Introduction
ABB’s new ReliaGear High Power Busway can be utilized in building and industrial
applications to deliver power to electrical loads. Available in copper and aluminum,
the ReliaGear High Power Busway serves as an alternative to traditional cabling.
ABB’s ReliaGear High Power Busway range is a 600 V, totally The product offering is complete with elbows, offsets, flanges,
encased, non-ventilated, low impedance sandwich construction tees, end and center feed units, expansion units and splices
with epoxy resin coated copper and aluminum conductors. commonly required for a busway installation. Installation hangers
are also available to order.
The range is available from 800A to 4000A in aluminum and up
to 5000A in copper with a maximum 6 cycle RMS symmetrical Bus plugs with fusible switches or circuit breakers are available
short circuit rating of 200KA. It is available with multiple bar from 15 through 800 amps.
configurations to suit project requirements, including neutral,
double neutral, ground and half ground. Features
• Copper and aluminum conductors available in tin or silver
The bar is housed in aluminum casing which also acts as a coated-finish.
ground and is available with a choice of ingress protection • Joint pack construction with double headed shear nuts, for
ratings from IP40 to IP55 and IP 67 on request. It is available as quick installation.
Indoor feeder, indoor plug-in and sprinkler proof configura- • Up to five bus plug points per side on a 12-ft length.
tions. The busway is painted in grey (RAL 7035). Other colors • All bus plugs have mechanical/electrical interlocks with a
can be accommodated on request. ground first, break last safety feature.
• Pressed out tags for bus plug connections.
RELIAGEAR HIGH POWER BUSWAY 5
—
Standards
Standards
ReliaGear High Power Busway is UL857 listed and manufactured in a certified management system environment where Quality ISO
9001, Safety OHSAS 18001 and Environmental ISO 14001 standards are applied to all aspects of the manufacturing and installation
processes. We meet the requirements of NEMA, CSA (cUL), IEEE, ANSI, IEC & CE.
UL Listed
ABB completed extensive testing at UL accredited laboratories to ensure the product we supply meets UL requirements.
UL 857
Sub-clauses Description
8.2.1 Verification of Temperature Rise Limits
8.2.2 Verification of Dielectric Voltage Withstand Test
8.2.2.2 Clamped Joint Test
8.2.2.3 Reduced Insulation Thickness Test
8.2.3 Verification of Short Circuit Withstand
8.2.3.1.1.2 Dielectric Test Withstand Tests
8.2.6 Verification of Insulation Resistance and Dielectric Withstand After Exposure to Rain
8.2.7.1 Verification of Bending Resistance
8.2.7.2 Verification of Impact Strength
8.2.7.3 Verification of Crushing Resistance
8.2.7.4 Verification of Resistance to Bus Bar Pull Out
8.2.8 Verification of Overload and Endurance of Non-Switching Plug-in Devices
8.2.9 Verification of Resistance to Aging
8.2.10 Verification of Metallic Coating Thickness
8.2.11 Verification of Insulation Base and Support Strength
8.2.12 Gasket Tests
Ref to ANSI/UL 50 Type Rating Tests (Ingress Protection Tests) for the 2 series
Seismic compliance
The product range is certified for Seismic withstand capability and has a qualification level - high (Zone-5) in accordance to IEEE
standard 693-2005.
—
Technical features
Conductor/insulation system The plug-in busway lengths have tabs pressed into the conductor
ReliaGear High Power Busway is constructed from high purity to allow busplug units to be connected. This patented method
99.99% conductivity copper and high density 55% conductivity for creating the tabs does not require any welding process,
aluminum. The conductors are insulated with a Class B meaning the integrity of the conductor is not compromised.
(130 °C/266 °F) epoxy insulation applied uniformly by our
automated electrostatic coating process. The epoxy coating is Housing details
non-hygroscopic, chemical resistant and has outstanding heat The ReliaGear High Power Busway UL857 range is constructed
transfer characteristics making it ideal for sandwich construction with a rugged extruded all-aluminum housing with powder
applications. Epoxy has excellent dielectric strength, is flame coated paint finish. Aluminum offers numerous advantages
retardant and is impact resistant. The copper busbar is either when compared to steel housings.
tin or silver plated at the contact areas. Class F (155 °C/311 °F)
is also available on request. • Aluminum is a very light metal, about a third the weight of
steel on a per foot basis. This reduces transportation costs
The low impedance sandwich design: and makes the product much easier to install.
