HVDC Station Layout, Equipment

LCC & VSC and Integration of


Renewables using HVDC

Dr. Dietmar Retzmann


Siemens AG
dietmar.retzmann@siemens.com

1 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Overview

1. Introduction
2. HVDC Station Layout and Equipment – LCC
3. HVDC Station Layout and Equipment – VSC
4. Integration of Renewable Energy Sources
using HVDC
5. Conclusions

2 10-2011 DC Station Layout & GA Cigré Tutorial 2012


1.
ntroduction
HVDC – Green Energy
HVDC – Security of Supply
3 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Reuters: Wind Power & HVDC – January 26, 2011

4 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Electric Power Markets – they need HVDC

 Increasing Demand for Power Generation* – from


3,620 GW in 2000 to
5,324 GW in 2010 and to
9,669 GW in 2030
 Strong Environmental Constraints – Limitation
on Power Plant Expansions
 Natural Energy Resources far away from the
Load Centers
 Severe Right-of-Way Constraints
 A crucial Issue in many Countries,
in Europe in particular
* Source: Siemens E ST, 2011

5 10-2011 DC Station Layout & GA Cigré Tutorial 2012


2.
S tation Layout and
Equipment LCC
6 10-2011 DC Station Layout & GA Cigré Tutorial 2012
High-Voltage Direct Current

HVDC
Configuration
Possibilities

7 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Configurations Bipolar

Bipolar, Metallic Return


System needs three Lines !

Bipolar, Ground Return – System with two Lines

8 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Configurations Monopolar *

* Examples with one Pole


out of Service

Monopolar, one DC Line and Ground Return

Monopolar, Metallic Return Monopolar, two DC Lines and Ground Return

9 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Multiterminal HVDC

Terminals in series

Terminals in parallel

Parallel:
Parallel:the
the“Standard”
“Standard”Version
Version

10 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC Back-to-Back Station

AC AC AC
System 1 System 2

Controls, Protection, Monitoring


1 AC Switchyard

2 AC Filters, C-Banks

3 Converter Transformers
AC AC
Filter Filter
4 Thyristor Valves

1 2 3 4 5 4 3 2 1 5 Smoothing Reactors

11 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Bipolar HVDC Station – LDT with OHL

AC AC AC
System 1 System 2

To/ from
Controls, Protection, Monitoring other 1 AC Switchyard
Terminal

2 AC Filters, Capacitor
Banks
DC
filter Pole 1
3 Converter Transformers

AC
filter 4 Thyristor Valves
DC Pole 2
filter

5 Smoothing Reactors
and DC Filters
1 2 3 4 5 6 6 DC Switchyard

12 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC Basic Design: Arrester Arrangement

8 9 DC Line
AC-Filter Bus Lsmooth
1 Arr Arr
C1 B4 D
7
3
Arr
AC-Bus 2 B3
L1 Arr
6 C Fdc Fdc
Fachv 4 Arr Arr
A B2
FacIv 5
L2
Arr
Arr Arr
C2 B1
AC-Filter E1 E2

10 Neutral 11

13 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC Thyristor Valves – Principle Circuit
of a 12-Pulse Group

Valve Tower Arrangement


12-Pulse Group

Neutral

4
A
3
Multiple B
Valve Unit
(Quadruple C
Valve)
2
1
A B C Valve Arm Example 500 kV
to DC Line: + or -
14 10-2011 DC Station Layout & GA Cigré Tutorial 2012
LDT – Configurations Monopolar/Bipolar

With Monopolar
System, only “Ground
Return” available

Option to use the 2nd


Conductor for
“Metallic Return”

15 10-2011 DC Station Layout & GA Cigré Tutorial 2012


DC Overhead Lines and Tower Configurations
Nominal DC Voltage
Description Unit ± 300 kV ± 400 kV ± 500 kV ± 800 kV
Suitable Power Rating MW 600 ~ 1,000 1,000 ~ 2,000 1,500 ~ 3,000 3,000 ~ 7,500
DC System Configuration - Monopolar / Bipolar Monopolar / Bipolar Monopolar / Bipolar Monopolar / Bipolar
No. of Conductors per Pole Bundle 2x / 3x / 4x 2x / 3x / 4x / 6x 4x / 6x / 8x 6x / 8x
Economical Transmission km 300 -750 500 ~ 1,000 700 ~ 1,500 1,500 ~ 5,000
Distance of Line
Required Right-of-Way m 40 45 ~ 50 55 ~ 70 85 ~ 90
Minimum Required Ground m 8.50 10.00 – 11.00 11.00 – 13.00 16.00
Clearance (Subject to local
Regulations)
Typical Suspension Tower -
Outline
(not to scale)

