Andover Continuum TM

Infinet II
i2810 Series Local Controllers
The i2810 Series controllers are designed for control
of Air Handling Units, Roof Top Units, and other
mechanical plant equipment.
02

Andover Continuum Infinet II


i2810 Series Local Controllers
Features

Choose the i2810 model with the


configuration that matches your application:

• The i2810, designed for stand-alone equipment


control of Roof Top Units, Air Handling Units, or
other packaged mechanical equipment, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus eight program-controlled digital
outputs.
• The i2814, designed for stand-alone equipment
control of Roof Top or Air Handling Units, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus four program-controlled digital
outputs and four analog outputs for direct control
of devices requiring 0-10 volt control signals.
Note: The i2814 is only compatible with Andover
Continuum.

PRODUCT AT A GLANCE Both models feature an additional room sensor input,


which supports Andover Continuum Smart Sensor,
or any standard room temperature sensor. The i2810
• Powerful, Flexible Local Controller for the Series also features universal inputs, a real-time clock,
Most Demanding Applications override switches on all outputs, two-piece removable
• Expandable I/O Meets Additional Point connectors, and the ability to expand the I/O for
Count Needs additional points.
• Non-Volatile Flash Memory Provides Utmost
Reliability — Stores Both Application Program
The i2810 Series features Flash memory, increased
and Operating System
user memory, and a fast (32-bit) processor for faster
scan times, with plenty of memory available for data
• Optional Display/Keypad Provides Easy logging of your critical data.
Operator Interface (Mounted Separately)

• Local, Extended Storage of Log Data The i2810 communicates with the entire Andover
• View and Modify Information with Optional
Continuum Infinet RS-485 field bus (i.e. both
Smart Sensor Display
Andover Infinet and Andover Infinet II controllers)
and is compatible with both the Andover
• Local, On-Board Service Port Continuum CyberStation and Infinity SX 8000 front-
ends. The i2814 is only compatible with Andover
Continuum. Up to 254 Andover Continuum
Infinet devices can be networked to any Andover
Continuum network controller.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-I2810-US.BU.N.EN.11.2011.0.00.CC
03

Andover Continuum Infinet II


i2810 Series Local Controllers
Features (continued)

Dimensional Drawings
Increased Reliability with Flash Memory
The i2810’s non-volatile Flash memory stores your
operating system and application programs, so that
in the event of a power loss, your application will
be restored when power is returned. In addition,
the Flash memory allows for easy upgrades of your 1
operating system via software downloads, eliminating
the need to swap out proms.
2
The i2810 controllers include an on-board battery to
safeguard your runtime data — protecting all point
data and log data from being lost if power is removed.

Inputs
The input configuration on the i2810 Series consists 4
of eight full range, 12-bit universal inputs that accept
voltage (0-10VDC), digital (on/off), counter signals
(up to 4Hz), temperature signals, or supervised
alarm circuits for security applications or broken wire
3
detection. The i2810 Series offers an additional input
to support the Andover Continuum Smart Sensor, or
any standard room temperature sensor.

Outputs
The i2810 contains eight Form C relay outputs,
each rated for 24 VAC/30 VDC, 3 amp, while the
i2814 contains four Form C relay outputs and four
analog outputs (0-10V). Both the relay and analog
outputs have manual override switches, with software
feedback of the switch position.

I/O Expansion
The i2810 contains an I/O expansion port for
the addition of up to two Andover Continuum xP
expansion modules directly on the bottom of the
controller. The xP family of modules includes the
xPUI4, xPDI8, xPDO2, xPDO4, xPAO2, and xPAO4.
In addition to two input/output modules, the I/O bus
supports the xP Local Display Module, which allows
the user to view and change point values.

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-I2810-US.BU.N.EN.11.2011.0.00.CC
AC POWER
24 VAC
30 VA
50/60 HZ 04
1
Andover Continuum Infinet II
i2810 Series Local Controllers
2 N

Features (continued) 3 L +
DC POWER
12-28 VDC
20W
AC POWER
24 VAC
30 VA TD
50/60 HZ
Dimensional
4 1+ Drawings
Software Capabilities 5 - RS-485
The dynamic memory of the i2810 can be allocated 2 N
AC POWER
24 VAC
6 SHLD 30 VA

for any combination of programs, scheduling, 1


50/60 HZ

alarming, and data logging using the powerful 3 L2 N + RD


Andover Continuum Plain English programming +
DC POWER
3 L

language. Our object-oriented Plain English language SERVICE

B
DC POWER
PORT 12-28
12-28 VDC VDC

REV:
20W
with intuitive keywords provides an easy method to 20W
CPU

PLACARD, INPUT,
tailor the controller to meet your exact requirements. 1 PowerTDDrawing

