NTPC LIMITED

(A Government of India Enterprise)

VOLUME – III

TECHNICAL SPECIFICATIONS &


SCOPEOF WORK

VERSION 1.0
TECHNICAL SPECIFICATIONS

BOQ Qty Technical Specifications


Item No.
10 20 GLOBE VALVE 1", 1500 CLASS,A105,FULL BORE,HAND
OPERATED,SW,RISING STEM,WELDED BONNET,SW ENDS TO ASME
B16.34,MATERIAL FOR BODY & BONNET:ASTM A 105(FCS),TRIM: API
602 TRIM NO.08, TESTED IN ACCORDANCE WITH API
598.DESIGN:API602/BS5352/ASME B16.34.
20 20 C.I. SLUICE/GATE VALVE FOR WATER WORKS AS PER IS14846 : 2000
(REAFFIRMED 2005), SIZE OF VALVE-50 MM, TYPE OF OPERATION –
MANUAL HANDWHEEL OPERATED, HANDWHEEL - REQUIRED, LOCKING
ARRAGEMENT FOR HANDWHEEL – REQUIRED, APPLICATION- WATER
PIPELINE, TEST REQUIRED- OPEN END TEST, POSITION OF VALVE –
HORIZONTAL, BYPASS ARRANGEMENT – NOT REQUIRED, AIR RELEASE
PLUG – NOT REQUIRED, DRAIN PLUG – NOT REQUIRED, GEAR
ARRANGEMENT – NOT REQUIRED. PN – 1.0, VENDOR HAS TO SUPPLY 2
NO. OF MS MATING FLANGES WITH EACH VALVE ASSEMBLY.
30 20 C.I. SLUICE/GATE VALVE FOR WATER WORKS AS PER IS14846 : 2000
(REAFFIRMED 2005), SIZE OF VALVE – 80 MM, TYPE OF OPERATION –
MANUAL HANDWHEEL OPERATED, HANDWHEEL - REQUIRED, LOCKING
ARRAGEMENT FOR HANDWHEEL – REQUIRED, APPLICATION- WATER
PIPELINE, TEST REQUIRED- OPEN END TEST, POSITION OF VALVE –
HORIZONTAL, BYPASS ARRANGEMENT – NOT REQUIRED, AIR RELEASE
PLUG - NOT REQUIRED, DRAIN PLUG – NOT REQUIRED, GEAR
ARRANGEMENT – NOT REQUIRED. PN – 1.0,VENDOR HAS TO SUPPLY 2
NO. OF MS MATING FLANGES WITH EACH VALVE ASSEMBLY.
40 10 C.I. SLUICE/GATE VALVE FOR WATER WORKS AS PER IS14846 : 2000
(REAFFIRMED 2005), SIZE OF VALVE – 100 MM, TYPE OF OPERATION –
MANUAL HANDWHEEL OPERATED, HANDWHEEL - REQUIRED, LOCKING
ARRAGEMENT FOR HANDWHEEL – REQUIRED, APPLICATION- WATER
PIPELINE, TEST REQUIRED- OPEN END TEST, POSITION OF VALVE –
HORIZONTAL, BYPASS ARRANGEMENT – NOT REQUIRED, AIR RELEASE
PLUG - REQUIRED, DRAIN PLUG – NOT REQUIRED, GEAR ARRANGEMENT
– NOT REQUIRED. PN – 1.0, VENDOR HAS TO SUPPLY 2 NO. OF MS
MATING FLANGES WITH EACH VALVE ASSEMBLY.
50 10 C.I. SLUICE/GATE VALVE FOR WATER WORKS AS PER IS14846 : 2000
(REAFFIRMED 2005), SIZE OF VALVE – 150 MM, TYPE OF OPERATION –
MANUAL HANDWHEEL OPERATED, HANDWHEEL - REQUIRED, LOCKING
ARRAGEMENT FOR HANDWHEEL – REQUIRED, APPLICATION- WATER
PIPELINE, TEST REQUIRED- OPEN END TEST, POSITION OF VALVE –
HORIZONTAL, BYPASS ARRANGEMENT – NOT REQUIRED, AIR RELEASE
PLUG - REQUIRED, DRAIN PLUG – NOT REQUIRED, GEAR ARRANGEMENT
– NOT REQUIRED. PN – 1.0, VENDOR HAS TO SUPPLY 2 NO. OF MS
MATING FLANGES WITH EACH VALVE ASSEMBLY.
60 10 200 MM ,CAST IRON (IS :210 FG260), SIZE OF VALVE – 200 MM,
TYPE OF OPERATION – MANUAL HANDWHEEL OPERATED, HANDWHEEL -
REQUIRED, LOCKING ARRAGEMENT FOR HANDWHEEL – REQUIRED,
APPLICATION- WATER PIPELINE, TEST REQUIRED- OPEN END TEST,
POSITION OF VALVE – HORIZONTAL, BYPASS ARRANGEMENT – NOT
REQUIRED, AIR RELEASE PLUG - REQUIRED, DRAIN PLUG – NOT
REQUIRED, GEAR ARRANGEMENT – NOT REQUIRED. PN – 1.0, VENDOR
HAS TO SUPPLY 2 NO. OF MS MATING FLANGES WITH EACH VALVE
ASSEMBLY.