Range of Tower Heights m 25 ~ 40 Lattice Tower: 36 ~ 51 / 31 ~ 51 39 ~ 93


Monopole: 49.18 ~ 48.18
Typical Insulator Type - Cap & Pin / Cap & Pin / Cap & Pin /
Porcelain Longrod / Porcelain Longrod / Porcelain Longrod / Cap & Pin /
Composite Composite Composite Porcelain Longrod
Practicable Length of m 4.34 (Porcelain Cap & 5.06 (Composite) / 7.33 12.94
Suspension Insulator String Pin) / 3.60 (Composite) 6.18 (Porcelain) (Composite Longrod) (Cap & Pin)

16 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Basslink HVDC: remote Infeed of Green Energy

Hydro Plants for: Benefits of HVDC:


 Base Load and  Clean Energy
 Pump Storage  CO2 Reduction

“flexible”

Plus Wind
Power  no additional
Thermal Plants
 Cost Reduction
“fuzzy”
17 10-2011 DC Station
Covering
17 Base
10-2011 and Peak-Load Demands
DC Station Layout & GA Cigré Tutorial 2012
Basslink HVDC:
 Converter
 Arial View

Example of HVDC “Classic”

500 MW
2006

18 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Basslink HVDC – AC Filters

19 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Basslink HVDC – DC Wall Bushing and DC Reactor

20 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Optimization of the Transmission System

Loy Yang McGaurans Five Mile Georgetown


Beach Bluff

3.2 km 57.4 km 6.4 km 295 km 1.7 km 8.9 km 2.1 km

Bass Strait

Converter Underground Underground Converter


Station Cable Cable Station
Sea Cable
500 kV Transition Transition 220 kV
Substation Station Station Substation
10 hrs Overload
Commercial Operation: 2006 System Data:

Transmission Capacity: 500 / 600 MW


21 10-2011 DC Station Layout & GA DC Voltage: 400 kV
Cigré Tutorial 2012
Examples of DC Lines – Basslink 400 kV
From “Small” to “Large” Line

22 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Basslink 400 kV DC Line: Right-of-Way

For Comparison: 300 kV DC Tower


23 10-2011 DC Station Layout & GA Cigré Tutorial 2012
From DC Line to Cable – Basslink HVDC

Welcome great
Outdoors !

24 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC Cable Options
 MI: Insulated with special Paper, impregnated with High-Viscosity
Compound
 SCFF: Insulated with special Paper, impregnated with Low-Viscosity Oil
 Extruded: Insulated with extruded Polyethylene-Based Compound
Mass Impregnated Self-Contained Fluid Filled Extruded
Conductors up to 2,700 mm2
Voltages up to 600 kV DC.

Conductors up to 3,000 mm2


Voltages up to 600 kV DC.

Conductors up to 3,000 mm2 (Al)


Voltages up to 320 kV DC.
Photos: Prysmian Cables and Systems, 2009 – Data: Status 2011
25 10-2011 DC Station Layout & GA Cigré Tutorial 2012
DC Cable Laying
Cable Termination

Source: Prysmian Cables and Systems, 2008

Joints

Maximal Length of the Cable Sections

Sea Cable: Land Cable:

100 km  1 km only !
26 10-2011 DC Station Layout & GA Cigré Tutorial 2012
300 MW TNB-EGAT HVDC Interconnection

GURUN HVDC CONVERTER STATION

“Hotel DC”

Adaptation to
the local
Architecture 2001
Source: 10-2011
27 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Europe – HVDC Moyle Interconnector
The Task: World's first HVDC with LTT
Sea-Cable Transmission and wafer-integrated BOD
2001 Operated by:
Moyle Interconnector
Ltd., Northern Ireland

System Data:
Rating 2 x 250 MW
Voltage 250 kV DC
Thyristor 8 kV LTT
Cable Length 64 km
Auchencrosh
Power Exchange
Ballycronan More by Sea Cable
Sharing of
Reserve Capacity

