UTILITY
MV0
Q001HV 250A
Q002HV 100A
500 kVA
11/0,4KV
TRANSFORMER T001
A DYN11
Q001LV 800A
A
Q005LV 800A
Q006LV 800A
GENERATOR 1 GENERATOR 2
455kVA Continuous Power Rating 455kVA Continuous Power Rating
@ 0,8 pf (360kW DCC) @ 0,8 pf (360kW DCC)
Generator 1 Generator 2
800A 800A
Circuit Breaker in canopy Circuit Breaker in canopy
MVG1 MVG2
B B
QF01:1 800A QF01:2 800A QF01:3 LOAD QF01:4 NG 125L QF02:1 800A QF02:2 800A QF02:3 LOAD QF02:4 NG 125L
BANK C 63A BANK C 63A
50kA 50kA
SURGE SURGE
BREAKERS BREAKERS
SPD SPD
MV1 MV2
3x CT'S 3x CT'S 3x CT'S 3x CT'S 3x CT'S
800/5 800/5 800/5 800/5 800/5
C SP20-G1B
STAND BY POWER
SOURCE
SP20-G2B
STAND BY POWER
MONITORING
UP10-A
UTILITY POWER
MONITORING
SP20-G1B
STAND BY POWER
SOURCE
SP20-G2B
STAND BY POWER
MONITORING
C
Q1A Q2A Q3A Q6A Q6B Q1B Q2B
NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A
5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC
MV-A MV-B
SPS A SPS B
POWER
SUPPLY
3x CT'S
800/5
3x CT'S
800/5
TOTAL SPS B DISTRIBUTION
POWER
SUPPLY
D
FROM
CONTROL-
UNIT Comms
to Control
SPS A-TD40-F1,F2,F3
C60x3
1A
SPS B-TD40-F1,F2,F3
C60x3
1A
Comms
to Control
FROM
CONTROL-
UNIT SWITCHGEAR MLVDB B, ENERGY CENTER B (EC B)
SPS A-TD40 SPS B-TD40
SPS A-Q10 SPS A-Q11 SPS A-Q4 SPS B-Q4 SPS B-Q12 SPS B-Q10
UPS A UPS A NG 125L NG 125L UPS B UPS B
MAIN INPUT WRAP C 63A C 63A WRAP MAIN INPUT
NSX 400N AROUND 50kA 50kA AROUND NSX 400N
50KA NSX 300N 300A SURGE SURGE NSX 300N 300A 50KA
MLC 2.3 50KA BREAKERS BREAKERS 50KA MLC 2.3
UPS SYSTEM A (IT) MLC 2.3 MLC 2.3 UPS SYSTEM B (IT)
SPD SPS A SPD SPS B
E E
F F
G G