Professional Documents
Culture Documents
11 - Chapter 3
11 - Chapter 3
CHAPTER 3
3.1 INTRODUCTION
Khodr et al. (2002) fixed the standards for the losses in the
electrical distribution as low, medium, and high (below 0.6, 0.6 -1.85, above
1.85%). NEMA Standard TPI (2002) catered the standard and optimum
efficiency for transformer having both linear and non-linear loads. Wei Jen
Lee & Kenarangawi (2002) gave a suggestion to release the load on
transformer by reducing the inrush current of motors to improve power factor
and increase the efficiency with use of soft starter. Aleksandar (2004)
suggested minimising the error in the transformer loss calculation by taking
care the additional current due to non-linear loads and the voltage drop during
the voltage transformation between primary and secondary.
with the same capacity is suggested by to make the network more efficient.
Liang et al. (2012) gave a solution for avoiding the over load on transformer
with nonlinear loads by minimising harmonic level. Trinh Trong Chuong etal
(2015) indicated that voltage stability is increased through reduction of
additional reactive power requirement due to variation in load and this results
reduction in loading of service equipment like transformers. Fatih and Yilmaz
(2015) recommended amorphous core type transformer having low loss
compared to the steel core transformer is recommended for efficiency
increase in transformer for the same loading level. Saidi and Hammami (2015)
insisted to reduce the CO2 emission through optimum loading and efficient
usage of energy with service equipment keeping the same productivity.
by the transformer. The results are verified with the field study with energy
measurement at input and output of the transformer.
3.3 METHODOLOGY
e) Compute the apparent power of the transformer which is actual load and
express as per cent of its rated capacity.
30
f) Calculate the losses from actual load test results and derive its operating
efficiency and energy wastage as a per cent of total energy consumption of
the industry.
Measurements
Transformer rated Capacity = kVA1
Existing Reactive Power at PCC = kVAr1 (in general, it is inductive)
Reactive power compensated with = kVAr2
capacitors at PCC
Reactive power at PCC = kVAr3
aftercompensation
Measured full load Active power = kW
(Adding active power of all feeder values)
Measured full load Apparent power = kVA2
(Adding apparent of all feeder values)
Apparent Power at PCC = kVA3
after reactive power compensation
START
TRANSFORMER RATED
CAPACITY=KVA
% LOADING= ×100
IS LOADING No
50-60% of
TRANSFORMER
CAPACITY
Yes
DO TRANSFORMER LOAD SHARING/ARGUMENTATION
END
35
3.8.4 Results
With the data obtained from study, analysis was done with
conventional method (secondary current) and proposed method (power flow
analysis) to estimate the loading per cent of transformer and the result is
shown in Table 3.5.
Per cent
Loading estimation by Measured Rated
Loading
733.5 A 722 A 101.6 %
Conventional Method
Proposed Method 527.2 kVA 500 kVA 105.4 % *
3.8.5 Interpretation
107
105.4 %
105
Loadin g in per cent
103
101.6 %
101
99
Secondary Current Method Power Flow Method
Transformer Loading Estimation
0.8
Transformer Losses
0.4
0.2
0
Theoritical Estimation Units Actual Measurement Units
Loss due to Over Loading
3.10 CONCLUSION