TN GENERAL NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE NOTED.
2. ALL ELEVATIONS ARE REFERENCED TO THE PROJECT DATUM AND ARE IN METRES.
CL
CL CL
3. UNLESS OTHERWISE NOTED ON THE DWGS, DIMENSIONS ARE GIVEN IN MM & LEVELS IN M.
M CL CL 4. LENGTHS GIVEN IN THE BBS SCHEDULES ARE IN MM.
5. UNLESS OTHERWISE INDICATED, CONCRETE GRADE (CYLINDER STRENGTH AT 28 DAYS)
SHOULD BE:
(i). FOR PILE CAP CONCRETE GRADE fc' 45MPa
(ii). FOR COLUMN & WALL CONCRETE GRADE fc' 45MPa
6. DEFORMED HIGH TENSILE STEEL REINFORCEMENT HAVING A MIN YIELD STRENGTH OF
420N/MM2 SHALL BE USED & CONFORMING TO ASTM A615M STANDARDS.
7. THE CONCRETE PROTECTIVE COVER FOR REINFORCEMENT SHALL BE AS FOLLOW:
DECK TOP - 75mm
DECK EXTERNAL, SIDES END, SOFFITS - 50mm
PIERS, COLUMNS, ABUTMENT WALLS ALL FACES - 75mm
PILE CAP
BOTTOM - 125mm
TOP & SIDE - 75mm
8. WHEN REINFORCEMENT IS SHOWN ON PLAN:
(i). DASHED LINES DENOTE TOP REINFORCEMENT
(ii). CONTINUOUS LINES DENOTE BOTTOM REINFORCEMENT
9. LAP LENGTHS OF REINFORCEMENT SHALL BE AS SHOWN ON DRAWINGS
(REFER THE LAP TABLE)
10. ALL STRUCTURE ARE DESIGNED 2 HOURS FIRE RATED
11. BAR MARKS TO BE READ AS:
REBAR DETAIL
(TYP.)
1020
2x1 T20 01 300 B1
750
(TYP.)
BAR PLACING NOTES
1500
1375
1020
1375
1500
1375
19-T20-(01)-75-LINKS 19-T20-(01)-75-LINKS SPACING OF BARS
750
1500
1350 1350 19-T20-(01)-75-LINKS BAR MARK
1350 BAR TYPE & DIAMETER (mm)
NUMBER OF BARS
DETAIL-A 1375 MULTIPLIERS
DETAIL-A
1500
1375
DETAIL-A 31-T20-(01)-75-LINKS 31-T20-(01)-75-LINKS
(TYP)
1350
1550
(TYP)
1375 1375 1350 LEGEND :
1550
1500
(TYP.)
(TYP.)
31-T20-(01)-100-LINKS 32-T20-(01)-100-LINKS B3 - BOTTOM THIRD LAYER
1550
1550
450
2x20-T32-(11)-V ALT. (TYP.) - TYPICAL.
450
(TYP.)
14-T32-(08)-V 4025 2x20-T32-(13)-V ALT.
1550
1350 1350
2335 V - VERTICAL T1 - TOP FIRST LAYER
14-T32-(03)-V 4300 14-T32-(04)-V 4425 13-T32-(09)-V ALT. 2475 2785
H - HORIZONTAL T2 - TOP SECOND LAYER
13-T32-(02)-V ALT. 2750 13-T32-(05)-V ALT. 2875
100
FF - FAR FACE T3 - TOP THIRD LAYER
5212 ~ 5272
6098 ~ 6151
5685 ~ 5738
SF - SIDE FACE
100
100
NF - NEAR FACE
5997 ~ 6080
300
1375
300
14-T32-(09)-V 2475 1375
5685 ~ 5738
18-T20-(01)-100-LINKS EF - EACH FACE SB - SPACER BARS
14-T32-(02)-V 2750 14-T32-(05)-V 2875 13-T32-(08)-V ALT. 4025 23-T20-(01)-100-LINKS ES - EACH SIDE ABR - ALTERNATE BAR REVERSED
1375 1350 1350
13-T32-(03)-V ALT. 4300 13-T32-(04)-V ALT. 4425 28-T20-(01)-100-LINKS B1 - BOTTOM FIRST LAYER ALT. - ALTERNATE
(TYP.)
1550
1350 B2 - BOTTOM SECOND LAYER TH. - THREADED
450
75 COVER
(TYP.)
(TYP.)
