Paper 0292
Eskom Distribution recognized that reliability The performance analysis study will evaluate the
transformers manufactured up to 1998. The
improvement required a lifespan performance study on implementation of the reliability improvement initiatives
large power transformers. spans from 1998 – 2006. The study was confined to the
three regions A, B and C, for which reliable data was
The paper provides results of a performance study on available.
large power transformers on a section of the Eskom
Distribution network. The data is analysed and The failures have been defined according to the failure
interpreted in terms of its probability density function definition given in IEC 60050 as:
(PDF), its survival function and hazard function to
determine an onset of unreliability in transformer life and The termination of the ability of a transformer to perform
its specific function.
its survival time thereafter. The data is also investigated
against the major component failures with its associated The data set includes the failures of 58 transformers
PDF, survival function and hazard function. . within the 10MVA - 160 MVA rating range and 22kV -
132kV primary voltage range, manufactured up to 1998
The paper then reviews the initiatives taken by Eskom in and failing in the period 1996 – 2006. The analysis was
terms of design, operation and maintenance to improve set at component level.
the reliability of large power transformers.
The three investigated regions represent a sample space
population of 4914 transformers observed over a period
INTRODUCTION of 11 years. This is equivalent to approximately 38% of
The distribution network of Eskom, the national utility, the number of transformers and approximately 44% of
covers most of the country’s geographical area of about the installed capacity, within the specified rating and
1.2 million km2 and is divided into six regions, shown in manufacturing range, on the distribution network in the
Fig 1. period 1996 – 2006.
Paper 0292
• Higher failure rates in early life that could be with design or manufacturing problems. The survival
associated with design or manufacturing time for these units is approximately 45 years.
problems.
• Constant or low failure rates, representing From the hazard function a period of low failure rates can
normal life be observed up to 20 years, representing normal
• Increasing failure rates after a certain age that transformer life.
which can be associated with end of life wear
out failures
After 20 years, the failure rate increases with age, and is
associated with end of life wear out related failures. A
PERFORMANCE ANALYSIS large portion of the population would have aged within
the next 10 years, thus increasing the risk of failure due
Transformer Population for 1996 – 2006 to higher failure rates experienced in older units.
0.80
Failure Rate
Probability
0.15
0.1
The nominal design life is 35 years. 0.40
0.05
0.20
0.00 0
250 0 5 10 15 20 25 30 35 40 45
Age (Years)
Survival PDF Hazard
200
150
0
35%
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
Age (Years)
30%
25%
Figure 2: Transformer Population – Age
Failures
20%
15%
10%
Transformer Failure Analysis Results
5%
Paper 0292
1.2 0.25
The failure probability distribution with respect to
1
0.2 voltage level shown in figure 8 indicates that failure
0.8 probabilities are generally higher with increasing voltage
Failure Rate
Probability
0.6
0.15
levels.
0.1
0.4
0.3
0.05
0.2 0.25
0 0 0.2
Probability
0 5 10 15 20 25 30 35 40
0.15
Age (Years)
0.05
1
1
66 2
1
2
66 33
1
2
13 33
.6
88 2
.6
1 3 .1
1 3 .6
13 1
13 2
13 3
2/ 6
2/ 1
2/ 2
1 3
2/ 88
2 / .6
2
/1
/1
/2
/1
/2
/1
/2
1
2
3
13 2/6
2
1 3 6 /1
1 3 6 /2
/3
/2
/6
/6
5
6
1 3 /6
/
6/
2/
2/
2/
13 32/
22
33
33
66
66
66
88
88
88
2/
2/
66
88
88
/6
6
6
Rated Voltage (kV)
1.20 0.25
Figure 8: Probability of Failure by Rated Voltage
1.00
0.20
0.80
Transformers older than 35 years are predominantly of
the higher primary voltage, larger rating range. No
Failure Rate
Probability
0.15
0.60
statistically significant changes were observed in the
0.10
0.40 failure probability distribution with MVA rating.
0.05
However, the failures on larger rating units are
0.20
considered as a higher risk in terms of MVA-loss and
0.00
0 5 10 15 20 25 30 35 40 45
0.00 their associated age profiles.
