TECHNICAL SPECIFICATION OF LV POWER, CONTROL & INSTRUMENT CABLE

This document is the INTELLECTUAL PROPERTY of


ANDRITZ HYDRO Pvt. Ltd.

FOR APPROVAL

24.12.2019 Lokesh Chauhan

Date Representative

OWNER/CLIENT: M/s. BUNGAL HYDRO PVT. LTD. OWNER’S ENGINEER:

PROJECT : UPPER SANIGAD HEP


(2x5.35MW + 10%COL)

0 First Issue / Initial Release PRAVEEN LOKESH 24.12.2019


LOKESH
Rev Modifications Prepared Checked By
Date
Approved BY
TITLE: By
TECHNICAL SPECIFICATION OF LV POWER, CONTROL& INSTRUMENT CABLE

Client M/s. Bungal Hydro Pvt. Ltd. Prepared PRAVEEN 24.12.2019 File name -
Plant UPPER SANIGAD HEP (2 x 5.35MW + 10% COL) Cheked by LOKESH 24.12.2019
Contract NO. C-90-830525 Approved LOKESH 24.12.2019 File date 24.12.2019
=
Internal No.
+
Page 1
Document No. US-PC-02-0360 Rev 00 of 2
A4
TECHNICAL SPECIFICATION OF LV POWER, CONTROL & INSTRUMENT CABLE

PROJECT INFORMATION
Supplier Comments
Description Input
if any
Client M/s. BUNGAL Hydro Pvt. Ltd.
Design Temperature 40 °C
Ambient Air Temperature 24.7 °C
Minimum Temperature 11.5 °C
Seismic Maximum Horizontal
Acceleration 0.18 g
This document is the INTELLECTUAL PROPERTY of

Seismic Maximum Vertical Ac-


celeration 0.09 g
ANDRITZ HYDRO Pvt. Ltd.

Relative Air Humidity 58.03%


Altitude in meter 1300 m
Pollution Level Heavy
Powerhouse type Surface

ENCLOSURES:
**Andritz QAP is enclosed for major equipment’s, supplier to confirm same. In case of no response from
supplier on QAP, it will be considered as confirmed.
Please refer attached ‘Annexures’ for more details.

Client M/s. Bungal Hydro Pvt. Ltd. Prepared PRAVEEN 24.12.2019 File name -
Plant UPPER SANIGAD HEP (2 x 5.35MW + 10% COL) Cheked by LOKESH 24.12.2019
Contract NO. C-90-830525 Approved LOKESH 24.12.2019 File date 24.12.2019
=
Internal No.
+
Page 2
Document No. US-PC-02-0360 Rev 00 of 2
A4
ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : BILL OF MATERIAL


Sr No. Description for Cable Quantity in mtr Unit Price Total Price Remarks
DC Cable:
1 2C x 2.5 Sqmm|Armoured|Copper|FR|XLPE Cable 2500
2 2C x 4 Sqmm|Armoured|Copper|FR|XLPE Cable 3500 CT & PT more
3 2C x 25 Sqmm|Armoured|Copper|FR|XLPE Cable 200
AC Cable:
1 3.5C x 35 Sqmm|ARM.|CU|FR|XLPE Cable 200
2 3.5C x 150 Sqmm|ARM.|CU|FR|XLPE Cable 250
Control & Instrumentation Cable:
1 4C X 4 Sqmm|ARM.|CU|FR|XLPE Cable 6000 CT & PT more
2 7C X 1.5 Sqmm|ARM.|CU|FR|PVC Cable 3000
3 12C X 1.5 Sqmm|ARM.|CU|FR|PVC Cable 5000
4 2X2X0.75 Sqmm|ARM.|CU|FR|PVC Cable 1000
5 7X2X0.75 Sqmm|ARM.|CU|FR|PVC Cable 800

