HEAT PUIMP
MODEL:ESDAW-9CH
L240602020 1505
If you want to install the controller on the wall inside your house, first fix the back cover on
the wall by screws, then combine the controller and the back cover together as shown in the
23
28
11. Appendix 29
31
Unscrew the screws, then you can remove the back cover from the
plate as shown in picture 7.
picture 7
step 4
Combine the controller and its back cover together as shown in the
following pictures, then you will get the whole controller.
picture 8
picture 9 picture 10
picture 11 picture 12
30
APPENDIX
Instructions on how to take the control panel out from the unit and install it indoors
step 1
Open the waterproof case outside the controller, then you will see
the two holes as shown in the picture 1.
Put the screwdriver into the hole in the left and operate as shown
in the picture2 and 3.
picture 1
+
picture 2 picture 3
step 2
Do the same operation in the right hole as the last step for
removing the controller.
picture 4
After the last two steps, you can remove the controller as shown in Expansion screws:
picture 5.
X4
picture 5
step 3
After removing the controller outside the waterproof case, you will
see that the back cover of the controller is fixed on the plate by two
screws in the place as shown in picture 6.
picture 6
29 2
L240201000
A1 A2
L180003416 L180003417
M1 C KM1 L180003416 L180003418
S R L180003419 L180003424
V2 L180003455 L180003456
C1
MODEL:ESDAW-9CH
CN19
OUT1 OUT2
V1 R1
OUT3
CN7 R2
OUT4
R3
A1 CN4
M2 OUT5 R4
AC-N R5
28
C2
R6
CN1 CN2 CN3 SW1
9.3 Parameter
Note: Delta temp F is the temp difference between the setting temp and temp
to restart the unit. For example, when Tset is 55℃, F is 2 , the unit stops
running when the water temp gets to 55℃ ,and it will restart when the
water temp <Tset-F (55℃-2℃=53℃)
25
Failure Possible causes Solutions
1. Liquid refrigerant into the 1. Check the cause and
High noise of
compressor eliminate it
compressor
2. compressor crash 2. change the compressor
No running of fan 1.Relay failure 1. change the relay
motors 2. fan motor destroyed 2. change the fan motor
1. completely leakage of 1. examine leakage and supply
The compressors are refrigerant refrigerant
running, but the unit 2. Tube-in-tube heat exchanger 2. change the tube-in-tube heat
is not cooling/heating ruined exchanger
3. Compressors fault 3. Change compressors
1. Wash the filter or discharge
1. water flow shortage
Low water temperature the air in the system
protection 2. Low setting value on
2. Reset the temperature
temperature
1. wash the filter or discharge
Low water flow 1. water flow shortage
the air in the system
protection
2. water switch damage 2. Change the switch
9.2System Status
24
9.1
Failure Possible causes Solutions
1. turn off the switch and
1. Power source failure
check the power source
No running of the unit
2. Loosened wiring 2. find the caused and repair
3. The power fuse has broke 3. change a new fuse
1. Water leakage of the water 1. check the water supply
The pump is running system device and inject water
without water 2. There is air in the system 2. Discharge the air
recycling or with high 3. the valves are not open
3. open the valves completely
noise entirely
4. Filter blockage 4. Wash the filter
1. check leakage and supply
1. refrigerant shortage
refrigerant
Low refrigerant capacity
2. bad water thermal insulation 2. Improve the insulation
while
3. bad heat elimination of air 3. wash the heat exchanger
compressors are running
heat exchanger and improve condensing
4. Water flow shortage 4. Wash the filter
1. discharge unwanted
1. Excessive refrigerant
Over-high outlet refrigerant
pressure of compressors 2. Bad heat elimination of air 2. Wash the heat exchanger
heat exchanger and improve condensing
1. check leakage and supply
1. refrigerant shortage
refrigerant
2. filter or capillary blockage 2. change new filter or capillary
Over-low inlet pressure
3. wash the filter or discharge
of compressors 3. water flow shortage
the air in the system
4. Capillary in the expansion
4. change the expansion valve
valve cracks
1. examine the power source
1. power source failure
and eliminate the failure
2. compressor contactor
2. change the contactor
failure
3. loosened wiring 3. check and repair it
No running of
4. Compressor over loading 4. compressor over loading
compressors
protection protection
5. wrong setting for inlet water
5. Reset it
temperature
6. Wash the filter or discharge
6. Water flow shortage
the air in the system
23
Terminal on water pump
9 22
7.12.1 Time clock setting
1) Press button “SET “for 3 seconds to enter into the time clock setting interface. Then you
will see the flashing “hour” and “min”;
2) When the “hour” and “min” are both flashing, press button “SET”, there will be only the
“hour” flashing. Then press “▲”and “▼”to set the required hour;
3) After the hour setting, press button “SET”, there will be only “min” flashing, then press
“▲”and “▼”to set the required minute;
4) After the minute setting, press button “SET”for confirming and saving the time setting,
then system will come back to main interface.