Benefits No Increase in
Short-Circuit Power

28 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC Moyle Interconnector – An Arial View

Example of HVDC “Classic”

29 10-2011 DC Station Layout & GA Cigré Tutorial 2012


New DC Cable Link Neptune RTS, USA

30 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Neptune HVDC – Station Sayreville

660 MW
2007

Example of HVDC “Classic”

31 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Neptune HVDC – Station Duffy Avenue
‘Snapshots’ from
the Inauguration
on 10-11-2007

32 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Neptune HVDC – Station Duffy Avenue
‘Snapshots’ from
the Inauguration
on 10-11-2007

33 10-2011 DC Station Layout & GA Cigré Tutorial 2012


DC Station Neptune – with DC Cable 500 kV

Valve Hall
Control Building
DC Hall
Transformers

AC Switchgear

AC Filters

34 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Europe – The HVDC Portfolio is growing …

Storebælt Customer: 2010


Energinet.dk
System Data:
Rating 600 MW
Voltage 400 kV DC
Thyristor 8 kV LTT
Cable Length 56 km

2011
BritNed
Power Exchange
Customer: by Sea Cable
BritNed Developm. Ltd.
Sharing of
System Data:
Rating 2 x 500 MW Reserve Capacity
Voltage ± 450 kV
Thyristor 8 kV LTT
No Increase in
Cable Length 260 km Short-Circuit Power

35 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Storebælt: Station Herslev – DC Yard

2010

600 MW

36 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Storebælt: Station
Fraugde – DC Converter

37 10-2011 DC Station Layout & GA Cigré Tutorial 2012


BritNed: Station Maasvlatke – AC Yard

2011

2 x 500 MW

38 10-2011 DC Station Layout & GA Cigré Tutorial 2012


BritNed: Station Maasvlatke – AC Yard

39 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Sustainability in Transmission – HVDC
in India: East-South Interconnector and Ballia-Bhiwadi
DC versus AC 2010

*2,500
2,500MW
MW
2 x 3-ph AC 400 kV 800 km

India
1 x +/- 500 kV
Example of HVDC
Ballia-Bhiwadi: 1,450 km … too long for 400 kV AC

Reduction in CO2: 2,000/2,500 MW


688,000 tons p.a.
through 37 % less 2003/2007
Transmission
Losses at*
40 10-2011 DC Station Layout & GA Cigré Tutorial 2012
HVDC Ballia-Bhiwadi, India – DC Yard

2010
2,500 MW

41 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Sustainability in Transmission – HVDC
in Europe: COMETA, Spain-Mallorca DC Interconnector
Customer:
Red Eléctrica de España
System Data:
Rating 2 x 200 MW
Voltage ± 250 kV DC
Thyristor 8 kV LTT
Cable Length 250 km

Reduction in CO2:
1.2 m tons p.a. (52 %)
by using Energy-Mix
from the Mainland – 2011
versus local Supply with a new Oil-fired Power Plant on the Island

42 10-2011 DC Station Layout & GA Cigré Tutorial 2012


COMETA, Spain-Mallorca DC Interconnector –
Indoor AC Yard … and Converter Halls

400 MW
2011
Example of HVDC “Classic”

43 10-2011 DC Station Layout & GA Cigré Tutorial 2012


COMETA, Spain-Mallorca DC Interconnector –
Transformers mounted

44 10-2011 DC Station Layout & GA Cigré Tutorial 2012


More Power
out of the
Grid …

plus CO2 Reduction

Technology Issues
for UHV DC Transmission
45 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Overview of an ± 800 kV DC Transmission System
DC Wall Bushing

- 800 kV D
C
Line Arresters
Voltage Divider - 400 kV
DC

+ 400 k
V DC
DC Filters
Disconnectors &
Grounding Switches

Bypass Switches
+ 800
kV DC
Smoothing Reactors

DC Wall Bushing

46 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Air-Core, Air-cooled Smoothing Reactor and
Converter Transformer – The Dimensions are “huge”

500 kV DC in Pictures – have mean-


while been extended to 800 kV DC

Mostly an Issue of Mechanics –

but not only …


47 10-2011 DC Station Layout & GA Cigré Tutorial 2012
UHV DC Reactor – in Test Field

Ø 4.6 m
800 kV DC
3,125 A
14.3 m
75 mH
28 tons !

