Professional Documents
Culture Documents
Internship Report
Project: Protection Relays
Protection settings for new EE-620 Panels to be replaced in Plant-1 turn
around
I&E Department
Engro Fertilizers Limited
ACKNOWLEDGEMENT
The internship opportunity I had with Engro Fertilizers Limited was a great chance for learning
and professional development. Therefore, I consider myself as a very lucky individual to be
provided with this opportunity. I am also grateful for having a chance to meet so many
wonderful people and professionals who led me through this internship period.
I am thankful to Mr. Hamid Anjum (Group Leader Electrical) for providing me with the best of
professional assistance. I choose this moment to acknowledge his contribution gratefully.
I perceive this opportunity as a big milestone in my career development. I will strive to use the
gained skills and knowledge in the best possible way, and I will continue to work on their
improvement, in order to attain desired career objectives. Hope to continue cooperation with
all of you in future.
Sincerely,
Aima Nadeem
25 August, 2016
PREFACE
The purpose of this report is to explain what I did, learned and achieved during my internship
period with Engro Fertilizers Limited. The report primarily focuses on the project assigned to me
which is protection relays. Protection settings for new EE-620 Panels to be replaced in Plant-1
turn around
The scope of this report primarily deals with the calculations and application of protection
settings done on MICOM protection relays. Some of MICOM non protective features have also
been discussed in the latter sections.
It is hoped that this report will provide compiled information to my colleagues to enhance their
knowledge and expertise.
Contents
Plant SLD (Single line diagram) ..................................................................................................................... 6
Synchronous generator/alternator ............................................................................................................... 6
Types of excitations ....................................................................................... Error! Bookmark not defined.
Synchronous Motor ...................................................................................................................................... 7
Induction Motor ............................................................................................................................................ 8
Power Factor correction ............................................................................................................................... 9
FLA (Full Load Amperage): ............................................................................................................................ 9
Locked rotor code: ........................................................................................................................................ 9
Current Limiting Devices ............................................................................................................................. 10
Reactor ............................................................................................................................................ 10
Is- Limiter ........................................................................................................................................ 10
DOL (direct on line) Starters ....................................................................................................................... 11
SWITCH GEAR.............................................................................................................................................. 12
Voltage Level Switch gear Properties: ................................................... Error! Bookmark not defined.
Motor control centers:.................................................................................................................................. 9
Current transformers .................................................................................................................................. 12
Types ........................................................................................................................................................... 13
Bar type ................................................................................................................................................... 13
Window type ........................................................................................................................................... 13
Wound type ............................................................................................................................................ 13
Potential transformer ................................................................................................................................. 14
Circuit Breaker ............................................................................................................................................ 14
RELAYS......................................................................................................................................................... 18
CLASSIFICATION OF RELAYS: ....................................................................................................................... 18
Contactors ................................................................................................................................................... 19
Disconnecting fuse ...................................................................................................................................... 19
MG set (motor generator set)..................................................................................................................... 19
Neutral grounding resistance (NGR) ........................................................................................................... 19
Leakage reactance ........................................................................................................................................ 9
Pickup current ............................................................................................................................................. 20
Plug Setting Multiplier ................................................................................................................................ 20
(Current transformer) CT ratio ....................................................................... Error! Bookmark not defined.
Over current protection .............................................................................................................................. 20
1. Instantaneous over current ............................................................................................................ 20
2. Definite time over current .............................................................................................................. 20
3. Inverse time over current (IDMT) ................................................................................................... 20
Classification of Inverse time relays............................................................................................................ 21
Study of 6.6kV, 40kA switchgear outgoing panels ...................................................................................... 25
Lock out relay .......................................................................................................................................... 26
Earth switch ............................................................................................................................................ 27
Core balance CT or zero sequence CT ..................................................................................................... 25
Surge arrestor ......................................................................................................................................... 26
Capacitive voltage indicator.................................................................................................................... 26
Limit switches.......................................................................................................................................... 26
Watch dog ............................................................................................................................................... 26
Trip circuit supervision ............................................................................... Error! Bookmark not defined.