• Aluminum is non-magnetic and has a significant reduction in
• Improves heat dissipation. reactance and magnetic flux leakage when compared to steel.
• Improves short circuit rating. • Unlike steel which rusts, aluminum naturally produces a
• Reduces voltage drop/ impedance compared to cable. protective oxide coating which makes it highly corrosion
• Removes potential pathways for the propagation of flame, resistant. This means the product is more durable and
smoke and gas through the busway system. requires less maintenance.
• Aluminum is excellent at conducting heat and electricity
which means that the housing can be used as a ground along
the length of the busway.
—
Technical features
—
Straight lengths
Busplug shutter
Copper Aluminum
Busway Construction Busway size Busway Construction Busway size
rating type rating type
(amps) (amps)
Width Height Width Height
in mm in mm in mm in mm
800A Single 3.74" 95mm 5.83" 148mm 800A Single 4.72" 120mm 5.83" 145mm
1000A Single 4.33" 110mm 5.83" 148mm 1000A Single 5.51" 140mm 5.83" 145mm
1200A Single 4.72" 120mm 5.83" 148mm 1200A Single 6.30" 160mm 5.83" 145mm
1350A Single 5.32" 135mm 5.83" 148mm
1350A Single 6.89" 175mm 5.83" 145mm
1600A Single 6.30" 160mm 5.83" 148mm
1600A Single 8.07" 205mm 5.83" 145mm
2000A Single 7.87" 200mm 5.83" 148mm
2000A Single 10.24" 260mm 5.83" 145mm
2500A Single 9.84" 250mm 5.83" 148mm
3000A Double 13.58" 345mm 5.83" 148mm 2500A Double 14.76" 375mm 5.83" 145mm
4000A Triple 19.69" 500mm 5.83" 148mm 3000A Double 17.13" 435mm 5.83" 145mm
5000A Triple 23.82" 605mm 5.83" 148mm 4000A Triple 23.82" 605mm 5.83" 145mm
Note: The maximum and minimum sizes are not the extent of our offerings, but are a guildeline to help you choose the correct product. Dimensions are
taken from the center of the joint.
RELIAGEAR HIGH POWER BUSWAY 9
—
Elbows
Flatwise elbows
y Flatwise elbows are typically used to make 90° changes in the
direction of the busway system. There are two main types:
y flatwise up and flatwise down.
y
There are two main types: edgewise right and edgewise left.
These can be used to turn the busway route up or down if it is
running on its flat, or to turn the busway left and right if it is
running on its edge.
Custom elbows
While elbows are typically 90°, ABB can manufacture special angle
elbows if necessary for both flatwise and edgewise products.
Copper
Flatwise elbow (up or down)
Ratings (amps) Minimum leg size Standard leg size Maximum leg size
X Y X Y X Y
in mm in mm in mm in mm in mm in mm
800A 9.06" 230mm 9.06" 230mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
1000A 9.37" 238mm 9.37" 238mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
1200A 9.57" 243mm 9.57" 243mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
1350A 9.84" 250mm 9.84" 250mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
1600A 10.35" 263mm 10.35" 263mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
2000A 11.14" 283mm 11.14" 283mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
2500A 12.13 " 308mm 12.13" 308mm 14" 355mm 14" 355mm 30" 762mm 30" 762mm
3000A 13.98" 355mm 13.98" 355mm 20" 508mm 20" 508mm 30" 762mm 30" 762mm
4000A 17.05" 433mm 17.05" 433mm 20" 508mm 20" 508mm 30" 762mm 30" 762mm
5000A 19.13" 486mm 19.13" 486mm 20" 508mm 20" 508mm 30" 762mm 30" 762mm
—
Elbows
Aluminum
Flatwise elbow (up or down)
Ratings (amps) Minimum leg size Standard leg size Maximum leg size
X Y X Y X Y
in mm in mm in mm in mm in mm in mm
800A 9.763" 248mm 9.763" 248mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
1000A 9.960" 253mm 9.960" 253mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
1200A 10.551" 268mm 10.551" 268mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
1350A 10.826" 275mm 10.826" 275mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
1600A 11.220" 285mm 11.220" 285mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
2000A 12.322" 313mm 12.322" 313mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
2500A 14.330" 364mm 14.330" 364 mm 13.779" 350mm 13.779" 350mm 29.527" 750mm 29.527" 750mm
3000A 15.708" 399mm 15.708" 399mm 19.685" 500mm 19.685" 500mm 29.527" 750mm 29.527" 750mm
4000A 17.874" 454mm 17.874" 454mm 19.685" 500mm 19.685" 500mm 29.527" 750mm 29.527" 750mm
—
Offsets
Combination possibilities
x Flatwise offset up
x
Flatwise offset down
Edgewise offset right
Edgewise offset left
Offset sections
y y An offset is used to avoid obstacles such as pipes or steel
columns and to conform to the structure of the building. It is
basically two elbows fabricated into one single piece.
