CAT.No. 12ODT8 12ODT4 11ODT8 11ODT4 15ODT4 12BDT4 11BDT4 15BDT4 17ODTA 12SDT0
SERIES MICON™ - 175
10 VA
12ODT4
11ODT4
1 NO + 1 NO 12BDT4
11BDT4
Ag Alloy / AgSnO2 AgNi
15ODT4
Expectancy 12ODT8
(5 A at 250 VAC),
11ODT8
(3 A at 30 VDC)
Timing Ranges 6 Ranges 3s - 30s, 3m - 30m, 3hr - 30hr 10 s 3 s to 120 s 1. It is not recommended to change Timing preset
during Power ON condition as it will reset elapsed
Pause Time N.A 60 ms (fixed) time.
Setting Accuracy +/- 5% of full scale 2. Changing Range Preset in power ON condition
will have no effect. It has to be set before Power
R ON the timer.
Pollution Degree 2
Connection Diagram :
A
1 2 3
B
Timing Diagram :
22 1.25
A1 - A2 - 240 VAC 24 0.63
A3 - A2 - 24 DC
or
A3
/ 15BDT4
Conducted Susceptibility IEC 61000-4-6 Level III IEC61000-4-6 Level 3 Sensor Connection Diagrams :
Voltage Dips & Interruptions (AC) IEC 61000-4-11 All Levels NA
NPN Proximity Sensor PNP Proximity Sensor AC 2-Wire Proximity Sensor
Voltage Dips & Interruptions (DC) IEC 61000-4-29 All Levels IEC 61000-4-29 All Levels (With Separate Power Supply)
Conducted Emission CISPR 14-1 Class A CISPR-11 Class A PROXY SENSOR
(24VDC sensor TIMER
24VDC
Radiated Emission CISPR 14-1 Class A CISPR-11 Class A (sensor
power supply)
power supply)
TIMER
L/+ +
Fig.1-a TIMER PROXY SENSOR A1
Safety : All dimensions are in mm
A3
A3
Relay Coil R
Test Voltage Between I/P & O/P 2 kV Din Rail Mounting : 12/24
+ B1
Enclosure + A2
A2 -
Impulse Voltage Between I/P & O/P IEC 6092004 47-5-1 2 kV A2
Operates with Relay ON
Single Fault IEC 61010-1 Relay coil voltage should be as per supply
Operates with Transistor ON Operates with Transistor ON
for sensor
Insulation Resistance UL 508 > 50K
Leakage Current UL 508 (1999-01) < 3.5 mA AC 240V 2-Wire Proximity Sensor AC 24V 2-Wire Proximity Sensor NO or NC contact of Switch/Relay/
L N L N Contactors
Degree of Protection IP - 20 for Terminal; IP - 40 for Housing PROXY SENSOR TIMER PROXY SENSOR TIMER
TIMER
Pollution Degree II
A1 A3
Type of Insulation Reinforced L A1
Environmental : B1 B3 I/P R
Voltage Dips & Interruptions (AC) IEC 61000-4-11 All Levels (Note: For 24 VAC, Performance Criteria B)
Voltage Dips & Interruptions (DC) IEC 61000-4-29 All Levels (Note: For 24 VDC, Performance Criteria B) A3 15
Conducted Emission CISPR 11 Class A
Radiated Emission CISPR 11 Class A
Safety : ON
INT
DLY
Test Voltage Between I/P & O/P IEC60947-5-1/UL508 2 kV
Mode
Test Voltage Between all terminal & IEC60947-5-1/UL508 2.5 kV
Enclosure
Impulse Voltage Between I/P & O/P IEC 60947-5-1 2 kV 1m
10m
1h
Single Fault IEC 61010-1 10s 10h
1s
Insulation Resistance UL 508 > 50K .5 T 100h
.7
Leakage Current UL 508 < 3.5 mA .3
.9
.1 1
Degree of Protection IP - 20 for Terminal; IP - 40 for Housing xt
Pollution Degree II GIC
Type of Insulation Reinforced
Environmental :
16
Cold Heat IEC 60068-2-1
Dry Heat IEC 60068-2-2
Vibration IEC 60068-2-6 10-55 Hz 18 A2
Repetitive Shock IEC 60068-2-27 40 g, 6 ms
Non-repetitive Shock IEC 60068-2-27 30 g, 15 ms
1LL018_00
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CMDT0 1CMDTB
SUPPLY CHARACTERISTIC: MULTI-FUNCTION
Supply Voltage 12 - 240 VAC / DC
Supply Variation -15 % to +10 % of
Cat. No.: 1CMDT0
Frequency 50 to 60 Hz, (± 3 Hz)
1CMDTB
Power Consumption (Max.) 2 VA
SIGNAL CHARACTERISTICS:
Signal sensing time > = 40 ms (For Un > = 110 VAC / DC) and > = 60 ms (for Un < 110 VAC / DC)
Signal impedance >6K@10VAC/DC; >70K@110VAC/DC; >150K@240VAC/DC
Signal switch current requirement Switching capacity of the switch or contact should be>10mA
RoHS
RELAY O/P CHARACTERISTICS:
Contact Arrangement 1 C/O Potential free contacts
Contact Rating (Resistive Load) 8A (Res.) @ 240 V AC, 5A at 24 VDC CAUTION:
AgNi 1. Always follow instructions stated in this product leaflet.
