Professional Documents
Culture Documents
1. Introduction
500-kVXLPE cables are scheduled to be installed to urban Treated portion of cable screen ~$~t~~i;forcing
areas in order to cope with the growing demand for electric
power in recent years. Jointless 500-kV XLPE cable has
already been in practical use for underground transmission layer
ReinforciAg insulationUSemiconductor
cables in power generation stations [l], however its
application to long-distance power transmission lines tl :Thickness of reinforcing
requires development of highly reliable joints. Iin response insulation
to this need, we have conducted various basic research on t2:Thickness of cable
einforcing insulati o
extrusion molded joints (EMJ) [2]. Also, based on the data insulation
which was obtained in the basic research, actual-size EMJs
were designed and fabricated, their elecaical performance
was evaluated, and the validity of the design was c o n f i e d .
10 10
c:
k, degradation coefficients
b;, h':tolerances with respect to uncertain elements (1.1)
k,ELrrp:minimum insulation breakdown stress with
1 0' 10'
respect to commercial frequency and lightning impulse
-:
e e e
n : Cumulative counts of defects e . Size (,urn)
contaminants o r voids (counts/mm')
semiconductors layer protrusions (counts/mm*)
Figure 2: Comparison of 275-kV EMJ and cable defects
637
ac imr,
E, before improvement (kV/mITI) 28 74
1.20 1.25 2.3 1.0
E,after improvement (kv/mm) 37 85
B. Treatmentportion of cable screen Performance improvementratio (%) 132 115
The required insulation thickness as determined in cable
design is 25 mm[3], but the insulation thickness of a 500-kV
XLPE cable having intermediate joints is determined by the
performance of the treatment portion of the cable screen of
the EMJ.
The electrical field Emin of the treatment portion of
cable screen is determined by the structure of the cable. The
minimum insulation breakdown stress Kmin required for this
portion is given by formulas (4) and (3,which the cable
must be designed to satisfy.
-.U
10
1- 6- 11- 16- 21-
-Performance required for commercial-frequency voltage e" , (
%xk, xk, xk, Figure 3: Protrusion level of treated portion of cable screen
Emin = 4 3 and performance improvement ratio
(+) x In( ?)
(4)
cross-sectional area
01 conductor : 2500mm'
21=130--155mm, 11 =36mm.
fiz=105-160mm t=27mm
3-2. Tests of Breakdown Stress for Reduced Insulation Joint
Figure 4: Structural dimensions of 500-kVEMJ The thickness of the reinforcing insulation was designed in
consideration of the fact that the reinforcing insulation has
The minimum breakdown stress, E, for 500kV EMJ, which the same kind of thickness dependence of E, as cable. This
serves as the basis for calculating the reinforcing insulation test was carried out for the purpose of confming the validity
thickness, is determined by the E, of 12 mm thick EMJ and of this approach. The samples were made to the same size
the formula(3) including 10% safety allowance. The results as a 500-kV EMJ represented in Figure 6 , except the
are given in Table 3. According to this, when the required reinforcing insulation thickness above the conductor sleeve.
insulation thickness for commercial-frequency voltage and The reinforcing insulation thickness was reduced to 9, 15,
lightning impulse voltage were calculated using (1) and (2), and 20 mm in order to make breakdown at this portion. A
we get tac = 35.7 mm, timp = 32.7 mm, thus the reinforcing breakdown test was performed for both ac and imp, with 4
insulation thickness was set to 36 mm [2]. samples each (a total of 24 samples). The test voltage
The Kmin for the treatment portion of cable screen was conditions are listed in Table 5. The starting voltage was
calculated by taking the value for a 275kV EMJ fabricated by equivalent to 90% of minimum breakdown stress
the conventional technique, multiplying it by the Et ,obtained by thickness dependence formula of Figure 5.
performance improvement factor (ac:1.32 imp:1.15). The
results are given in Table 3. From this, the insulation Table 5: Breakdowntest conditions
thickness of the cable required by the performance of
treatment portion of cable screen was set to 27 mm.
3-3. Evaluation Test of Crosslinking Temperature Control investigation method would be the n-1 distribution, which
As stated in the previous chapter, according to the determined in detail the distribution of type and number of
crosslinking temperature conditions, the unique defects (see defects from 1 slice. In addition, this time, 100 slices (x 4
Figure 1) can arise at the edges of reinforcing insulation of companies) would be sampled from the reinforcing
the EMJ, which reduce the electrical performance. The insulation and the largest contaminants (blacWmetal) in each
crosslinking temperature conditions were conducted for the slice would be examined, and their distribution would be
purpose of evaluating whether there is a tolerance with evaluated.
respect to the reduction in performance arising fiom these
unique defects. 4. Results of development tests
Shown in Figure 7, T1 is defined as the temperature of the 4-1. Tests of Minimum Insulation Breakdown Stress
conductor sleeve, when crosslinking degree of reiiforcing The test results are summarized in Figures 8 and 9. The
insulation near the conductor sleeve reaches 90%. T2 is results of the reinforcing insulation and the treated portion of
defined as the temperature of the conductor sleeve, when cable screen were evaluated by stress separately. In each case,
crosslinking degree at edge of reinforcing insulation reaches the data exceeded the design value and it has sufficient
90%. And A T is defined as the difference between T1 and initial value.
T2.It has been reported that the unique defects tend to occur , -
as A T is large 161. Thus samples were fabricated under E
E 70 ............
special crosslinking temperature conditions whereby a 3
5
temperature difference is A T'( = A T(standard condition) E
..................................................................................................