x x
There are four types of offset sections: flatwise offset up and
down, and edgewise offset left and right.
Flatwise offset Edgewise offset
Copper
Flatwise offset (up or down)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 9.06" 230mm 2" 51mm 26" 660mm 18.11" 460mm
1000A 9.37" 238mm 2" 51mm 26" 660mm 18.74" 476mm
1200A 9.57" 243mm 2" 51mm 26" 660mm 19.13" 486mm
1350A 9.84" 250mm 2" 51mm 26" 660mm 19.69" 500mm
1600A 10.35" 263mm 2" 51mm 26" 660mm 20.71" 526mm
2000A 11.14" 283mm 2" 51mm 26" 660mm 22.28" 566mm
2500A 12.13" 308mm 2" 51mm 26" 660mm 24.25" 616mm
3000A 13.98" 355mm 2" 51mm 26" 660mm 27.95" 710mm
4000A 17.05" 433mm 2" 51mm 26" 660mm 34.10" 866mm
5000A 19.13" 486mm 2" 51mm 26" 660mm 38.26" 972mm
—
Offsets
Aluminum
Flatwise offset (up or down)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 9.763" 248mm 2" 51mm 26" 660mm 19.527" 496mm
1000A 9.960" 253mm 2" 51mm 26" 660mm 19.921" 506mm
1200A 10.551" 268mm 2" 51mm 26" 660mm 21.102" 536mm
1350A 10.826" 275mm 2" 51mm 26" 660mm 20.866" 550mm
1600A 11.220" 285mm 2" 51mm 26" 660mm 22.440" 570mm
2000A 12.322" 313mm 2" 51mm 26" 660mm 24.645" 626mm
2500A 14.330" 364mm 2" 51mm 26" 660mm 28.661" 728mm
3000A 15.708" 399mm 2" 51mm 26" 660mm 31.417" 798mm
4000A 17.874" 454mm 2" 51mm 26" 660mm 35.748" 908mm
—
Combinations
Combination possibilities
Edgewise right/flatwise up
y
z
Edgewise right/flatwise down
Edgewise left/flatwise up
Edgewise left/flatwise down
x
Flatwise up/edgewise left
Flatwise up/edgewise right
y Flatwise down/edgewise left
Flatwise down/edgewise right
x z Combination elbows
Combination elbows are used to conform to the buildings'
Edge right flatwise up Flatwise up edgewise structure and to utilize a small amount of space to change
direction by combining both flatwise and edgewise elbows.
