resistance
testing
A complete solution—
for every application.
Why perform
insulation
testing?
Safety Equipment uptime Insulation
The most important reason In addition, insulation testing is regulations
for testing insulation is to important to protect and prolong The International Electrical
ensure public and personal the life of electrical systems Testing Association (NETA)
safety. By performing a high and motors. Periodic mainte- provides representative and
dc voltage test between nance tests can provide valuable minimum insulation values
de-energized current-carrying information about the state of for various voltage ratings of
(hot), grounded, and grounding deterioration and will help in equipment for use when manu-
conductors, you can eliminate predicting possible failure of the facturer’s data is not available.
the possibility of having a system. Correcting problems will
life-threatening short circuit result not only in a trouble-free Insulation testers are essen-
or short to ground which could system, but will also extend the tial in any electrical system
lead to a fire. operating life for a variety of for proper and safe equip-
equipment. ment operation per industry
standards, IEEE Std 43-2000
Insulation resistance testers (Recommended Practice for
can be used to determine the Testing Insulation Resistance of
integrity of windings or cables Rotating Machines), and other
in motors, transformers, switch- recognized organizations.
gear, and electrical installations.
The test method is determined
by the type of equipment
being tested and the reason for
testing. Spot-reading/short time
resistance tests can be used for
low-capacitance equipment,
while trending tests such as step
voltage or dielectric-absorption
tests can be used for time-
dependent currents that will last
for hours.
2
The International Electrical Testing Association (NETA) also
provides recommended test voltages when manufacturer’s
data is not available:
3
Insulation spot test Polarity index
This can be used to verify the and dielectric
condition of the insulation over
the life of a motor by connecting
absorption ratio
Megohmeter to measure resis- These are timed ratio tests
tance of each winding to ground that check the absorp-
while recording reading onto tion characteristics of wet or
graph. contaminated insulation. The
PI test is performed over a 10
minute period whereas the
Insulation step DAR ratio test is performed over
voltage a 60 second span. There are
Creates electrical stress on minimum acceptable polariza-
internal insulation cracks to tion index values depending
reveal aging or damage not on the insulation class—IEEE
found during other motor insula- Standard 43-2000 covers
tion tests. This test is done by measurement of polarization
testing the insulation at two or index testing:
more voltages and comparing
the results. Insulation Index value
Class A 1.5
Class B 2.0
6
Class F 2.0
Class H 2.0
4
Insulation
resistance
The latest test tools from the testing experts.
Recommended for:
Fluke 1587 FC: Industrial plant maintenance,
industrial and utilities electricians, field
service contractors and commercial HVAC/R
technicians
Fluke 1577: Electrical contractors and
commercial electricians
Fluke 1507/1503
Insulation Resistance Testers
With their multiple test voltages, the compact Fluke 1507 and
1503 Insulation Testers are ideal for many troubleshooting,
commissioning, and preventative maintenance applications.
Additional features, like the remote probe on these tools,
reduces the time needed to perform repetitive testing.
The Fluke 1507 is the best compact, lightweight, handheld Key features
insulation tester for advanced industrial and electrical insula-
• Insulation test range
tion testing. Its full feature set offers the ability to easily and
1507: 0.01 MΩ to 10 GΩ
quickly perform advanced insulation resistance testing. Its
1503: 0.1 MΩ to 2000 MΩ
handy size makes it easy to pack and use. And its reasonable
price makes it an excellent value. • Insulation test voltages
1507: 50 V, 100 V, 250 V, 500 V, 1000 V
For basic electrical insulation testing, choose the compact 1503: 500 V, 1000 V
Fluke 1503—a rugged, compact tool that handles the most • Save both time and money with automatic
common tests at a most affordable price. calculation of Polarization Index and Dielectric
Absorption Ratio (1507 only)
• Make repetitive tests simple and easy with the
Compare (Pass/Fail) function (1507 only)
• Repetitive or hard-to-reach testing is easy with
the remote test probe
• Live circuit detection prevents insulation test
if voltage > 30 V is detected for added user
protection
• Auto-discharge of capacitive voltage for added
user protection
• AC/DC voltage: 0.1 V to 600 V
• Lo ohms/earth-bond continuity (200 mA)
• Resistance: 0.01 Ω to 20.00 KΩ
Recommended for: • Remote probe, test leads, probes and alligator
Fluke 1507: Electrical contractors, clips included with each tester
industrial and commercial electricians • One-year warranty
Fluke 1503: Residential and
commercial electricians
Product
ProductComparison
ComparisonCharts
Chartson
onpage
page11.
11. 99
Fluke has created combo kits to help maximize your
productivity and help you solve problems faster and
reduce downtime, all with significant savings over
buying each product individually.
10
10 Product Comparison Charts on page 7.
Choose the best fit
Insulation
0.01 MΩ to 2 GΩ 0.01 MΩ to 600 GΩ 0.01 MΩ to 2000 GΩ 0.01 MΩ to 10 GΩ 250 k to 1 TΩ 250 k to 2 TΩ
resistance range
PI/DAR • • • •
Auto discharge • • • • • •
Timed ramp test
(Breakdown) • •
Pass/fail
comparison • • •
Hold/lock • • • • • •
Multimeter features
AC/DC volts • •
Current • •
Resistance • •
Note: Not all product features and specifications are listed in this table.
Continuity beeper • • For more complete information, see individual product data sheets.
Temperature
(contact) • Footnotes:
1 Function useful for checking connections and motor windings.
Lo-pass filter
2
• Also useful for users who are required to perform earth-bond continuity
measurements during installation testing.
Capacitance • 2 Filter for variable-speed motor drive measurements.
Diode test •
Frequency •
MIN/MAX •
Other features
Backlight • • • •
Fluke Connect FlukeView® Forms Fluke View® Forms
Software compatible Basic Basic
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0)40 267 5100 or
Fax +31 (0)40 267 5222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006, 2010, 2015 Fluke Corporation.
Printed in U.S.A. 9/2015 2461452d-en
Modification of this document is not permitted
without written permission from Fluke Corporation.