Opto isolator ............................................................................................................................................... 27
Buccholz relay ............................................................................................................................................. 27
Watch dog ...................................................................................................... Error! Bookmark not defined.
Trip circuit supervision ................................................................................................................................ 39
MICOM P122 ............................................................................................................................................... 28
Phase rotation ............................................................................................................................................. 41
Positive phase sequence ..................................................................................................................... 41
Negative phase sequence ................................................................................................................... 41
Broken conductor detection ....................................................................................................................... 41
Cold load pickup .......................................................................................................................................... 41
Protection settings ...................................................................................................................................... 32
MICOM P141 .................................................................................................. Error! Bookmark not defined.
PSL Logic settings ........................................................................................................................................ 37
BASICS:
Synchronous generator/alternator
In a synchronous generator, a dc current is applied to the rotor winding, which produces a rotor
magnetic field. The rotor of the generator is then turned by a prime mover, producing a rotating
magnetic field within the machine. This rotating magnetic field induces a three-phase set of voltages
within the stator windings of the generator.
Paralleling Conditions:
Rms line voltages of 2 generators must be equal
Same phase sequence
Frequency of incoming generator must be slightly higher than frequency of the running system.
Synchronous Motor
In a synchronous motor, the field coil of stator is excited by a 3 phase AC supply. This will produce a
revolving magnetic field (RMF), which rotates at synchronous speed. Rotor is excited by a D.C power
supply which produces a constant magnetic field.
f
Ns= 120. P
A synchronous motor has many important torques that determine the ability of the motor to start,
accelerate, pull its connected load into step, and operate it through anticipated peak loads within its
design limits.
2. Accelerating torque.
This is the motor torque developed from stand-still to pull-in speed minus the load torque.
3. Pull-up torque.
This is the minimum torque developed between stand-still and the pull-in.
4. Pull-in torque.
This is the torque developed during the transition from slip speed to synchronous speed and generally is
defined at 95% speed.
5. Synchronous torque.
This is the steady state torque developed during operation. It is load dependent.
6. Pull-out torque.
This is defined as the maximum steady state torque developed by the motor, for one minute, before it
pulls out of step due to overload.
Induction Motor
No dc current is required to run the machine. It is a self starting motor. Such machines are called
induction machines because the rotor voltage (which produces the rotor current and the rotor magnetic
field) is induced in the rotor windings rather than being physically connected by wires.
2 types of rotors
o Squirrel cage
o Wound round
Reactances of generators:
Xd: steady state reactance.
Xd”: sub transient reactance or short circuit impedance of the generator. The current is I’’ and time
constant is T’’.
Motor control centers: MCCs have motor starter, motor protection and frequency drives.
Similar to a synchronous motor whose shaft Group of parallel/ series identical capacitors
is not connected to anything but spins freely. used for reactive power compensation.
It either generates or absorbs reactive power
in order to adjust grid voltage.
FLA (Full Load Amperage): Motor’s rated current at rated load and rated voltage.
Locked rotor code: The starting kVA required by a motor starting at full voltage is determined from
the name plate on the motor.
Reactor
Is- Limiter
Reactor
Reactor is a current limiting device that;
Coil having a large number of turns and a greater ohmic resistance. Reactors have a non-magnetic core.
They are used to limit short circuit currents which can cause damage to the equipments of power
system. They have a considerable voltage drop across them.
Reactors at Plant:
Is-Limiter
IS limiters are fault current limiting devices that use chemical charges and current limiting fuses to
interrupt the fault current within the first quarter to half cycle (before the first peak).
It has no voltage drop across it. In a typical IS limiter design, the device is composed of two current paths
connected together in parallel – one path is an element rated for the full load current (which can have
high continuous current ratings, e.g. 3000A), and the other path provides the current limiting function
via a current-limiting fuse (which typically has a continuous current rating of <300A at 15kV).
