TECHNICAL SPECIFICATIONS ELECTRONIC TIMER

CAT.No. 12ODT8 12ODT4 11ODT8 11ODT4 15ODT4 12BDT4 11BDT4 15BDT4 17ODTA 12SDT0
SERIES MICON™ - 175

SUPPLY CHARACTERISTICS RoHS

240 VAC 240VAC,50/60Hz


50/60 Hz 24VDC Cat Nos.:

10 VA
12ODT4

11ODT4
1 NO + 1 NO 12BDT4

11BDT4
Ag Alloy / AgSnO2 AgNi
15ODT4

Expectancy 12ODT8
(5 A at 250 VAC),
11ODT8
(3 A at 30 VDC)

1200 opr. / hr.


15BDT4

nt panel Red LED: Relay ON


Star - Green LED 17ODTA
Delta - Red LED

FEATURE CHARACTERISTICS 12SDT0

Modes Available One shot On Delay Star - Delta

Timing Ranges 6 Ranges 3s - 30s, 3m - 30m, 3hr - 30hr 10 s 3 s to 120 s 1. It is not recommended to change Timing preset
during Power ON condition as it will reset elapsed
Pause Time N.A 60 ms (fixed) time.

Setting Accuracy +/- 5% of full scale 2. Changing Range Preset in power ON condition
will have no effect. It has to be set before Power
R ON the timer.

3. If user wants to reset timer one way to do this is


to switch off the timer & then set timing & range
preset to required position. In this case, Timer will
reset & will take new set time. If user modifies timing
in power ON condition, then elapsed time will be
100 - 200 ms discarded & new set time will start from zero.

4. After set time, i.e. after relay is on, variation in


timing preset will have no effect on relay condition.

5. The technical information provided in this


document is correct at the time of going to the press.
Product innovation being a continuous process, we
reserve the right to make any alteration without prior
65 gms. notice.

Operating Temperature -10 C to + 55 C

Pollution Degree 2

Degree of Protection IP - 20 for Terminals; IP - 40 for Enclosure

Enclosure Flame Retardant UL-94V0 1LL006_09


ELECTRONIC TIMER SERIES MICON™ - 175 STAR - DELTA :
is manufactured to a high precision Cat No. : 12SDT0 12ODT4,12BDT4, 12ODT8: Diag. 1 2 3
and accuracy. When the supply is applied, Output 17ODTA : Diag. 1 & 3
Star Relay turns ON. After completion of
set Star ON time, Star Relay turns OFF
and Delta Relay turns ON after 60 ms
(Pause Time) and remains ON till the
Supply is present.

Connection Diagram :

A
1 2 3
B
Timing Diagram :

11ODT4 , 11BDT4 & 11ODT8


A = 58.5 (without Dust Cover)
B = 65 (with Dust Cover)

AWG CURRENT (A)


Recommended Star - Delta Control 10 5.00
Circuit :
12 4.38
(Below circuit is for STAR - DELTA Timer) 3.75
14
CONTROL ON 16 3.13
17C
18 2.50
20 1.88
M2

22 1.25
A1 - A2 - 240 VAC 24 0.63
A3 - A2 - 24 DC

or
A3
/ 15BDT4

1) F1 - Mains Protection Fuse


2) O.L.R - Over Load Relay
3) M1 - First ‘NO’ Contact of Main Contactor
4) M2 - Second ‘NO’ Contact of Main Contactor
5) M - Main Contact of driving Motor
Terminal Details: 6)
7)
C
C1
- ‘NO’ Contactor
- ‘NO’ Contact of Star Contactor
8) C2 - ‘NO’ Contact of Star Contactor
9) C - Delta Contactor
10) C1 - ‘NC’ Contact of Delta Contactor
11) T - Star Contact of Timer ( - )
12) T - Delta Contact of Timer ( - )