Annexure_Cable BOM Page 1 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Remarks
o.
RD
AC & DC Power Cable:
1 No of Cores 3.5 CORE 3.5 CORE 2 CORE 2 CORE 2 CORE
2 Size in Sq.mm. 150 35 2.5 4 25
3 Name of Manufacturer
4 Cable Type XFY(P) /FR XFY(P) /FR XFY(P) /FR XFY(P) /FR XFY(P) /FR
5 Armoured/Unarmoured type armoured armoured armoured armoured armoured
6 Applicable Standard IS/IEC IEC 60502-1 IEC 60502-1 IEC 60502-1 IEC 60502-1 IEC 60502-1
7 Voltage Grade (kV) KV 0.6/1.0 (1.2) 0.6/1.0 (1.2) 0.6/1.0 (1.2) 0.6/1.0 (1.2) 0.6/1.0 (1.2)
Suitability for earthed / unearthed
8 For both For both For both For both For both
System
Permissible Voltage & frequency
9 % ± 10 ± 10 ± 10 ± 10 ± 10
variation for Satisfactory operation
Max. rated conductor temp.
10 Deg C 90 90 90 90 90
(Continuous Operation)
Max. allowable conductor
11 Deg C 250 250 250 250 250
temperature during short circuit(
12 Conductor
Electrolytic Grade Electrolytic Grade Electrolytic Grade
H4 Grade Aluminium H4 Grade Aluminium
Copper Stranded Copper Stranded Copper Stranded
a Material Stranded Class-2 As Stranded Class-2 As
Class-2 As Per IEC Class-2 As Per IEC Class-2 As Per IEC
Per IEC 60228 Per IEC 60228
60228 60228 60228
b Shape Sector Sector Circular Circular Circular
c Cross Sectional area mm2 150 35 2.5 4 25
d Minimum No. of strands Nos
37.000/3.180 7.000/2.520 ## ## ##
e Nominal dia of each strand mm
f Whether strands are tinned (Yes/No) Y/N N N N N N
Temperature coefficient of resistance Cu - 0.00403 Cu - 0.00403 Cu - 0.00403 Cu - 0.00403 Cu - 0.00403
g
at 20 Deg C Al - 0.00393 Al - 0.00393 Al - 0.00393 Al - 0.00393 Al - 0.00393
13 Insulation
THE EXTRUDED THE EXTRUDED THE EXTRUDED THE EXTRUDED THE EXTRUDED
CROSSLINKABLE CROSSLINKABLE CROSSLINKABLE CROSSLINKABLE CROSSLINKABLE
a Material mm
COMPOUND (XLPE) COMPOUND (XLPE) COMPOUND (XLPE) COMPOUND (XLPE) COMPOUND (XLPE)
As Per IEC 60502-1 As Per IEC 60502-1 As Per IEC 60502-1 As Per IEC 60502-1 As Per IEC 60502-1
b Nominal Thickness mm 1.8 0.9 0.7 0.7 0.7
c Calculated dia over Insulation ## ## ## ## ##
Red,Yellow,Blue & Red,Yellow,Blue &
d Core identification ohm-cm Red,Black Red,Black Red,Black
Black Black
Minimum value of resistivity at 20
e ohm-cm 1 x 1014 1 x 1014 1 x 1014 1 x 1014 1 x 1014
Deg C