In the event of a fault, the device operates by physically destroying the continuous current path using
one or more chemical charges triggered by an electronic sensing and control unit. The fault current is
thus forced through the current-limiting fuse.
1. Circuit Breaker (to provide protection from large short circuit currents)
2. Contactor (to ensure smooth flow and assistance in interrupting when needed)
3. Overload Relay (to provide protection from overheating due to overload conditions)
DOL starter consists of two circuits: a power circuit and a control circuit.
The power circuit runs from the line to the motor. Electricity passes through the contacts of
a starter, the overload relay and out to the motor. The power (main) contacts carry the
motor current.
The control circuit operates the contactor (on/off). The contacts that interrupt or allow the
main current to flow to the motor are controlled by opening or closing the contacts in the
control circuit.
The control circuit energizes the coil creating an electromagnetic field that pulls the power
contacts closed, thereby connecting the motor to the line. The control circuit makes remote
operation possible.
The control circuit can get its power on one of two ways. If the control circuit gets its power
from the same source as the motor, this is termed Common Control.
The other type is Separate Control. This is the most common form of control. In this
arrangement, the control circuit gets its power from a separate source, usually lower in
voltage than the motor's power source.
SWITCH GEAR
In an electric power system, switchgear is the combination of electrical disconnecting switches, fuses or
circuit breakers used to control, protect and isolate electrical equipment.
Switchgear is used both to de-energize equipment to allow work to be done and to clear faults
downstream. This type of equipment is directly linked to the reliability of the electricity supply.
Current transformers
Current transformers are used for protection, instrumentation, metering and control. They reduce high
currents to a much lower value and provide a convenient way of safely monitoring the actual electrical
current flowing in an AC transmission line using a standard ammeter. The principal of operation of a
current transformer is no different from that of an ordinary transformer.
Types
Bar type
In this type of current transformer, the primary winding is nothing but a bar of suitable size. The
insulation on the bar types primary is bakelized paper tube or resin directly moulded on the bar. Such
bar type primary is the integral part of the current transformer. The core and the secondary windings
are same in bar type transformer.
Window type
This is a very common type of construction is the so-called “window,” “through” or donut type current
transformer in which the core has an opening through which the conductor carrying the primary load
current is passed. This primary conductor constitutes the primary winding of the CT (one pass through
the “window” represents a one turn primary), and must be large enough in cross section to carry the
maximum current of the load.
Wound type
In the Wound Primary current Transformer, the primary winding is also constructed inside the current
transformer body. The primary winding is usually of a single turn. Wound Primary Current transformers
are used in applications which require small current transformation ratios. They are more accurate and
have a higher burden capacity. The wound primary is usually designed with toroidal cores for high
efficiency.
Difference between metering CT and protection CT:
Metering CT Protection CT
Designed near the knee point. Function only Have to protect faults, so they are not
till the full load current then it will saturate. supposed to saturate during fault current ad
they should transform secondary current
exactly replica of the fault current.
PS Protection Special
M Measuring CT
Potential transformer
Potential transformers are connected in parallel to measure bus voltage levels.
Circuit Breaker
Circuit breaker is an electromechanical device which can
HVX 12 40 12 E
Type Rated voltage Rated short Rated current Drawing unit
circuit breaker
current
ACB internal(C.T)
Air Circuit Upto 10,000 A. current
Breaker is a transformer
device used to Protective Relay
LV/MV provide over
current and
Short Circuit
Protection.
VCB External (C.T)
When the current
contacts in transformer
vacuum 3000 A potential
interrupter 1-72 kV/ transformer
separate, the 72.5kV-800 kV Protective Relay
current to be Bushing
MV/ HV interrupted
initiates a metal
(insulation)
vapour arc
discharge and
flows through
the plasma until
the next current
zero.
OCB
In such circuit 1- 72 Kv
breakers some
insulating oil is
used as an arc
MV quenching
medium.
SF6 Bushing
In an SF6 (insulation)
circuit-breaker, From 72.5 kV upto 800 Instrument
the current kV transformers
HV continues to relays
flow after
contact
separation
through the arc
whose plasma
consists of
ionized SF6 gas.
