalpy free-cooling
the black-box and alarm logging functions for enhanced analysis of the unit operation. Supervision can be easily developed UÊSet-up for remote connectivity with ModBus/Echelon
via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Echelon
LonWorks. Compatibility with the remote keyboard managing up to 10 units. Availability of an internal real time clock for
protocol cards
operation scheduling (4-day profiles with 10 hour belts). UÊRemote keyboard (distance to 200m and to 500m)

320
r HFC
R-410A
PLATE CENTRIFUGAL SCROLL FREE COOLING HEATING COOLING

WET-RTF-R / B
Models 0102 0122 0152 0182 0202 0252 0302 0352 0364 0404
COOLING ONLY
Cooling capacity + Recovery (1) kW 44,8 55,5 65,1 74,4 89,4 114 126 143 147 169
Sensible cooling capacity +
kW 33,8 39,5 47,9 54,5 66,1 85,8 91,3 101 107 122
Recovery (1)
Compressor power input (1) kW 6,95 9,24 10,6 11,2 13,7 18,4 20,3 21,7 22,5 27,3
HEATING ONLY
Heating capacity + Recovery (2) kW 52,1 66 76,8 85,8 103 135 150 166 172 202
Compressors power input (2) kW 7,48 11,5 11,6 12,6 15,6 20,3 24 23,9 25,2 32,2
PLATE EXCHANGER
Water flow m3/h 6,32 7,99 9,36 10,6 12,6 16,4 18,1 20,4 21,1 24,5
OUTLET FANS
Supply air flow rate m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500
Available static pressure (3) Pa 264 314 210 365 240 275 330 350 350 440
Power Input kW 1,50 2,20 2,20 4 3 4,40 6 8 8 11
SUCTION FANS/BLOWERS (3)
Nominal air flow m3/h 6500 7800 8600 10500 13000 15500 17500 21000 21000 23500
Useful static head Pa 194 223 188 235 159 150 200 150 150 150
Power Input kW 1,10 1,50 1,50 2,20 2,20 3 4,40 6 6 8
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2
NOISE LEVELS
Sound power dB(A) 78 78 78 78 84 84 84 89 89 89
SIZE
A mm 4500 4500 4500 4500 5470 5470 5470 5470 5470 5470
B mm 1780 1780 1780 1780 2330 2330 2330 2330 2330 2330
H mm 1490 1490 1490 1490 1640 1640 1640 1640 1640 1640
Operating weight kg 1300 1360 1370 1400 1860 1910 1940 2180 2230 2370

Models 0454 0504 0604 0704 0804 0904 1004 1104 1204
COOLING ONLY
Cooling capacity + Recovery (1) kW 200 219 250 297 348 382 420 446 468
Sensible cooling capacity +
kW 145 155 177 211 249 278 297 305 311
Recovery (1)
Compressor power input (1) kW 32,2 36,3 40,6 49,6 57,1 64,2 69,5 76,3 85,2
HEATING ONLY
Heating capacity + Recovery (2) kW 234 263 292 334 390 429 473 505 552
Compressors power input (2) kW 35,7 42,7 46,8 57,2 61,8 70,1 76,7 85,4 100
PLATE EXCHANGER
Water flow m3/h 28,9 32 36,6 41,8 49,2 53,8 60,1 64,4 68,7
OUTLET FANS
Supply air flow rate m3/h 27000 29000 32000 45000 50000 54000 56000 56000 56000
Available static pressure (3) Pa 240 370 460 290 365 200 370 370 370
Power Input kW 8 11 15 12 16 22 30 30 30
SUCTION FANS/BLOWERS (3)
Nominal air flow m3/h 27000 29000 32000 45000 50000 54000 56000 56000 56000
Useful static head Pa 125 189 258 295 380 200 450 450 450
Power Input kW 6 8 11 12 16 22 30 30 30
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
NOISE LEVELS
Sound power dB(A) 94 94 94 * * * * * *
SIZE
A mm 5470 5470 5470 9500 9500 9500 9500 9500 9500
B mm 2330 2330 2330 2330 2330 2330 2330 2330 2330
H mm 2240 2240 2240 2240 2240 2240 2240 2240 2240
Operating weight kg 2690 2740 2830 4450 4650 4700 4780 5000 5050
Note:
1 Cooling: Outdoor air 35°C 50% R.H. / Indoor air 27°C 47% R.H. / Mix 50% / Water loop temperature IN 29°C OUT 35°C
2 Heating: Outdoor air 7°C 87% R.H. / Indoor air 20°C 50% R.H. / Mix 50% / Water loop temperature OUT 10°C
3 ESP for standard configuration (optional accessories not included/calculated)

