TEST SEPARATOR INTERFACE LEVEL

Inhibition_Ind95
IND_INH_NUM IND_INH_NUM INH Fx_ILALL110106_IS
INHIBITION VALUE FOR 241 IND_VAL LO-LO MAINT. INHIBIT STATUS
INH_SET INH_SET
SET INHIBITION INH_RESET
INH_RESET
RESET INHIBITION

AI_LL07
Fx_ILIT110106_A AI1_IN AI_VALUE Fx_ILI110106
LEVEL INDICATING AI1_Ch_Err
Fx_ILIT110106_A_Ch_Err AI2_IN AI_LL_ALARM Fx_ILALL110106
AI 1 CHANNEL ERROR AI2_Ch_Err LO-LO ALARM
Fx_ILIT110106_B 100 AI_MAX AI_LOOP_FAULT Fx_ILAF110106
LEVEL INDICATING 0 AI_MIN LOOP FAULT STATUS
Fx_ILIT110106_B_Ch_Err 50 AI_TLL AI_LL_TRIP Fx_ILALL110106_TRIP
AI 2 CHANNEL ERROR Alarm:
T#1S AI_FLT 1=alarm
0=normal
2 AI_HYST
Fx_ILALL110106_IS AI_INH Trip:
LO-LO MAINT. INHIBIT STATUS 745 AI_Err 0= Trip
1=normal
100 MULTIPLIER

START-UP_INH39
Fx_ILALL110106_TRIP ALARM TO_ESD_BAR Fx_ILALL110106_SIS_ESD
START-UP INHIBIT STATUS TO
Fx_ILALL110106_SIC ST_INH_CMD ST_INH_STS Fx_ILALL110106_SIS
START-UP INHIBIT COMMAND START-UP INHIBIT STATUS
T#2H DELAY_TMR

3 date name logic version rev *1605


2 made Date Name Total E&P Indonesie ELOP II Program coordinates M/-1
1 check Project5 page 378
revision date name status: LZ based replaced replaced of 1214 sh.