I2814 / I2810

ECO NUMBER:
4 + 45 45
TD

05-1001-223
Programs are entered into the i2810 using the 5 - RS-485
6 SHLD 1 44 1 44
Andover Continuum CyberStation. Programs are then 4 + RD 43 43
stored and executed by the i2810 controllers. 5 - RS-485
SERVICE
PORT
42 42
RESTARTCPU

ECO #11244
6 SHLD 2 41 2 41

ECO NUMBER:
Programming multiple i2810 Series controllers is 40 40
2 Communication

TITLE:
inherently easy with Plain English. A complete copy RD 39 39

P/N:
Drawing
RESTART
of one i2810 controller’s programs can be loaded 3 38 3 38
SERVICE

SCALE:
1 OF 1
FULL
directly into other i2810 controllers without changing PORT
37 37

SCALE:

SHEET:
any point names or programs. CPU 36 36

ECO NUMBER:
UNIVERSAL 4 35 4 35

ADOBE ILLUSTRATOR 10.0

11/3/04
INPUTS
Smart Sensor Interface UNIVERSAL7 RET 34 34

DATE:
8 IN 1
The i2810 provides a built-in connection for Andover INPUTS
9 IN 2

Continuum Smart Sensor. The Smart Sensor 7 RET


10 RET OFF ON

M.ROGERS
1
11 IN 3

8 IN 121 IN 4RESTART
2

provides a 2-character LED display and a 6-button 4


3

5
13 RET
programmable keypad that enables operators and 9 IN 142 IN 5
6
7
8

SOFTWARE:

DRAWN BY:
occupants to change setpoints, balance VAV boxes, 15 IN 6

10 RET16 RETOFF ON
monitor occupancy status, and turn equipment on 17 IN 7
1 33 I 33

SCALE:
11 IN 183 IN 8
and off. An enhanced version of the Smart Sensor is SMART2 5 32 5 V 32
SENSOR3

also available with a 4-digit custom LCD that provides 12 IN 419 SPWR 4 31 GND 31
20 RET
5
the following icons: PM, %, °, Setpoint, Cool, Heat, 13 RET21 IN 9
24VDC
6 30 I 30

CFM, Fan, OA, and SP. 180mA


14 UNIVERSAL
IN 5 EXP PORT PWR
7 6 29 6 V 29
8
INPUTS

SOFTWARE:
28 GND 28
15 IN 6
Local Display 7 RET 27 I 27
16 RET
The local display with keypad (xP-Display) allows for 8 IN 1 7 26 7 V 26
17 IN 7
the addition of a fully programmable local display 9 IN 2 25 GND 25

module that can be mounted within 10 feet (3 meters) 18 IN 8 OFF ON 24 I 24


10 RET SMART
8 23 8 V 23
of the controller. Connected via a ribbon cable, the SENSOR
1
11 IN 3 2 22 GND 22
xP-Display easily allows the Operator Interface to 19 SPWR
3
12 IN 4
be mounted on the door of an enclosure or on a wall 20 RET 4
13 RET
5 i2810 i2814
below or next to the controller. 21 IN 9 6
7
14 IN 5
24VDC 8
SOFTWARE:

180mA
Optional Wireless Andover Continuum Infinet 15 IN 6
The i2810 Series Andover Continuum Infinet EXP PORT PWR
3 16Smart
RET Sensor and 4 Outputs Drawing
controllers can also communicate using a wireless Inputs Drawing
17 IN 7
mesh network. Simply plug Andover Continuum
18 IN 8
Wireless Adapters into the service ports of these SMART
controllers with wireless compatible firmware to create SENSOR
a wireless mesh network that sends and receives 19 SPWR

Andover Continuum Infinet messages. 20 RET


21 IN 9
24VDC
180mA

Schneider Electric One High Street, North Andover, MA 01845 USA EXP+1
Telephone: PORT
978PWR
975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-I2810-US.BU.N.EN.11.2011.0.00.CC
05