Minimum clearance required


0102-1204
Switchboard side mm 1500
Raising points side mm 2000

321
Y
YS
YSTE
322
EMS systems

systems

323
Systems

MANAGER 3000

Group regulation device Features


OPTIONS
Integration in BMS /BAS via ModBus, Echelon LonTalk or
Bacnet protocols
Unit Description Modem or ADSL router
Manager3000 allows the regulation within a group of hydronic units. The controller Log of main variables and alarm events
features high-level algorithms and user interface. The controller is suitable for the WebManager, with capabilities of remote access and
management of 2- or 4-pipe systems, with regulation on one water circuit, for chiller- optionale display of logged data charts.
or heat pump units and relevant mode change-over, and also with regulation on two
VPF implementation.
circuits, with independent set-points and parameters, thus exploiting the simultaneous
supply of chilled- and hot water. The controller manages up to 8 units, with activation
logic focused at the balancing of operation times and at the achievement of the highest Models MANAGER
energy efficiency. It is possible to define conditions of dynamic stand-by and priority max number of managed units 8
as regards the units activation. It is also feasible the rotation among the systems Management of hydronic units X
units, also in cases of constant load. The alarm management is featured, with plain Regulation on one water circuit X
text descriptions and possible notification to remote recipients. Two relay outputs are Regulation on two water circuits (4 pipe systems) X
User interface with display and commands,
available, associated to unit- and device alarms. The user interface allows a safe and X
touchscreen, multi-language
easy use, thanks to its touch-screen display, back-lit 8.4” type. The multi-level menu Alarm management X
features the language selection and differentiated access profiles(user and maintenance). Management of stand-by, priority, rotation X
The circuit temperatures and the status of both system- and unit- operation are Supervision via web pages (WebManager) opt
displayed, via one overview page plus detailed pages. The regulation can be based Integration into BMS/BAS systems opt
on proportional- or proportional+integral logics, or also on a dead-band algorithm with Acquisition and log of the main operating
opt
dynamic adjustment, with relevant temperature inputs managed by the device. Features variables
Modem gprs or pstn, integrated opt
as set-point offset, also referred to the outdoor temperature, and demand limit are Router ADSL, integrated opt
included, with relevant analog inputs. The device is integrated in the best way with the Compatibility with variable primary flow systems opt
units, preventing simultaneous activations or resources and optimizing efficiency, overall Compatibility with metering device Demetra opt
inrush current values and also operation of water pumps possibly associated to the
units. The WebManager option allows the access to the device and its settings, via any
computer, with direct- or LAN-based connection, therefore also via internet resources;
this is associated to the availability of historical charts for the main operating variables.
The “Variable Primary Flow” option represents a unique regulation dedicated to hydronic
systems with variable water flow. This represents a crucial contribution to the reduction
of the costs related to the hydraulic plant and its operation. It is available as option the
interface with the Demetra metering device: thus it is possible to acquire and log the
values of the system units electric consumption, together with their operating status;
this allows therefore to analyze the systems operating performances throughout time, in
terms of both absorbed energy and cooling / heating capacities, consistently with the
implementation of enhanced energy management policies for the building.

324
Systems

SEQUENCER
SEQUENCER÷SEQUENCER

Group regulation device Features


Integration in BMS /BAS via ModBus, Echelon LonTalk or
Bacnet protocols

Unit Description Models SEQUENCER


The device allows the regulation within a group of hydronic units. The controller features Regulation of multiple units, 1 water circuit X
a high-level algorithm (regulation profile GR2000). The controller is suitable for the Regulation of multiple units, 2 water circuits
management of 2-pipe systems, with regulation on one water circuit, for chiller- or heat Management of dynamic stand-by, priority,
X
pump units and relevant mode change-over. The controller manages up to 5 units, with demand limit
activation logic focused at the balancing of operation times and at the achievement of Integration in bms / bas systems opt
the highest energy efficiency. It is possible to define conditions of dynamic stand-by and Management of hydronic units X
priority as regards the units activation. The alarm management, with one relay output, Max number of devices 5
is available. On the LCD user interface the main variables, related to the system and the User interface with display and commands X
units, are displayed. The regulation can be based on proportional- or proportional+integral Monitoring of alarms and unit status X
logics. The device is integrated in the best way with the units, preventing simultaneous
activations of resources and optimizing the efficiency and the overall inrush current value.

325
Systems

DEMETRA

Metering device Models


max number of managed units
DEMETRA
8
Management of hydronic units X
Metering on one water circuit X
Metering on two water circuits (4 pipe systems) X
Compatibility with Manager3000 X
Compatibility with FWS3000 X

Unit Description
The new Demetra device represents the solution for the most evolved and up-to-date
requirements concerning the energy management of HVAC hydronic systems Demetra
(DEvice for Metering of Energy TRAnsfers) is associated to the Climaveneta devices,
Manager3000 or FWS3000 and enables the metering of both electric energy consumption
and cooling / heating performances. Demetra is compatible with hydronic systems with
one or two hydraulic circuits. The combination of Manager3000 and Demetra represents
the optimized integration between systems regulation and measurement of the benefits,
energy-wise, arising from such regulation. With Demetra it is possible the acquisition,
at selectable intervals, of the electric energy consumption for each unit, the water flow
rates (optional, care of customer) and of the outdoor air temperature. These values
are integrated with the operating status of each unit, as detected by Manager3000 or
FWS3000 (on these devices, the options of USB key and compatibility with Demetra
are required). Demetra is provided complete with power supply meters, associated to
each unit belonging to the system. The flow rate meters, for each hydraulic circuit, are
optional, care of customer. The enhanced features of this solution allow to obtain directly
the cooling- and heating energy values supplied, according to the operation conditions
detected on the units at each sampling. By this way, historical files are obtained, easily
downloadable also via LAN / internet, thus enabling a deep and complete analysis of
systems performances throughout time. In particular, the following data are managed:
Electric energy consumption Cooling energy output, for the relevant water circuit Heating
energy output, for the relevant water circuits Outdoor air temperature Water inlet- and
outlet temperatures, for the relevant water circuits Water flow rate, for the relevant water
circuits (optional, care of customer) Duration time for the different operating regimes, for
each unit

326
Systems

FWS3

Supervisory device Features


Integration in bms / bas systems, with modbus protocol
Modem or ADSL router
Log of main variables and alarm events