The timers shall be placed in an enclosure that is


minimum 200% of the size of the timer in the end
use application. Use Cu wire of 75°C only. 1LL006_09
TECHNICAL SPECIFICATIONS
Cat. No.: 11RDT4 12RDT4 15DDT4
Terminal Details : Signal Off Delay Timer ELECTRONIC TIMER
Cat. No.: 11RDT4, 12RDT4 , 15DDT4 SERIES : MICON-175 TM
Function SIGNAL OFF Delay Timer
Supply Characteristics : 0.5 N.m (4.4lb.in) to
Mode Description :
Ø4......5.0mm 0.7N.m (6.2lb.in)
Supply Voltage( ) 110VAC /24VAC/DC 240VAC /24VAC/DC 12VDC Combi Head Bit./Flat When the supply voltage is applied & the Cat. No. : 11RDT4
Supply Variation -15 % to +10 % of +/- 20 %
2 x 2.5 mm
2 B1 input is energized the output relay 12RDT4
Supply Frequency 47 Hz to 63 Hz –
Solid / Standard Wire energizes. When B1 is de-energized time ‘Ts’ 15DDT4
Power Consumption 0.75W@24VDC/3.50 VA@110VAC 0.75W@24VDC/7VA@240VAC 0.8W@12VDC
commences. At the end of ‘Ts’ the output relay
Signal Characteristics : AWG 24 to 10 De-energizes. If B1 is energized again before the RoHS
Signal Sensing time Guaranteed signal present 50 msec
end of Ts, Ts resets to zero so that when B1 is
Signal Impedance (Approx.) 175K@110VAC; 95K@24VAC/DC 120K@240VAC;95K@24VAC/DC 51K@12VDC AWG CURRENT (A) de-energized the full set time of ‘Ts’ operates. Features :
Signal stabilization Delay at Power ON 150 msec (Initiate time + Signal sensing time)
Feature Characteristics : 10 5.00 Timing Diagram : 1. Wide Input Supply and Signal Range.
Setting Accuracy +/-5 % of full scale 12 4.38 2. Wide Timing Range-300ms to 30hr.
Repeat Accuracy +/-1% Mode Function Diagram 3. Suitable for Din-Rail & Base Mounting.
Initiate Time
14 3.75 4. Compact Size & Easy to install.
100 msec. (Max.)
Reset Time 100 msec. (Max.) 16 3.13 5. High Precision & Accuracy.
U 6. Sensor compatibility: PNP, NPN & 2-Wire
Timing Ranges (T) 3s, 30s, 3m, 30m, 3hr and 30hr Signal Off
18 2.50 B1
Timing Adjustment Ranges (t) 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1 Delay 24VAC/240VAC proximity Sensors .
Timing adjustment knobs Flush 20 1.88 R
Ts Ts Caution :
Storage Temperature -20° C to+ 80° C -20° C to+ 70° C 22 1.25 Ts = T x t 1.Always follow instructions stated in this
Operating Temperature -15° C to+ 60° C
24 0.63 product leaflet.
Relative Humidity 95% (Rh) Wiring Diagrams :
Housing Flame Retardant UL 94-V0 NOTE: Use Cu Wire of 75°C Only. 2.Before installation, check that the
11RDT4/12RDT4/15DDT4:
Dimensions in mm ( W X H X L ) 17.5
(+0.5/-0.0)
X 65 X 90 specifications agree with the intended
Installation :
Weight (Packed) 85 g (Approx). 79 g (Approx). x A1 application.
DIN - Rail Mounting : The Timer should L/+ +ve
3.Installation to be done by skilled
Mounting DIN Rail (35 mm Sym.) B1 A3 A3
be mounted on 35 mm symmetrical
Status Indication on front panel Relay ON : Red LED ON, Power ON : Green LED ON L electrician.
DIN - Rail. B3 B3
Green LED Fast Blinking (50ms ON/OFF) =<1 minute off delay time remaining
110VAC/
12 VDC 4.If user wants to reset timer, one way to
Screw Mounting: For screw mounting, pull 240VAC
Green LED Slow Blinking (1sec ON/OFF) >1 minute off delay time remaining N do this is to switch off the timer & then
out the DIN Rail clips half way. Use 2 no’s of
Relay O/P Characteristics : set timing & range preset to required
M4 screws to mount the product directly on
Contact Rating 5A (Res.) @ 240 VAC / 28 VDC position. In this case, Timer will reset &
back. -ve
Contact Material AgSno2
N/- will take new set time.
Mechanical Life 7 Overall Dimension : 5.Setting of all the potentiometers should
1 X 10 operations x A1
5 N/- -ve be in clockwise direction only.
Electrical Life 1 X 10 operations Base Mounting : A3 A3
+0.5
B1 6.Use 250 mA slow blow fuse in series
Contact Arrangement 1 C/O N
-0.0 110VAC/
B3 B3 with the above mentioned products.
Certification : CE, RoHS 240VAC 12 VDC 7.The timers shall be placed in an enclosure
Product Reference Standard L
IEC 61812-1 Ed. 2.0 (2011-5) that is minimum 200% of the size of the
EMI/EMC : timer in the end use application. Use Cu
Harmonic Current Emissions IEC 61000-3-2 Class A IEC61000-3-2 Class A wire of 75°C for connections.
L/+ +ve
ESD IEC 61000-4-2 Level II IEC61000-4-2 Level 2 8.Product innovation being a continuous
Radiated Susceptibility IEC 61000-4-3 Level III IEC61000-4-3 Level 3 Do not apply more than 27VAC/DC to A3 terminal of process, we reserve the right to make
11RDT4 & 12RDT4.
Electrical Fast Transient IEC 61000-4-4 Level IV IEC61000-4-4 Level 3 any alteration without prior notice.
Do not apply more than 14.4VDC to A3 terminal of 15DDT4.
Surge Test between supply Terminals *IEC 61000-4-5 Level IV 110/240VAC and Level III 24VAC/DC IEC61000-4-5 Level I