+ 10' c ). E
W
(Designed ELimp)
The test voltage conditions are given in Table 6. v1
E
v)
I t e m e r a t u r e of conductor sleeve E
2
2I 10 -.............................................. I...................................................
T2
100 ; f 0
' AC breakdown dala
6 AC cut-on dala
9 ' IMP breakdown data
6 IMP cui-otfdam 1
L m temDerature 1 QO'C
n
f Figure 8: Breakdown stress of reinforcing insulation
of r e i n f o r c i n g insulation
crosslinked degree
near conductor sleeve
.
x
0 0
Passed Tine 1 hours
2 50
-0=2 40 n d a r d deviation
Table 7: Electrical test results I .-
a
3
) 30
~
$? 20
z8 10
1 2 3 4 5 6 7 8- 9 10 11 12 13 14 15 16 17 18 19 2021 2 2 2 3
Size of contaminants (pm)
119 125 127 129 86.2 Figure 11: State of distribution of largest contaminants in
106 114 115 125 78.6 raw direction
101 105 110 122 74.6
5. Evaluation and conclusions
4-3. Evaluation Tests of Crosslinking Temperature Control 5-1. Temperatme coefficients
The electrical test results are given in Table 9. It was The E, values, as well as the 63.2%breakdown probability
confirmed that the performance is about the same as for test values, at room temperature and at 90" C were determined
samples made under standard crosslinking temperature by the results of the Tests of Minimum Insulation Breakdown
condition (see ac data at r.t. in Figure 9). Also, after Stress (E3. The ratio of values at room-temperature and at
dismantling, no unique defects were found near the edge of 90" C was determined, and it was selected as a temperature
reinforcing insulation by microscopic observation. These coefficient. These values are presented in Table 10. From
results confmed that the current crosslinking conditions are these evaluation results, the temperature coefficients for
adequate with respect to occurrence of the unique defects commercial-frequency voltage were 1-1.05, and those for
near the edge of reinforcing insulation. lightning impulse voltage were 1.15-1.21. It was confirmed
that adopting the design values (ac: 1.20, imp: 1.25) results
Table 9: .Electricaltest results on the safe side.
shown in Figures 12 and 13. It was confirmed ithat the E, 5-4. Performance improvement factor at treated portion of
value obtained from the breakdown test data is gireater than cable screen
the design value, and that there is a tolerance with respect For 500-kV EMJ a cable insulation thickness of 27 mm was
to the design value. adopted, identical to the 275-kV case, as a result of
improvement of the treated portion of cable screen by
treatment method improvements. Table 11 shows the
results of calculating the performance improvement ratio of
the E, value determined in the preceding section and the E,
value of 275-kV EMJ (cable insulation thickness 27 mm)
without improvement of the treatment method.
1 5 I 5 10 50 100 Approximately the same value was obtained as that of a
IkVfmml
model EMJ with a cable insulation thickness of 10 mm.
Figure 12 Weibull analysis results (reinforcing insulation)
Table 11: Comparison of improvementratio
of minimum breakdown stress
137% 132%
121% 115%
subsequent paper [7]. Transmission Line -- Part 11: Jointing Techniques --",
Based on the results of this development program, a model EEEE 1994 PES Winter Meeting, 94WM040-6PWR-D
line with eight EMJs was installed using the same techniques [3] T. Kubota et al.: "Development of 500-kV XLPE
as commercial lines, and subjected to long-term loading CabIes and Accessories for Long-Distance Underground
cycle tests at 450 kV for approximately 10 months. Details Transmission Line -- Part I: Insulation Design of Cables -
will be presented in a subsequent report, but as of December -",IEEE 1994 PES Winter Meeting, 94WM097-6PWRD
1994, long-term tests have been satisfactorily completed, [4] Kohashi et al.: "Research on Extrusion Molded Joint
verifying the long-term reliability of commercial-scale Defect Factors by Previous Cutoff Tests", 1993 Electrical
systems. Association Power and Energy Division Conference, 467
With a view to the construction of commercial lines, we [SI H. Ishihara et al.: "Improvement in Reliability of
are working on a comprehensive quality control method Extrusion Type Molded Joint for 275-kV XLPE Cable",
covering everything from materials acceptance to final h e EEE Transactions on Paper Delivery, Vol. 7, No. 4,1992
commissioning. [6] Takahashi et al.: "Study of Performance Improvements
for Extrusion Molded Joints", 1992 Electrical Association
National Convention, 1477
[7] M. Fukawa et al.: "Development of 500-kV XLPE Cables
and Accessories for Long-Distance Underground
References Transmission Line -- Part IU: Electrical Properties of
[l] K. Kaminaga et al.: "Research and Development of 500-kV XLPE Cables --",E E E 1995 PES Summer
500-kV XLPE Cables", IEEE Symposium on Electrical Meeting proceedings, submitted.
Insulation, 1986
[2]T. Kubota et al.: "Development of 500-kV XLPE Cables
and Accessories for Long-Distance Underground
643
Biography
Naoki Takeda was born in Kanagawa, Japan, on Atsushi Nakatani was born in Ishikawa, Japan on
November 27, 1963. He received a B.S. degree in November 11,1950. He graduated from Kanazawa
electrical engineering from Nihon University, Technical Collage, Ishikawa, Japan in 1971.
Japan in 1986. He joined Sumitomo E l d c Industries, Ltd. in
He joined the Tokyo Eledric Power Co., Inc., in 1971, He has been engaged in research and
1986. He has been engaged in design of development of accessories of EHV cables.
underground transmission lines and research and
development of EHV cables and their accessories.
He is a menber of the Institute of Electrical
Engineers of Japan 0.