450
SI. PIER COLUMN CONCRETE
1550
1550
2x20-T32-(10)-V EX. CP.- EXTENDED THREAD WITH COUPLER
(TYP)
REINF. TYPE 2x20-T32-(12)-V
1550
(TYP)
(TYP.) 4185
1550
4635
NO NAME TYPE
12. TYPE OF CEMENT FOR COLUMN:SRC
1 EB-C14 C2 TYPE 1
2 EB-C29 C2 TYPE 1
SI. PIER COLUMN CONCRETE
REINF. TYPE PIER
Abbreviation (SIM.) should be
NO NAME TYPE PIER
SI. CONCRETE SI. CONCRETE added to avoid any
3 EB-C41 C2 TYPE 1 COLUMN REINF. TYPE COLUMN REINF. TYPE
1 EB-C12 C2 TYPE 1 NO TYPE NO TYPE PIER
4 EB-C52 C2 TYPE 1
NAME NAME SI.
COLUMN
CONCRETE
REINF. TYPE
misunderstanding
2 EB-C13 C2 TYPE 1 1 EB-C259 C2 TYPE 1 1 EB-C265 C1 TYPE 2 NO TYPE
1500
NAME SHEET NOTES
1500
5 EB-C216 C2 TYPE 1
1500
1500
1500
3 EB-C27 C2 TYPE 1 2 EB-C260 C2 TYPE 1 2 EB-C266 C1 TYPE 2 1 EB-C263 C1 TYPE 2
6 EB-C237 C2 TYPE 1 4 EB-C28 C2 TYPE 1 2 EB-C264 C1 TYPE 2
7 EB-C238 C2 TYPE 1 5 EB-C39 C2 TYPE 1
6 EB-C40 C2 TYPE 1
150 KICKER
8 EB-C239 C2 TYPE 1
(TYP.)
7 EB-C50 C2 TYPE 1
8 EB-C51 C2 TYPE 1
FOR REINF. DETAILS REFER DRG NO: 9 EB-C214 C2 TYPE 1
MI-PB-B1-C01.00-SR-02-01011-07-00 & 01021-07-00
10 EB-C215 C2 TYPE 1
11 EB-C236 C2 TYPE 1
COLUMN TYPE-1-1 COLUMN TYPE-1-2 COLUMN TYPE-1-3 COLUMN TYPE-2-1 COLUMN TYPE-2-2
SCALE 1:50 (2 Nos.)
SCALE 1:50 (8 Nos.) SCALE 1:50 (11 Nos.) SCALE 1:50 (2 Nos.) SCALE 1:50 (2 Nos.)
450
450
450 450
450 450
450 450
2x1-T25-(32)-125-T2 ES
2x1-T25-(24)-125-T1 ES 3100
3040
2x1-T25-(31)-125-T2 ES
450
450
2x1-T25-(23)-125-T1 ES 2815
2875
CL 2x1-T25-(30)-125-T2 ES
450
450
2015
2x1-T25-(22)-125-T1 ES 2075
2x1-T25-(29)-1000-SPACER BARS ES 975
CL CL
80
13502
1350
2x14-T20-(17)-75-LINKS 280
2x3-T20-(18)(a-c)-150-LINKS ES
REMOVE 40 1310
1325
1325
11709
1170
1375
1375
2120 2120
1930
~1335
1475
1335
2x10-T20-(20)(a-j)-75-U BARS ES
420
420
285
285
~2020
CL BAR BENDING SCHEDULE DOC. NO:
2x2x10-T20-(36)(a-j)-75-U BARS ES 1565
MI-PB-B1-C01.00-SC-02-60011-07-00
1700
1700
(TYP.)
2x2x1-T20-(19)-150-U BARS T&B ES
1020
1310
750
1850
1850
380
2x5-T20-(37)(a-e)-75-U BARS ES
185
185
1375 1350
1500
1455
31-T20-(01)-75-LINKS 00 19-12-2019 ISSUED FOR CONSTRUCTION
1100
1350
2x2x9-T20-(38)(a-i)-75-U BARS ES 285 285 Rev # Rev Date Revision Description
1500
1275 1535
00 19-12-2019 PB -
1375
75 COVER
4-T20-(01)-75-LINKS DETAIL-A Current Rev # and Date Orig. Signature ABV Approval Signature
1350 General Notes :
(TYP)
1550
425
2x2x4-T32-(39)-150- V ES 1905 THE CONSULTANT RETAINS COPYRIGHT OF ALL DOCUMENTS PREPARED BY HIM.