Conducted Susceptibility IEC 61000-4-6 Level III IEC61000-4-6 Level 3 Sensor Connection Diagrams :
Voltage Dips & Interruptions (AC) IEC 61000-4-11 All Levels NA
NPN Proximity Sensor PNP Proximity Sensor AC 2-Wire Proximity Sensor
Voltage Dips & Interruptions (DC) IEC 61000-4-29 All Levels IEC 61000-4-29 All Levels (With Separate Power Supply)
Conducted Emission CISPR 14-1 Class A CISPR-11 Class A PROXY SENSOR
(24VDC sensor TIMER
24VDC
Radiated Emission CISPR 14-1 Class A CISPR-11 Class A (sensor
power supply)
power supply)
TIMER
L/+ +
Fig.1-a TIMER PROXY SENSOR A1
Safety : All dimensions are in mm
A3
A3
Relay Coil R
Test Voltage Between I/P & O/P 2 kV Din Rail Mounting : 12/24
+ B1

Test Voltage Between all terminal & 2.5 kV VDC


--
12/24
-
B3 VDC -
-- B3 N/-

Enclosure + A2
A2 -
Impulse Voltage Between I/P & O/P IEC 6092004 47-5-1 2 kV A2
Operates with Relay ON
Single Fault IEC 61010-1 Relay coil voltage should be as per supply
Operates with Transistor ON Operates with Transistor ON
for sensor
Insulation Resistance UL 508 > 50K
Leakage Current UL 508 (1999-01) < 3.5 mA AC 240V 2-Wire Proximity Sensor AC 24V 2-Wire Proximity Sensor NO or NC contact of Switch/Relay/
L N L N Contactors
Degree of Protection IP - 20 for Terminal; IP - 40 for Housing PROXY SENSOR TIMER PROXY SENSOR TIMER
TIMER
Pollution Degree II
A1 A3
Type of Insulation Reinforced L A1

Environmental : B1 B3 I/P R

Cold Heat IEC 60068-2-1 RB RB Supply B1

Dry Heat IEC 60068-2-2 A2 A2


N A2
Vibration IEC 60068-2-6 10-55 Hz A
Operates with Proxy switch ON Operates with Proxy switch ON
Repetitive Shock IEC 60068-2-27 40 g, 6 ms A = 58.5 Suggested value of Bleeder (RB) is 22K,5W Suggested value of Bleeder(RB) is 2.2K,1W Operates with Relay ON
Fig.1-b
Non-repetitive Shock IEC 60068-2-27 30 g, 15 ms 2-Wire Proximity Sensor: Bleeder resistors are calculated considering maximum leakage
current of 2.5mA.
*Note: If supply is looped with relay pole, then surge level III will be applicable (For 11RDT4 & 12RDT4).
1LL013_03
TECHNICAL SPECIFICATIONS
Cat. No.: 11WDTC 12WDTC
Terminal Details : ON-Delay and Interval Timer ELECTRONIC TIMER
TM
Function ON-Delay and Interval Cat. No.: 11WDTC, 12WDTC SERIES : MICON 175
Supply Characteristics : Function Diagram :
Supply Voltage( ) 110VAC /24VAC/DC 240VAC /24VAC/DC Cat. No. : 11WDTC
1. ON Delay :
Supply Variation -20 % to +10 % of
Solid/ 12WDTC
Supply Frequency 47 Hz to 63 Hz
When the supply voltage is applied, timing starts.
Power Consumption 0.5W@24VDC/1 VA@24VAC/5VA@110VAC, 50 Hz 0.5W@24VDC/1VA@24VAC/6VA@240VC, 50 Hz
After the set timing ‘Ts’ has elapsed, output relay
Timing and Accuracy : RoHS
turns ON and remains ON till the supply is removed.
Setting Accuracy +/-5 % of full scale
Repeat Accuracy +/-1% AWG CURRENT (A)
Initiate Time 100 msec. (Max.)
Reset Time 12 5.00 Features :
100 msec. (Max.)
Timing Ranges (T) 1s, 10s, 1m, 10m, 1hr, 10 hr and 100hr 14 3.33 1. Wide Timing Range-100ms to 100hr.
Timing Adjustment Ranges (t) 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9 and 1 2. Suitable for DIN-Rail & Base Mounting.
16 1.67
Range of Timing Operation 100 msec to 100 hr 3. Compact Size & Easy to install.
Timing adjustment knobs Flush NOTE: Use Cu Wire of 75°C Only. 15 -18 4. High Precision & Accuracy.
Mode selection knobs On Delay or Interval
Switching Frequency (max) 1000 operations/ hr Installation :
Ts Caution :
Status Indication on front panel Relay ON : Red LED ON, Power ON : Green LED ON DIN - Rail Mounting : The Timer should Ts = T x t
Storage Temperature -20° C to+ 70° C be mounted on 35 mm symmetrical DIN - Rail. 1.Always follow instructions stated in this
Operating Temperature -15° C to+ 60° C product leaflet.
Relative Humidity 95% (Rh) Wiring Diagrams : 2.Before installation, check that the
2. Interval :
Housing Flame Retardant UL 94-V0 11WDTC/12WDTC: specifications agree with the intended
Dimensions in mm ( W X H X L ) 18 x 65 x 85 (in mm) When the supply voltage is applied, output relay application.
Weight (Packed) 85 g (Approx). turns ON and timing starts. Output relay turns 3.Installation to be done by skilled
A1
Mounting DIN Rail (35 mm Sym.) L/+ off after the set timing ‘Ts’ has elapsed and electrician.
Green LED Fast Blinking (50ms ON/OFF) =<1 minute set time remaining A3
remains off until next power on. 4.If user wants to reset timer, one way to
L
Green LED Slow Blinking (1sec ON/OFF) >1 minute set time remaining do this is to switch off the timer & then
110VAC/
Relay O/P Characteristics : 240VAC set timing & range preset to required
Contact Rating 5A (Res.) @ 240 VAC / 28 VDC N
position. In this case, Timer will reset &
Contact Material AgSnO2 will take new set time.
Mechanical Life 7
1 X 10 operations 5.Setting of all the potentiometers should
N/-
Electrical Life 5
1 X 10 operations (NO, 8A at 250 VAC) 15 -18 be in clockwise direction only.
4 Do not apply more than 27VAC/DC to A3 terminal of
5 X 10 operations ( NO, 10A at 250 VAC) 11WDTC & 12WDTC.
6.Use 250 mA slow blow fuse in series
Contact Arrangement Ts with the above mentioned products.
1 C/O
Ts = T x t 7.The timers shall be placed in an enclosure
Certification : CE, RoHS
that is minimum 200% of the size of the
Product Reference Standard IEC 61812-1 timer in the end use application. Use Cu
EMI/EMC : wire of 75°C for connections.
Harmonic Current Emissions IEC 61000-3-2 Class A Overall dimension : 8.Product innovation being a continuous
ESD IEC 61000-4-2 Level II process, we reserve the right to make
Radiated Susceptibility IEC 61000-4-3 Level III DIN Rail Mounting : Base Mounting : any alteration without prior notice.
Electrical Fast Transient IEC 61000-4-4 Level IV 18.0
Surge Test between supply Terminals IEC 61000-4-5 Level IV 110/240VAC and Level III 24VAC/DC
Conducted Susceptibility IEC 61000-4-6 Level III A1