Copper
Combination elbows
Ratings (amps) Minimum leg size
X (edgewise side) Y Z (flatwise side)
in mm in mm in mm
800A 10" 254mm 6.77" 172mm 9.06" 230mm
1000A 10" 254mm 7.05" 179mm 9.37" 238mm
1200A 10" 254mm 7.24" 184mm 9.57" 243mm
1350A 10" 254mm 7.56" 192mm 9.84" 250mm
1600A 10" 254mm 8.03" 204mm 10.35" 263mm
2000A 10" 254mm 8.82" 224mm 11.24" 283mm
2500A 10" 254mm 9.80" 249mm 12.13" 308mm
3000A 10" 254mm 11.36" 297mm 13.98" 355mm
4000A 10" 254mm 14.69" 373mm 17.05" 433mm
5000A 10" 254mm 16.73" 425mm 19.13" 486mm
Combination elbows
Ratings (amps) Maximum leg size
X (edgewise side) Y Z (flatwise side)
in mm in mm in mm
800A 24" 610mm 19.06" 484mm 30" 762mm
1000A 24" 610mm 19.37" 492mm 30" 762mm
1200A 24" 610mm 19.57" 497mm 30" 762mm
1350A 24" 610mm 19.84" 504mm 30" 762mm
1600A 24" 610mm 20.35" 517mm 30" 762mm
2000A 24" 610mm 21.14" 537mm 30" 762mm
2500A 24" 610mm 22.13" 562mm 30" 762mm
3000A 24" 610mm 23.98" 609mm 30" 762mm
4000A 24" 610mm 27.05" 687mm 30" 762mm
5000A 24" 610mm 29.13" 740mm 30" 762mm
14 RELIAGEAR HIGH POWER BUSWAY
—
Combinations
Aluminum
Combination elbows
Ratings (amps) Minimum leg size
X (edgewise side) Y Z (flatwise side)
in mm in mm in mm
800A 10" 254mm 7.181" 182.4mm 9.763" 248mm
1000A 10" 254mm 7.574" 192.4mm 9.960" 253mm
1200A 10" 254mm 7.968" 202.4mm 10.551" 268mm
1350A 10" 254mm 8.263" 209.9mm 10.826" 275mm
1600A 10" 254mm 8.854" 224.9mm 11.220" 285mm
2000A 10" 254mm 9.937" 252.4mm 12.322" 313mm
2500A 10" 254mm 12.200" 309.9mm 14.330" 364mm
3000A 10" 254mm 13.381" 339.9mm 15.708" 399mm
4000A 10" 254mm 16.728" 424.9mm 17.874" 454mm
Combination elbows
Ratings (amps) Maximum leg size
X (edgewise side) Y Z (flatwise side)
in mm in mm in mm
800A 24" 610mm 19.763" 502mm 30" 762mm
1000A 24" 610mm 19.960" 507mm 30" 762mm
1200A 24" 610mm 20.551" 522mm 30" 762mm
1350A 24" 610mm 20.826" 529mm 30" 762mm
1600A 24" 610mm 21.220" 539mm 30" 762mm
2000A 24" 610mm 22.322" 567mm 30" 762mm
2500A 24" 610mm 24.330" 618mm 30" 762mm
3000A 24" 610mm 25.708" 653mm 30" 762mm
4000A 24" 610mm 27.874" 708mm 30" 762mm
RELIAGEAR HIGH POWER BUSWAY 15
—
Flanges
Flange connections
Flange connections provide a direct connection to low voltage
switchgear, transformer enclosures and other electrical
equipment. Cut out details, dimensions and drilling plans are
provided with the customer drawings and it is the responsibility
of the switchgear manufacturer to provide the opening, drill
fixing holes, connecting hardware and busway risers in their
equipment.
Copper
Panel flange
Ratings (amps) Minimum Maximum
X X
in mm in mm
800A 9" 229mm 33" 838mm
1000A 9" 229mm 33" 838mm
1200A 9" 229mm 33" 838mm
1350A 9" 229mm 33" 838mm
1600A 9" 229mm 33" 838mm
2000A 9" 229mm 33" 838mm
2500A 9" 229mm 33" 838mm
3000A 9" 229mm 33" 838mm
4000A 9" 229mm 33" 838mm
5000A 9" 229mm 33" 838mm
Aluminum
Panel flange
Ratings (amps) Minimum Maximum
X X
in mm in mm
800A 9" 229mm 33" 838mm
1000A 9" 229mm 33" 838mm
1200A 9" 229mm 33" 838mm
1350A 9" 229mm 33" 838mm
1600A 9" 229mm 33" 838mm
2000A 9" 229mm 33" 838mm
2500A 9" 229mm 33" 838mm
3000A 9" 229mm 33" 838mm
4000A 9" 229mm 33" 838mm
16 RELIAGEAR HIGH POWER BUSWAY
—
Combination flanges
Combination possibilities
x Panel flange/edgewise left Edgewise left/panel flange
Panel flange/edgewise right Edgewise right/panel flange
x
Panel flange/edgewise up Flatwise up/panel flange
Panel flange/edgewise down Flatwise down/panel flange
Combination flanges
A flange combination elbow is a combination of a standard
elbow and a standard flange. Flange combination elbows are
typically used when the minimum leg lengths for either the
standard elbow or the standard flange cannot be maintained.