(TYP)
1750
1550
340
450
2x20-T32-(34)-V ALT. 2x20-T32-(06)-V ALT. 2725 ALL RELEVANT DETAILS, LEVELS AND DIMENSIONS ARE TO BE CHECKED ON SITE
3235 PRIOR TO COMMENCEMENT OF WORK.
5662 ~ 5719
ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT. THE ARCHITECT ACCEPTS NO RESPONSIBILITY FOR ERRORS
6031 ~ 6150
100
RESULTING FROM MISINTERPRETATION OF THE DRAWINGS.
300
1375
ALL WORK TO BE CARRIED OUT STRICTLY IN ACCORDANCE WITH NATIONAL
27-T20-(01)-100-LINKS BUILDING
1375
1350
31-T20-(01)-100-LINKS REGULATIONS AND LOCAL AUTHORITY REGULATIONS. ALL DIMENSIONS ARE IN
1350 MILLIMETRES U.N.O.
31-T20-(01)-100-LINKS
450
DO NOT SCALE THIS DRAWING.
2x20-T32-(35)-V 2x20-T32-(07)-V
(TYP)
(TYP)
USE FIGURED DIMENSIONS ONLY.
1550
1550
5085 4375
1500
1500
3 EB-C85 C2 TYPE 2
4 EB-C92 C2 TYPE 2
2x1-T25-(22)-125-T1 ES
5 EB-C93 C2 TYPE 2
2x1-T25-(23)-125-T1 ES
SECTION 1-1 6 EB-C94 C2 TYPE 2
SCALE 1:25 PIER
SI. CONCRETE 7 EB-C137 C2 TYPE 2
COLUMN REINF. TYPE
NO TYPE
NAME
8 EB-C138 C2 TYPE 2
1 EB-C261 C1 TYPE 2
9 EB-C139 C2 TYPE 2
2 EB-C262 C1 TYPE 2
2x1-T25-(26)-125-T1 ES
10 EB-C146 C2 TYPE 2
Owner :
11 EB-C147 C2 TYPE 2
Kingdom of Saudi Arabia
12 EB-C148 C2 TYPE 2 Ministry of Interior
2x1-T25-(24)-125-T1 ES
2x20-T32-(10)-V COLUMN TYPE-2-3 15 EB-C175 C2 TYPE 2
SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH
2x20-T32-(11)-V ALT.
SCALE 1:50 (2 Nos.)
16 EB-C223 C2 TYPE 2
Engineer / Owner's Representative :
COLUMN TYPE-2-4 17 EB-C224 C2 TYPE 2
SCALE 1:50 (18 Nos.)
18 EB-C225 C2 TYPE 2
2x2x1-T20-(19)-150-U BARS T&B ES 2x10-T20-(14)-150-U BARS T&B Al Hudaiba Awards Bldg., 5/F, Unit 510 Block B,
2x2x1-T20-(21)-150-U BARS T&B ES 2x2x1-T20-(19)-150-U BARS T&B ES
1 Mina Rashid/ Jumeirah 1 Road
P O Box 112025 Block B
2x3-T20-(18)(a-c)-150-LINKS ES 2x2x1-T20-(21)-150-U BARS T&B ES
Tel 971 4 350 3800/ 358 6803, Fax 971 4 358 6800
E-mail: pt.dubai@p-t-group.com,Website:www.p-t-group.com
2x3-T20-(18)(a-c)-150-LINKS ES
NOTE:1 Structural Consultant: MEPF Consultant:
ALL VERTICAL BARS TO BE BUNDLED.
2x14-T20-(17)-75-LINKS
2x2x4-T32-(39)-150- V ES NOTE:2
LINK SPACING IN PIER NORMAL CIRCULAR LINKS ARE DETAILED IN PLACE
2x2x4-T32-(39)-150- V ES T20-100-LINKS
HEAD IS 75mm NOT 100mm OF SPIRAL LINKS TO EASE CONSTRUCTION.
2x27-T32-V
NOTE:3 Sub Consultant :
1 THE DIMENSIONS AND LEVELS CAN BE OBTAINED
2x2x4-T32-(39)-150- V ES 1 FROM THE DETAIL DESIGN DRAWINGS.
2x2x4-T32-(39)-150- V ES
2x14-T20-(15)-75-U BARS ES
(JEDDAH HOSPITAL)
SECTION 2-2
SCALE 1:25
1- FOR BAR MARK (18) & (19) & (21) & (39), DWG No.
750
T.O.P (REFER THE LAP TABLE)
(TYP.)
