AIR TO WATER

HEAT PUIMP

MODEL:ESDAW-9CH

L240602020 1505
If you want to install the controller on the wall inside your house, first fix the back cover on
the wall by screws, then combine the controller and the back cover together as shown in the

23
28
11. Appendix 29

31
Unscrew the screws, then you can remove the back cover from the
plate as shown in picture 7.

picture 7

step 4
Combine the controller and its back cover together as shown in the
following pictures, then you will get the whole controller.

picture 8

picture 9 picture 10

picture 11 picture 12

30
APPENDIX
Instructions on how to take the control panel out from the unit and install it indoors

step 1
Open the waterproof case outside the controller, then you will see
the two holes as shown in the picture 1.
Put the screwdriver into the hole in the left and operate as shown
in the picture2 and 3.

picture 1

+
picture 2 picture 3

step 2

Do the same operation in the right hole as the last step for
removing the controller.

picture 4

After the last two steps, you can remove the controller as shown in Expansion screws:
picture 5.
X4

picture 5

step 3
After removing the controller outside the waterproof case, you will
see that the back cover of the controller is fixed on the plate by two
screws in the place as shown in picture 6.

picture 6
29 2
L240201000
A1 A2
L180003416 L180003417
M1 C KM1 L180003416 L180003418
S R L180003419 L180003424
V2 L180003455 L180003456
C1
MODEL:ESDAW-9CH

CN19

OUT1 OUT2
V1 R1
OUT3
CN7 R2
OUT4
R3
A1 CN4
M2 OUT5 R4
AC-N R5
28

C2
R6
CN1 CN2 CN3 SW1

Ext A1 main control board F1 high pressure switch


A2 wire controller F2 low pressure switch
E1 V1 4-way valve F3 water flow switch
F3 F2 F1 V2 electrical expansion valve R1 suction gas sensor
M1 compressor R2 ambient sensor
M2 fan R3 coil sensor
E1 transformer R4 water outlet sensor
A2 KM1 comp AC contactor R5 water inlet sensor
C1 compressor capacitor R6 cooling coil sensor
T2 T1
SET AUX C2 fan motor capacitor T1 power supply
AC220V M
Ext connection for timer/thermostat T2 to water pump
The faults’ description

