DAIKIN V.R.

V PIPING CHART
Piping between refrigerant branch kits
 Choose from the following table in accordance with the total capacity index of all the indoor units
connected below this.
 Do not lat the connected piping exceed the main refrigerant piping size. (Unit : mm)

Indoor Unit Total Capacity Piping Size (Out Door)


Index Gas Pipe Liquid Pipe
< 149 Ø 15.9
150 < x < 199 Ø 19.1 Ø 9.5
200 < x < 289 Ø 22.2
290 < x < 619 Ø 12.7
Ø 28.6
620 < x < 639 Ø 15.9
640 < x < 919 Ø 34.9
Ø 19.1
920 < x Ø 41.3

 Choose the REFNET joints other than that for the first branch from the following table in accordance
with the total capacity index of all the indoor units connected below the REFNET joint.
Indoor Unit Capacity Index Refrigerant Branch Kit Name
< 199 KHRP26A22T
200 < x < 289 KHRP26A33T
290 < x < 639 KHRP26A72T
640 < KHRP26A73T+ KHRP26M73TP

How to select the REFNET header


 Choose from the following table in accordance with the total capacity index of all the indoor units
connected below the REFENET header.
 Note: 250 Type cannot be connected below the REFNET header.
Indoor Unit Capacity Index Refrigerant Branch Kit Name
< 199 KHRP26M22H (Max.4 branch)
200 < x < 289 KHRP26M33H (Max.8 branch)
290 < x < 639 KHRP26M72H (Max.8 branch)
640 < KHRP26M73H (Max.8 branch) + KHRP26M73HP

Piping between Outdoor unit and first refrigerant branch kit.


Piping between first Outdoor unit multi connected piping kit and first refrigerant branch kit. (Part A)
 Choose from the following table in accordance with the outdoor unit capacity type.
Piping between Outdoor unit multi connected piping kits. (Part B)
Piping between outdoor unit and Outdoor unit multi connection piping kit. (Part C)
 Choose from the following table in accordance with the total capacity type of all the indoor units
Connected above Outdoor unit multi connection piping kit. (Unit :
mm)
Piping Size (Out Door)
Outdoor Unit Capacity Type
Gas Pipe Liquid Pipe
5 HP Type Ø15.9
8 HP Type Ø19.1 Ø9.5
10 HP Type Ø22.2
12 - 16 HP Type Ø28.6 Ø12.7
18 - 22 HP Type Ø15.9
DAIKIN V.R.V PIPING CHART
24 HP Type
Ø34.9
26 - 34 HP Type
Ø19.1
36 - 60 HP Type Ø41.3
How to select the REFNET joint
 When using REFNET joint at the first branch counted the outdoor unit side.
Choose from the following table in accordance with the outdoor unit capacity type.
(Example: REFNET joint A)

Outdoor Unit Capacity Index Refrigerant Branch Kit Name


5 HP Type KHRP26A22T
8, 10 HP Type KHRP26A33T
12-22 HP Type KHRP26A72T
24 HP Type- KHRP26A73T+ KHRP26M73TP

How to select the outdoor unit multi connected piping kit (This is required when the system is multi outdoor
unit system.)
 Choose from the following table in accordance with the number of outdoor units.
Number of Outdoor nit Connection Piping Kit Name
2 Units BHFP22P100
3 Units BHFP22P151

Piping between refrigerant branch kit and indoor unit


 Match to the size of the connected piping on the indoor unit. (Unit : mm)
Piping Size ( In Door )
Indoor Unit Capacity Type
Gas Pipe Liquid Pipe
20, 25, 32, 40, 50 Type Ø12.7 Ø6.4
63, 80, 100, 125 Type Ø15.9
200 Type Ø19.1 Ø9.5
250 Type Ø22.2