Professional Documents
Culture Documents
Presentacion Cigre Proyectos PDF
Presentacion Cigre Proyectos PDF
1. Introduction
2. HVDC Station Layout and Equipment – LCC
3. HVDC Station Layout and Equipment – VSC
4. Integration of Renewable Energy Sources
using HVDC
5. Conclusions
HVDC
Configuration
Possibilities
Terminals in series
Terminals in parallel
Parallel:
Parallel:the
the“Standard”
“Standard”Version
Version
AC AC AC
System 1 System 2
2 AC Filters, C-Banks
3 Converter Transformers
AC AC
Filter Filter
4 Thyristor Valves
1 2 3 4 5 4 3 2 1 5 Smoothing Reactors
AC AC AC
System 1 System 2
To/ from
Controls, Protection, Monitoring other 1 AC Switchyard
Terminal
2 AC Filters, Capacitor
Banks
DC
filter Pole 1
3 Converter Transformers
AC
filter 4 Thyristor Valves
DC Pole 2
filter
5 Smoothing Reactors
and DC Filters
1 2 3 4 5 6 6 DC Switchyard
8 9 DC Line
AC-Filter Bus Lsmooth
1 Arr Arr
C1 B4 D
7
3
Arr
AC-Bus 2 B3
L1 Arr
6 C Fdc Fdc
Fachv 4 Arr Arr
A B2
FacIv 5
L2
Arr
Arr Arr
C2 B1
AC-Filter E1 E2
10 Neutral 11
Neutral
4
A
3
Multiple B
Valve Unit
(Quadruple C
Valve)
2
1
A B C Valve Arm Example 500 kV
to DC Line: + or -
14 10-2011 DC Station Layout & GA Cigré Tutorial 2012
LDT – Configurations Monopolar/Bipolar
With Monopolar
System, only “Ground
Return” available
“flexible”
Plus Wind
Power no additional
Thermal Plants
Cost Reduction
“fuzzy”
17 10-2011 DC Station
Covering
17 Base
10-2011 and Peak-Load Demands
DC Station Layout & GA Cigré Tutorial 2012
Basslink HVDC:
Converter
Arial View
500 MW
2006
Bass Strait
Welcome great
Outdoors !
Joints
100 km 1 km only !
26 10-2011 DC Station Layout & GA Cigré Tutorial 2012
300 MW TNB-EGAT HVDC Interconnection
“Hotel DC”
Adaptation to
the local
Architecture 2001
Source: 10-2011
27 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Europe – HVDC Moyle Interconnector
The Task: World's first HVDC with LTT
Sea-Cable Transmission and wafer-integrated BOD
2001 Operated by:
Moyle Interconnector
Ltd., Northern Ireland
System Data:
Rating 2 x 250 MW
Voltage 250 kV DC
Thyristor 8 kV LTT
Cable Length 64 km
Auchencrosh
Power Exchange
Ballycronan More by Sea Cable
Sharing of
Reserve Capacity
Benefits No Increase in
Short-Circuit Power
660 MW
2007
Valve Hall
Control Building
DC Hall
Transformers
AC Switchgear
AC Filters
2011
BritNed
Power Exchange
Customer: by Sea Cable
BritNed Developm. Ltd.
Sharing of
System Data:
Rating 2 x 500 MW Reserve Capacity
Voltage ± 450 kV
Thyristor 8 kV LTT
No Increase in
Cable Length 260 km Short-Circuit Power
2010
600 MW
2011
2 x 500 MW
*2,500
2,500MW
MW
2 x 3-ph AC 400 kV 800 km
India
1 x +/- 500 kV
Example of HVDC
Ballia-Bhiwadi: 1,450 km … too long for 400 kV AC
2010
2,500 MW
Reduction in CO2:
1.2 m tons p.a. (52 %)
by using Energy-Mix
from the Mainland – 2011
versus local Supply with a new Oil-fired Power Plant on the Island
400 MW
2011
Example of HVDC “Classic”
Technology Issues
for UHV DC Transmission
45 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Overview of an ± 800 kV DC Transmission System
DC Wall Bushing
- 800 kV D
C
Line Arresters
Voltage Divider - 400 kV
DC
+ 400 k
V DC
DC Filters
Disconnectors &
Grounding Switches
Bypass Switches
+ 800
kV DC
Smoothing Reactors
DC Wall Bushing
Ø 4.6 m
800 kV DC
3,125 A
14.3 m
75 mH
28 tons !