Voltage Dips & Interruptions (AC) IEC 61000-4-11 All Levels (Note: For 24 VAC, Performance Criteria B)
Voltage Dips & Interruptions (DC) IEC 61000-4-29 All Levels (Note: For 24 VDC, Performance Criteria B) A3 15
Conducted Emission CISPR 11 Class A
Radiated Emission CISPR 11 Class A

Safety : ON
INT
DLY
Test Voltage Between I/P & O/P IEC60947-5-1/UL508 2 kV
Mode
Test Voltage Between all terminal & IEC60947-5-1/UL508 2.5 kV
Enclosure
Impulse Voltage Between I/P & O/P IEC 60947-5-1 2 kV 1m
10m
1h
Single Fault IEC 61010-1 10s 10h

1s
Insulation Resistance UL 508 > 50K .5 T 100h
.7
Leakage Current UL 508 < 3.5 mA .3
.9
.1 1
Degree of Protection IP - 20 for Terminal; IP - 40 for Housing xt
Pollution Degree II GIC
Type of Insulation Reinforced
Environmental :
16
Cold Heat IEC 60068-2-1
Dry Heat IEC 60068-2-2
Vibration IEC 60068-2-6 10-55 Hz 18 A2
Repetitive Shock IEC 60068-2-27 40 g, 6 ms
Non-repetitive Shock IEC 60068-2-27 30 g, 15 ms

1LL018_00
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CMDT0 1CMDTB
SUPPLY CHARACTERISTIC: MULTI-FUNCTION
Supply Voltage 12 - 240 VAC / DC
Supply Variation -15 % to +10 % of
Cat. No.: 1CMDT0
Frequency 50 to 60 Hz, (± 3 Hz)
1CMDTB
Power Consumption (Max.) 2 VA
SIGNAL CHARACTERISTICS:
Signal sensing time > = 40 ms (For Un > = 110 VAC / DC) and > = 60 ms (for Un < 110 VAC / DC)
Signal impedance >6K@10VAC/DC; >70K@110VAC/DC; >150K@240VAC/DC
Signal switch current requirement Switching capacity of the switch or contact should be>10mA
RoHS
RELAY O/P CHARACTERISTICS:
Contact Arrangement 1 C/O Potential free contacts
Contact Rating (Resistive Load) 8A (Res.) @ 240 V AC, 5A at 24 VDC CAUTION:
AgNi 1. Always follow instructions stated in this product leaflet.
Contact Material
2. Before installation, check to ensure that the
Electrical Life 50000 Operations min. specifications agree with the intended application.
Mechanical Life 10000000 Operations min. 3. Installation to be done by skilled electrician.
FEATURE CHARACTERISTICS: 4. Automation & Control devices must be properly
installed so that they are protected against any risk of
Set Time (Ts) 0.1 seconds to 100 hrs
involuntary actuations.
Setting Accuracy +/- 5% of full scale 5. Suitable dampers should be provided in case of
Repeat Accuracy +/- 1% excessive vibrations.
Mode Adjustment Refer “Timing diagrams of Functions” 6. Use of 250 mA fuse in series with product supply is
recommended.
Supply Indication on front panel Green LED for power Yellow LED for Relay.
7. The timers shall be placed in an enclosure that is
Mounting Din-Rail minimum 200% of the size of the timer in the
Dimensions ( W X H X D ) 18 x 60 x 85 ( in mm) end use application.
Weight (Unpacked) 72 gms. 8. Setting of all potentiometers must be in clockwise
direction only.
Humidity 95% Rh Non Condensing
Operating Temperature -10° C to + 60° C NOTE:
Storage Temperature -15° C to + 70° C Product innovation being a continuous process, we
Housing Color Dark Gray Light Gray reserve the right to alter specifications without any
Max. Operating Altitude 2000 m prior notice.
Housing Flame retardant (UL 94-V0)
Degree & Protection IP - 20 for Terminal, IP - 40 for Housing. TERMINAL DETAILS:
Pollution Degree II
Isolation ( I/P and O/P) 2 kV
0.6 N.m (6 Lb.in)
Isolation (Terminal and Casing ) 4 kV Terminal screw - M3
3.5...4.0 mm
Type of Insulation Reinforced
Certifications CE, RoHS 1 x 4.0 mm
Initiate Time Max. 100 ms Solid / Stranded Wire
Reset Time Max. 200 ms
EMI / EMC: AWG 1 x 20 to 10
Harmonic Current Emissions IEC 61000-3-2 Class A Use Cu wire of 75°C only.
ESD IEC 61000-4-2 Level II
AWG CURRENT (A)
Radiated Susceptibility IEC 61000-4-3 Level III
12 5.00
Electrical Fast Transient IEC 61000-4-4 Level IV 14 3.33
Surge IEC 61000-4-5 Level III 16 1.67