1020
VARIES 10. ALL STRUCTURE ARE DESIGNED 2 HOURS FIRE RATED
750
T.O.P T.O.P 11. BAR MARKS TO BE READ AS:
1375
VARIES VARIES REBAR DETAIL
31-T20-(01)-75-LINKS
1350 2x1 T20 01 300 B1
1375
1500
425
1500
BAR PLACING NOTES
3x20-T32-(20)-V TH. DETAIL-A 3x20-T32-(23)-V TH. 1300 31-T20-(01)-75-LINKS
4502
950 2x20-T32-(18)-V TH.
1350 SPACING OF BARS
1375 DETAIL-A 1375 1375 20-T32-(32)-V TH. 375
1500
1500
DETAIL-A
4502
BAR MARK
1500
20-T20-(01)-75-LINKS 1350
20-T20-(01)-75-LINKS 1350
20-T20-(01)-75-LINKS 1350
BAR TYPE & DIAMETER (mm)
NUMBER OF BARS
MULTIPLIERS
LEGEND :
(TYP.)
(TYP)
(TYP.) - TYPICAL.
1550
1550
2x20-T32-(04)-V 2750
V - VERTICAL
1850
1850
1850
T1 - TOP FIRST LAYER
450
2x20-T32-(26)-V ALT. H - HORIZONTAL T2 - TOP SECOND LAYER
275
3x20-T32-(21)-V TH. ALT. 2800 3x20-T32-(22)-V TH. ALT. 3150 3625 FF - FAR FACE
4504
2x20-T32-(19)-V TH. ALT. T3 - TOP THIRD LAYER
NF - NEAR FACE
6431~6570
225 1375 SF - SIDE FACE
20-T32-(31)-V TH. ALT. EF - EACH FACE
4504
31-T20-(01)-100-LINKS
6377
SB - SPACER BARS
300
300
1350 ES - EACH SIDE
6031
5987
6031~6115
1725
1725 1725 B2 - BOTTOM SECOND LAYER ALT. - ALTERNATE BAR
17-T25-(02)-300-SPACER
2x20-T32-(03)-V ALT. 4300 16-T25-(02)-300-SPACER 17-T25-(02)-300-LINKS 1180 EX. CP.- EXTENDED THREAD WITH COUPLER
1180 1180
450
1375
(SPACER BARS) 2x20-T32-(27)-V 12. TYPE OF CEMENT FOR COLUMN:SRC
(TYP.)
34-T20-(01)-100-LINKS
(TYP)
1550
1550
1550
1550
1550
5475
1375 1375 1375 1350
30-T20-(01)-100-LINKS 30-T20-(01)-100-LINKS 34-T20-(01)-100-LINKS
1350 1350 1350
SHEET NOTES
KICKER
KICKER
KICKER
1500
1500
1500
1500
1500
150
150
150
KICKER
KICKER
FOR REINF. DETAILS REFER DRG NO:
150
150
MI-PB-B1-C01.00-SR-02-01011-07-00 & 01021-07-00 (TYP.)
3250
1200
1550
1200
~
400
400
400
400
2x12-T20-(09)(a-l)-75-U BARS ABR. 5-T25-(07)(a-e)-150-T2 ~
COVER
MI-PB-B1-C01.00-SR-02-60013-07-00 4000 4900
75
2120
400
400
400
400
5-T25-(14)(a-e)-150-T3 ~
3575
1100
2x9-T20-(08)-75-U BARS ABR. 3950 4850 4-T25-(15)-1000-SPACER BARS 1300
1250 00 19-12-2019 ISSUED FOR CONSTRUCTION
935
935
1-T20-(34)-150-LINKS 1250 Rev # Rev Date Revision Description
1125
30-T20-(01)-100-LINKS
845
845
1-T20-(35)-150-LINKS 1125 00 21-03-2019 PB -
1040
1040
1280
1280
2x3-T20-(33)(a-c)-150-LINKS ES ~ THE CONSULTANT RETAINS COPYRIGHT OF ALL DOCUMENTS PREPARED BY HIM.
1 EB-C01 & C02 C1 TYPE 2 1310 1310
ALL RELEVANT DETAILS, LEVELS AND DIMENSIONS ARE TO BE CHECKED ON SITE
2 EB-C05 C1 TYPE 2 2x20-T32-(04)-V PRIOR TO COMMENCEMENT OF WORK.
ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE
210 260 2x20-T32-(03)-V ALT.
1350
1350
1350
1350
3 EB-C08 C1 TYPE 2 14-T20-(17)-75-LINKS ARCHITECT. THE ARCHITECT ACCEPTS NO RESPONSIBILITY FOR ERRORS
14-T20-(16)-75-LINKS 210 975 260 RESULTING FROM MISINTERPRETATION OF THE DRAWINGS.