DC (2 hrs) 1,175 kV
AC (1 min) 1,020 kV
PR (90/90/45 min) 935 kV
SI 1,790 kV
Test Voltages LI (FW/CW) 2,080/2,320 kV
DC Neutral
LV 12-Pulse Bridge
400 kV Valve Hall 400 kV DC
400 kV DC
to 800 kV DC Line
HV 12-Pulse Bridge
“Ready for Transmission”
51 10-2011 800 kV Valve Hall
10-2011 DC Station Layout
DC Station
& GA Layout & GA PowerCigré
Transmission
Cigré
Tutorial
Tutorial
2012
Solutions
2012
Testing of UHV DC Bypass Switches …
800 kV DC
6.2 m
400 kV DC 9.5 m
Test Set-up
800 kV DC
Technical Data
Rated Voltage: 816 kV DC
11.4 m
Operating Voltage: 800 kV DC
Withstand Voltage: 1,200 kV DC 13 m
Switching Impulse Voltage:1,790 kV
Lightning Impulse Voltage: 2,205 kV
Operating Current: 5,000 A DC
Short-Circuit Current: 50 / 20 kA – 1 s
Creepage path: 38,746 mm
No. of Operating Cycles: 2,000 CO
Weight: 6,000 kg
Test Set-up
Special Challenges
Two Resin-Paper Capacitor Windings with a total Weight of 4,000 kg
Design of the Windings and Production with no Shrinkage Holes
12.8 m
800 kV DC
9m
56 10-2011 DC
DCStation
StationLayout
Layout&&GA
GA Cigré
CigréTutorial
Tutorial2012
2012
All Tests are … and the Power
completed … is flowing
- 800 k
V DC
- 400
kV DC
+ 400
kV D
C
+ 80
0 kV
DC
57 10-2011 DC
DCStation
StationLayout
Layout&&GA
GA Cigré Tutorial 2012
More Power
out of the
Grid …
Yunnan-Guangdong
plus CO2 Reduction
2009/2010
61 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Back to Germany: All UHV DC Transformer
Tests completed, ready for Shipping to China
… a crucial Issue
DC Side
800 kV DC
Sources:
Xiangjiaba-Shanghai
World’s biggest and longest UHV DC in Operation
72 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Schematic Arrangement of Xiangjiaba-Shanghai
Converters
Double Valve Towers of a Fulong 6-Pulse Bridge at the 800 kV Converter End
74 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Arrangement of 800 kV Converters for Fulong Station
DC Current Capability of
more than 4,500 A
Optimum Blocking Voltage
of 8.5 kV
Joining of the Silicon Pellet
to a Molybdenum Carrier Disk
using low-Temperature high-
Pressure Sintering
Excellent thermal Coupling
Low thermal Resistance
Outstanding Short-Circuit
Current Capability: > 80 kA 6“ high-Power Thyristor – compared
High Reliability, Failure Rate < 10 fit with 4“ and 5“ Elements
The Solution
for Bulk Power
Transmission
up to 4 GW
“Standard”:
500 kV DC PDC ≤ 3 GW
Increase in
New Level: Transmission
660 kV DC PDC ≤ 4 GW Capacity – and
Reduction in
Losses
77 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Ningdong-Shandong: World’s first EHV DC at 660 kV
HVDC
Types of
Electrodes
Sea Electrodes
PM 2 PM 2 PM 2
Converter Reactors Vd
ud
PM 1 PM 1 PM 1
D1 PM 2 PM 2 PM 2
IGBT1
D2 PM n PM n PM n
IGBT2
Phase Unit
84 10-2011 DC Station Layout & GA Cigré Tutorial 2012
The Result: MMC – a perfect Voltage Generation
VConv.
VAC 0
- Vd /2
P = 400 MW
Q = +/- 170-300 MVAr Dynamic Voltage Support
Space
Saving
HVDC PLUS
Example 400 MW
HVDC
89 10-2011 “Classic”
DC Station Layout & GA Cigré Tutorial 2012
Example of HVDC PLUS Station: 2 x 100 MW
les
b
Options: Ca
DC
a) 2B
B
D C
b )
85 m 96 m
(315 feet)
(279 feet)
Half the Width by vertical Arrangement: 2 Reactors and 2 Converter Modules on Top of each other
Footprint:
150 x 110 m
(492 x 361 ft)
Converter DC Switchyard
Reactors Cable Sealing End
Converter Hall
90
m
0m DC Chopper
13
Converter Transformer
3-Phase / ODAN
~ ~ ~
= = =
= = =
= = =
= = =
~ ~ ~
DC Solution for
Grid Access
33 kV AC
HVDC PLUS
132 kV AC 132 kV AC
33 kV AC
≤ 320 kV DC
HVDC PLUS
SVC PLUS AC Solution for
33 kV AC Grid Access
132 kV AC
= == ~ =
~
= =
~
= =
~
The Modular Multilevel Converter
Technology (MMC) reduces Comp- 101
lexity and therefore the Space
101
required 10-2011
for Installation DC Station Layout & GA Cigré Tutorial 2012
Prospects and Locations of Tennet’s Offshore
Projects – one with AC and all others with DC Links
Source:
Source: http://www.tennet.eu/
103 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Prospects and Locations of Tennet’s DC
Offshore Projects – Example of
Source: http://www.tennet.eu/
104 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Grid Access of Green Energy with HVDC PLUS:
WIPOS® – Advanced self-lifting Offshore Platform Layout
400 kV AC (HV) – 1.8 GVA / 2.3 GVA (directly buried / Tunnel or Outdoor)
500 kV AC (EHV) – 2.3 GVA / 2.9 GVA (directly buried / Tunnel or Outdoor)
550 kV AC (EHV) – Substation: Standard 3.8 GVA / Special 7.6 GVA **
800 kV AC (EHV) – Tunnel: 5.6 GVA ***
109 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Summary: Features and Benefits of HVDC