Annexure_TECH. DATA (Power) Page 2 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Remarks
o.
RD
AC & DC Power Cable:
1 No of Cores 3.5 CORE 3.5 CORE 2 CORE 2 CORE 2 CORE
2 Size in Sq.mm. 150 35 2.5 4 25
Minimum value of resistivity at 90 12 12
f 1 x 10 1 x 10 1 x 1012 1 x 1012 1 x 1012
Deg C
g Average dielectric strength mm 40 40 40 40 40
Suitability with regard to moisture,
h Good Good Good Good Good
acid,oil and alkaline surroundings
i Calculated Laid up dia ## ## ## ## ##
14 Inner Sheath
Extruded FR Extruded FR Extruded FR Extruded FR Extruded FR
a Material mm compound as per compound as per compound as per compound as per compound as per
IEC 60502-I IEC 60502-I IEC 60502-I IEC 60502-I IEC 60502-I
b Extruded or Wrapped mm Extruded Extruded Extruded Extruded Extruded
c Thickness (Min.) 0.6 0.4 0.4 0.4 0.4
d Calculated dia over I/Sh. ## ## ## ## ##
15 Armour
SINGLE G S FLAT SINGLE G S FLAT SINGLE G S SINGLE G S SINGLE G S
a Material mm TYPE A As Per IEC TYPE A As Per IEC ROUND WIRE As ROUND WIRE As ROUND WIRE As
60502-1 60502-1 Per IEC 60502-1 Per IEC 60502-1 Per IEC 60502-1
b Type of Armour mm STRIP-A STRIP-A ROUND WIRE ROUND WIRE ROUND WIRE
c Nominal Dimensions 4 x 0.8 ## ## ## ##
d Calculated diameter over armour ## ## ## ## ##
16 Outer Sheath
Extruded FR Extruded FR Extruded FR Extruded FR Extruded FR
a Material mm compound as per compound as per compound as per compound as per compound as per
IEC 60502-I IEC 60502-I IEC 60502-I IEC 60502-I IEC 60502-I
b Whether extruded type Extruded Extruded Extruded Extruded Extruded
c Thickness (Min.) 2.12 1.24 1.24 1.24 1.24
d Colour of outer sheath mm Black Black Black Black Black
Whether anti-termite treatment has
e mm Yes Yes Yes Yes Yes
been given in the outer
f Tolerance of cable under sheath mm As per IEC 60502-1 As per IEC 60502-1 As per IEC 60502-1 As per IEC 60502-1 As per IEC 60502-1
Calculated. Dia of the cable under
17 Kg/KM ## ## ## ## ##
the sheath
18 Appr. Overall Dia. of Cable A ## ## ## ## ##
19 Appr. Weight of Cable Deg.C ## ## ## ## ##
Continuous Current carrying
20 Deg.C
capacities for conditions
a Air Temperature cm 40 40 40 40 40

Annexure_TECH. DATA (Power) Page 3 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Remarks
o.
RD
AC & DC Power Cable:
1 No of Cores 3.5 CORE 3.5 CORE 2 CORE 2 CORE 2 CORE
2 Size in Sq.mm. 150 35 2.5 4 25
Deg C-
b Ground Temperature 30 30 30 30 30
cm/W
21 Depth of laying A 75 75 75 75 75
22 Thermal Resistivity of soil A 150 150 150 150 150
a In ground (A) A ## ## ## ## ##
b In duct (A) mm ## ## ## ## ##
kg/sq.m
c In air (A) ## ## ## ## ##
m
12 times of Over all 12 times of Over all 12 times of Over all 12 times of Over all 12 times of Over all
d Minimum bending radius kA
Diameter Diameter Diameter Diameter Diameter
Safe Pulling force Pulled by pulling (ohm/km 3 kg/sq.mm of 3 kg/sq.mm of 5 kg/sq.mm of 5 kg/sq.mm of 5 kg/sq.mm of
23
eye (kg) ) Aluminium area Aluminium area Copper area Copper area Copper area
Short ckt current carrying capacity of (ohm/km
24 ## ## ## ## ##
conductor for one second )
Max. DC Resistance of Conductor at
25 Deg C ## ## ## ## ##
20 Deg C (ohm/km)
Max.AC Resistance at 90 °C
26 Deg C ## ## ## ## ##
(ohms/km)
(ohm/km
27 Voltage drop ## ## ## ## ##
)
Max permissible conductor
28
temperature
a Under Continuous full load condition 90 90 90 90 90
b Under Transient loading condition mm 250 250 250 250 250
27 Loss Tangent at normal frequency mm 0.004 0.004 0.004 0.004 0.004
29 Reactance at 50 Hz (ohm/km) mm 0.0711 ## ## ## ##
30 Capacitance at 50 Hz (μF/km) Kg 0.616 ## ## ## ##
31 Cable Drum +2%
a Over all dimensions of the drum
b Approx. Flange dia %
c Approx. Barrel dia Deg C 2000 x 800 x 940 ## ## ## ##
d Approx. Traverse dia %
Approx. total weight of the empty
e % ## ## ## ## ##
drum
Max Length that can be supplied in
f 500 1000 1000 1000 1000
single drum
32 Flame Retardant Prop. FR FR FR FR FR