4 EB-C11 C1 TYPE 2 (TYP.) ALL WORK TO BE CARRIED OUT STRICTLY IN ACCORDANCE WITH NATIONAL
BUILDING
1375
1450
1450
1050
2100
5 EB-C16 C1 TYPE 2 2x2x5-T20-(06)(a-e)-150-U BARS T & B ES ~ REGULATIONS AND LOCAL AUTHORITY REGULATIONS. ALL DIMENSIONS ARE IN
1125 (TYP.,) 1310 1310 MILLIMETRES U.N.O.
845
845
935
1900
1900
(TYP.)
PIER COLUMN CONCRETE 2x11-T20-(05)-150-U BARS T & B
1475
9 EB-C35 C1 TYPE 2 SI. 1310
NO REINF. TYPE
NAME TYPE
(TYP.)
1020
10 EB-C38 C1 TYPE 2
(TYP.)
1020
SECTION 1-1
750
1125
1125
300
SCALE 1:25
300
12 EB-C48 & C49 C1 TYPE 2 2x8-T20-(10)(a-h)-75-U BARS ABR. ~
3 EB-C09 & C10 C1 TYPE 2
13 EB-C61 C1 TYPE 2
1375
1375 14 4 EB-C15 C1 TYPE 2
EB-C65 C1 TYPE 2 31-T20-(01)-75-LINKS
1500
400
18 EB-C82 C1 TYPE 2 8 EB-C33 & C34 C1 TYPE 2
290
1375 1375 2x2x4-T32-(30)-V ES
19 EB-C88 C1 TYPE 2 9 EB-C36 & C37 C1 TYPE 2
35-T20-(01)-100-LINKS 35-T20-(01)-100-LINKS 4865
1350 1350 EB-C42 & C43
20 EB-C91 C1 TYPE 2 10 C1 TYPE 2
(TYP)
(TYP)
1550
450
300
450
2x20-T32-(29)-V 2x20-T32-(24)-V
(TYP)
(TYP)
1550
1550
5825 5950
27 EB-C118 C1 TYPE 2 17 EB-C68 C1 TYPE 2 SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH
1500
KICKER
150
COVER
46 EB-C192 C1 TYPE 2 36 EB-C167 C1 TYPE 2
75
47 EB-C194 C1 TYPE 2 37 EB-C169 C1 TYPE 2
48 EB-C196 C1 TYPE 2 38 EB-C176 & C177 C1 TYPE 2
COLUMN TYPE 2-7 49 EB-C201 C1 TYPE 2 COLUMN TYPE 2-8 39 EB-C179 & C180 C1 TYPE 2
SCALE 1:25 (82 NOS.) 50 EB-C204 C1 TYPE 2 SCALE 1:25 (78 NOS.) 40 EB-C182 & C183 C1 TYPE 2
Sub Consultant :
51 EB-C207 C1 TYPE 2 41 EB-C189 C1 TYPE 2
30-T20-(01)-100-LINKS
52 EB-C210 C1 TYPE 2 42 EB-C191 & C193 C1 TYPE 2
53 EB-C213 C1 TYPE 2 43 EB-C195 C1 TYPE 2 3x20-T32-(20)-V TH.
54 EB-C219 C1 TYPE 2 44 EB-C199 & C200 C1 TYPE 2 3x20-T32-(21)-V TH. ALT.
55 EB-C227 & C228 C1 TYPE 2 45 EB-C202 & C203 C1 TYPE 2
56 EB-C230 & C231 C1 TYPE 2 46 EB-C205 & C206 C1 TYPE 2 16-T25-(02)-300-SPACER CAD/BIM Filename : Floor : Scale :
20-12-2019 5:29:19 PM
400
400
400
58 EB-C241 TO C243 C1 TYPE 2 48 EB-C211 & C212 C1 TYPE 2 5-T25-(07)(a-e)-150-T2 ~ Drawing Title :
4000 4900
59 EB-C245 & C246 C1 TYPE 2 49 EB-C217 & C218 C1 TYPE 2 FRONT ELEVATED DRIVEWAY BRIDGE STRUCTURE
400
400
400
400
5-T25-(14)(a-e)-150-T3 ~
3950 4850
60 EB-C248 & C249 C1 TYPE 2 50 EB-C220 C1 TYPE 2 COLUMN REINFORCEMENT DETAILS
PRINTED/EXPORTED ON:
61 EB-C251 & C252 C1 TYPE 2 51 EB-C226 C1 TYPE 2 (JEDDAH HOSPITAL) (SHEET 02 OF 03)
62 EB-C254 & C255 C1 TYPE 2 52 EB-C229 C1 TYPE 2
63 EB-C257 & C258 C1 TYPE 2 53 EB-C232 C1 TYPE 2
PLAN VIEW A-A SECTION 3-3 DWG No.