Age (Years)
Survival PDF Hazard
RELIABILITY INITIATIVES
0.15
0.6 Initiatives in the design specification phase of large
0.4
0.10 power transformers concerned mainly the bushings, on-
0.05
load tap changers and winding designs. These changes
0.2
were effected after 1998 and the effects would not be
0
0 5 10 15 20 25 30 35
0.00
reflected in the performance analysis above.
Age (Years)
Paper 0292
operation cycle. low failure rates and periods where wear out sets in. The
wear out periods starts after about 20 years, with various
The colour of the paint applied to the external body of the components behaving differently, so that most of the 58
main tank was changed from Dark Admiralty Grey to units failed within the intended design life of 35 years.
Cloud Grey to reduce the impact of solar heating.
No high failure rates were observed in early life that
Temperature rise limits in the specification were reduced could be associated with design or manufacturing
by 10 oC compared to IEC 60076 to improve thermal problems, although the onset of unreliability occurs in
performance in the South African environment. In this period.
addition, thermally upgraded paper and limiting the
ONAN/ONAF ratio to 0.7 p.u. are included in the Bushing, winding and tap changer related failures
specification. The maximum flux density in the core legs contribute to the largest percentage of the failures
and yoke is limited to 1.72 T. The cooling duct width recorded.
was set at a minimum of 3 mm to promote oil flow.
Dissolved Gas Analysis tests are required directly after Failure probabilities are higher with increasing voltage
the heat run test. levels with no significant changes being observed in the
failure probability distribution with rating. Units older
The short circuit performance of the transformer was than 35 years are predominantly of the higher voltage and
strengthened with the inclusion of a fixed winding larger ratings, and their failures are considered as a
arrangement. In a two winding configuration the higher risk on the network in terms of MVA-loss.
specified order is LV-HV-regulating and in an auto
transformer the order is Tertiary-common-regulating- The failure distributions presented were based on the
series. The specific stress ( aver) of the inner winding is failure data of three regions and the inference drawn from
set at a minimum of 50 % of the copper conductor yield them could differ from that of the entire distribution
strength for epoxy bonded CTC windings while the aver network.
of the outer winding is set at a minimum of 80 %.
The effect of the design and operating and maintenance
The specification includes digital type thermal indicators, changes introduced to reduce the effects of the
to assist with condition monitoring and aging analysis. operational stresses will only be visible after the start of
Moisture in paper insulation after drying process is set at the wear out period in 15 to 20 years time.
a maximum of 1% and the onset degree of
polymerization value at a minimum of 950. ACKNOWLEDGEMENTS
Detailed design reviews for thermal, insulating and short The authors would like to recognize the assistance from
circuit designs have been introduced recently. J. Mostert, B. Meyer and D. De Goede of Eskom and D
Scott of Expoitech.
Operating and maintenance
The in-service transformer life management process is REFERENCES
supported by an on-going life assessment process as
described in [4]. Critical risks are identified and [1] J.A. Lapworth, 2006, "Transformer Reliability
reviewed; maintenance strategies adapted and input given Surveys", CIGRE 2006 Paris Session, A2-114
to capital investment committees as far as network [2] W. Nelson, 1982, Applied Life Data Analysis,
reliability is concern. Publisher, John Wiley & Sons, New York, USA, 15-
28.
New initiatives include on-line moisture assessment and [3] A. Bossi, 1983, "An International Survey on Failures
removal, assessing the need for on-line tap changer in Large Power Transformer in Service” – Final
maintenance by the monitoring of oil condition and Report of CIGRE Working Group 12.05, CIGRE
number of tap operations, and investigations into on-line Electra, No. 88, pp. 20-48.
filtration of tap-changers in the event of moisture being [4] L.M. Geldenhuis, 2005, "Power Transformer Life
the only indicator to perform maintenance on on-load tap Management", CIRED Turin Session, vol. 1, 26/1-
changers. 26/3
CONCLUSION
The lifespan performance study on the 58 failed
transformers manufactured up to 1998 indicate an
increasing failure rate with age, with periods of relatively