Andover Continuum Infinet II


i2810 Series Local Controllers
Specifications

i2810 Series Local Controllers


Electrical Communications Inputs/Outputs
Power Communications Interface Inputs
24VAC, 12-24VDC - auto sensing, Through Andover Andover Continuum 8 Universal inputs: Voltage (0-10 VDC);
+10% -15%, 50/60 Hz Infinet RS-485 field bus to network Temperature -30°F to 230°F (-34°C to 110°C),
Power Consumption controller Digital (on/off), Counter (up to 4Hz at 50%
30 VA Communications Speed duty cycle, 125 ms min. pulse width).
Overload Protection 1200 to 19.2K baud Supervised Alarm (single or double resistor).
Fused with 3 amp fuse. Bus Length Current input (0 - 20 mA) using external 500
MOV protected 4,000 ft. (1,220m) standard for ohm resistor
Real-Time Clock Andover Continuum Infinet, i2 Infilink 1 Smart Sensor Temperature Input (32°F to
Battery-backed real-time clock module allows extension to longer distances 105°F) (0°C to 41°C)
and is required after every group of Input Voltage Range
Mechanical 32 units on the network. 0-10 volts DC
Operating Environment Bus Media Input Impedance
32°–120°F (0–49°C), Andover Continuum Infinet: twisted, 30.1K ohm to 10V or 5M ohm with
10–95% RH (non-condensing) shielded pair, low capacitance cable pull-up resistor disabled
Size RS-485 port for implementing Wireless Input Resolution
9.51˝ H x 7.26˝ W x 2.14˝ D Infinet II connection, including: 2.5 mV
(241 H x 184 W x 54 D) mm Standard service port, four-position Input Accuracy
Weight shrouded connector ±7.5mV (±0.25°C from -23°C to
1.65 lbs. (0.75 kg) Comm. Error Checking +54°C) or (±0.46°F from -10°F to +130°F)
Enclosure Type International Standard CRC 16
UL Open class, IP 10. Compatibility Digital Outputs
Flammability rating of UL94-5V Andover Continuum Cyberstation
8 single pole single throw (SPST) Form C
Mounting and Infinity SX 8000 systems
relays (4 Form C on i2814)
Panel mount Note: The i2814 is compatible with
(Any two consecutive Form C outputs can
Andover Continuum software version 1.5
be configured as one Form K Tri-state)
Battery (or later).
Output Rating
Battery Backup Maximum 3A, 24VAC/30VDC,
Replaceable, non-rechargeable, ±1500V transients (Tested according
lithium battery. Provides 5 years to EN61000-4-4)
typical accumulated power failure Output Accuracy
backup of RAM memory 0.1 sec. for pulse width modulation

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings

SDS-I2810-US.BU.N.EN.11.2011.0.00.CC
06

Andover Continuum Infinet II


i2810 Series Local Controllers
Specifications (continued)

i2810 Series Local Controllers


Analog Outputs Connections General
4 analog outputs (i2814 only) Power Memory
Output Rating 3-position fixed screw terminal connector 256K SRAM, 1MB FLASH
0-10V or 0-20mA Inputs Processor
For 0-10V: 5mA maximum source, Removable two-piece terminal strip Motorola 32-Bit Coldfire
1mA maximum sink Outputs
2K ohm minimum impedance (sourcing only), Removable two-piece terminal strip Agency Listings
For 0 – 20mA: 750 ohm maximum Smart Sensor UL/CUL 916, FCC CFR 47 Part 15,
+/-1000V transients (Tested according to Removable two-piece terminal strip ICES-003, EN55022, ASIN2S 3548,
EN61000-4-4). Fuse-protected only Communications Class A, CE
on the i2814. Removable 3-position terminal
Output Resolution connector Models
0.1V for 0-10V, 0.1mA for 0-20mA Expansion Port i2810
Output Overrides 6-position shrouded connector Infinet II i2810 Local Controller
Each output is equipped with a manual Service Port i2810-WL
override switch. Software feedback 4-position shrouded connector Wireless Infinet II i2810 Local Controller
of the switch position is provided, i2814
for display and alarming User LEDs/Switches Infinet II i2814 Local Controller
Expansion Bus Status Indicator LEDs i2814-WL
Interfaces to optional xP I/O CPU CPU Active Wireless Infinet II i2814 Local Controller
Expansion Modules TD Transmit Data
RD Receive Data
Output Output Status (per
output) (Digital only)
EXPANSION
PORT PWR Power Status
Switches
RESET
Input Pull-up Resistor Switch (per input)
Individual Output Override Switches