1100
1100
300
300
7-T20-(20)-150-LINKS 9. LAP LENGTHS OF REINFORCEMENT SHALL BE AS SHOWN ON DRAWINGS
1100
1100
5-T20-(16)-150-V 360 5-T20-(18)-150-V 400
310 (REFER THE LAP TABLE)
1100
1100
4-T20-(14)-150-V
44 43 42 10. ALL STRUCTURE ARE DESIGNED 2 HOURS FIRE RATED
1100
1100
5-T20-(14)-150-V 460 Should be 4 not 3 41 11. BAR MARKS TO BE READ AS:
45 40
450
460
1100
1100
4-T20-(19)-150-V 46
500
39 REBAR DETAIL
1100
1100
4-T20-(12)-150-V
1100
1100
260
3-T20-(14)-150-V 47 38 2x1 T20 01 300 B1
600
400
BAR PLACING NOTES
49 36 SPACING OF BARS
1100
1100
500 3-T20-(16)-150-V
EB-C117 EB-C114 BAR MARK
35
350
50
350
360
7-T20-(17)-150-LINKS 500
EB-C125 BAR TYPE & DIAMETER (mm)
500 EB-C103 NUMBER OF BARS
51 34
400
400
EB-C129 EB-C111 B3 MULTIPLIERS
7-T20-(15)-150-LINKS 500 B3 EB-C123 EB-C120 EB-C108
52 EB-C105 EB-C99 33
600 EB-C127 EB-C115 LEGEND :
500
500
7-T20-(13)-150-LINKS 600 EB-C124 EB-C109 EB-C101 EB-C97 (TYP.) - TYPICAL. B3 - BOTTOM THIRD LAYER
EB-C131
53 EB-C137 EB-C128 B4
B4 B4
EB-C104
EB-C92 32 V - VERTICAL T1 - TOP FIRST LAYER
B1
EB-C133
EB-C130 EB-C121 EB-C118 EB-C112 EB-C102 B1 H - HORIZONTAL T2 - TOP SECOND LAYER
B4 FF - FAR FACE T3 - TOP THIRD LAYER
(BEARING SIZE 600X450) B1 EB-C135 EB-C126 EB-C106 EB-C95 SF - SIDE FACE
(BEARING SIZE 700X600) (BEARING SIZE 600X500) (BEARING SIZE 500X400) EB-C140 EB-C89 NF - NEAR FACE
54 31 EF - EACH FACE SB - SPACER BARS
DETAIL-B1 DETAIL-B2 DETAIL-B3 DETAIL-B4 EB-C138
EB-C132 EB-C100 EB-C93 ES
B1
- EACH SIDE
- BOTTOM FIRST LAYER
ABR
ALT.
- ALTERNATE BAR REVERSED
- ALTERNATE
SCALE 1:10 (22 Nos.) EB-C143 EB-C134 EB-C98 EB-C86
SCALE 1:10 (18 Nos.) SCALE 1:10 (18 Nos.) SCALE 1:10 (26 Nos.) B2 B2 EB-C90 B2 - BOTTOM SECOND LAYER TH. - THREADED
55 EB-C141 EB-C136 EB-C96 30 EX. CP.- EXTENDED THREAD WITH COUPLER
B2 B2
EB-C139 EB-C94 12. TYPE OF CEMENT FOR COLUMN:SRC
EB-C146 B1 EB-C83
B1 EB-C144 EB-C87
EB-C142
EB-C91 29
56 B1
EB-C149 EB-C88 EB-C84
EB-C147
50 COVER
B2
B2 EB-C145
(TYP
EB-C81
28
30 MIN
57 EB-C85 B2 SHEET NOTES
MIN
5-T20-(14)-150-V EB-C148
90
B2
700 EB-C150 EB-C78
EB-C151
50 COVER EB-C82
CJ
(TYP.)