Temperature sensor fault: AIR TO WATER HEAT PUMP SPECIFICATIONS


When the fault code of the temp sensor occurs, please check if the wiring of the sensor
is loose, if the wiring is connected well and firm, possibly the sensor itself is broken, in Model ESDAW-9CH
this case, the sensor needs to be replaced by a new one. ELECTRICAL INPUT
Voltage/Phase/Frequency 220-240V/1PH/50HZ
EE 01: high pressure protection
It means that the pressure in the system is high, so the system stops for protecting the Amps Per Phase 12.7Amps
unit. The possible reasons are as the below: Running Current 16.5Amps
1. loose wiring of the high pressure switch Wire Size 14AWG
Circuit Breaker Size 20Amps
2. water flow rate in the system is not enough, so the heat exchanging between the
hot gas and water is not sufficient, which cause the high pressure. In this case, please
PERFORMANCE
check the water flow rate of the water pump and the flow rate of the whole water circuit Heating Capacity 8.9KW
system, to see if the water pump itself has weak flow and if there is any block inside the Heating Power Input 2.8KW
water circuit system, such as the filter blockage, blockage inside water pipings...
Heating COP※ 3.2
3. Air evacuation is not done before the system is running Heating COP※※ 3.5
If the system is not air evacuated, there is air resistence when water flow goes through Sound Level 52dB(A)@3m
the pipes, so the flow rate will be reduced. So before running the system, please make
sure the air inside the system is evacuated.
TECHNICAL DATA
Compressor
Type Rotary
EE 02: low pressure protection
It means that the pressure in the system is too low, so the system stops for protecting the Number Per Unit 1
unit. The possible reasons are as the below: FLA (Full Load Amp) 13.3Amps
Voltage/Phase 220-240V/1PH
1. loose wiring of the low pressure switch
Fan
2. low gas volume: Type Propeller
In this case, probably there is gas leak somewhere, then we need to check the following
Number Per Unit 1
positions.
Power Input 0.2KW
a) the charge port, where the gas is charged, check if the port cover fixed correctly and
firmly. Voltage/Phase 220~240V/1PH
b) pressure gauge connections Fan Speed 720Rpm
c) copper connections, where there is welding points. HEAT EXCHANGER (Water Side)
Type Double Pipe Heat Exchanger
3. the low pressure switch itself is broken.
3
Water Flow Rate (m /h) 1.5
Max. Outlet Water Temp 55℃
EE 03: water flow fault Water Connections 3/4 Inch
The possible reasons are as the below:
Hot Water Supply (L/H) 191
a) water flow rate in the system is not sufficient because of small flow rate of the water pump GENERAL INFORMATION
itself or any blockage inside the water circuit, such as filter blockage... Refrigerant R410A
b) system is not air evacuated, so the flow rate is reduced.
c) small pipe size, or big resistance of the floor lines... Defrost Automatic Hot Gas Injection
d) loose wiring of the water flow switch Min. Operating Temperature -15℃
e) the water flow switch itself is broken Shipping Weight 86 kg
Dimensions L x W x H (cm) 111 x 46 x 68.7
※Heating: Outdoor Air Temp:7℃ DB ,6℃WB, Water Temp: 40℃
※※Heating: Outdoor Air Temp:15℃ DB ,11℃WB, Water Temp: 35℃
27 4
Protection/Alarm Error Code Operation/Error indicator light
Standby state off
Booting normally on
Water inlet temp. sensor
PP 01 ☆●(Flashes on once and off once)
fault
Water outlet temp. sensor
PP 02 ☆☆●( Flashes on twice and off once)
fault
Coil temp. sensor fault PP 03 ☆☆☆●( Flashes on 3 times and off once)
☆☆☆☆●( Flashes on 4 times and off
Suction temp. sensor fault PP 04
once)
Ambient temp. sensor ☆☆☆☆☆●( Flashes on 5 times and off
PP 05
fault once)
Water outlet and inlet
temp. differences PP 06 on
overlarge protection
Sub-cooling protection
PP 07 on
under cooling mode
The First-degree
antifreezing protection in PP 07 off
winter
The Second degree
antifreezing protection in PP 07 off
winter
Cooling coil temp. sensor ☆☆☆☆☆☆☆☆☆●( Flashes on 9 times
PP 08
fault and off once )
☆☆☆☆☆☆●( Flashes on 6 times and off
High pressure protection EE 01
once )
☆☆☆☆☆☆☆●( Flashes on 7 times and
Low pressure protection EE 02
off once)
☆☆☆☆☆☆☆☆●( Flashes on 8 times
Water flow fault EE 03
and off once)
Phase sequence ☆☆☆☆☆☆☆☆☆☆☆☆●(Flashes on 12
EE 04
protection times and off once)
Water outlet and inlet ☆☆☆☆☆☆☆☆☆☆●(Flashes on 10
EE 05
temp. overlarge fault times and off once)
Discharge temp. ☆☆☆☆☆☆☆☆☆☆☆●(Flashes on 11
EE 06
overlarge protection times and off once)
Defrosting ☆☆☆☆☆☆☆☆……(Always flashing)
(The fault is only effective on remote
Communication fault EE 08
controllers)
26
Air To Water Heat Pump

9.3 Parameter

Paremeter Function Range Value


Water inlet temperature
00 8~28℃ 12℃
during cooling mode
Water inlet temperature
01 15~60℃ 45℃
during heating mode
02 Defrosting cycle 30~90min 45min
Coil temp. to start the
03 0~30℃ -9℃
defrosting
Coil temp. to stop the
04 2~30℃ 13℃
defrosting
05 The defrosting duration 1~12min 10min
Electronic expansion valve
06 0~1(0:Manual /1:Automatic) 1
control
07 Power down memory function 0~1(0:No /1:Yes) 1
0~3(0:Cooling only /1:Cooling
and heating /2:Cooling and
08 Model heating plus electric heating 1
/3:Heating only plus electric
heating)
09 Work pattern of water pump 0(Ordinary)/1(Special) 0
Automatic water inlet
A 8~60℃ 45℃
temp.setting
Target superheat temp.
b -15~15℃ 5℃
(heating mode)
Manual adjustment of
c 10~50 35
electronic expansion valve
Target superheat temp.
d -15~15℃ 5℃
(cooling mode)

Note: Delta temp F is the temp difference between the setting temp and temp
to restart the unit. For example, when Tset is 55℃, F is 2 , the unit stops
running when the water temp gets to 55℃ ,and it will restart when the
water temp <Tset-F (55℃-2℃=53℃)