Unit Description
Supervisory device for one Climaveneta unit. Supervision can be operated via any Models FWS3
computer, with direct- or LAN-based connection. It is therefore achieved the internet- Supervision via web pages X
based management of the resources, thanks to the built-in web-server and to the Integration in bms / bas systems opt
availability of web pages specifically defined.The supervision achieved by this way does Access via lan X
not require the installation of any additional software on the computer and utilizes the Management of rooftop- or wet units X
most common browsers. This allows the use of any computer connected to the network Management of hydronic units X
Monitoring of alarms and unit status X
or web.A RS-485 serial connection is available for the communication with the slave Remote notification of alarms X
device (hydronic unit: chiller or heat pump. Rooftop).The access to the supervision is easy Log of main regulation variables and alarm events opt
and safe, thanks to the use of password. It is possible to visualize a complete list of unit Built-in modem, gprs or pstn type opt
operational variables: temperatures, humidity, indoor air quality, status of the unit. It is Built-in adsl router opt
also available the display of alarms, with plain text descriptions and possible notification
to remote recipient. The setting of the main operational parameters, for each unit, is also
allowed: unit status, mode, set-point, time scheduling (based on 4 days, 10 time belts per
day).

327
Systems

FWS3000

Supervisory device Features


Customization of the web pages
Application package dedicated to high-attendance or
cinema applications
Application package dedicated to the energy metering and
billing, with water-loop systems
Unit Description Integration in bms / bas systems, with modbus protocol
Supervisory device for a system composed of Climaveneta units. Supervision can be Modem or ADSL router
operated via any computer, with direct- or LAN-based connection. It is therefore achieved Log of main variables and alarm events
the internet-based management of the resources, thanks to the built-in web-server and to
the availability of web pages specifically defined both for the overall system monitoring and
the access to detailed information about each unit. The supervision achieved by this way
does not require the installation of any additional software on the computer and utilizes the Models FSW3000
max number of managed units 15
most common browsers. This allows the use of any computer connected to the network or
Management of packaged or hydronic systems X
web. A RS-485 serial connection is available for the communication with the slave devices, Alarm management X
up to 15 connected units. FWS3000 is particularly effective for the supervision of systems Supervision via web pages X
composed of packaged or WET units. The access to the supervision is easy and safe, Integration into BMS/BAS systems opt
thanks to the use of password. It is possible to visualize a complete list of unit operational Acquisition and log of the main operating
opt
variables: temperatures, humidity, indoor air quality, status of the unit. This is associated to variables
the availability of historical charts for the main operating variables. It is also available the Modem gprs or pstn, integrated opt
Router ADSL, integrated opt
display of alarms, with plain text descriptions and possible notification to remote recipient.
Compatibility with metering device Demetra opt
The setting of the main operational parameters, for each unit, is also allowed: unit status,
mode, set-point, time scheduling (based on 4 days, 10 time belts per day). Various levels
of customization are offered, for both the web pages and connectivity-related functions.
It is available as option the interface with the Demetra metering device: thus it is possible
to acquire and log the values of the system units electric consumption, together with their
operating status; this allows therefore to analyze the systems operating performances
throughout time, in terms of both absorbed energy and cooling / heating capacities,
consistently with the implementation of enhanced energy management policies for the
building.

328
329
SYSTEMS

Standard functions
MANAGEMENT
For each terminal, provided with wall-mount or built-in
controller, it is possible to select set-point, operation
mode, fan speed. These settings can be further modified
either locally, by acting on each controller, or in a centra-
lized way, by acting on the touch-screen. For the water
chillers and heat pumps, centralized access allows to
switch the units on and off and selecting the operation
mode.
SUPERVISION
At any moment it is possible to display via touch-screen
the operation status of the terminals connected to the
serial line. For each room: temperature, set-point, opera-
tion mode are displayed. For the water chillers and heat
pumps: operation mode, temperatures and possibly active
alarms can be displayed.
QUICK SETTINGS
Via centralized access it is possible to switch all terminals
on or off simultaneously; for the water chillers and heat
pumps, it is allowed to select the set-point value, the ope-
ration mode and to command the switch-on.
TIMER
A timer function is implemented, enabling to switch on or
off the whole system or selected zones, with scheduling
on daily and weekly basis.
LIMITS
At local level, the setting ability can be limited, by disa-
Centralised hydronic air-conditioning system bling some or all functions of each controller (ventilation,
operation mode), or reducing the adjustable range of set-
for cooling, heating and domestic hot water point values to few degrees (e.g. ±1°C). By the same way,
each controller can be disabled in order to prevent any
production change at local level and assign full control of the zone to
the supervision.
ECONOMY CONTACT
Description Local controllers of the terminals are provided with an Eco-
Centralized management and control system, via a user interface consisting in a compact nomy contact which, connected to voltage-free contacts
PC for flush mounting, which features Touch Screen commands. of various types (room access badge, window contact,
Capability of control up to 224 devices (terminals, chillers or heat pumps, other components) presence detector, etc.) thus allowing to manage an “eco-
for each serial network. nomy” operation profile (minimum speed ventilation, set-
point value increased in summer mode and decreased in
winter mode). The operation profile is reset to normal by
closing the contact.
COMPONENTS MANAGEMENT
It is furthermore possible to manage, by means of dedi-
cated voltage-free contacts, the on-off switching of fur-
ther components of the cooling / heating system, such as
pumps, zone valves or boilers.