Conducted Susceptibility IEC 61000-4-6 Level III


Voltage Dips & Interruptions (AC) IEC 61000-4-11 For < 24 VAC/DC, Performance Criteria B
Conducted Emission CISPR 14-1 Class B
Radiated Emission CISPR 14-1 Class A 1LL007_06
ELECTRONIC TIMER - SERIES MICON™ 175 2) INTERVAL INSTALLATION:
MULTI-FUNCTION Select mode (iL) ON Impulse. If Switch (S) is closed
a. DIN-Rail Mounting:
Series 175 1M MULTIMODE Timer is manufactured between A1-B1 before making power supply ON and
The Timer should be mounted on 35 mm symmetrical
during execution of timing, it will work as Interval.
to a high degree of precision & accuracy. The time DIN Rail.
inf) Impulse On/Off
settings are stepless and can be set with the SENSOR CONNECTION DIAGRAM:
R energizes for the period Ts when Switch (S) is opened or
knob. closed. When timing commences, changing state of NPN Proximity Sensor With & PNP Proximity Sensor
Without Open collector output
FUNCTION DIAGRAM : Switch (S) does not affect R but resets timer. (With separate power supply)
(With common power supply)
Overall product dimensions and mounting details :
-+
stn) Signal On Delay: 24VDC TIMER
(24VDC sensor
power supply)
(sensor TIMER
Timing starts when Switch (S) is closed. R energizes at power supply) SENSOR
A1
end of period Ts and de-energizes when Switch (S) is SENSOR
A1
24
opened. + VDC+
24
-
VDC -
B1
- B1
- --
A2
iL) ON Impulse, Constant Supply A2

When switch (S) is closed and remains closed output relay --


Operates with Transistor ON Operates with Transistor ON
energizes until timing is over. If Switch (S) is Opened
cnf) Cyclic On/Off: On start during period Ts, R resets. AC 2-Wire Proximity Sensor Switch/Relay NO Contact
Initially the relay (R) is On for period Ts after the power is (With Separate Power Supply)

applied. The relay (R) keeps on changing its status till L/+ TIMER TIMER
+
power is removed with On and period = Ts. A1
L/+
A1

I/P R
Relay Coil R
B1 Supply B1
OVERALL DIMENSIONS N/-
it) OFF Impulse, Constant Supply 65.0X85.0X18.0 A2 A2
- N/-
When Switch (S) is opened, R energizes and de-energizes WIRING DIAGRAM:
cfn) Cyclic Off/ On : Off start when timing is over. If Switch (S) is closed during period Ts Operates with Relay ON
Relay coil voltage should be as per supply for sensor
Operates with Relay ON

Initially the relay (R) is Off for period Ts after the power is R resets.
applied. The relay (R) keeps on changing its status till
power is removed with On and Off period = Ts.

sbi) Leading Edge Bi-stable or Step relay


sf) OFF Delay, Constant Supply (Signal Off Delay)
After every Signal, the output contact changes state, Safety:
R energizes when Switch (S) is closed. Timing commences
alternately switching from open to closed & vice versa.
after Switch (S) is opened and then the relay de-
Test Voltage between I/P and O/P IEC 60947-5-1/UL 508 2 kv
energizes.
Test Voltage between all terminals and enclosure IEC 60947-5-1/UL 508 2.5 kv