25
Failure Possible causes Solutions
1. Liquid refrigerant into the 1. Check the cause and
High noise of
compressor eliminate it
compressor
2. compressor crash 2. change the compressor
No running of fan 1.Relay failure 1. change the relay
motors 2. fan motor destroyed 2. change the fan motor
1. completely leakage of 1. examine leakage and supply
The compressors are refrigerant refrigerant
running, but the unit 2. Tube-in-tube heat exchanger 2. change the tube-in-tube heat
is not cooling/heating ruined exchanger
3. Compressors fault 3. Change compressors
1. Wash the filter or discharge
1. water flow shortage
Low water temperature the air in the system
protection 2. Low setting value on
2. Reset the temperature
temperature
1. wash the filter or discharge
Low water flow 1. water flow shortage
the air in the system
protection
2. water switch damage 2. Change the switch

9.2System Status

Code Description Range Remark

IN Water inlet temp. -9℃~99℃ Actual value


OUT Water Outlet temp. -9℃~99℃ Actual value
P1 Coil temp. -9℃~99℃ Actual value
P2 Suction temp. -9℃~99℃ Actual value
P3 Ambient temp. -9℃~99℃ Actual value
P4 Cooling coil temp. -9℃~99℃ Actual value
Step of electronic expansion
P5 0P~500P Actual value
valve

24
9.1
Failure Possible causes Solutions
1. turn off the switch and
1. Power source failure
check the power source
No running of the unit
2. Loosened wiring 2. find the caused and repair
3. The power fuse has broke 3. change a new fuse
1. Water leakage of the water 1. check the water supply
The pump is running system device and inject water
without water 2. There is air in the system 2. Discharge the air
recycling or with high 3. the valves are not open
3. open the valves completely
noise entirely
4. Filter blockage 4. Wash the filter
1. check leakage and supply
1. refrigerant shortage
refrigerant
Low refrigerant capacity
2. bad water thermal insulation 2. Improve the insulation
while
3. bad heat elimination of air 3. wash the heat exchanger
compressors are running
heat exchanger and improve condensing
4. Water flow shortage 4. Wash the filter
1. discharge unwanted
1. Excessive refrigerant
Over-high outlet refrigerant
pressure of compressors 2. Bad heat elimination of air 2. Wash the heat exchanger
heat exchanger and improve condensing
1. check leakage and supply
1. refrigerant shortage
refrigerant
2. filter or capillary blockage 2. change new filter or capillary
Over-low inlet pressure
3. wash the filter or discharge
of compressors 3. water flow shortage
the air in the system
4. Capillary in the expansion
4. change the expansion valve
valve cracks
1. examine the power source
1. power source failure
and eliminate the failure
2. compressor contactor
2. change the contactor
failure
3. loosened wiring 3. check and repair it
No running of
4. Compressor over loading 4. compressor over loading
compressors
protection protection
5. wrong setting for inlet water
5. Reset it
temperature
6. Wash the filter or discharge
6. Water flow shortage
the air in the system

23
Terminal on water pump

Terminal on main power

9 22
7.12.1 Time clock setting

1) Press button “SET “for 3 seconds to enter into the time clock setting interface. Then you
will see the flashing “hour” and “min”;

2) When the “hour” and “min” are both flashing, press button “SET”, there will be only the
“hour” flashing. Then press “▲”and “▼”to set the required hour;

3) After the hour setting, press button “SET”, there will be only “min” flashing, then press
“▲”and “▼”to set the required minute;

4) After the minute setting, press button “SET”for confirming and saving the time setting,
then system will come back to main interface.

7.12.2 Timer setting

“ ” button

1) In the main interface, press “ ” button for three seconds to enter timing setting
interface;

2) In timing setting interface, “ON”flasing shows timing switch on, “OFF” flashing shows
timing switch off. Press “ ” button to change the setting between “hour” and “min”,
using “▲”and “▼”to set the required time;

3) In timing setting interface, press “ ” button to save the current setting time, then exit
the timing setting interface and back to main interface;

4) In timing setting interface, press “SET”button to cancel all of the setting time, then exit
the timing setting interface and back to main interface.

21
sor will run.

1) When the exist conditio

3. Parameter setting on the defrosting

Please refer to the parameter table on page 25.


Parameter 02 defrosting cycle, the default value is 45min. It means that the system runs in
heating mode for 45min,then automatically to check if the condition to start the defrosting
is satisfied. If the condition to start the defrosting is satisfied, the system will go to
defrosting mode.

Parameter 03, the coil temp to start the defrosting, the default value is -9℃. When the coil
temperature (it can be check by parameter code P1) gets to -9℃, the system will enter into
defrosting mode. In defrosting mode, the system is in cooling mode and will absorb heat
from room /house to melt the ice. So in defrosting period, there is no heat to come to the
house.