Products suitable to integration


Hydronic terminals
UÊ*ÀœviÃȜ˜>Êv>˜‡VœˆÃÊ܈̅ÊÃޘV…Àœ˜œÕÃʓœÌœÀÊiiVÌÀœ˜ˆVÊÃ܈ÌV…iÃʈ‡
UÊ*ÀœviÃȜ˜>Êv>˜‡VœˆÃÊ܈̅ÊV>Lˆ˜iÌʜÀÊVœ˜Vi>i`ÊÛiÀȜ˜Ê܈̅ÊVi˜ÌÀˆvÕ}>Êv>˜Ê>‡
UÊ*ÀœviÃȜ˜>Êv>˜‡VœˆÃÊVœ˜Vi>i`ÊÛiÀȜ˜Ê…ˆ}…Ê…i>`Ê>‡ Ê*
UÊ,iÈ`i˜Ìˆ>Êv>˜‡VœˆÃÊ܈̅ÊV>Lˆ˜iÌʜÀÊVœ˜Vi>i`ÊÛiÀȜ˜Ê /

>ÃÃiÌÌiÊÌÞ«iÊv>˜‡VœˆÃÊȘ}iÉ`œÕLiÊVœˆÊvœÀÊ`œÕLiÉvœÕÀÊ«ˆ«iÊVœ˜˜iV̈œ˜ÃÊ8 1
UÊ ÕVÌi`ÊÌÞ«iÊv>˜‡VœˆÃÊÜ>‡“œÕ˜Ìi`ÊVœ˜ÌÀœÃʜÀÊ܈̅ÊÀi“œÌiÊVœ˜ÌÀœÊ7

Water chillers and heat pumps


UÊœ`iÃÊ«ÀiÃi˜Ìʜ˜Ê
ˆ“>Ûi˜iÌ>Êœ“iÊ-ÞÃÌi“Ê­ ,/]Ê , ]Ê
-]Ê
-‡ ]iÌV°®Ê>˜`Ê
œ““iÀVˆ>ÊEʘ`ÕÃÌÀˆ>ÊV>Ì>-
logues

Auxiliary components suitable to be managed via digital contact


UÊ"˜‡"vvÊLœˆiÀÃ]Ê"˜‡"vvʫՓ«Ã]Ê✘iÊÛ>ÛiÃ]ÊiÌV°

330
Operation diagram

Note
1. StarTouch: Compact user interface panel, with a 5,7” TFT colour display, suitable for Windows CE-based applications. I/O board includes 2 USB connectors type A
(host), 1 RJ45 connector for Ethernet 10/100, 1 DB9 connector for the RS232 serial port, screw terminals for the RS485 serial port, 1 USB connector client type.
2. BusAdapter: Interface enabling the connection of the electronic controllers AT/ATW to a RS485 network; one interface required for each controller.
3. AT: Plug-in control; features: on-off, operation mode, fan speed mode, set-point selection, economy contact, window contact, remote cool/heat, hot start and too-cool
functions.
4. ATW: Wall-mounted control; features: on-off, operation mode, fan speed mode, set-point selection, economy contact, window contact, remote cool/heat, hot start and too-cool
functions.
5. BusCE: kit including controller and BusAdapter; to be used when it is necessary to conceal both components, managing the terminal via supervision or infra-red remote
control.
6. IR: kit for the infra-red remote control composed of an infra-red receiver and associated remote keypad, which replicates all functions of the electronic controller.
7. HSW7: Mini-chiller control; it can be directly integrated in the serial line via BusAdapter (standard on units: BRAT, BRAN, BRA, BRH, etc.).
8. PowerBusCE: Interface enabling the connection of the auxiliary plant components (pumps, boilers, valves, etc.) and some type of chillers and heat pumps.
9. Serial cable: Serial communication cable: 2-conductor twisted pair, shielded, cross section reference AWG22. For wiring length over 1.5 km, feasibility assessment is
required.

This operation diagram is purely representative and qualitative. Refer to the available technical documentation for compatibility and connection mode.

331
332
A
AHU
333
AHU

AHU
AHU

WIZARD
Features
UNIT COMPLETE WITH REGULATION
The unit includes the controller for the regulation of all the
parameters required for the air treatment. The electrical
board is built-in and complete with wiring, while the
components such as 3-way valves, probes, damper
motors and humidifiers (optional) are provided factory-
mounted and wired
CE MARKING
As the unit does not require any further on-site
intervention upon it, Climaveneta provides Wizard
Automatic completed with CE marking, Class A
REDUCED TIMING
Thanks to the use of a unit ready to operate without any
further intervention, the commissioning timing results
strongly reduced.
SAFETY AND RELIABILITY
Climaveneta becomes the single contact reference for any
malfunctioning related to the unit.
MINIMAL SYSTEM START-UP COSTS
The on-site placement of a “plug & play” unit remarkably
reduces the use of skilled labour, associated to the
commissioning of a traditional air handling unit, thus
reducing the costs

Air handling unit

0-115000 m3/h
Unit Description
The Wizard range of Air-Handling Units incorporate the entire design experience of
Climaveneta in order to fully satisfy all market requirements in the various sectors of
application. Tailored though massproduced industrial products, these high quality and reliable
units guarantee total safety.Traditional sectors: residential building, airports, banks, shops,
hotels, museums, theatres, cinemas, auditoriums, television studios, libraries and data
processing centres. Specific sectors: pharmaceutical, food, hospital, electronic, maritime
applications and temperature- or contamination-controlled production processes.

