Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
1
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
2
we shall see, it does not predict accurately the peak pressure Fig. 4.
for the fault and tank considered, but rather provides an upper
bound value for design purposes.
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
3
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
4
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
5
of 2.83 in2; much less than the physical size of the actual
pipes. With this smaller area, and considering again instant
opening and closing of the valves, the shortest duration for
injecting 4.8 MJ with an initial pressure of 3,000 psi would be
about 250 ms. However, since the valves have finite opening
and closing times, we found that at 3,000 psi, the duration
required to inject 4.8 MJ with our system would be longer. For
this reason, the impact of a longer duration of injection in
relation to an actual arc of 50 ms was investigated. Since the
injection would take place within water as opposed to oil, this
effect was also investigated as described below.
2) Differences between an arc in oil and injection of air
into a water-filled tank
To study whether injecting air into a water-filled tank pro-
duces effects similar to an actual arc in oil, we used explicit
Fig. 7. Tank set-up.
dynamic analysis to simulate both situations for a 50-ms 20-
MJ fault. Fig. 9 first presents a comparison of the average
pressure within the tank under consideration for the two meth-
ods. Similar results were obtained for the maximum average
pressure: 394 kPa for arc in oil versus 409 kPa for air injec-
tion, a 3% difference. The design pressure of 556 kPa from (1)
is also shown. It is noteworthy that the latter is about 20%
higher than the pressure calculated by dynamic simulation;
this is not surprising as (1) was determined to cover a whole
range of tanks of different flexibilities and is therefore gener-
ally conservative. Several simulations outside the scope of the
present paper, on many different tanks, also confirmed this.
Fig. 9 also presents a comparison between the plastic work
Fig. 8. Schematic of gas injection system with respect to the tank. accumulated in the tank through plastic deformations. It is
E. Determination of test parameters using explicit dynamic observed that the air injection method leads to greater plastic
simulations work by about 13% over the arc in oil, with 904 kJ for air
Explicit dynamic simulation is a numerical methodology injection and 798 kJ for the arc in oil. This is explained by the
fully suited to the investigation of short duration phenomena, difference in rigidity between the liquids used inside the tank;
water is more rigid than oil, with a bulk modulus of 2.20 GPa
such as faults within transformers. We have used it in the past
to obtain representative results [4], [19], [21] of actual fault for water versus 1.47 GPa for oil. Since water is more rigid, it
situations and tests; the reader is referred to these latter refer- stores less energy from compression than oil. Thus, water
transfers more energy to the tank (there is also a variation
ences for a deeper description of its use. The test parameters
were determined using this methodology, as described below. between the energy stored in the gas bubble between oil de-
1) Theoretical test parameters versus test installation ca- composition and air injection since their specific heat ratios
pabilities are different: 1.4 for air versus 1.352 for oil [19]).
The design test required that the effects of a These comparisons show that the injection of air in a water-
20 MJ arc/50 ms duration be reproduced. As discussed, this filled tank generates overpressure similar to an arc in oil for
corresponds to injecting 24% of 20 MJ in the form of mechan- equivalent energy and duration, but produces slightly more
ical energy, or 4.8 MJ in 50 ms. In order to inject this amount tank plastic deformation. Therefore, injecting air in a water-
of energy, the initial pressure in the pressure vessel must be filled tank produces conservative, yet representative results.
determined, as well as the duration during which the valves
must be opened.
Considering the 3,000-psi maximum working pressure of
the pressure vessel and pipe sizes (2 x 2 inch diameter pipes
corresponding to a throat area A of 6.28 in2) available to us to
inject the gas, the shortest possible theoretical duration to
inject 4.8 MJ, assuming instant opening and closing of the
valves, is determined using (3) and (4) to be about 100 ms.
However, due to the restrictions introduced by the valves and
piping system, it was determined experimentally that the ef-
fective area of the injection system at hand corresponded to
two pipes of 1.25 inch diameter, for an effective throat area A
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
6
Fig. 9. Comparisons between arc in oil and air injection for a 20 MJ/50 ms versus 394 kPa), yet both methods yield the same plastic work
fault.
as required. It is also observed that the pressure with the air
3) Investigation on the duration length
injection methodology still remains under the design pressure.