“ ” button
1) In the main interface, press “ ” button for three seconds to enter timing setting
interface;
2) In timing setting interface, “ON”flasing shows timing switch on, “OFF” flashing shows
timing switch off. Press “ ” button to change the setting between “hour” and “min”,
using “▲”and “▼”to set the required time;
3) In timing setting interface, press “ ” button to save the current setting time, then exit
the timing setting interface and back to main interface;
4) In timing setting interface, press “SET”button to cancel all of the setting time, then exit
the timing setting interface and back to main interface.
21
sor will run.
Parameter 03, the coil temp to start the defrosting, the default value is -9℃. When the coil
temperature (it can be check by parameter code P1) gets to -9℃, the system will enter into
defrosting mode. In defrosting mode, the system is in cooling mode and will absorb heat
from room /house to melt the ice. So in defrosting period, there is no heat to come to the
house.
Parameter 04, coil temp to stop the defrosting, the default value is 13℃.When the coil temp
gets to 13℃, the defrosting will stop.
Parameter 05, the time duration of defrosting, default value is 10 min. When the defrosting
lasts for 10min, the defrosting will end.
For parameter 04 and parameter 05, any of them gets to the setting value, the defrosting
will end.
All of the above parameters are adjustable according to the real needs.
7.3 Initialization and standby state
As we know, when the air temp is below 0℃, the unit is easy to ice up. But when the air
temp is above 0℃ and the air humidity is high, there is also the possibility that the unit ices
up. Please refer to the below review.
20
Fault PP01: Water inlet
temperature sensor fault
19
7.5.2 How to regulate the modes
Please see the following view.
The parameter 08 should first be set correctly. For heat pump, the value of the parameter
08 should be set at 1 (for heating and cooling machine), then it will function when we switch
the mode between the heating mode and cooling mode.
In standby mode, press SET key to enter into the parameter pages, and we can go from one
parameter page to the next one by pressing the SET key. When we go to the parameter 08
page, then adjust the value via the up and down keys. After setting value 1, please wait the
page recovers to the original standby mode, then check the mode, if it’s not in the mode we
want, regulate it via the MODE key to be heating/cooling mode.
1
Fault EE01:
High pressure fault
The mode can be switched between heating and cooling both in standby mode Fault EE02:
or ON mode. Low pressure fault
(1) In standby mode (the unit is plugged to the power supply, but not been switched on to
operate), if the mode is in cooling (the symbol is the snow flake on the left of the screen),
please press the MODE key, then the screen will change to be in heating mode, with Sun
Icon on the right. After this switch is successful, then switch on the heat pump by on/off
key to operate, the unit will run in heating mode.
(2) In ON mode (when the unit is in running), if it is in cooling mode, then press the MODE
key, then the screen will change to be in heating mode, with Sun Icon on the right of the Fault EE04:
screen. Then the fan and compressor will stop, after around 3 minutes, the fan and Phase sequence
compressor will re-start and then unit will run in heating mode. protection
Please note that, if you adjust mode by the second way, after the heating mode is set, the
unit will have a stop, then just leave the unit there and wait for the restarting, we don't
need to put the on/off key to turn on it.
Fault EE08:
If you want to try the first way, please switch off the unit, after the unit stops and back in Communication connection fault
standby mode, press the MODE key to change the mode to be in heating,then switch on
the unit, it will run in heating.
It is the same way as above to change cooling mode into heating mode.
18
7.6.1 Temperature setting
14
7.6.2 Detailed Instruction on temperature setting.
The parameter setting should be done in the standby mode. In the ON mode of the unit,
we can check the current values of the parameters, but we can't modify them. So please
set the parameter value in the standby mode.
Standby mode means that the unit is plugged to the power supply,
but is not turned on to run.
(a) In the standby mode, press SET button to enter into the parameter setting page. After
pressing the SET button, we also have entered into the first parameter setting page. It will
display parameter 0 (water inlet temp in cooling mode)
(b) Press SET button again, then we enter into the second parameter setting page. It will tate
display parameter 1 (water inlet temp in heating mode), then adjust the temperature by up e. In the ON state, you can see the curr
or down keys, till to the temperature we want.
f. Please pay attention that, when we are in the setting page of parameter 2,we need to first
( Press the SET key to switch the parameter page from one to the next.) press the “up” and “down” key at the same time till we hear a tick, then we can enter into
the following setting pages by pressing key SET and set the value by “up” and “down”keys.
Please pay attention that, when we are in the setting page of parameter 02,we need to
press the “up” and “down” keys are the same time till we hear a tick, then we can switch
into the following setting pages by pressing key SET and set the value by “up” and “down”
keys.
in standby mode press SET key enter into setting page of parameter 0
Parameter 05:
Defrosting duration
Or press the down key to A few seconds later after the setting, the screen will
adjust the value lower recover to be the initial status in the standby mode,
then we can turn on the unit by on/off key to operate.
15