Commands
AHU3000
The AHU3000 controller is featured as option for the air handling units. It offers functions and regulations able to satisfy the
numerous combinations possible with these units. Furthermore this option enhances and simplifies the units commissioning,
allowing also the interfacing towards other resources and devices. The keypad features aesthetic design, easy-to-use
interface, smart LCD display. The regulation integrates numerous characteristics, depending on the units configuration and
selected options: command of the dampers and of the free-cooling; regulation of the resources for heating, cooling as well
as humidity and air quality; regulation and control of supply- and return fans. The diagnostics includes a complete alarm
management, with the the “black-box” and alarm logging functions for enhanced analysis of the unit operation. Supervision
can be easily developed via proprietary devices or the most common protocols as ModBus, Echelon LonWorks. Compatibility
with the remote keyboard managing up to 10 units. Availability of an internal real time clock for operation scheduling (4-day
profiles with 10 hour belts).

334
LEAKAGE CONTROLLER PLUG FAN CENTRIFUGAL RE-HEATING HUMIDIFICATION HEATING COOLING

WIZARD numerous executions available:

335
OTH
336
HER other

other

337
other

BRAT-MC 0011÷0121
Versions
B base version
SL super-low noise version

Features
Coil protection grid for models 0011÷0061.
Structure and base in hot-dip galvanised steel with
epoxy powder paint finish.
External access to control with anti-tamper device.
Finned coils made with copper pipes and aluminium fins
with large exchange surface area, tested for leaks with
dried air at 30 bar.
User interface with display.
Phase sequence controller for models 0071÷0121

Condensing unit Main accessories


UÊRubber anti-vibration mounting kit
4,9 - 32,9 kW UÊCoil protection grid for models 0071÷0121
UÊExternal main switch kit
UÊHSW10 remote keyboard
Unit Description
Outdoor split-system unit working with R410A refrigerant for connection with direct
expansion coils or remote exchangers, with hermetic rotary scroll compressor and
axial-flow fans. External panels and basement and base in galvanised sheet steel with
paint finish.

338
r HFC
R-410A
AXIAL SCROLL COOLING

BRAT-MC / B
Models 0011 0021 0025 0031 0041 0021 0025 0031
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 5,6 6,6 7,5 9,6 12,7 6,1 7,5 9,3
Total absorbed power (1) kW 1,9 2,2 2,5 3,4 4,1 2,0 2,4 3,2
Absorbed current A 9,2 9,8 12,4 15,6 18,7 4,2 4,4 5,9
Operational weight kg 80 85 100 105 125 85 100 105
No. fans N. 1 1 1 1 2 1 1 1
Airflow m3/h 2400 3500 3500 4200 6800 3500 3500 4200
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A
Sound pressure level (2) dB(A) 51 52 52 52 54 52 52 52
Sound power dB(A) 65 66 66 66 69 66 66 66
Electrical power supply V-Ph~Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 900 900 900 900 900
H mm 640 640 940 940 1240 640 940 940
P mm 370 370 370 370 370 370 370 370

Models 0041 0051 0061 0071 0091 0101 0121


COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 12,7 14,3 16,5 20,8 23,5 29,5 35,8
Total absorbed power (1) kW 4,3 4,7 5,3 6,9 7,9 8,4 11,4
Absorbed current A 8,4 9,0 9,7 14,6 15,8 21,7 24,6
Operational weight kg 125 145 155 245 250 320 325
No. fans N. 2 2 2 1 1 2 2
Airflow m3/h 6800 6800 6400 9800 9800 14000 14000
Compressor type SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A R410A R410A R410A
Sound pressure level (2) dB(A) 54 54 54 61 61 63 63
Sound power dB(A) 69 69 69 76 76 79 79
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 900 900 900 1450 1450 1450 1450
H mm 1240 1240 1390 1200 1200 1700 1700
P mm 370 370 420 550 550 550 550

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Noise level measured at 1 m in open field conditions

BRAT-MC / SL
Models 0071 0091 0101 0121
COOLING ONLY VERSION
Nominal Cooling capacity (1) kW 20,1 22,7 27,8 33,4
Total absorbed power (1) kW 6,9 8,0 8,8 11,8
Absorbed current A 12,4 13,6 18,6 21,5
Operational weight kg 245 250 320 325
No. fans N. 2 2 3 3
Airflow m3/h 7000 7000 10500 10500
Compressor type SCROLL SCROLL SCROLL SCROLL
Refrigerant R410A R410A R410A R410A
Sound pressure level (2) dB(A) 59 59 60 60
Sound power dB(A) 74 74 76 76
Electrical power supply V-Ph~Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz 400V-3N~50Hz
DIMENSION
L mm 1450 1450 1450 1450
H mm 1200 1200 1700 1700
P mm 550 550 550 550

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C..
2 Noise level measured at 1 m in open field conditions

Dimension

H
H H

P
P
P
L L L

339
other

HCAT 0152÷0604
Versions
B base version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Features
TOTAL VERSATILITY
Condensing units with scroll compressors in 4 versions,
designed to satisfy all service system and application
requirements.
CONTINUAL FAN SPEED CONTROL
The standard bi-compressor type HCAT units come
fitted with continual fan speed control to guarantee more
flexibility and adaptability
INTEGRAL SAFETY DEVICES
Standard units are all fitted with high and low pressure
switches, high-pressure safety valve and magnetothermal
circuit breakers on loads (bi-compressor unit only)

Condensing unit

38 - 160 kW
Unit Description
Outdoor split-system unit for connection with direct expansion coils or remote exchangers,
with hermetic rotary scroll compressors, axial-flow fans, compressor inlet and outlet valves
with servicing plugs and liquid tap. External panels in Peraluman and base in galvanised
sheet steel with paint finish. Refrigerant R407C, units with two and four-compressors, two
refrigerant circuits.