y y
For example: when the busway must lay close to the top of the
Flatwise elbow flange Edgewise elbow flange
switchgear to avoid other services or when there is reduced
head height above the switchgear.
Copper
Flange/elbows (flatwise)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 9.06" 230mm 3.85" 98mm 30" 762mm 18.11" 460mm
1000A 9.37" 238mm 4.13" 105mm 30" 762mm 18.74" 476mm
1200A 9.57" 243mm 4.33" 110mm 30" 762mm 19.13" 486mm
1350A 9.84" 250mm 4.65" 118mm 30" 762mm 19.69" 500mm
1600A 10.35" 263mm 5.12" 130mm 30" 762mm 20.70" 526mm
2000A 11.14" 283mm 5.91" 150mm 30" 762mm 22.28" 566mm
2500A 12.13" 308mm 6.89" 175mm 30" 762mm 24.25“ 616mm
3000A 13.98" 355mm 8.78" 223mm 30" 762mm 27.95" 710mm
4000A 17.05" 433mm 11.81" 300mm 30" 762mm 34.09" 866mm
5000A 19.13" 486mm 13.90" 353mm 30" 762mm 38.27" 972mm
Flange/elbows (edgewise)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1200A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1350A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1600A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
2000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
2500A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
3000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
4000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
5000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
RELIAGEAR HIGH POWER BUSWAY 17
Aluminum
Flange/elbows (flatwise)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 9.763" 248mm 3.149" 80mm 30" 762mm 19.527" 496mm
1000A 9.960" 253mm 3.543" 90mm 30" 762mm 19.921" 506mm
1200A 10.551" 268mm 3.937" 100mm 30" 762mm 21.102" 536mm
1350A 10.826" 275mm 4.232" 107.5mm 30" 762mm 21.653" 550mm
1600A 11.220" 285mm 4.822" 122.5mm 30" 762mm 22.440" 570mm
2000A 12.322" 313mm 5.905" 150mm 30" 762mm 24.645" 626mm
2500A 14.330" 364mm 6.496" 165mm 30" 762mm 28.661" 728mm
3000A 15.708" 399mm 7.677" 195mm 30" 762mm 31.417" 798mm
4000A 17.874" 454mm 12.677" 322mm 30" 762mm 35.748" 908mm
Flange/elbows (edgewise)
Ratings (amps) Minimum leg size Maximum leg size
X Y X Y
in mm in mm in mm in mm
800A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1200A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1350A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
1600A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
2000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
2500A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
3000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
4000A 10" 254mm 5" 127mm 24" 610mm 20" 508mm
18 RELIAGEAR HIGH POWER BUSWAY
—
Specials
Flatwise tees
Flatwise tees are used to split one busway run into two runs
x going in different directions. This can be very useful in utilizing a
small amount of space and supplying two different areas of a
building with power. Flatwise tees are a combination of a feeder
length and a flatwise elbow.