48 10-2011 DC Station Layout & GA Cigré Tutorial 2012


800 kV HVDC Transformers under Construction
250/244 MVA Single-Phase* Transformers
48** Transformers – for the Yunnan-Guangdong UHV DC Project
Core Design: 3 Limbs & 2 Return Limbs
L x W x H: 26 x 6.4 x 15.2 m
Total Weight: 512 tons
* for Transportation Reasons
** plus 8 Spare Units

DC (2 hrs) 1,175 kV
AC (1 min) 1,020 kV
PR (90/90/45 min) 935 kV
SI 1,790 kV
Test Voltages LI (FW/CW) 2,080/2,320 kV

49 10-2011 DC Station Layout & GA Cigré Tutorial 2012


“Snapshots” from DC Transformer Testing …

… at Transformer Factory Test Lab –


Nuremberg, Germany

50 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Valve Hall Configuration – for UHV DC

DC Neutral
LV 12-Pulse Bridge
400 kV Valve Hall 400 kV DC

Each Valve Group can be bypassed … n-1 Criterion

400 kV DC
to 800 kV DC Line
HV 12-Pulse Bridge
“Ready for Transmission”
51 10-2011 800 kV Valve Hall
10-2011 DC Station Layout
DC Station
& GA Layout & GA PowerCigré
Transmission
Cigré
Tutorial
Tutorial
2012
Solutions
2012
Testing of UHV DC Bypass Switches …
800 kV DC
6.2 m

400 kV DC 9.5 m

Test Set-up

… at Siemens High-Voltage Test Lab Berlin, Germany

52 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Testing of UHV DC Disconnectors …

800 kV DC

53 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Disconnectors – Data and Dimensions
2m

Technical Data
 Rated Voltage: 816 kV DC
11.4 m
 Operating Voltage: 800 kV DC
 Withstand Voltage: 1,200 kV DC 13 m
 Switching Impulse Voltage:1,790 kV
 Lightning Impulse Voltage: 2,205 kV
 Operating Current: 5,000 A DC
 Short-Circuit Current: 50 / 20 kA – 1 s
 Creepage path: 38,746 mm
 No. of Operating Cycles: 2,000 CO
 Weight: 6,000 kg

54 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Capacitor-controlled Wall Bushing
Technical Data
 Rated Voltage: 816 kV DC
 Operating Voltage: 800 kV DC 20.8 m
 AC Test Voltage: 1,100 kV
 DC Test Voltage: 1,455 kV DC
 Creepage Path Outdoor: 42,500 mm
 Creepage Path Indoor: 26,630 mm
 Rated Current: 3,700 A DC
 Weight: 5,600 kg

Test Set-up

Special Challenges
 Two Resin-Paper Capacitor Windings with a total Weight of 4,000 kg
 Design of the Windings and Production with no Shrinkage Holes

55 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Testing of UHV DC Bushing, 10.6 m
DC Arrestor and Voltage Divider

12.8 m

800 kV DC

9m

56 10-2011 DC
DCStation
StationLayout
Layout&&GA
GA Cigré
CigréTutorial
Tutorial2012
2012
All Tests are … and the Power
completed … is flowing

- 800 k
V DC

- 400
kV DC
+ 400
kV D
C

+ 80
0 kV
DC

57 10-2011 DC
DCStation
StationLayout
Layout&&GA
GA Cigré Tutorial 2012
More Power
out of the
Grid …

Yunnan-Guangdong
plus CO2 Reduction

World’s first 800 kV HVDC – 5,000 MW


In China Southern Power Grid
58 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Single-Line Diagram of Yunnan-Guangdong
HVDC System

59 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Yunnan-Guangdong – from ‘3D Models’ …

60 10-2011 DC Station Layout & GA Cigré Tutorial 2012


… to Reality: Sending Station Chuxiong

World’s first 800 kV UHV DC – 5,000 MW

Example of HVDC “Bulk”

2009/2010
61 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Back to Germany: All UHV DC Transformer
Tests completed, ready for Shipping to China

62 10-2011 DC Station Layout & GA Cigré Tutorial 2012


“Clearance” underneath Bridges in Germany

… a crucial Issue

63 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Arrived in China, small Roads – Transformers
just fitting well, as expected …

64 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Yunnan-Guangdong – UHV DC Valve Hall
800 kV DC

DC Side

65 10-2011 DC Station Layout & GA Cigré Tutorial 2012


UHV DC – Sending Station: from indoor to outdoor

800 kV DC

66 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Station Chuxiong – Disconnector & DC Filter

67 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Yunnan-Guangdong – 800 kV DC Line

68 10-2011 DC Station Layout & GA Cigré Tutorial 2012


800 kV DC Towers

69 10-2011 DC Station Layout & GA Cigré Tutorial 2012


800 kV DC Overhead Line
Welcome great
Outdoors !