340
r HFC
R-407C
AXIAL SCROLL COOLING

HCAT / B
Models 0152 0182 0202 0252 0302 0412 0512 0524 0604
COOLING
Cooling capacity (1) kW 37,7 47,0 54,7 66,5 79,8 112 139 141 160
Total power input (1) kW 14,5 17,9 20,3 25,3 29,6 39,4 47,8 55,6 64,7
COMPRESSORS
No. Compressors/No. Circuits N. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 78 79 79 81 81 85 85 94 94
Sound pressure (3) dB(A) 46 47 47 49 49 53 53 62 62
SIZE
A mm 1695 2195 2195 2745 2745 3245 3245 3110 3110
B mm 1120 1120 1120 1120 1120 1120 1120 2220 2220
H mm 1420 1420 1420 1420 1420 1620 1620 1700 1700
Operating weight kg 510 570 600 675 775 910 980 1520 1600

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

HCAT / HT
Models 0524 0604
COOLING
Cooling capacity (1) kW 146 170
Total power input (1) kW 53,3 60,3
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 94 94
Sound pressure (3) dB(A) 62 62
SIZE
A mm 3110 3110
B mm 2220 2220
H mm 1700 2150
Operating weight kg 1620 1700

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

HCAT / LN
Models 0524 0604
COOLING
Cooling capacity (1) kW 134 152
Total power input (1) kW 54,6 64,5
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 86 86
Sound pressure (3) dB(A) 54 54
SIZE
A mm 3110 3110
B mm 2220 2220
H mm 1700 1700
Operating weight kg 1520 1600

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

341
HCAT / SL
Models 0524 0604
COOLING
Cooling capacity (1) kW 132 152
Total power input (1) kW 54,1 63,3
COMPRESSORS
No. Compressors/No. Circuits N. 4/2 4/2
NOISE LEVELS
Sound power (2) dB(A) 79 79
Sound pressure (3) dB(A) 47 47
SIZE
A mm 3110 3110
B mm 2220 2220
H mm 1700 2150
Operating weight kg 1620 1700

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


0524-0604
Switchboard side mm 600
Switchboard opposite side mm 600
Condensation coil side mm 1000

A
B

342
343
other

MCAT 0501÷1422
Versions
B base version
HT high efficiency, high outdoor temperature
version
LN low noise version
SL super-low noise version

Features
TOTAL VERSATILITY
Condensing units with scroll compressors in 4 versions,
designed to satisfy all service system and application
requirements.
SEMI-HERMETIC RECIPROCATING COMPRESSORS
The MCAT units are fitted with semi-hermetic
reciprocating compressors with the possibility of extra
capacity control step
INCORPORATED LIQUID RECEIVER
Standard units are all fitted with liquid receiver to ensure
best operation of the condensing section

Condensing unit

119 - 325 kW
Unit Description
Outdoor split-system unit for connection with direct expansion coils or remote exchangers.
Semi-hermetic reciprocating compressors, axial-flow fans, liquid receiver, compressor inlet
and outlet valves with servicing plugs and liquid tap. External panels in Peraluman and base
in galvanised sheet steel with paint finish. Refrigerant R407C, units with 1 or 2 compressors,
single or double circuits.

344
r HFC
R-407C
AXIAL RECIPROCATING COOLING

MCAT / B
Models 0501 0601 0502 0602 0702 0802 0822 1002 1202 1222 1422
COOLING
Cooling capacity (1) kW 119 141 115 134 160 188 203 236 282 297 325
Total power input (1) kW 46,7 55,9 42,8 51,2 68,2 81,0 80,3 93,9 112 * *
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) * * * * * * * * * * *
Sound pressure (3) dB(A) * * * * * * * * * * *
SIZE
A mm 3110 3110 3110 3110 3110 3110 3110 3110 4110 * *
B mm 2220 2220 2220 2220 2220 2220 2220 2220 2220 * *
H mm 1540 1540 1540 1540 1540 1540 1990 1990 1990 * *
Operating weight kg 1260 1310 1350 1420 1500 1610 1690 1870 2060 * *
Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

MCAT / HT
Models 0501 0601 0502 0602 0702 0802 0822 1002 1202 1222 1422
COOLING
Cooling capacity (1) kW 127 149 122 143 174 211 223 256 305 321 351
Total power input (1) kW 46,6 55,5 43,2 51,5 63,9 76,5 77,3 89,5 109
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) * * * * * * * * *
Sound pressure (3) dB(A) * * * * * * * * *
SIZE
A mm 3110 3110 3110 3110 3110 4110 4110 4110 5110
B mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H mm 1540 1540 1540 1540 1990 1990 1990 1990 1990
Operating weight kg 1330 1390 1430 1500 1640 1880 1890 2100 2340
Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

MCAT / LN
Models 0501 0601 0502 0602 0702 0802 0822 1002 1202 1222 1422
COOLING
Cooling capacity (1) kW 115 135 111 129 154 179 195 226 271 285 312
Total power input (1) kW 48,0 57,7 43,9 52,6 70,2 83,7 82,5 97,4 115
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) * * * * * * * * *
Sound pressure (3) dB(A) * * * * * * * * *
SIZE
A mm 3110 3110 3110 3110 3110 3110 3110 3110 4110
B mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H mm 1540 1540 1540 1540 1540 1540 1990 1990 1990
Operating weight kg 1260 1310 1350 1420 1500 1610 1690 1870 2060
Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