RELAYS
A relay is an electrically operated switch. Many relays use an electromagnet to mechanically operate a
switch, but other operating principles are also used, such as solid-state relays.
Relays are used where it is necessary to control a circuit by a low-power signal (with complete electrical
isolation between control and controlled circuits), or where several circuits must be controlled by one
signal.
CLASSIFICATION OF RELAYS:
Electro-mechanical relays work on A solid state relay (SSR) is a device Numeric relays are programmable
the principle of coil energized that switches on or off when an relays where the characteristics
electrically external voltage is applied across its and behavior can be programmed.
causing plunger to move terminals and contain no Most numerical relays are also
mechanically. mechanical parts. multifunctional.
Contactors
A type of relay that can handle the high power required to directly control an electric motor or other
loads is called a contactor. Unlike a circuit breaker, contactor is not intended to interrupt a short circuit
current.
Disconnecting fuse
A fuse is an over current responsive safety device used to protect an electrical circuit from the effects of
excessive current. It is placed in series with the electrical circuit it is intended to protect. Its essential
component is a strip of metal that will melt when the electric current in the circuit exceeds the fuse's
rated value. The element (link) in the fuse melts and opens the circuit.
Grounding through resistance can be of two types High Resistance or Low Resistance which are
distinguished by the amount of current permitted to flow.
Important terms related to protection settings calculation:
Pickup current:
The current for which the relay initiates it operation is called pick up current of relay.
Time Setting
With time setting, we can adjust the time of operation of a relay
There are two types of time settings:
• Definite time (DT)
• Inverse time (TMS-Time Multiplier Setting)
• Very Inverse
• Extremely inverse
Time setting formulas for these curves are given as:
• If we have two different applications but the motor rating is the same.
The core balance current transformer can be connected to an earth fault relay which can be used to
generate the tripping signal.
Surge arrestor
Surge arrestor is used for protection of electrical equipment from all kinds of over voltages caused by
lightening or switching operations. It has a metal oxide varistor that at normal voltage acts as an
insulator but at high voltage acts as a conductor.
Limit switches
A limit switch is a switch operated by the motion of a machine part or presence of an object.
It is an electromechanical device that consists of an actuator mechanically linked to a set of contacts.
When an object comes into contact with the actuator, the device operates the contacts to make or
break an electrical connection.
Opto isolator
Uses short optical transmission to transfer an electrical signal between circuits while keeping them
electrically isolated.
Buccholz relay
A Buchholz relay is a safety device sensing the accumulation of gas in large oil filled transformers, which
will trigger the alarm on slow accumulation of gas or shut down the transformer if gas is produced
rapidly in the transformer oil. It is sensitive to the effects of dielectric failure inside equipment. The
contacts are not operated by an electric current but by the pressure of accumulated gas or oil flow.
MICOM P122
Protection available
– 50/51 Three-phase over-current
– 37 Undercurrent
Front layout:
Things to enter in MiCOM:
Which protection?
Which curve?