70 10-2011 DC Station Layout & GA Cigré Tutorial 2012


For Comparison – UHV AC Transmission Towers

1,000 kV Pilot Project

For Redundancy - 2 Lines:


System 1 System 2

Sources:

71 10-2011 DC Station Layout & GA Cigré Tutorial 2012


More Power
out of the
Grid … In Co-Operation with

Fulong Converter Station – HVDC


Transformers & Thyristor Valves
with new 6-inch Thyristors

plus CO2 Reduction

Xiangjiaba-Shanghai
World’s biggest and longest UHV DC in Operation
72 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Schematic Arrangement of Xiangjiaba-Shanghai
Converters

73 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Arrangement of 800 kV Converters for Fulong Station

Double Valve Towers of a Fulong 6-Pulse Bridge at the 800 kV Converter End
74 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Arrangement of 800 kV Converters for Fulong Station

Two HV and two LV


Valve Towers for
Fulong Converter Station
during Erection for the
dielectric Type Tests
in Xihari HV Test Field
in Xi‘an, China
(Arresters not yet
connected)

75 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Design of Thyristor Valves for Fulong Station:
Latest Development of Power Thyristors: 6“-ETT

 DC Current Capability of
more than 4,500 A
 Optimum Blocking Voltage
of 8.5 kV
 Joining of the Silicon Pellet
to a Molybdenum Carrier Disk
using low-Temperature high-
Pressure Sintering
 Excellent thermal Coupling
 Low thermal Resistance
 Outstanding Short-Circuit
Current Capability: > 80 kA 6“ high-Power Thyristor – compared
 High Reliability, Failure Rate < 10 fit with 4“ and 5“ Elements

76 10-2011 DC Station Layout & GA Cigré Tutorial 2012


From of UHV DC to EHV DC

The Solution
for Bulk Power
Transmission
up to 4 GW
“Standard”:
500 kV DC PDC ≤ 3 GW
Increase in
New Level: Transmission
660 kV DC PDC ≤ 4 GW Capacity – and
Reduction in
Losses
77 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Ningdong-Shandong: World’s first EHV DC at 660 kV

Indoor EHV DC Switchyard

78 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Yinchuan Dong – Sending Station: 660 kV DC Line

79 10-2011 DC Station Layout & GA Cigré Tutorial 2012


High-Voltage Direct Current

HVDC
Types of
Electrodes

80 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Types of HVDC Electrodes

 Sea Electrodes

 Shore (Pond) Electrodes

 Shore (buried) Electrodes

 Ground (Land) Electrodes

 Deep Hole Electrodes

81 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Solutions for HVDC Electrodes – Summary

82 10-2011 DC Station Layout & GA Cigré Tutorial 2012


3.
S tation Layout and
Equipment VSC
83 10-2011 DC Station Layout & GA Cigré Tutorial 2012
HVDC PLUS with MMC – Basic Scheme
Converter Arm Converter Module

Power Module Electronics (PME)


PM 1 PM 1 PM 1

PM 2 PM 2 PM 2

Power Module (PM)


PM n PM n PM n

Converter Reactors Vd
ud

PM 1 PM 1 PM 1

D1 PM 2 PM 2 PM 2
IGBT1

D2 PM n PM n PM n
IGBT2

Phase Unit
84 10-2011 DC Station Layout & GA Cigré Tutorial 2012
The Result: MMC – a perfect Voltage Generation

AC and DC Voltages controlled


by Converter Arm Voltages:
+Vd /2

VConv.