Annexure_TECH. DATA (Power) Page 4 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Remarks
o.
RD
AC & DC Power Cable:
1 No of Cores 3.5 CORE 3.5 CORE 2 CORE 2 CORE 2 CORE
2 Size in Sq.mm. 150 35 2.5 4 25
Min. 30% as per Min. 30% as per Min. 30% as per Min. 30% as per Min. 30% as per
a Oxygen Index
ASTMD 2863 ASTMD 2863 ASTMD 2863 ASTMD 2863 ASTMD 2863

Min. 280⁰C @ 21% Min. 280⁰C @ 21% Min. 280⁰C @ 21% Min. 280⁰C @ 21% Min. 280⁰C @ 21%
b Temperature Index Oxygen index as per Oxygen index as per Oxygen index as per Oxygen index as per Oxygen index as per
ASTMD 2863. ASTMD 2863. ASTMD 2863. ASTMD 2863. ASTMD 2863.
Smoke density 20% Smoke density 20% Smoke density 20% Smoke density 20% Smoke density 20%
Max. & Light Max. & Light Max. & Light Max. & Light Max. & Light
c Smoke Density Rating mm transmittace 80% transmittace 80% transmittace 80% transmittace 80% transmittace 80%
min as per ASTMD min as per ASTMD min as per ASTMD min as per ASTMD min as per ASTMD
2843 2843 2843 2843 2843
0.5% Max. (by 0.5% Max. (by 0.5% Max. (by 0.5% Max. (by 0.5% Max. (by
d Max. HCL Emission Weight) as per IEC Weight) as per IEC Weight) as per IEC Weight) as per IEC Weight) as per IEC
60754-1 60754-1 60754-1 60754-1 60754-1
As per IEC-60332- As per IEC-60332- As per IEC-60332- As per IEC-60332- As per IEC-60332-
e Flammability Test no/mm 1/SS-424-1475/IEEE- 1/SS-424-1475/IEEE- 1/SS-424-1475/IEEE- 1/SS-424-1475/IEEE- 1/SS-424-1475/IEEE-
383/IEC-60332-3 383/IEC-60332-3 383/IEC-60332-3 383/IEC-60332-3 383/IEC-60332-3
33 Embossing/Printing ## ## ## ## ##
34 Individual Screen
a Material mm N.A. N.A. N.A. N.A. N.A.
b Nominal Thickness mm N.A. N.A. N.A. N.A. N.A.
c Material of Drain Wire no/mm N.A. N.A. N.A. N.A. N.A.
d Size of Drain Wire N.A. N.A. N.A. N.A. N.A.
35 Collective Screen
a Material N.A. N.A. N.A. N.A. N.A.
b Nominal Thickness mm N.A. N.A. N.A. N.A. N.A.
c Material of Drain Wire N.A. N.A. N.A. N.A. N.A.
d Size of Drain Wire N.A. N.A. N.A. N.A. N.A.
Packing as per Andritz packing procedure
"##" MARKED FOR SUPPLIER INPUT. TO BE FILLED IN THE SUPPLIER DATA