EB-C79
27
58 EB-C153 EB-C154 EB-C75
450 400 4-T20-(12)-150-V
300
EB-C76 26
200
200
350 7-T20-(23)-150-LINKS
**
250
250
7-T20-(21)-150-LINKS 300
7-T20-(13)-150-LINKS EB-C156
350
59 EB-C159 B4 EB-C72 25
900
EB-C157
EB-C73
1100
1100
1100
1100
4-T20-(22)-150-V 3-T20-(24)-150-V EB-C160
210
** 60 B4
EB-C70 24
300
175
350
B3
B3 B4 EB-C71
EB-C161 EB-C68 23
FOR COLUMN DETAILS REFER DRG NO: 61 B4
EB-C162
MI-PB-B1-C01.00-SR-02-60011-07-00 & 60012-07-00 EB-C69
1100
1100
3-T20-(18)-150-V EB-C163
1100
1100
310 3-T20-(19)-150-V EB-C66
260
62 EB-C164 EB-C67 22
EB-C165 EB-C65 EB-C64
EB-C166 21
1500 63 B3
EB-C167 EB-C168 EB-C63 EB-C62
64 EB-C61 EB-C60 EB-C59 20
(BEARING SIZE 500X400) (BEARING SIZE 500X400) SECTION 1-1 EB-C169 EB-C170
DETAIL-B5 DETAIL-B6 SCALE 1:25
EB-C171 65 19
SCALE 1:10 (14 Nos.) SCALE 1:10 (2 Nos.) EB-C171 EB-C172
B2 EB-C58 EB-C57 EB-C56
B1
EB-C173 B2 66 EB-C53
EB-C174 EB-C175
B1
18
TILT BARS AT SITE TO SUIT COVER.
** EB-C176 EB-C177 EB-C178
67 EB-C55 EB-C54
B4 B1 B5
B4 B1 B5 17
EB-C179 EB-C180
68 EB-C52 EB-C51 EB-C50
EB-C181
EB-C48
EB-C182
69 16
EB-C183 EB-C184 EB-C49 EB-C47 EB-C46
B3 B1 B5
B3 B1 B5 70 15
EB-C185 EB-C186 EB-C188 EB-C45 EB-C44 EB-C43 EB-C42
B4 B2 B5
71 B4 B2 B5
14
EB-C189 EB-C190 EB-C41
EB-C40 EB-C39
72 13
EB-C191 EB-C192 EB-C38 EB-C37 EB-C36
C 73 12
C L EB-C193 EB-C194 EB-C35 EB-C34 EB-C33
L C
L
74 11
BAR BENDING SCHEDULE DOC. NO:
EB-C195 EB-C196 EB-C32 EB-C31 EB-C30
MI-PB-B1-C01.00-SC-02-60013-07-00
B3 B3
B3 B3 75 10
EB-C197 EB-C198 EB-C29 EB-C28 EB-C27
80-T20-(01)-100-LINKS 9
76
EB-C199 EB-C201
EB-C200 EB-C26 EB-C25 EB-C24 EB-C23 00 19-12-2019 ISSUED FOR CONSTRUCTION
75 C Rev # Rev Date Revision Description
OVE
R
EB-C202
77 EB-C21 EB-C19 EB-C17
00 19-12-2019 PB -
EB-C203 EB-C204 8 Current Rev # and Date Orig. Signature ABV Approval Signature
EB-C20 EB-C18
EB-C205 78 7 General Notes :
C 20-T32-(05)-V TH.
(TYP.)
1020
L EB-C206 EB-C207 EB-C22 EB-C16 EB-C15 THE CONSULTANT RETAINS COPYRIGHT OF ALL DOCUMENTS PREPARED BY HIM.
20-T32-(02)-V ALT. TH.
(TYP.)
750
T.O.P
1020
1375
31-T20-(01)-75-LINKS 750
1350
EB-C211 80 5 ALL WORK TO BE CARRIED OUT STRICTLY IN ACCORDANCE WITH NATIONAL
BUILDING
EB-C212 EB-C213 EB-C11 EB-C10 EB-C09
1500
4502
1350
20-T32-(06)-V 2x20-T32-(03)-V TH. B6
REGULATIONS AND LOCAL AUTHORITY REGULATIONS. ALL DIMENSIONS ARE IN
B1
1875
B3 MILLIMETRES U.N.O.
1500
B3
EB-C214 B6 EB-C06 USE FIGURED DIMENSIONS ONLY.
EB-C215 EB-C216 EB-C08 EB-C07
Keyplan Zone :
82 3 /
EB-C217
2x20-T32-(09)-V ALT. TH.