VAC 0

- Vd /2

85 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC PLUS: Trans Bay Cable Project, USA

Energy Project of the Year – American Society of


Civil Engineers, Region 9; Sacramento, 9th March 2011
Elimination of Transmission Bottlenecks

P = 400 MW
Q = +/- 170-300 MVAr Dynamic Voltage Support

86 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC PLUS: Trans Bay Cable Project, USA

87 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC PLUS – Options for Converter Modules and
Building Arrangements

A highly flexible Design

88 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Benefits of HVDC PLUS

Space
Saving

HVDC PLUS

Example 400 MW

HVDC
89 10-2011 “Classic”
DC Station Layout & GA Cigré Tutorial 2012
Example of HVDC PLUS Station: 2 x 100 MW

les
b
Options: Ca
DC
a) 2B
B
D C
b )

85 m 96 m
(315 feet)
(279 feet)

90 10-2011 DC Station Layout & GA Cigré Tutorial 2012


(148 feet)
HVDC PLUS Station – Option for 100 MW B2B

Half the Width by vertical Arrangement: 2 Reactors and 2 Converter Modules on Top of each other

91 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Layout of a 400 MW Converter Station

Footprint:
150 x 110 m
(492 x 361 ft)

92 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Onshore Station Layout –
Example 400 MW, +/- 200 kV

Converter DC Switchyard
Reactors Cable Sealing End

Converter Hall

90
m

0m DC Chopper
13

AC Busbars Converter AC Yard, Control & Protection


Insertion Resistors Auxiliaries, Spares
Neutral Reactors

Converter Transformer
3-Phase / ODAN

93 10-2011 DC Station Layout & GA Cigré Tutorial 2012


4.
I ntegration of
RES using HVDC
94 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Green Energy: EU’s Offshore Programme EEPR

2030: Up to 350 GW of Wind Power !

CE – Installed Capacity: 631 GW


Source: EEPR-Meeting 2011-03-15&16, Brussels

95 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Integration of large Offshore Wind Farms
into the Main Grid – the German Prospects
VSC HVDC – for
Onshore Grid
Access & Offshore
DC Multiterminal

~ ~ ~
= = =

= = =
= = =

= = =
~ ~ ~

HVDC Classic – for Load &


96 10-2011 Generation
E Reserve
DCT Station
PS S/ReLayout & Sharing
GA Cigré Tutorial 2012
Green Energy needs Grid Enhancement …
HVDC – Example of Germany

Strengthening the AC Grid with DC Overlay Grid


Source: DENA Study II Nov. 2010
97 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Solutions for Grid Access: AC and DC –
with SVC PLUS and HVDC PLUS

DC Solution for
Grid Access
33 kV AC
HVDC PLUS
132 kV AC 132 kV AC
33 kV AC
≤ 320 kV DC
HVDC PLUS
SVC PLUS AC Solution for
33 kV AC Grid Access

132 kV AC

98 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Turnkey Responsibility:
First and crucial Steps

 Definition of most economic Wind Farm Network and Grid Connection


(AC versus DC).
 Define Layout and specify Components of the entire Grid Connection.
 Load-Flow Studies and Short-Circuit Calculations of the whole System.
 Define the System Grounding Concept and perform Insulation
Coordination for the entire Grid Connection.
 Verification the static and dynamic Performance and Design of
Reactive Power Compensation and / or DC System.
 Evaluation of System Resonance Behavior driven by the Cables,
Transformers, Reactors and Wind Generators.
 Prove the Conformity with the GRID CODE.
 Design of Protection, Control (SCADA) and Communication System.
 System Efficiency: Evaluation of overall losses for various Scenarios.
 Evaluation of electro-magnetic Interferences for the Grid Connection.
 Optimization of System Reliability and Availability.

99 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Example of System and Design Studies:
Dynamic Modeling of a big Number of Wind Generators
 System Resonances and
 System Interactions

Grid Code & Power Quality:


 Fault-Ride Through and
 Reactive Power Injection
Source: EWIS Interim Report June-2008

 Voltage Dip Compensation

100 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC PLUS and WIPOS®: SylWin1, Germany –
World’s first Offshore MMC with 864 MW, BorWin2 and HelWin1&2
WIPOS – Siemens Wind Power
Offshore Substation +/- 320 kV
Siemens offers a Family of WIPOS 864 MW
2014
Designs with the Flexibility to meet SylWin1
a Variety of Offshore Weather, Tide,
2013
~
and Seabed Conditions with three
2015
= =
main Configurations: +/- 300 kV
+/- 320 kV
 WIPOS self-lifting Solution 800 MW 2013 690 MW
 WIPOS Topside Solution BorWin2
~
(Topside/Jacket)
~ +/- 250 kV = =
HelWin2
576 MW
= =
 WIPOS floating Solution
~
HelWin1
= =