Annexure_TECH. DATA (Power) Page 5 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Deviation
o.
RD
No of Cores 7 12 2P 7P 4
Size in Sq.mm. 1.5 1.5 0.75 0.75 4
1 Name of Manufacturer
Str Str
2 Cable Type Str XWY(P)/FR Str XWY(P)/FR XWY(P)/FR/ALT/I/O XWY(P)/FR/ALT/I/O Str XWY(P)/FR
Scr Scr
3 Armoured/Unarmoured type armoured armoured armoured armoured armoured
4 Applicable Standard IS/IEC IS:7098 Pt(1)/1988 IS:7098 Pt(1)/1988 IS:7098 Pt(1)/1988 IS:7098 Pt(1)/1988 IS:7098 Pt(1)/1988
5 Voltage Grade KV 1.1 (1.2) 1.1 (1.2) 1.1 (1.2) 1.1 (1.2) 1.1 (1.2)
Suitability for earthed / unearthed
6 For both For both For both For both For both
System
Permissible Voltage & frequency
7 % ± 10 ± 10 ± 10 ± 10 ± 10
variation for Satisfactory operation
Max. rated conductor temp.
8 Deg C 90 90 90 90 90
(Continuous Operation)
Max. allowable conductor
9 Deg C 250 250 250 250 250
temperature during short circuit
10 Conductor
Plain annealed Plain annealed Plain annealed Plain annealed Plain annealed
i Material Copper to Copper to Copper to Copper to Copper to
IS:8130/1984 IS:8130/1984 IS:8130/1984 IS:8130/1984 IS:8130/1984
ii Shape Stranded Circular Stranded Circular Stranded Circular Stranded Circular Stranded Circular
iii Cross Sectional area mm2 1.5 1.5 0.75 0.75 4
iv Minimum No. of strands Nos 7 7 7 7 7
v Nominal dia of each strand mm 0.53 0.53 0.37 0.37 ##
vi Whether strands are tinned (Yes/No) Y/N N N N N N
11 Insulation
Cross Linked
i Material Polyethylene (PVC) Polyethylene (PVC) Polyethylene (PVC) Polyethylene (PVC)
Polyethylene (XLPE)
ii Nominal Thickness mm 0.7 0.7 0.44 0.44 0.7
iii Calculated dia over Insulation mm 2.8 2.8 1.9 1.9 ##
Grey colour with Grey colour with
Red,Yellow,Blue,Bla
iv Core identification black number black number Black & Blue Black & Blue
ck
printing printing
Minimum value of resistivity at 20
v ohm-cm 1 x 1014 1 x 1014 1 x 1014 1 x 1014 1 x 1014
Deg C
Minimum value of resistivity at 90
vi ohm-cm 1 x 1012 1 x 1012 1 x 1012 1 x 1012 1 x 1012
Deg C

Annexure_TECH. DATA (Control) Page 6 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Deviation
o.
RD
No of Cores 7 12 2P 7P 4
Size in Sq.mm. 1.5 1.5 0.75 0.75 4
Suitability with regard to moisture,
viii Good Good Good Good
acid,oil and alkaline surroundings
ix Calculated Laid up dia mm ## 11.6 ##
12 Inner Sheath
PVC Type ST2 to PVC Type ST2 to PVC Type ST2 to PVC Type ST2 to PVC Type ST2 to
i Material
IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84
ii Extruded or Wrapped Extruded Extruded Extruded Extruded Extruded
iii Thickness (Min.) mm 0.3 0.3 0.3 0.3 0.3
iv Calculated dia over I/Sh. mm 8.2 12.2 ##
13 Armour
i Material Gal.Steel Gal.Steel Gal.Steel Gal.Steel Gal.Steel
Galvanized Wire Galvanized Wire Galvanized Wire Galvanized Wire Galvanized Wire
ii Type of Armour (Single layer (Single layer (Single layer (Single layer (Single layer
armouring) armouring) armouring) armouring) armouring)
iii Nominal Dimensions (min) mm 1.4 1.4 1.4 1.6 1.4
iv Calculated diameter over armour mm 11 15 11.8 16.4 ##
14 Outer Sheath
FR PVC Type 'ST2' FR PVC Type 'ST2' FR PVC Type 'ST2' FR PVC Type 'ST2' FR PVC Type 'ST2'
i Material
as per IS:5831/84 as per IS:5831/84 as per IS:5831/84 as per IS:5831/84 as per IS:5831/84
ii Whether extruded type Extruded Extruded Extruded Extruded Extruded
Thickness (Min.) for armoured cable
iii mm 1.24 1.24 1.4 1.4 1.24
Nominal for Unarmoured cable
iv Colour of outer sheath Black Black Black Black Black
Whether anti-termite & anti rodent
v treatment has been given in the Yes Yes Yes Yes Yes
outer
vi Tolerance of cable under sheath mm As per IS As per IS As per IS As per IS As per IS
Calculated. Dia of the cable under
vii mm 11 15 11.8 16.4 ##
the sheath
15 Appr. Overall Dia. of Cable mm ## 20 16 21 ##
16 Appr. Weight of Cable Kg/KM 473 761 384 898 ##
Continuous Current carrying
17
capacities for conditions
i In ground (A) @ 30 Deg. C A ## 17 NA NA ##
ii In duct (A) A ## 14 NA NA ##
iii In air (A) @ 40 Deg. C A ## 15 NA NA ##
12 times of Over all 12 times of Over all 12 times of Over all 12 times of Over all 12 times of Over all
18 Minimum bending radius mm
Diameter Diameter Diameter Diameter Diameter