790 SECTION 2-2 EB-C218 EB-C219 EB-C05 EB-C04 EB-C03
4502
905
2x20-T32-(08)-V ALT. TH. SCALE 1:25 83 2
4506
635
EB-C02 EB-C01
EB-C220 EB-C222
5110
2x20-T32-(07)-V TH.
4504
755 1725
B2 EB-C221
(TYP)
2x20-T32-(03)-V TH.
1850
B1
4508
18-T25-(04)-300-LINKS 84 1
1725 1180 B2 B1
(SPACER BARS) 1375
32-T25-(04)-300-LINKS EB-C223 EB-C224 EB-C225
1180 36-T20-(01)-100-LINKS
(SPACER BARS) 1350
1375 85
80-T20-(01)-100-LINKS
1350
EB-C226 EB-C227 EB-C228 A B D
86 C
1385
715 B5 88
10891~10892
B4 B2 B3
4508
20-T32-(05)-V TH.
865 EB-C236 EB-C237 EB-C238 EB-C239 Owner :
20-T32-(02)-V ALT. TH. 3x40-T32-(11)-V STG.
4506
4335
89 Kingdom of Saudi Arabia
ONE END EX. THREAD WITH COUPLER Ministry of Interior
EB-C240 EB-C241 EB-C242 EB-C243
OTHER END THREADED
90
EB-C244 EB-C245 EB-C246
COUPLERS TO BE PLACED AT ALTERNATE. SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH
91
(TYP)
(TYP)
1850
1850
1725
15-T25-(04)-300-LINKS EB-C247 EB-C248 EB-C249
1180
(SPACER BARS) Engineer / Owner's Representative :
45-T20-(01)-100-LINKS
1375
92
1350 EB-C250 EB-C251 EB-C252
6000
93
EB-C253 EB-C254 EB-C255
PIER
(TYP)
(TYP)
SI. CONCRETE
1550
1550
NO
COLUMN
TYPE
REINF. TYPE SI. PIER COLUMN CONCRETE
REINF. TYPE
NOTE:1 94
ALL VERTICAL BARS TO BE BUNDLED. Contractor: ABV Rock Group Co. Ltd.
NAME NO NAME TYPE EB-C256 EB-C257 EB-C258
1 EB-C78 C1 TYPE 3 B4 B5
1 EB-C75 C1 TYPE 3
NOTE:2 B4 B5 95
2 EB-C81 C1 TYPE 3 2 EB-C76 C1 TYPE 3 NORMAL CIRCULAR LINKS ARE DETAILED IN PLACE EB-C259 EB-C260
3 EB-C153 C1 TYPE 3 3 EB-C79 C1 TYPE 3 OF SPIRAL LINKS TO EASE CONSTRUCTION.
96
4 EB-C156 C1 TYPE 3 4 EB-C108 C1 TYPE 3 EB-C261
1500
1500
NOTE:3 EB-C262
5 EB-C109 C1 TYPE 3 THE DIMENSIONS AND LEVELS CAN BE OBTAINED ABV ROCK Group Co. Ltd. Lead Designer / Consultant :
T.O.F T.O.F FROM THE DETAIL DESIGN DRAWINGS. 97
+11.620 +11.320 6 EB-C111 C1 TYPE 3 EB-C263 EB-C264
Al Hudaiba Awards Bldg., 5/F, Unit 510 Block B,
Mina Rashid/ Jumeirah 1 Road
7 EB-C112 C1 TYPE 3
EB-C265
98 P O Box 112025 Block B
EB-C266 Tel 971 4 350 3800/ 358 6803, Fax 971 4 358 6800
KICKER
KICKER
8 EB-C113 C1 TYPE 3 B4 B4
E-mail: pt.dubai@p-t-group.com,Website:www.p-t-group.com
150
150
1800
11 EB-C117 C1 TYPE 3
12 EB-C120 C1 TYPE 3
D B A
13 EB-C121 C1 TYPE 3 C
Sub Consultant :
14 EB-C123 C1 TYPE 3 KEYPLAN
15 EB-C124 C1 TYPE 3 NTS
16 EB-C157 C1 TYPE 3
17 EB-C159 C1 TYPE 3
COLUMN TYPE-3-1 COLUMN TYPE-3-2 CAD/BIM Filename : Floor : Scale :
18 EB-C160 C1 TYPE 3
SCALE 1:50 (18 Nos.)
20-12-2019 5:27:20 PM
(JEDDAH HOSPITAL)
DWG No.
MI PB B1 C01.00 SR 02 60013 07 00
Project Originator Package Location Discipline Type Serial No. Phasing Rev
V1