EE-240
EE-2440
EE-641, EE-645
EE-642, 644
Housing outgoing feeder
MC-2D
PM&S-4 CWS
TX-A’s
Offsite outgoing feeder
MC-702
MG-2501
MP-421A
MP-421B
MP-2515D
Fault Level
Imin=4.13 kA
Imax=27.56 kA
IEmin = 0.2kA
IEmax= 1.316kA
Guide Line
Protection ANSI Pick-up Level Curve Time Dial Setting or
Function Code Type Time Delay
Time Delayed 51 1.05 x Motor Rated SI As per coordination
Over Current Current with motor current
Short Circuit 50 1.25 x Motor Starting DMT 50ms
Current
Earth Fault 50G 30% of Motor Rating DMT 50ms
Under Voltage 27 50% of Rated Voltage DMT 1 , 2 , 3 or 4 secs
Under Frequency 81 Depending upon ILMS DMT 0 secs
Group
Phase Fault
CT Ratio 200 / 1
I> 51 0.315 SI 1.35
I>> 50 2.45 DMT 50ms
Earth Fault
CT Ratio 160 / 1
Ie> 50G 0.1125 DMT 50ms
Under Voltage
PT Ratio 6600/110
V< 27 55 DMT 5 secs
Under Frequency
PT Ratio 6600/110
F< 81 48 DMT 0 secs
Guide Line
Protection ANSI Pick-up Level Curve Time Dial Setting or
Function Code Type Time Delay
Time Delayed 51 100 x Transformer Rated SI As per coordination
Over Current Current with upstream feeder
Short Circuit 50 Less than 80% of Min DMT 50ms
short circuit current
Earth Fault 50G 30% of Transformer DMT 50ms
Rating
Under Voltage 27 50% of Rated Voltage DMT 1 , 2 , 3 or 4 secs
Under Frequency 81 Depending upon ILMS DMT 0 secs
Group
Phase Fault
CT Ratio 600 / 1
I> 51 0.252 SI 0.54
I>> 50 10 DMT 50ms
Earth Fault
CT Ratio 160 / 1
Ie> 50G 0.284 DMT 50ms
Under Voltage
PT Ratio 6600/110
V< 27 55 DMT 5 secs
Under Frequency
PT Ratio 6600/110
F< 81 49 DMT 0 secs
SIGRADE
SIGRADE is a Siemens Software for over current protection coordination. We enter the protection
criteria, settings range and ratings of motors and SIGRADE calculates the protection settings for it
accordingly. It also plots over current coordination curves useful for time coordination of our electrical
network
SIGRADE COORDINATION CURVES
The following curve shows that motor takes inrush current for 5 seconds. We have to make sure that no
overlap takes place between circuit breaker curve and motor taking inrush current curve.
Software settings:
Opto Signal Input signal Output signal LED contact Relay contact Logic gates
Programming LEDs
This is how we program different LEDs according to the type of function we want them to light on:
VT supervision
The voltage transformer supervision (VTS) feature is used to detect the failure of ac voltage
inputs to the relay.
This may be caused by internal voltage transformer faults, overloading or faults on the
interconnecting wires to relays. This results in one or more VT fuses blowing.
Following a failure of AC voltage input there would be misinterpretation of the phase voltages
on the power system, as measured by the relay, which may result in mal-operation.
There are three main aspects to consider regarding the failure of VT supply. These are defined
below:
1. Loss of one or two-phase voltages
2. Loss of all three voltages under load conditions
3. Absence of three phase voltages upon line energization.
Should both sets of contacts be open, this would indicate one of the following conditions:
Should both sets of contacts be closed, only one of the following conditions would apply:
SCHEME:
This scheme provides supervision of the trip coil with the breaker open or closed,
however, pre-closing supervision is not provided.
When the breaker is closed, supervision current passes through the opto input, blocking
diode and trip coil.
When the breaker is open current still flows through the opto input and into the trip coil
via the 52b auxiliary contact.
Lockout relay:
Whenever any fault occurs, lock out relay is latched. We have to reset it manually because if lock out
relay is operated , breaker will not turn on.
Anti pumping relay
The function of an anti-pumping device is to prevent the circuit breaker closing and opening several
times in quick succession. This might be caused by the application of a closing pulse while the circuit
breaker is being tripped via the protection relays.
• FREJA 300 is intended primarily for secondary testing of protective relay equipment.
Local
• In the Local mode, you do not need a personal computer to perform the control functions.
Remote
• Software: FREJA Win
Remote mode: Time test
Secondary injection:
Select IEC inverse graph and then inject secondary current.
Conclusion
Henceforth, I was successfully able to do the protection setting calculations and hands on application
and testing of those settings on MiCOM 122,141 and 241 respectively. I learnt SIGRADE, FREJA testing
and Programmable Scheme Logic. Moreover, I also learnt about various non-protection functions of
MiCOM protection relays.