1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

UTILITY
MV0
Q001HV 250A

Q002HV 100A

500 kVA
11/0,4KV
TRANSFORMER T001
A DYN11

Q001LV 800A
A

Q002LV 800A Q003LV 800A Q004LV


BY-PASS NG 125L
C 63A
50kA
400 V SURGE
Automatic
AVR001 Voltage
BREAKERS
Regulator
SPD

Q005LV 800A

Q006LV 800A

GENERATOR 1 GENERATOR 2
455kVA Continuous Power Rating 455kVA Continuous Power Rating
@ 0,8 pf (360kW DCC) @ 0,8 pf (360kW DCC)
Generator 1 Generator 2
800A 800A
Circuit Breaker in canopy Circuit Breaker in canopy

MVG1 MVG2
B B
QF01:1 800A QF01:2 800A QF01:3 LOAD QF01:4 NG 125L QF02:1 800A QF02:2 800A QF02:3 LOAD QF02:4 NG 125L
BANK C 63A BANK C 63A
50kA 50kA
SURGE SURGE
BREAKERS BREAKERS

SPD SPD

MV1 MV2
3x CT'S 3x CT'S 3x CT'S 3x CT'S 3x CT'S
800/5 800/5 800/5 800/5 800/5

SP20-G1B-F1,F2,F3 SP20-G2B-F1,F2,F3 SP20-G1B-F1,F2,F3 SP20-G2B-F1,F2,F3


C60x3 C60x3 Comms C60x3 Comms C60x3 C60x3 Comms
1A 1A to Control 1A to Control 1A 1A to Control

C SP20-G1B
STAND BY POWER
SOURCE
SP20-G2B
STAND BY POWER
MONITORING
UP10-A
UTILITY POWER
MONITORING
SP20-G1B
STAND BY POWER
SOURCE
SP20-G2B
STAND BY POWER
MONITORING
C
Q1A Q2A Q3A Q6A Q6B Q1B Q2B
NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A
5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC

Q4A Q5A Q4B Q5B


NT06 H1/630A NT06 H1/630A NT06 H1/630A NT06 H1/630A
5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC

MV-A MV-B

Q1A Q2A Q1B Q2B


NW08 N1/800A NW08 N1/800A NW08 N1/800A NW08 N1/800A
5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC 5,0 MICROLOGIC

SPS A SPS B

D TOTAL SPS A DISTRIBUTION

POWER
SUPPLY
3x CT'S
800/5
3x CT'S
800/5
TOTAL SPS B DISTRIBUTION

POWER
SUPPLY
D
FROM
CONTROL-
UNIT Comms
to Control
SPS A-TD40-F1,F2,F3
C60x3
1A
SPS B-TD40-F1,F2,F3
C60x3
1A
Comms
to Control
FROM
CONTROL-
UNIT SWITCHGEAR MLVDB B, ENERGY CENTER B (EC B)
SPS A-TD40 SPS B-TD40

SPS A-Q10 SPS A-Q11 SPS A-Q4 SPS B-Q4 SPS B-Q12 SPS B-Q10
UPS A UPS A NG 125L NG 125L UPS B UPS B
MAIN INPUT WRAP C 63A C 63A WRAP MAIN INPUT
NSX 400N AROUND 50kA 50kA AROUND NSX 400N
50KA NSX 300N 300A SURGE SURGE NSX 300N 300A 50KA
MLC 2.3 50KA BREAKERS BREAKERS 50KA MLC 2.3
UPS SYSTEM A (IT) MLC 2.3 MLC 2.3 UPS SYSTEM B (IT)
SPD SPS A SPD SPS B

UPS A-Q20 Circuit Breaker UPS B-Q20 Circuit Breaker


NSX 300N 300A, 50 kA NSX 300N 300A, 50 kA

TOTAL UPS A DISTRIBUTION TOTAL UPS B DISTRIBUTION

POWER 3x CT'S 3x CT'S POWER


SUPPLY 250/5 250/5 SUPPLY
FROM FROM
CONTROL- UPS A-F1,F2,F3 UPS B-F1,F2,F3 CONTROL-
UNIT Comms C60x3 C60x3 Comms UNIT
to Control 1A 1A to Control

UPS A-TD20 UPS B-TD20

E E

F F

G G

DRAWN DESIGN CHECKED


Peter Carlstein Peter Carlstein Johan Thörnberg
2016-01-22 2016-01-22 2016-01-25
7505 ENERGY CENTRE
H eCENTRE H
DWG. CHECKED AND APPR. IN ACC. TO QCM 064.0
ICOLO, KENYA
- -
0 ISSUE FOR REVIEW PCA 2016-01-22 MJO 2016-01-22 JTH 2016-01-25 PROPRIETARY INFORMATION Dubbgatan 2
ELECTRICAL SINGLE LINE DIAGRAM
This drawing contains proprietary information belonging to Flexenclosure AB SE-534 50 Vara, Sweden
REFERENCE DRAWINGS/DOCUMENTS REVISION and may not be wholly or partially reproduced nor disclosed without prior Tel. +46 (0) 510-42 70 00
written permission. ® Flexenclosure AB 2007 7505-E-SLD-002 0
1 2 3 4 5 6 7 10 11 12 13 14 15 16