You are on page 1of 2

g Industrial Systems Secondary Substation Transformers

Test Application Data


Standard Tests Turn ratio test confirms the correct number of turns of
The following tests will be made on all Secondary each winding. The test is performed on the rated
Substation Transformers except as specifically stated voltage connection and on all tap connections at no
below. All tests will be made in accordance with the load conditions. Accuracy must be within 0.5% of
latest revision of: nameplate markings.

IEEE C57.12.00 Standard General Requirements for No-Load Loss & Exciting Current
Liquid-Immersed Distribution, Power, and Regulating No load losses are the losses of a transformer when
Transformers. excited at rated voltage and frequency, while not
under load conditions. No load losses include core
ANSI/IEEE C57.12.90 Standard Test Code for Liquid-
loss, dielectric loss, and loss in the winding due to
Immersed Distribution, Power, and Regulating
exciting current. The test is performed at rated
Transformers.
voltage.
ANSI/IEEE C57.12.01 General requirements for Dry-
Type Distribution and Power Transformers Including Impedance and Load-Loss Tests
Those With Solid Cast and/or Resin-Encapsulated A transformer under load, experiences an impedance
Windings which causes the ratio of the terminal voltages to
depart from the actual turns ratio. This internal
IEEE C57.12.91 Test Code for Dry-Type Distribution impedance consists of two components: 1) a
and Power Transformers. reactance, derived from the effect of leakage flux in
ANSI/IEEE C57.94 Recommended Practice for the winding, and 2) an equivalent resistance which
Installation, Application, Operation and Maintenance of represents all losses traceable to the flow of the load
Dry-Type General Purpose Distribution and Power current (I²R, Stray, and Eddie Loss). The voltage
Transformers. required to circulate rated current under short circuit
conditions when connected to the rated voltage tap is
NEMA Publication TR-1, Part 9 Audible Sound Level the impedance voltage, and the watt loss measured is
Tests the load loss. The standard tolerances by which the
Test equipment is periodically calibrated which can be impedance may vary are ± 7.5% of specified values
tied to the National Bureau of Standards and for two-winding transformers and ±10% for multi-
Technology (NIST) winding, auto, or other non-standard transformers.

Resistance Test Dielectric Tests


This test is performed to calculate the I²R losses of Dielectric tests confirms the transformers ability to
the transformer as well as assure the winding withstand the imposition of voltage associated with
conductor sizes, cable sizes, crimps, brazes, and the specified insulation level.
bolted bushing connections are correct. Resistance Applied Potential Test
measurements are made on all windings connected for Tests are performed between each independent winding
rated operation and on all odd numbered tap positions and all windings and ground. A normal power
(must include rated and tap extremes). Current can frequency of 60 Hz is used and the duration of the test
not have been applied to the transformer for at least 6 is one minute at the specified voltage.
hours prior to the test. All winding resistance
measurements are corrected to a standard reference Induced Potential Test
temperature of rated temperature plus 20°C. A specified test voltage is applied between the
terminals of one winding for 7,200 cycles or 60
Polarity & Phase Relation seconds, whichever is shorter. The test applies
Polarity and phase relation are of importance when greater than rated voltage per turn to the transformer,
paralleling or banking two or more transformers. the frequency of the applied voltage must be high
Phase relationship tests are made to determine enough to prevent the core from being over-excited.
angular displacement and relative phase sequence.
The present ANSI standard for angular displacement
has the HV 30 degrees ahead of the LV, regardless of
the connection.
Turn Ratio Test GE Quality Tests:

Data Subject to Change without Notice 9/3/99


g Industrial Systems Secondary Substation Transformers
Test Application Data
A Quality Control Partial Discharge Test is This test is performed to determine the insulation
conducted on each Cast Coil Transformer. resistance from individual windings to ground, or
Information is available for review in Rome but not between individual windings.
included on Test Reports.
Impulse Test
A Quality Control Impulse Test for the rated BIL is Lightning Impulse Test are design tests which
conducted on all Dry-Type (Cast Coil and VPI) simulates the most drastic overvoltage conditions a
Transfomers as a pass-fail test. No record of this test transformer properly protected by surge arresters is
is provided on the Test Report likely to encounter. The impulse tests precede the
low-frequecy applied and induced-voltage tests. For
Optional Tests Dry-Type and Cast Coil transformers a 1.2x50
Insulation Power Factor Test microsecond (µs) wave of positive polarity is used for
The tests checks the condition of the insulation. The reduced and full-impulse tests. We apply one
test checks the ratio of the power dissipated in the reduced full wave, two chopped waves, and one full
insulation in watts to the product of the effective wave to each of the specified HV and/or LV
voltage and current in volt-amperes. Comparative terminals. We compare the wave shapes of the
values of tests taken at periodic intervals are useful in reduced and full wave tests to confirm no possible
identifying potential problems rather than an absolute insulation failure.
value of insulation power factor.
Audible Sound-Level Test
Temperature Test Sound level measurements are made in an
Tests will be made on one unit only of an order environment having an ambient level of at least 5 dB
covering one or more units of a given rating. Tests below the combined level of the transformer plus
will be made only when there is not available a record ambient. Microphones are placed at half height
of a temperature test, made in accordance with ANSI approximately every three feet around the transformer
Standards, on a duplicate or essentially duplicate unit. enclosure with a minimum of eight microphones
Tests, when made, will be made under conditions required. For transformers enclosures over eight feet
specified in ANSI Standards for Transformers. in height, microphones are placed at one-third and
two-thirds heights. The A-weighted sound level is
Subject to the limitations of the preceding paragraph, determined by taking the arithmetic mean of all the
when a transformer is supplied with auxiliary cooling sound level measurements taken.
equipment to provide more than one KVA rating,
Temperature tests will be made on the self cooled Optional BIL Tests
nameplate KVA rating and the maximum nameplate Basic Impulse Level tests are performed which are
rating. greater then nameplate BIL.
The transformer will be tested under loaded conditions Certified Test Reports
to produce losses as near to nameplate rating as Standard ANSI format test reports will be furnished.
possible. Thermocouples are installed inside the
transformer. Once the thermocouples do not vary more
than 2°C during a consecutive 3 hour period from
ambient, the test current and voltage are removed and
resistance measurements are taken from the HV and LV
windings. The resistance of each of the HV and LV
windings are corrected back to the instant of shutdown
by plotting a time curve on one of the HV windings.
The average winding temperature rise is determined by
the change of resistance method from equations listed in
ANSI/IEEE C57.12. 91.

Insulation Resistance Test (Megger)

Data Subject to Change without Notice 9/3/99

You might also like