You are on page 1of 2

Fire Zone SIF Description Success Input Logic Output Success

PID No. SIF Number Initiators Main Final Elements Other Final Elements Assigned SIL Comments
ESD1 bar Design Intent Criteria Transmission Solver Transmission Criteria

On high-high pressure in Inlet


PSDV-13900 PSDV-13901
ID-PCK-SWPG-1080-512002 SD-3.12 PCK8A-SIF-01 Separator, close PSDV-13900 PAHH-13909 1oo1 Hardwire SSS Hardwire
PSDV-13902
upstream Inlet Separator

On low-low pressure in Inlet


PSDV-13901
ID-PCK-SWPG-1080-512002 SD-3.12 PCK8A-SIF-02 Separator, close PSDV-13900 PALL-13912 1oo1 Hardwire SSS Hardwire PSDV-13900
PSDV-13902
upstream Inlet Separator

On high-high level in in Inlet


PSDV-13901
ID-PCK-SWPG-1080-512002 SD-3.12 PCK8A-SIF-03 Separator, close PSDV-13900 LAHH-13900 1oo1 Hardwire SSS Hardwire PSDV-13900
PSDV-13902
upstream Inlet Separator

On low-low level in in Inlet


ID-PCK-SWPG-1080-512002 SD-3.14 PCK8A-SIF-04 Separator, close PSDV-13901 LALL-13900 1oo1 Hardwire SSS Hardwire PSDV-13901 PSDV-13902
upstream Inlet Separator

On high-high pressure in BC PSDV-xxxx Inlet BC


BC Package SD-3.13 PCK8A-SIF-05 Discharge, close inlet PSDV-xxxx PSHH-xxxx 1oo1 Hardwire SSS Hardwire PSDV-xxxx FG -
BC Package PSDV-xxxx outlet BC

On low-low pressure in Inlet PSDV-xxxx Inlet BC


BC Package SD-3.13 PCK8A-SIF-06 Separator, close inlet PSDV-xxxx BC PSLL-xxxx 1oo1 Hardwire SSS Hardwire PSDV-xxxx FG -
Package PSDV-xxxx outlet BC

On high-high temperature in BC PSDV-xxxx Inlet BC


BC Package SD-3.13 PCK8A-SIF-07 Discharge, close inlet PSDV-xxxx TSHH-xxxx 1oo1 Hardwire SSS Hardwire PSDV-xxxx FG -
BC Package PSDV-xxxx outlet BC

On high-high level in in in BC PSDV-xxxx Inlet BC


BC Package SD-3.13 PCK8A-SIF-08 Discharge, close inlet PSDV-xxxx LSHH-xxxx 1oo1 Hardwire SSS Hardwire PSDV-xxxx FG -
BC Package PSDV-xxxx outlet BC

On low-low pressure in Liquid


ID-PCK-SWPG-1080-512003 SD-3.15 PCK8A-SIF-09 Transfer Pump suction,close FG PALL-139135/13916 1oo1 Hardwire SSS Hardwire PSDV-13902
suppy to Liquid Transfer Pump

On high-high pressure in Liquid


ID-PCK-SWPG-1080-512003 SD-3.15 PCK8A-SIF-10 Transfer Pump discharge, close FG PAHH-13910/13911 1oo1 Hardwire SSS Hardwire PSDV-13902
suppy to Liquid Transfer Pump

Page 1 SIF Table


Fire Zone SIF Description Success Input Logic Output Success
PID No. SIF Number Initiators Main Final Elements Other Final Elements Assigned SIL Comments
ESD1 bar Design Intent Criteria Transmission Solver Transmission Criteria

On low-low pressure in Liquid


ID-PCK-SWPG-1080-512003 SD-3.15 PCK8A-SIF-11 Transfer Pump discharge,close FG PALL-13913/13914 1oo1 Hardwire SSS Hardwire PSDV-13902
suppy to Liquid Transfer Pump

On high-high pressure in FG
PSDV-13902
ID-PCK-SWPG-0103-500016 SD-3.15 PCK8A-SIF-12 scruberr, close FG suppy to Liquid PSHH-13121A 1oo1 Hardwire SSS Hardwire
FG System Shutdown
Transfer Pump

On high-high level in FG scruberr,


PSDV-13902
ID-PCK-SWPG-0103-500016 SD-3.15 PCK8A-SIF-13 close FG suppy to Liquid Transfer LSHH-13120 1oo1 Hardwire SSS Hardwire
FG System Shutdown
Pump

On low-low pressure in WHCP,


WHCP ESD-1.11 PCK8A-SIF-14 PALL-13111 2oo3 Hardwire SSS Hardwire
close all DHSV & other final element

Note: Success criteria of the final elements is determined based on the number of main final elements which directly meet its design intent.