Annexure_TECH. DATA (Control) Page 7 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Deviation
o.
RD
No of Cores 7 12 2P 7P 4
Size in Sq.mm. 1.5 1.5 0.75 0.75 4
Safe Pulling force Pulled by pulling kg/sq.m 5 kg/sq.mm of 5 kg/sq.mm of 5 kg/sq.mm of 5 kg/sq.mm of 5 kg/sq.mm of
19
eye (kg) m Copper area Copper area Copper area Copper area Copper area
Short ckt current carrying capacity of
20 kA 0.21 0.21 NA NA ##
conductor for one second
Max. DC Resistance of Conductor at (ohm/km
21 12.1 12.1 NA NA ##
20 Deg C (ohm/km) )
Max.AC Resistance at 90 °C (ohm/km
22 15.5 15.5 ##
(ohms/km) )
i Under Continuous full load condition Deg C 90 90 90 90 90
ii Under Transient loading condition Deg C 250 250 250 250 250
Reactance at 50 Hz (ohm/km
26 0.108 0.108 115 115 ##
(ohm/km)(between two cores) )
27 Capacitance at 50 Hz (μF/km) (μF/km) 0.161 0.161 NA NA ##
28 Cable Drum
Over all dimensions of the drum(It
i can vary According to drum Avaiblity ## ## ## ## ##
)
Approx. Flange dia(It can vary
ii mm ## ## ## ## ##
According to drum Avaiblity )
Approx. Barrel dia(It can vary
iii mm ## ## ## ## ##
According to drum Avaiblity )
iv Approx. Traverse dia mm ## ## ## ## ##
Approx. total weight of the empty
v drum(It can vary According to drum Kg ## ## ## ## ##
Avaiblity )
Max Length that can be supplied in
vi single drum(It can vary According to +2% ## ## ## ## ##
drum Avaiblity )
29 FR Properties FR FR FR FR FR
i Oxygen Index % Min. 29% Min. 29% Min. 29% Min. 29% Min. 29%
ii Temperature Index Deg C Min. 250 deg C Min. 250 deg C Min. 250 deg C Min. 250 deg C Min. 250 deg C
iii Smoke Density Rating % Max. 60% Max. 60% Max. 60% Max. 60% Max. 60%
iv Max. HCL Emission Max. 20% by weight Max. 20% by weight Max. 20% by weight Max. 20% by weight Max. 20% by weight
v Flammability Test As per IS As per IS As per IS As per IS As per IS
30 Printing (For every one metre) ## ## ## ## ##
31 Individual Screen

Annexure_TECH. DATA (Control) Page 8 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : TECHNICAL DATA SHEET