Since the duration at hand is much longer than an actual
Using injection tests directly in ambient air (unconnected to
20 MJ/50 ms fault, Fig. 10 presents the effects of using differ-
the tank), it was identified that this amount of energy could be
ent durations for the same energy, in the case of air injection
injected in about 550 ms.
in the same water-filled tank. It is observed that
· the maximum average pressure is nearly independent F. Test results and comparisons with simulations
on the duration, although the residual pressure (stabi- 1) Design test
lized pressure once dynamic effects have subsided) The tank under consideration was subjected to air injection
increases with the duration of injection; equivalent to a 30 MJ fault in approximately 550 ms, from an
· the amount of plastic work decreases with the dura- initial pressure of 3,000 psi (20.7 MPa) in the pressure vessel
tion; used. The tank withstood the test without any rupture, projec-
· the maximum average pressure and plastic work for tion of parts, or leak, despite significant (permanent) plastic
the 250 ms and the 500 ms injection durations are deformations. Fig. 12 shows the tank before and after the test.
nearly identical, indicating a convergence of results
from a duration of 250 ms and up.
It is therefore obvious that the duration has a very signifi-
cant effect on tank plastic deformation: significant dynamic
effects are present for shorter durations, while longer durations
lead to a more monotonous rise of pressure with fewer oscilla-
tions. The fact that the residual pressure is higher for longer
durations is explained by the fact that since the tank is less
deformed for these (less plastic work), the volume of the gas
bubble is smaller (this volume being almost the same as the
tank volume increase since the fluid is nearly incompressible),
which corresponds to a higher pressure within it and therefore
within the tank.
Fig. 11. Comparisons between a 20 MJ/50 ms arc in oil, and a 30 MJ/250 ms
air injection.
Fig. 10. Effects of air injection duration (pressure: solid lines; plastic work: Fig. 12. Tank deformation before and after the design energy test.
dashed lines).
Fig 13 shows the pressure variation within the tank for the
4) Determination of the injection energy
nine sensors, as well as their average; all signals shown were
Since the tank design is based on its deformation under
filtered using a 20-point moving average. Also shown is the
pressure as discussed, it was decided to adjust the injected
average pressure within the tank from the simulation for a
amount of energy in order to obtain plastic work similar to a
500 ms injection duration. A good qualitative agreement is
20 MJ/50 ms arc in oil. To identify the corresponding amount
obtained between the simulation and the experimental results.
of required energy, several simulations were performed with
The maximum average pressure from the test is 430 kPa,
increased values of energy, using a 250 ms duration (since it
while the maximum average pressure from the simulation is
produces plastic work equivalent to longer durations but re-
488 kPa; a difference of 13%. Also, the design pressure at
quires less computational time). It was found that the mechan-
556 kPa of the nonlinear finite-element analysis is confirmed
ical energy corresponding to a 30 MJ fault was necessary in
as a safe design approach. Considering the phenomena in-
order to obtain about the same plastic work as a 20 MJ/50 ms
volved, such as large plastic deformations over a short dura-
fault. Fig. 11 presents a comparison between both sets of dura-
tion, as well as the idealizations inherent to the computer
tion and energy for the average pressure and plastic work. It is
model, the agreement between the test and simulation is very
observed that the peak average pressure is higher for the
good in our opinion. The observed differences may be ex-
30 MJ/250 ms air injection than for the arc in oil (513 kPa
plained by different factors. First, the computer simulation
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
7
idealized the way the gas is injected, by introducing it directly that from that point on, water was forcefully ejected onto the
within the tank [4], as opposed to the test, where the gas was ground through the vertical pipe attached to the end of the
introduced through a series of pipes ending in a corrugated valve. After 1 s, the average pressure was 417 kPa, while it
hose attached to the tank (Fig. 8). Due to this, and the finite was 220 kPa after 5 s. It is hence observed that the effect of
opening time of the valves, a delay is observed in the pressure the PRD opening is rather slow in comparison to a 3-cycle
rise during the test, as it is observed that the simulated pres- fault duration (50 ms). It is therefore inferred that while such
sure rise has an earlier onset. It was also observed that as the devices cannot be used effectively as a protection for low-
tank deformed during the test, the corrugated hose attached to impedance faults of short durations, their effectiveness is
the tank was progressively kinked, and it is believed that this probably adequate for high-impedance faults of much longer
introduced energy losses during the injection process. Also, durations.
there are probably other unaccounted energy losses in the 2) Rupture test
piping system due to their construction and changes in pipe For this test, water was added to the tank until it was com-
area, as well as losses introduced by valve construction and pletely refilled, replacing the volume change obtained from
operation. the design test. In order to generate rupture conditions within
the tank and verify that it would fail at the tank cover as de-
signed, the same test procedure was repeated without reclosing
the valves once opened, from the same initial pressure of
3,000 psi within the pressure vessel. This corresponded to a
potential release of energy amounting to a 66 MJ fault for the
complete emptying of the pressure vessel.