345
MCAT / SL
Models 0501 0601 0502 0602 0702 0802 0822 1002 1202 1222 1422
COOLING
Cooling capacity (1) kW 114 140 110 129 154 187 203 230 280 295 323
Total power input (1) kW 49,0 56,7 44,9 53,3 67,9 80,9 79,9 95,4 113
COMPRESSORS
No. Compressors/No. Circuits N. 1/1 1/1 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
NOISE LEVELS
Sound power (2) dB(A) * * * * * * * * *
Sound pressure (3) dB(A) * * * * * * * * *
SIZE
A mm 3110 3110 3110 3110 4110 4110 4110 4110 5110
B mm 2220 2220 2220 2220 2220 2220 2220 2220 2220
H mm 1540 1990 1540 1990 1990 1990 1990 1990 1990
Operating weight kg 1370 1450 1460 1560 1780 1880 1890 2100 2340

Note:
1 Saturated intake temperature = 5°C; Condenser air (in) = 35°C.
2 Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units; in compliance with ISO 3744 for non-certified units.
3 Average sound pressure level, at 10m distance, unit in a free field on a reflective surface; non-binding value obtained from the sound power level.

Minimum clearance required


0501-1422
Switchboard side mm 1500
Switchboard opposite side mm 1100
Condensation coil side mm 2000

A
B

346
347
altro

NCE 118A÷428C
Versioni
B base version
LN base version
SL super-low noise version

Remote condenser with axial fans

Unit Description
Remote condensers with axial-type fans for outdoor installation. Installation may be vertical
with a horizontal air outflow or, using special brackets, horizontal with an upward air
outflow. The very low noise, adjustable-speed fans are excellent for use for both industrial
and commercial applications.

348
r HFC
R-410A
AXIAL

NCE/B
Models 118A 218A 318A 328A 118B 218B 318B 328B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 55 110 160 301 68 135 197 389
Total power input (1) kW 11,7 23 38 77,6 15,8 30,1 42,9 87,6
VENTILATION
Air flow m3/h 21200 42400 63600 123600 19600 39000 58800 114000
Sound power (2) dB(A) 81 84 86 89 81 84 86 89
SIZE
L (3) mm 1880 3230 3230 5930 1880 3230 4580 4580
P (3) mm 800 800 800 800 800 800 800 800
H (3) mm 1370 1370 1370 1370 1370 1370 1370 1370
Weight kg 145 279 413 680 157 302 447 742

Models 418B 428B 118C 218C 318C 328C 418C 428C


NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 270 511 75 150 228 430 300 566
Total power input (1) kW 60,2 110 18,3 33,9 48,1 97,8 67,9 123
VENTILATION
Air flow m3/h 78400 152000 18400 36800 55200 106200 73600 141600
Sound power (2) dB(A) 86 90 81 84 86 89 86 90
SIZE
L (3) mm 4580 5930 1880 3230 4580 4580 5930 5930
P (3) mm 800 800 800 800 800 800 800 800
H (3) mm 1370 1370 1370 1370 1370 1370 1370 1370
Weight kg 592 982 168 324 481 804 637 1065

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

NCE/LN
Models 118A 218A 318A 328A 118B 218B 318B 328B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 49 97 141 264 58 116 169 331
Total power input (1) kW 12,2 23,9 39,5 81,2 16,7 31,6 44,8 50,5
VENTILATION
Air flow m3/h 17000 34000 51000 97800 15500 31000 46500 88800
Sound power (2) dB(A) 75 78 80 83 75 78 80 83
SIZE
L (3) mm 1880 3230 4580 4580 1880 3230 4580 4580
P (3) mm 800 800 800 800 800 800 800 800
H (3) mm 1370 1370 1370 1370 1370 1370 1370 1370
Weight kg 145 279 413 680 157 302 447 742

Models 418B 428B 118C 218C 318C 328C 418C 428C


NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 169 435 63 125 191 354 191 466
Total power input (1) kW 49,7 115 19,5 35,9 50,9 105 57,6 130
VENTILATION
Air flow m3/h 46500 118400 14400 28800 43200 81000 43200 108000
Sound power (2) dB(A) 80 84 75 78 80 83 80 84
SIZE
L (3) mm 4580 5930 1880 4580 4580 5930 5930 5930
P (3) mm 800 800 800 800 800 800 800 800
H (3) mm 1370 1370 1370 1370 1370 1370 1370 1370
Weight kg 447 982 168 324 481 804 481 1065

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

349
NCE/SL
Models 216A 218A 316A 318A 328A 418A 428A 216B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 45 79 67 115 215 158 295 49
Total power input (1) kW 12,6 25,5 15,8 31,6 64,7 46 94,2 14,3
VENTILATION
Air flow m3/h 11600 24400 17400 36600 69600 48800 92800 10400
Sound power (2) dB(A) 68 71 70 73 76 74 77 68
SIZE
L (3) mm 2630 3230 3770 4580 4580 5930 4580 2630
P (3) mm 600 600 600 600 600 600 600 600
H (3) mm 1230 1230 1230 1230 1230 1230 1230 1230
Weight kg 150 279 221 413 680 547 900 166

Models 318B 328B 418B 428B 528B 218C 328C 418C


NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 133 259 182 340 430 95 273 190
Total power input (1) kW 40,4 71 51,7 106 115 28,9 80,5 57,6
VENTILATION
Air flow m3/h 33000 62400 44000 83200 104000 20200 57600 40400
Sound power (2) dB(A) 73 76 74 77 78 71 76 74
SIZE
L (3) mm 4580 4580 5930 4580 7280 3230 4580 5930
P (3) mm 600 600 600 600 600 600 600 600
H (3) mm 1230 1230 1230 1230 1230 1230 1230 1230
Weight kg 447 742 592 982 1222 324 804 637

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

350
351
altro

FCE 218A÷828C
Versioni
B base version
LN base version
SL super-low noise version

Remote condenser with axial fans

75,8 - 1088 kW
Unit Description
Remote condensers with axial-type fans for outdoor installation. Installation may be vertical
with a horizontal air outflow or, using special brackets, horizontal with an upward air
outflow. The very low noise, adjustable-speed fans are excellent for use for both industrial
and commercial applications.