UNIT/
Sl.N
PARTICULARS STANDA Cable Description Cable Description Cable Description Cable Description Cable Description Deviation Deviation
o.
RD
No of Cores 7 12 2P 7P 4
Size in Sq.mm. 1.5 1.5 0.75 0.75 4
Aluminium Aluminium
i Material N.A. N.A. Mylar/Polyester Mylar/Polyester N.A.
Tape Tape
ii Nominal Thickness mm mm N.A. N.A. 0.05 0.05 N.A.
iii Material of Drain Wire N.A. N.A. ATC ATC N.A.
iv No & Size of Drain Wire No./mm N.A. N.A. 7/0.3 7/0.3 N.A.
32 Collective Screen
Aluminium Aluminium
i Material N.A. N.A. Mylar/Polyester Mylar/Polyester N.A.
Tape Tape
ii Nominal Thickness mm mm N.A. N.A. 0.075 0.075 N.A.
iii Material of Drain Wire N.A. N.A. ATC ATC N.A.
iv No & Size of Drain Wire No./mm N.A. N.A. 7/0.3 7/0.3 N.A.

Packing as per Andritz packing procedure


"##" MARKED FOR SUPPLIER INPUT. TO BE FILLED IN THE SUPPLIER DATA

Annexure_TECH. DATA (Control) Page 9 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : GENERAL REQUIREMENTS


S.
DESCRIPTION SUPPLIER REMARKS
No
A LV CABLES
The cables will be 660 / 1100V grade, single/ multicore, and stranded Copper conductor, extruded
A.1
XLPE insulated with taped PVC inner sheath, armoured cable.
A.2 The cables will conform to IS-7098-Part-1 (1988), IEC-502 (I) (1983).
A.3 Cables shall be of armoured type.
A.4 Cables will be armoured.
B INSTRUMENTATION CABLE
0.75 sq.mm copper, individually and overall screened cables for governor circuiting shall be
B.1
provided.
C CONTROL CABLE
1100V grade, multicore, minimum 1.5 sq.mm cross section, stranded copper conductor having 7
C.1 strands, PVC insulated, inner extruded PVC sheathed, armoured cable. The cables will conform to
IS: 1554 (part-I) - 1988 / IEC-502 (1983) in all other respects.

Annexure_GEN. REQ. Page 10 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : DOCUMENT LIST


Submission
Sr. No. Document No. Document title
Category
1 US-PC-02-0366 Cross Section Drawing of Cables Approval
2 US-PC-03-0363 GTP of LV Power, Control & Instrumentation cable Approval
3 Packing List Approval
Note: Above are the minimum documents which supplier shall submit after 1-2 weeks of PO . Any other
documents apart of the above can also be submitted.

Annexure_Document List Page 11 of 12


ANNEXURES: TECHNICAL SPECIFICATION OF LV POWER, CONTROL INSTRUMENT CABLE

ANNEXURE : BID QUALIFICATION FORM


Project Code No: C-90-830525 Project Name: Upper Sanigad HEP Supplier Technically Qualified ( Yes/ No):
PR No.: RFQ Number: Supplier Commercially Qualified ( Yes/ No): Package Cable
Specification
Supplier Deviations / Supplier Observation on Andritz Andritz Observation on Supplier
Number / Drawing Supplier Comments Andritz Comments
Observations Comments Comments
Number Specification
S.No. Clause No. /
(Put all applicable (Compliance Yes/ No (Deviation has impact (Deviation Accepted Yes/ No
Page No.
Specification / if Yes deviation? on cost Yes/No. If yes if Yes deviation? Is their any+/- Implication of Cost. if any If any
Drawing numbers) What is the deviation) what amount?) If No "Reason"

Remarks: 1. Filled Bid Qualification Form should be enclosed with offer.


2. Our Specifications & agreed Bid Qualification Form are the final bindings if order is finalised on You. No deviation is acceptable.
3. Supplier hereby agrees to supply the material as per our specifications, drawings , Bid Qualification form & Any material required for
the successful operation & completion of system without any cost implication.

Annexure_BQF Page 12 of 12

You might also like