9VolumeIIITechnicalSpecificationsAndScopeOfWork Page 2 of 3
SPECIAL INSTRUCTION APPLICABLE FOR ALL ITEM UNDER THIS ENQUIRY:

1.THE VENDOR SHOULD SUBMIT MATERIAL TEST CERTIFICATE.


CERTIFICATE SHOULD BE EITHER FROM MANUFACTURER OR FROM NTPC
APPROVED LAB.

2. VENDOR HAS TO SUBMIT GUARANTEE CERTIFICATE FOR THE ITEMS TO


BE SUPPLIED TOWARDS ANY MANUFACTURING DEFECTS & POOR
WORKMANSHIP, VALID FOR 12 MONTHS FROM THE DATE OF FIRST
OPERATION/INSTALLATION OR 18 MONTHS FROM THE DATE OF DELIVERY
WHICHEVER IS EARLIER

3. THE VENDOR SHALL SPECIFY ALL THE ABOVE TECHNICAL


SPECIFICATIONS /CONDITIONS IN THEIR OFFER.IN CASE THERE IS ANY
DEVIATION THE SAME SHOULD BE CLEARLY BROUGHT OUT IN THE OFFER.IN
ABSENCE OF ANY SPECIFIC DEVIATION ASKED BY THE VENDOR IN THE
OFFER,IT WILL BE CONSIDERED THAT THE VENDOR HAS ACCEPTED ALL THE
DETAILS AS MENTIONED IN THE TECHANICAL SPECIFICATIONS & SPECIAL
INSTRUCTIONS OF THE ENQUIRY IN TOTALITY

4. ACCEPTANCE SHALL BE BASED ON VISUAL INSPECTION, AND REVIEW OF


TEST CERTIFICATE ON RECEIPT AT NTPC STORES. TEST CERTIFICATE
INCLUDES TEST CERTIFICATE(CHEMICAL & MECHANICAL PROPERTIES),
HYDO TEST CERTICATE CARRIED OUT AT MANUFACTURING FACILITY ETC AS
PER APLLICABLE STANDARD.

Signature Not Verified


Digitally signed by Nirmalendu Kumar Nayak
Date: 2018.08.16 14:44:06 IST
Location: NTPC Limited eProcurement Portal
9VolumeIIITechnicalSpecificationsAndScopeOfWork Page 3 of 3
DIMENSIONS TABLE (All Dimension are in mm) Materials Construction
Stem Dia. Qty.
NB n Sl. No. Parts Name Materials Specification
50 178 165 125 16 4 19 22 20
1 Body
80 203 200 160 21 4 19 22 20
2 Bonnet
100 255 220 180 22 8 19 27 10
150 267 285 240 23 8 23 27 10 3 Wedge
Cast Iron IS : 210 FG 200
200 292 340 295 24.5 8 23 32 10 4 Wheel
5 Gland
6 Stuffing Box/Thrut Plate
4 7 Body Seat Ring
Bronze IS : 318 LTB - 2
8 Wedge Facing Ring
9
9 Stem Stainless Steel AISI 410/12Cr12
5 10 Stem Nut Bronze IS : 318 LTB - 2
6 11 Gasket Rubber IS : 638 Type B
6
12 Bolt & Nut Carbon Steel IS : 1363 Cl. 4.0 & 4.6
13 13 Packing Jute & Hemp IS: 5414
NOTE:
2 1. Valves will generally Conforming to IS : 14846/2000, PD, PN 1.0
FOR Upto 150 MM SIZE 2. All Dimensions are in mm, otherwise specified.
12
3. Flanged Drill as per IS: 1538 Flat Face.
11 4. Others Tolerance as per General Engineering Practice.
5. Flange OD & Thickness as per Dimension Table.
10
6. The Valve will be operated by Hand Wheel.
8 7. Marking (Cast/Punched) : KPM/SIZE/RATING/HEAT NO./ISI Mark
8. Hydro Test Pressure - Body - 15 Kg/cm2 Seat - 10 kg/cm2
7
D
C

3 Works: Dasnagar, Howrah Amta Road, Howrah, West Bengal.


Ph: 033 - 2653 0673 : E-mail: kpmondolandsons@gmail.com
1 GENERAL ARANGEMENT DRAWING FOR SLUICE VALVE WITH COMPONENT DETAILS

CLIENT NTPC Ltd., Darlipali Super Thermal Power Project


T NIT No. 9900163007
APPROVAL STAMP
L DRG. N.T.S. DRG. NO.:KPM/SV/052/18-19

DRAWN. T. DUTTA 27.08.2018


CHECKED A. ADAK 27.08.2018
APPROVED. S. MONDAL 27.08.2018

You might also like