352
r HFC
R-134a
AXIAL

FCE/B
Models 218A 228A 218B 228B 318B 328B 428B 518B 528B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 78,8 150 98,1 182 123 237 386 259 894
Total power input (1) kW 22,9 42,7 28 48,6 30,9 61,5 103 70,8 231
VENTILATION
Air flow m3/h 42400 82400 39200 76000 58800 114000 152000 98000 190000
Sound power (2) dB(A) 84 87 84 87 86 89 90 88 91
SIZE
L (3) mm 3230 3230 3230 3230 4580 4580 5930 7280 7280
P (3) mm 800 800 800 800 800 800 800 800 800
H (3) mm 1370 2390 1370 2390 1370 2390 2390 1370 2390
Weight kg 279 462 302 502 447 742 982 737 1222

Models 628B 828B 228C 328C 418C 428C 518C 528C 628C
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 534 755 203 329 219 440 293 506 572
Total power input (1) kW 137 204 56,2 87 59,4 121 78,4 130 140
VENTILATION
Air flow m3/h 228000 236800 70800 106200 73600 141600 92000 177000 212400
Sound power (2) dB(A) 91 94 87 89 87 90 88 91 92
SIZE
L (3) mm 8630 11330 3230 4580 5930 5930 7280 7280 8630
P (3) mm 800 800 800 800 800 800 800 800 800
H (3) mm 2390 2390 2390 2390 1370 2390 1370 2390 2390
Weight kg 1461 1942 543 804 637 1065 794 1325 1585

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

FCE/LN
Models 218A 228A 328A 218B 228B 318B 328B 428B 518B 528B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 77,1 147 220 95,3 177 120 265 374 252 436
Total power input (1) kW 23,6 44,2 69,3 29,2 50,6 32 78,5 107 74,3 121
VENTILATION
Air flow m3/h 34000 65200 97800 31000 59200 46500 88800 118400 77500 148000
Sound power (2) dB(A) 78 81 83 78 81 80 83 84 82 85
SIZE
L (3) mm 3230 3230 4580 3230 3230 4580 4580 5930 7280 7280
P (3) mm 800 800 800 800 800 800 800 800 800 800
H (3) mm 1370 2390 2390 1370 2390 1370 2390 2390 1370 2390
Weight kg 279 462 680 302 502 447 742 982 737 1222

Models 628B 828B 228C 328C 418C 428C 518C 528C 628C
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 521 732 197 318 214 423 283 489 556
Total power input (1) kW 143 213 59 92,3 62,9 129 82,5 137 147
VENTILATION
Air flow m3/h 177600 236800 54000 81000 57600 108000 72000 135000 162000
Sound power (2) dB(A) 86 88 81 83 81 84 82 85 86
SIZE
L (3) mm 8630 11330 3230 4580 5930 5930 7280 7280 8630
P (3) mm 800 800 800 800 800 800 800 800 800
H (3) mm 2390 2390 2390 2390 1370 2390 1370 2390 2390
Weight kg 1461 1942 543 804 637 1065 794 1325 1585

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

353
FCE/SL
Models 318A 416A 418A 428A 318B 328B 418B 428B 518B 528B 628B
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 94,8 75,8 131 252 114 215 148 287 196 274 433
Total power input (1) kW 29,4 24,2 39,4 74,3 34,7 62,5 43,6 80,7 59,2 107 124
VENTILATION
Air flow m3/h 36600 23200 48800 92800 33000 82200 44000 83200 55000 104000 124800
Sound power (2) dB(A) 73 71 74 77 73 76 74 77 75 78 79
SIZE
L (3) mm 4580 4910 5930 5930 4580 4580 5930 5930 7280 7280 8630
P (3) mm 800 600 800 800 800 800 800 800 800 800 800
H (3) mm 1370 1230 1370 2390 1370 2390 1370 2390 1370 2390 2390
Weight kg 413 292 547 900 447 742 592 982 737 1222 1461

Models 728B 828B 228C 328C 418C 428C 528C 628C 728C 828C
NOMINAL CHARACTERISTICS
Nominal capacity (1) kW 511 575 156 225 173 321 396 481 544 647
Total power input (1) kW 147 162 48 66,9 52,2 91 119 140 152 183
VENTILATION
Air flow m3/h 145600 1664000 38400 76200 40400 76800 96000 115200 134400 153600
Sound power (2) dB(A) 79 80 74 76 74 77 78 79 79 80
SIZE
L (3) mm 9980 11330 3230 4580 5930 5930 7280 8630 9980 11330
P (3) mm 800 800 800 800 800 800 800 800 800 800
H (3) mm 2390 2390 2390 2390 1370 2390 2390 2390 2390 2390
Weight kg 1702 1942 543 804 637 1065 1325 1585 1845 2106

Note:
1 Outdoor air temperature = 30°C; delta temperature condenser side = 17°C
2 Sound power on the basis of measurements made in compliance with ISO 3744.
3 Without legs kit configuration ; horizontal air flow

354
355

You might also like