Parameter 04, coil temp to stop the defrosting, the default value is 13℃.When the coil temp
gets to 13℃, the defrosting will stop.

Parameter 05, the time duration of defrosting, default value is 10 min. When the defrosting
lasts for 10min, the defrosting will end.

For parameter 04 and parameter 05, any of them gets to the setting value, the defrosting
will end.

All of the above parameters are adjustable according to the real needs.
7.3 Initialization and standby state
As we know, when the air temp is below 0℃, the unit is easy to ice up. But when the air
temp is above 0℃ and the air humidity is high, there is also the possibility that the unit ices
up. Please refer to the below review.

As shown in the view, the dotted area is the possible


frosting area, and the shadow part is inevitable/certain
frosting area.

20
Fault PP01: Water inlet
temperature sensor fault

Fault PP02: Water outlet


temperature sensor fault

Fault PP03: Defrosting


temperature sensor fault

Fault PP04: Suction


temperature sensor fault

Fault PP05: Ambient


temperature sensor fault

19
7.5.2 How to regulate the modes
Please see the following view.
The parameter 08 should first be set correctly. For heat pump, the value of the parameter
08 should be set at 1 (for heating and cooling machine), then it will function when we switch
the mode between the heating mode and cooling mode.

In standby mode, press SET key to enter into the parameter pages, and we can go from one
parameter page to the next one by pressing the SET key. When we go to the parameter 08
page, then adjust the value via the up and down keys. After setting value 1, please wait the
page recovers to the original standby mode, then check the mode, if it’s not in the mode we
want, regulate it via the MODE key to be heating/cooling mode.

1
Fault EE01:
High pressure fault

The mode can be switched between heating and cooling both in standby mode Fault EE02:
or ON mode. Low pressure fault

(1) In standby mode (the unit is plugged to the power supply, but not been switched on to
operate), if the mode is in cooling (the symbol is the snow flake on the left of the screen),
please press the MODE key, then the screen will change to be in heating mode, with Sun
Icon on the right. After this switch is successful, then switch on the heat pump by on/off
key to operate, the unit will run in heating mode.

(2) In ON mode (when the unit is in running), if it is in cooling mode, then press the MODE
key, then the screen will change to be in heating mode, with Sun Icon on the right of the Fault EE04:
screen. Then the fan and compressor will stop, after around 3 minutes, the fan and Phase sequence
compressor will re-start and then unit will run in heating mode. protection

Please note that, if you adjust mode by the second way, after the heating mode is set, the
unit will have a stop, then just leave the unit there and wait for the restarting, we don't
need to put the on/off key to turn on it.
Fault EE08:
If you want to try the first way, please switch off the unit, after the unit stops and back in Communication connection fault
standby mode, press the MODE key to change the mode to be in heating,then switch on
the unit, it will run in heating.

It is the same way as above to change cooling mode into heating mode.

18
7.6.1 Temperature setting

14
7.6.2 Detailed Instruction on temperature setting.
The parameter setting should be done in the standby mode. In the ON mode of the unit,
we can check the current values of the parameters, but we can't modify them. So please
set the parameter value in the standby mode.

Standby mode means that the unit is plugged to the power supply,
but is not turned on to run.

(a) In the standby mode, press SET button to enter into the parameter setting page. After
pressing the SET button, we also have entered into the first parameter setting page. It will
display parameter 0 (water inlet temp in cooling mode)

(b) Press SET button again, then we enter into the second parameter setting page. It will tate
display parameter 1 (water inlet temp in heating mode), then adjust the temperature by up e. In the ON state, you can see the curr
or down keys, till to the temperature we want.
f. Please pay attention that, when we are in the setting page of parameter 2,we need to first
( Press the SET key to switch the parameter page from one to the next.) press the “up” and “down” key at the same time till we hear a tick, then we can enter into
the following setting pages by pressing key SET and set the value by “up” and “down”keys.
Please pay attention that, when we are in the setting page of parameter 02,we need to
press the “up” and “down” keys are the same time till we hear a tick, then we can switch
into the following setting pages by pressing key SET and set the value by “up” and “down”
keys.

Please refer to the following views:

Parameter 03: Coil temp


to start defrosting

in standby mode press SET key enter into setting page of parameter 0

Parameter 04: Coil temp


to stop defrosting

press SET key again to enter into


the next page parameter 1 (water inlet temp.), press the up key to adjust the value
higher

Parameter 05:
Defrosting duration

Or press the down key to A few seconds later after the setting, the screen will
adjust the value lower recover to be the initial status in the standby mode,
then we can turn on the unit by on/off key to operate.

15