It was observed that the tank cover failed (Fig. 15) approx-
imately 450 ms after the start of the injection process, at an
average pressure of 486 kPa based on the peaks from the fil-
tered signals at the nine measurement locations; the unfiltered
signals revealed short time duration peaks over 1,000 kPa at
some locations but it is difficult to assess if these are real or
simply related to the dynamic response of the sensors.
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2019.2922505, IEEE
Transactions on Power Delivery
8
sized that this tank could withstand a fault of about 30 MJ in [10] M. Foata and G. Khouzam, "Power Transformer Tank Rupture," Cana-
dian Electrical Association, Engineering and Operating Division, To-
50 ms before rupturing (50 MJ/1.5). Additional dynamic simu- ronto, ON, March 1994.
lations following the same steps as the two experiments here [11] R. E. Kothmann, and D. G. Thompson, "Power Transformer Tank
(first experiment, tank refilled, second experiment) supported Rupture: Risk Assessment and Mitigation," EPRI, Technical Report TR-
104994, April 1995.
this hypothesis. A dynamic simulation of 30 MJ in 50 ms
[12] H. Murakami, T. Kobayashi, Y. Shirasaka and Y. Ebisawa, “Tank
yielded a peak pressure of about 1,000 kPa in the area close to Design for Low Rupture Risk – Japanese Practice,” Presented at CIGRÉ
the cover, in good agreement with the 946 kPa rupture pres- Transformer Technology Conference, Sydney, Australia, 2008.
sure obtained from the tank design static calculations. [13] Atlas of stress-strain curves, Second ed., ASM International, 2002.
[14] G. E. Dieter and L. C. Schmidt, “Engineering Design,” 5th ed., Ed. New
From the difference of approximately 10 MJ between the York: McGraw-Hill, 2013, pp. 628-679.
energy level at rupture (30 MJ) and the design energy level [15] S. Bélanger, S. Brodeur, J.B. Dastous and N. Soucy, "Experimental and
(20 MJ), it can be concluded that this particular design pos- Numerical Studies of Large Steel Plates Subjected to High Pressure
Loading," in Proc. World Congress on Computational Mechanics Ses-
sesses a safe leeway before rupture at the cover. sion, Barcelona, Spain, 2014.
[16] R. J. Ringlee and N. W. Roberts, "Tank Pressures Resulting from Inter-
IV. CONCLUSIONS nal Explosions," AIEE Trans., vol. 78, pt. III-B, pp. 1705-1710, 1959.
[17] S. Muller, M. Petrovan-Boiarciuc and M. Périgaud, “Pressure wave
This study demonstrates that it is feasible to design a power propagation induced by short circuits inside power transformers: Devel-
transformer to withstand high-energy low-impedance faults of opment of a simulation tool, comparisons with experiments and applica-
tions,” The International Journal of Multiphysics, vol. 3, no. 4, pp. 361-
short duration, which fail safely at the cover at fault energies 386, 2009.
above the design fault energy. The governing design principle [18] M. Foata, M. Iordanescu, C. Hardy, “Computational methods for the
to achieve this was based on increasing the tank flexibility analysis of explosions in oil-insulated equipment,” IEEE Transactions
on Power Systems, Vol. 3, No.1, February 1988.
while providing sufficient strength. The tank was designed [19] J.-B. Dastous and M. Foata, "Analysis of Faults in Distribution Trans-
using nonlinear finite-element analysis, using a rupture criteri- formers with MSC/PISCES-2DELK," presented at the MSC World Us-
on that is safe from a design point of view and proved by the ers Conf., Los Angeles, CA, 1991.
[20] I. G. Currie, Fundamental Mechanics of Fluids. McGraw-Hill Publish-
experiments. The tests were designed using explicit dynamic
ing Company, 1974, pp. 356-383.
simulations in order to reproduce the effects of an arc in oil by [21] J.-B. Dastous, M. Foata and A. Hamel, “Estimating Overpressures in
injecting pressurized air. It is noteworthy that the tank per- Pole-Type Distribution Transformers Part II: Prediction Tools,” IEEE
formed with a relatively good agreement with the finite- Trans. Power Delivery, vol. 18, no. 1, pp. 120-127, Jan. 2003.
[22] A. Hamel, J.-B. Dastous and M. Foata, “Estimating Overpressures in
element and explicit dynamic simulations results. The energy Pole-Type Distribution Transformers Part I: Tank Withstand Evalua-
levels used in the tests reported are, to our knowledge, the tion,” IEEE Trans. Power Delivery, vol. 18, no. 1, pp. 113-119, Jan.
largest ever reported. 2003.
0885-8977 (c) 2019 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.