Impulse Voltage between I/P and o/p IEC 60947-5-1 Level IV

Single Fault IEC 61010-1


Derived Modes :
sfn) Signal Off/On Insulation Resistance UL 508 > 50 k
1) ON Delay
When Switch (S) is closed or opened for preset time Ts, Leakage Current UL 508 < 3.5 mA
the relay changes its state after time duration Ts. 1. Select mode signal On Delay (stn) and close Switch (S)
or short A1-B1 before power ON, it will work as ON Delay. Product IEC 61812-1
2. Select mode Accumulative On Delay (san) keeping
signal open before power ON and during execution of Environmental:
time as well, it will work as ON Delay.
Cold Heat IEC 60068-2-1

san) Accumulative Delay On Signal Dry Heat IEC 60068-2-2


Repetitive Shock IEC 60068-2-27, 40 g, 6 ms
Time commences as supply is present and Switch (S) is
open. Closing Switch (S) pauses timing. Timing resumes Non-Repetitive Shock IEC 60068-2-27, 30 g, 15 ms
when Switch (S) opened again R energizes at the end of
timing.

1LL007_06
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CQDT9
SUPPLY CHARACTERISTIC: MULTI-FUNCTION
Supply Voltage 12 - 240 VAC / DC
Cat. No.: 1CQDT9
Supply Variation -15 % to +10 % of
Frequency 50 to 60 Hz, (±2 Hz)
Power Consumption (Max.) AC: 3 VA, DC: 1.7W
SIGNAL CHARACTERISTICS:
Signal sensing time 60 ms
Signal impedance >6K@10VAC/DC; >70K@110VAC/DC; >150K@240VAC/DC RoHS
Signal switch current requirement Switching capacity of the switch or contact should be>10mA
RELAY O/P CHARACTERISTICS: CAUTION:
1. Always follow instructions stated in this product leaflet.
Contact Arrangement 1 C/O Potential free contacts
2. Before installation, check to ensure that the
Contact Rating (Resistive Load) 16A at 250 VAC (resistive load (AC-1/4000VA))
specifications agree with the intended application.
Contact Material AgSnO2 3. Installation to be done by skilled electrician.
Electrical Life 3X10 7 4. Automation & Control devices must be properly
5
Mechanical Life 0.7X10 installed so that they are protected against any risk of
involuntary actuations.
FEATURE CHARACTERISTICS: 5. Suitable dampers should be provided in case of
Set Time (Ts) 0.1 sec to 100 hr excessive vibrations.
Setting Accuracy +/- 5% of full scale 6. Use of 250 mA fuse in series with product supply is
Repeat Accuracy +/- 0.2% recommended.
7. The timers shall be placed in an enclosure that is
Mode Adjustment 10 modes for details Refer “Timing diagrams of Functions” minimum 200% of the size of the timer in the
Supply Indication on front panel Green LED for power; Yellow LED for Relay. end use application.
Mounting Din-Rail 8. Setting of all potentiometers must be in clockwise
Dimensions ( W X H X D ) 18 x 65 x 90 ( in mm) direction only.
Weight (Unpacked) 72 gms. NOTE:
Humidity 95% Rh Non Condensing Product innovation being a continuous process, we
Operating Temperature -20° C to + 60° C reserve the right to alter specifications without any
prior notice.
Storage Temperature -30° C to + 70° C
Housing Color Dark Gray TERMINAL DETAILS:
Max. Operating Altitude 2000 m
Housing Flame retardant (UL 94-V0) 0.4 N.m (3.6 Lb.in)
Degree & Protection IP - 20 for Terminal, IP - 40 for Front Side, IP - 30 for Housing. 3.5...3.8 mm
Pollution Degree II 2
1 x 2.5 mm
Isolation ( I/P and O/P) 2 kV Solid / Stranded Wire
Isolation (Terminal and Casing ) 2.5 kV
AWG 1 x 24 to 12
Type of Insulation Reinforced
Certifications CE, RoHS Use Cu wire of 75°C only.
Initiate Time Max. 100 ms AWG Sq.mm. Max. Current (A)
Reset Time Max. 200 ms 12 2.5 16*
EMI / EMC: 14 2.0 15
Harmonic Current Emissions IEC 61000-3-2 Class A 16 1.5 10
ESD IEC 61000-4-2 Level II 18 1.0 7
Radiated Susceptibility IEC 61000-4-3 Level III 20 0.75 5
Electrical Fast Transient IEC 61000-4-4 Level IV 22 0.5 3
Surge IEC 61000-4-5 Level III 24 0.2 2
Conducted Susceptibility IEC 61000-4-6 Level III *This maximum rating has been decided
Voltage Dips & Interruptions (AC) IEC 61000-4-11 For < 24 VAC/DC, Performance Criteria B on basis of maximum current capacity of
the product.
Conducted Emission CISPR 14-1 Class A Note: Maximum current values are
Radiated Emission CISPR 14-1 Class A mentioned for resistive load. 1LL014_00
ELECTRONIC TIMER - SERIES MICON™ 175 san) Accumulative Delay On Signal 2) INTERVAL INSTALLATION:
MULTI-FUNCTION Select mode (iL) ON Impulse. If Switch (S) is closed
Time commences as supply is present and Switch (S) is between A1-B1 before making power supply ON and a. DIN-Rail Mounting:
open. Closing Switch (S) pauses timing. Timing resumes during execution of timing, it will work as Interval. The Timer should be mounted on 35 mm symmetrical
Series 175 1M MULTIFUNCTION Timer is manufactured
when Switch (S) opened again R energizes at the end of DIN Rail.
to a high degree of precision & accuracy. The time timing.
SENSOR CONNECTION DIAGRAM:
settings are stepless and can be set with the
NPN Proximity Sensor With &
knob. Without Open collector output
PNP Proximity Sensor
(With common power supply)
(With separate power supply)
Overall product dimensions and mounting details :
FUNCTION DIAGRAM : -+
24VDC (24VDC sensor
TIMER power supply)
(sensor TIMER

inf) Impulse On/Off power supply)