Copper
Flatwise tee
Ratings (amps) Minimum leg size Standard leg size Maximum leg size
X Y X Y X Y
in mm in mm in mm in mm in mm in mm
800A 18.11" 460mm 9.06" 230mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
1000A 18.39" 476mm 9.37" 238mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
1200A 19.13" 486mm 9.57" 243mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
1350A 19.69" 500mm 9.84" 250mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
1600A 20.71" 526mm 10.35" 263mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
2000A 22.28" 566mm 11.14" 283mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
2500A 24.25“ 616mm 12.13" 308mm 28" 711mm 14" 356mm 60" 1524mm 26" 660mm
3000A 27.95" 710mm 13.98" 355mm 40" 1016mm 20" 508mm 60" 1524mm 26" 660mm
4000A 34.09" 866mm 17.05" 433mm 40" 1016mm 20" 508mm 60" 1524mm 26" 660mm
5000A 38.27" 972mm 19.13" 486mm 40" 1016mm 20" 508mm 60" 1524mm 26" 660mm
Aluminum
Flatwise tee
Ratings (amps) Minimum leg size Standard leg size Maximum leg size
X Y X Y X Y
in mm in mm in mm in mm in mm in mm
800A 19.527" 496mm 9.763" 248mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
1000A 19.921" 506mm 9.960" 253mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
1200A 21.102" 536mm 10.551" 268mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
1350A 21.653" 550mm 10.826" 275mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
1600A 22.440" 570mm 11.220" 285mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
2000A 24.645" 626mm 12.322" 313mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
2500A 28.661" 728mm 14.330" 364mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
3000A 31.417" 798mm 15.708" 399mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
4000A 35.748" 908mm 17.874" 454mm 28" 711mm 28" 356mm 60" 1524mm 26" 660mm
RELIAGEAR HIGH POWER BUSWAY 19
—
Miscellaneous
Expansion units
Expansion units are fittings used to accommodate the expansion and contraction of
a busway system and building movement. Expansion units are typically installed in
the center of long busway runs, and might also be used at the beginning of riser runs
to minimize the stress on the lower section of the busway run. Another common use
is where a busway crosses an expansion joint of a building.
Expansion units are recommended when a straight busway run exceeds 60m.
Expansion units allow for a 40mm movement along the length of the busway.
20 RELIAGEAR HIGH POWER BUSWAY
—
Splice
If any red disks are still present after installation, the joints
have not been properly secured.
RELIAGEAR HIGH POWER BUSWAY 21
—
Installation
Installation
Busway can either be installed to run on its “flat" or on its “edge." This installation decision is governed by a number of factors:
Special sections
We manufacture a variety of more specialized units and components to meet unique system requirements ranging from edgewise
tees, flatwise crosses, step up/step down reducers, phase rotation units, in-line disconnect cubicles, in-line busplug units, custom
built busway connection units.
ABB has the ability to manufacture a wide range of specialize busway for various and unique applications.
Please contact ABB with your specialized application, our engineering team will work with you to customize a solution.
22 RELIAGEAR HIGH POWER BUSWAY
—
Technical data—copper
—
Technical data—aluminum
—
Quick reference guide
Busplug clearances:
• Ensure adequate space is given to allow the busplug unit to
be operated both easily and safely. Ambient temperature (°F) Multiplier
131 1
Feeder busway length: 140 0.95
• Minimum length – 2 ft 149 0.9
• Maximum length – 12 ft 158 0.85
167 0.8
Plug-in busway length: 176 0.74
• Minimum length – 2 ft
185 0.68
• Maximum length – 12 ft
Critical details
• Busway drawing must have all relevant dimensions.
• Center-line dimensions are standard, please highlight any
dimensions that are not center-line dimensions.
• Walls and floors must be located, shown and dimensioned.
• The front of all switchboards must be given and the phasing
for any existing boards provided.
• Transformer connections require full details.
• When using rising busway, please note the phase orientation
of the plug-in sections.
• Horizontal plug-in busway positioned on its flat must always
be oriented with the neutral phase to the top.
RELIAGEAR HIGH POWER BUSWAY 27
—
ABB Inc.
Electrification Products
8155 T&B Boulevard
Memphis, TN 38125
abb.com/lowvoltage
Technical Support: 888-385-1221
7:00 a.m. - 5:00 p.m., CST, Monday-Friday
ABB
Electrification Products
800 Hymus Boulevard
Saint-Laurent, Quebec, Canada
H4S 0B5
abb.ca/lowvoltage
Phone: 514-856-6266
Toll Free: 888-856-6266
ep.support@ca.abb.com
—
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With regard
to purchase orders and/or contracts, the
agreed particulars shall prevail. ABB Inc.
does not accept any responsibility what-
soever for potential errors or possible lack
of information in this document.