= == ~ =
~
= =
~

= =
~
The Modular Multilevel Converter
Technology (MMC) reduces Comp- 101
lexity and therefore the Space
101
required 10-2011
for Installation DC Station Layout & GA Cigré Tutorial 2012
Prospects and Locations of Tennet’s Offshore
Projects – one with AC and all others with DC Links

Source:

102 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Prospects and Locations of Tennet’s DC
Offshore Projects – Example of

Source: http://www.tennet.eu/
103 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Prospects and Locations of Tennet’s DC
Offshore Projects – Example of

Source: http://www.tennet.eu/
104 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Grid Access of Green Energy with HVDC PLUS:
WIPOS® – Advanced self-lifting Offshore Platform Layout

105 10-2011 DC Station Layout & GA Cigré Tutorial 2012


HVDC in China: Bulk Power Transmission of “Green Energy”

106 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Super Grid for DESERTEC – with HVDC
Source: DESERTEC Foundation
An Initiative of the Club of Rome

Siemens has a commitment in the Desertec Industrial


Initiative (DII). The objective of this initiative is to
develop over the mid-term a technical and economic
concept for solar power from Africa. Work will also
focus on the clarification of legal and political issues.

107 10-2011 DC Station Layout & GA Cigré Tutorial 2012


5.
onclusions
The Position of HVDC
in Comparison with AC
108 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Solutions for Smart & Bulk Power Transmission
Solutions with Overhead Lines
Note: Power AC @ 1 System 3 , Power DC @ Bipole +/-
 High-Voltage DC Transmission:
 HVDC “Classic” with 500 kV (HV) / 660 kV (EHV) – 3 to 4 GW
 HVDC “Bulk” with 800 kV (UHV) – 5 GW to 7.6 GW Option UHV DC 1,100 kV: 10 GW
For Comparison: HVDC PLUS (VSC) ≤ 1,100 MVA The Winner
 AC Transmission: is HVDC !
 400 kV (HV) / 500 kV AC (EHV) – 1.5 / 2 GVA
 800 kV AC (EHV) – 3 GVA
 1,000 kV AC (UHV) – 6 to 8 GVA

Solutions with DC Cables * * Distances over 80 km: AC Cables too complex

 500 / 600 kV DC – per Cable, Mass Impregnated: 1 GW to 2 GW (actual - prospective)


** Reference: Bowmanville, Canada, 1985 - Siemens
Solutions with GIL – Gas Insulated Lines *** Reference: Huanghe Laxiwa Hydropower Station,
China, 2009 - CGIT (USA)

 400 kV AC (HV) – 1.8 GVA / 2.3 GVA (directly buried / Tunnel or Outdoor)
 500 kV AC (EHV) – 2.3 GVA / 2.9 GVA (directly buried / Tunnel or Outdoor)
 550 kV AC (EHV) – Substation: Standard 3.8 GVA / Special 7.6 GVA **
 800 kV AC (EHV) – Tunnel: 5.6 GVA ***
109 10-2011 DC Station Layout & GA Cigré Tutorial 2012
Summary: Features and Benefits of HVDC

HVDC – High-Voltage DC Transmission: It makes P flow


 Three HVDC Options available: PLUS (VSC), “Classic” and “Bulk”
 With DC, Overhead Line Losses are typically 30-50 % less than with AC
 For Cable Transmission (over 80 km), HVDC is the only Solution
 HVDC can be integrated into the AC Systems
 HVDC supports AC in Terms of Stability
 System Interconnection with HVDC and Integration of HVDC:
 DC is a “Firewall” against Cascading Disturbances
 Bidirectional Control of Power Flow – quite easy
 Frequency, Voltage and POD Control available
 Staging of the Links – with DC quite easy
 No Increase in Short-Circuit Power
 DC is a Stability Booster

110 10-2011 DC Station Layout & GA Cigré Tutorial 2012


Thank You for Your Attention

111 10-2011 DC Station Layout & GA Cigré Tutorial 2012