A1
SENSOR
A1
stn) Signal On Delay: SENSOR
24
R energizes for the period Ts when Switch (S) is opened or + VDC+
Timing starts when Switch (S) is closed. R energizes at closed. When timing commences, changing state of
24
-
VDC -
B1
- B1
- --
end of period Ts and de-energizes when Switch (S) is Switch (S) does not affect R but resets timer. sfn san
A2
inf
A2
opened. cfn sf
cnf
stn
iL

sbi
it

Mode

--

68.0

90.0
10m

10s
1m 1h
10h Operates with Transistor ON Operates with Transistor ON
1s
.5
T 100h
.7
.3
.9
.1 1 AC 2-Wire Proximity Sensor Switch/Relay NO Contact
xt
(With Separate Power Supply)
L/+ TIMER TIMER
iL) ON Impulse, Constant Supply + L/+
A1 A1
cnf) Cyclic On/Off: On start When switch (S) is closed and remains closed output relay
I/P R
Relay Coil R
energizes until timing is over. If Switch (S) is Opened B1 Supply B1
Initially the relay (R) is On for period Ts after the power is OVERALL DIMENSIONS
during period Ts, R resets.
applied. The relay (R) keeps on changing its status till 65.0X90.0X18.0
N/-
A2 A2
power is removed with On and period = Ts. - N/-

WIRING DIAGRAM: Operates with Relay ON Operates with Relay ON


Relay coil voltage should be as per supply for sensor

16A/240VAC

it) OFF Impulse, Constant Supply

cfn) Cyclic Off/ On : Off start When Switch (S) is opened, R energizes and de-energizes B1
when timing is over. If Switch (S) is closed during period Ts
Initially the relay (R) is Off for period Ts after the power is R resets.
applied. The relay (R) keeps on changing its status till
power is removed with On and Off period = Ts.

Safety:

Test Voltage between I/P and O/P IEC 60947-5-1/UL 508 2 kv


sbi) Leading Edge Bi-stable or Step relay
Test Voltage between all terminals and enclosure IEC 60947-5-1/UL 508 2.5 kv
After every Signal, the output contact changes state,
sf) OFF Delay, Constant Supply (Signal Off Delay) alternately switching from open to closed & vice versa. Impulse Voltage between I/P and o/p IEC 60947-5-1 Level IV

R energizes when Switch (S) is closed. Timing commences Single Fault IEC 61010-1
after Switch (S) is opened and then the relay de-
Insulation Resistance UL 508 > 50 k
energizes.
Leakage Current UL 508 < 3.5 mA

Derived Modes : Product IEC 61812-1

1) ON Delay Environmental:
1. Select mode signal On Delay (stn) and close Switch (S)
Cold Heat IEC 60068-2-1
sfn) Signal Off/On or short A1-B1 before power ON, it will work as ON Delay.
2. Select mode Accumulative On Delay (san) keeping Dry Heat IEC 60068-2-2
When Switch (S) is closed or opened for preset time Ts, signal open before power ON and during execution of
the relay changes its state after time duration Ts. Repetitive Shock IEC 60068-2-27, 40 g, 6 ms
time as well, it will work as ON Delay.
Non-Repetitive Shock IEC 60068-2-27, 30 g, 15 ms

Vibration IEC 60068-2-6,10Hz to 55Hz

1LL014_00
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CJDT0 ASYMMETRIC ON OFF / OFF ON TIMER
SUPPLY CHARACTERISTICS:
Supply Voltage 12 - 240 VAC / DC Cat. No.: 1CJDT0
Supply Variation -15 % to +10 % of
Frequency 50 to 60 Hz, (± 3 Hz)
Power Consumption (Max.) 2 VA
RELAY O/P CHARACTERISTICS:
RoHS
Contact Arrangement 1 C/O Potential free contacts
Contact Rating (Resistive Load) 8A (Res.) @ 250 V AC, 5A at 24 VDC
Contact Material AgNi
Electrical Life 50000 Operations min.
Mechanical Life 10000000 Operations min.
FEATURE CHARACTERISTICS:
Timing Ranges 0.1 s; 1 s; 10 s; 1 min.; 10 min.; 1 h; 10h; 100h
Setting Accuracy +/- 5% of full scale Supply
Repeat Accuracy +/- 1% Indication LED
Mode Adjustment Flush (Refer “Functions diagram”)
Supply Indication on front panel Green LED for power Amber LED for Relay. Relay
Mounting Din-Rail Status LED
Dimensions ( W X H X D ) 18 x 60 x 85 ( in mm)
Detent pots for
Weight (Unpacked) 72 gms. Time Selection
Humidity 95% Rh Non Condensing
Operating Temperature -10° C to + 60° C
Storage Temperature -15° C to + 70° C Smooth pots
Housing Color Dark Gray for Range
Selection
Max. Operating Altitude 2000 m
Housing Flame retardant (UL 94-V0)
Degree & Protection IP - 20 for Terminal, IP - 40 for Housing.
Pollution Degree II
Isolation ( I/P and O/P) 2 kV
Isolation (Terminal and Casing ) 4 kV TERMINAL DETAILS:
Type of Insulation Reinforced
Certifications CE, RoHS
Torque 0.6 N.m (6 Lb.in)
Initiate Time Max. 100 ms
Terminal screw - M3
Reset Time 3.5...4.0 mm
Max. 200 ms
EMI / EMC: 2
1 x 4.0 mm
Harmonic Current Emissions IEC 61000-3-2 Class A Solid / Stranded Wire
ESD IEC 61000-4-2 Level II
AWG 1 x 20 to 10
Radiated Susceptibility IEC 61000-4-3 Level III
Electrical Fast Transient IEC 61000-4-4 Level IV Use Cu wire of 75°C only.
Surge IEC 61000-4-5 Level III AWG CURRENT (A)
Conducted Susceptibility IEC 61000-4-6 Level III 10 5.00
Voltage Dips & Interruptions (AC) IEC 61000-4-11 For < 24 VAC/DC, 12 5.00
14 3.33
Performance Criteria B
16 1.67
Conducted Emission CISPR 14-1 Class B
18 1.00
Radiated Emission CISPR 14-1 Class A 20 1.00

1LL009_02
ELECTRONIC TIMER - SERIES MICON™ 175 MODE SELECTION: CAUTION:
ASYMMETRIC ON OFF / OFF ON TIMER
MODE SELECTION 1. Always follow the instructions stated in this product
leaflet.
ASYMMETRIC OFF - ON Do not connect Link 2. Before installation, check to ensure that the
Series 175 Asymmetric On Off / Off On Timer is
between A1 & B1 specifications agree with the intended application.
manufactured to a high degree of precision & accuracy.
ASYMMETRIC ON - OFF Connect Link between 3. Installation to be done by skilled electrician.
The time settings are stepless and can be set with the A1 & B1 4. Automation & Control devices must be properly
knob. installed so that they are protected against any risk of
involuntary actuations.
Overall product dimensions and mounting details :
5. Suitable dampers should be provided in case of
Feature:
excessive vibrations.
Asymmetric On-Off / Off-On Timer: 6. Use of 250 mA fuse in series with product supply is
17.5mm wide recommended, for protection.
Time setting from:0.1 s; 1 s; 10 s; 1 min; 10 min; 7. The timers shall be placed in an enclosure that is
1 h; 10 h; 100 h. minimum 200% of the size of the timer in the
LED status indicators: Power On (Green) and Relay end use application.
status (Amber). 8. Setting of all potentiometers must be done in the
Cadmium free contact material. clockwise direction only.
9. At power on to detect the proper mode, 100 ms
FUNCTION DIAGRAM : (minimum) stable signal input should be present.
10.Keep at least 1 cm clearance from both side while
A) ASYMMETRIC OFF - ON : using this product.
If the link is not connected at A1-B1 and Supply is turned
ON. Timing starts and Output Relay remains OFF for set
NOTE:
Time. After set OFF Time has elapsed, Output Relay turns
ON and remains ON till the set ON time has elapsed and OVERALL DIMENSIONS Product innovation being a continuous process, we
the cycle repeats. 65.0X85.0X18.0 reserve the right to alter specifications without any
INSTALLATION: prior notice.
B) ASYMMETRIC ON - OFF :
If the link is connected at A1-B1 and supply is turned ON,
Output Relay turns On and Timing starts. Output Relay a. DIN-Rail Mounting:
turns OFF after the Set ON time has elapsed and remains The Timer should be mounted on 35 mm symmetrical
OFF till the Set OFF time has elapsed and the cycle DIN Rail.
repeats.

Safety:
Test Voltage between I/P and O/P IEC 60947-5-1 2 kv
Test Voltage between all terminals and enclosure IEC 60947-5-1 4 kv
Impulse Voltage between I/P and o/p IEC 60947-5-1 Level IV
Single Fault IEC 61010-1
NOTE: Insulation Resistance UL 508 > 50 k
1. T1 and T2 are detent pots for Time selection
Leakage Current UL 508 < 3.5 mA
2. t1 and t2 are smooth pots for Range Selection
Product IEC 61812-1
Environmental:
Connection Diagram:
Cold Heat IEC 60068-2-1
Dry Heat IEC 60068-2-2
Repetitive Shock IEC 60068-2-27, 40 g, 6 ms
Non-Repetitive Shock IEC 60068-2-27 ., 30 g, 15 ms

1LL009_02