Contact Material
2. Before installation, check to ensure that the
Electrical Life 50000 Operations min. specifications agree with the intended application.
Mechanical Life 10000000 Operations min. 3. Installation to be done by skilled electrician.
FEATURE CHARACTERISTICS: 4. Automation & Control devices must be properly
installed so that they are protected against any risk of
Set Time (Ts) 0.1 seconds to 100 hrs
involuntary actuations.
Setting Accuracy +/- 5% of full scale 5. Suitable dampers should be provided in case of
Repeat Accuracy +/- 1% excessive vibrations.
Mode Adjustment Refer “Timing diagrams of Functions” 6. Use of 250 mA fuse in series with product supply is
recommended.
Supply Indication on front panel Green LED for power Yellow LED for Relay.
7. The timers shall be placed in an enclosure that is
Mounting Din-Rail minimum 200% of the size of the timer in the
Dimensions ( W X H X D ) 18 x 60 x 85 ( in mm) end use application.
Weight (Unpacked) 72 gms. 8. Setting of all potentiometers must be in clockwise
direction only.
Humidity 95% Rh Non Condensing
Operating Temperature -10° C to + 60° C NOTE:
Storage Temperature -15° C to + 70° C Product innovation being a continuous process, we
Housing Color Dark Gray Light Gray reserve the right to alter specifications without any
Max. Operating Altitude 2000 m prior notice.
Housing Flame retardant (UL 94-V0)
Degree & Protection IP - 20 for Terminal, IP - 40 for Housing. TERMINAL DETAILS:
Pollution Degree II
Isolation ( I/P and O/P) 2 kV
0.6 N.m (6 Lb.in)
Isolation (Terminal and Casing ) 4 kV Terminal screw - M3
3.5...4.0 mm
Type of Insulation Reinforced
Certifications CE, RoHS 1 x 4.0 mm
Initiate Time Max. 100 ms Solid / Stranded Wire
Reset Time Max. 200 ms
EMI / EMC: AWG 1 x 20 to 10
Harmonic Current Emissions IEC 61000-3-2 Class A Use Cu wire of 75°C only.
ESD IEC 61000-4-2 Level II
AWG CURRENT (A)
Radiated Susceptibility IEC 61000-4-3 Level III
12 5.00
Electrical Fast Transient IEC 61000-4-4 Level IV 14 3.33
Surge IEC 61000-4-5 Level III 16 1.67
applied. The relay (R) keeps on changing its status till L/+ TIMER TIMER
+
power is removed with On and period = Ts. A1
L/+
A1
I/P R
Relay Coil R
B1 Supply B1
OVERALL DIMENSIONS N/-
it) OFF Impulse, Constant Supply 65.0X85.0X18.0 A2 A2
- N/-
When Switch (S) is opened, R energizes and de-energizes WIRING DIAGRAM:
cfn) Cyclic Off/ On : Off start when timing is over. If Switch (S) is closed during period Ts Operates with Relay ON
Relay coil voltage should be as per supply for sensor
Operates with Relay ON
Initially the relay (R) is Off for period Ts after the power is R resets.
applied. The relay (R) keeps on changing its status till
power is removed with On and Off period = Ts.
1LL007_06
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CQDT9
SUPPLY CHARACTERISTIC: MULTI-FUNCTION
Supply Voltage 12 - 240 VAC / DC
Cat. No.: 1CQDT9
Supply Variation -15 % to +10 % of
Frequency 50 to 60 Hz, (±2 Hz)
Power Consumption (Max.) AC: 3 VA, DC: 1.7W
SIGNAL CHARACTERISTICS:
Signal sensing time 60 ms
Signal impedance >6K@10VAC/DC; >70K@110VAC/DC; >150K@240VAC/DC RoHS
Signal switch current requirement Switching capacity of the switch or contact should be>10mA
RELAY O/P CHARACTERISTICS: CAUTION:
1. Always follow instructions stated in this product leaflet.
Contact Arrangement 1 C/O Potential free contacts
2. Before installation, check to ensure that the
Contact Rating (Resistive Load) 16A at 250 VAC (resistive load (AC-1/4000VA))
specifications agree with the intended application.
Contact Material AgSnO2 3. Installation to be done by skilled electrician.
Electrical Life 3X10 7 4. Automation & Control devices must be properly
5
Mechanical Life 0.7X10 installed so that they are protected against any risk of
involuntary actuations.
FEATURE CHARACTERISTICS: 5. Suitable dampers should be provided in case of
Set Time (Ts) 0.1 sec to 100 hr excessive vibrations.
Setting Accuracy +/- 5% of full scale 6. Use of 250 mA fuse in series with product supply is
Repeat Accuracy +/- 0.2% recommended.
7. The timers shall be placed in an enclosure that is
Mode Adjustment 10 modes for details Refer “Timing diagrams of Functions” minimum 200% of the size of the timer in the
Supply Indication on front panel Green LED for power; Yellow LED for Relay. end use application.
Mounting Din-Rail 8. Setting of all potentiometers must be in clockwise
Dimensions ( W X H X D ) 18 x 65 x 90 ( in mm) direction only.
Weight (Unpacked) 72 gms. NOTE:
Humidity 95% Rh Non Condensing Product innovation being a continuous process, we
Operating Temperature -20° C to + 60° C reserve the right to alter specifications without any
prior notice.
Storage Temperature -30° C to + 70° C
Housing Color Dark Gray TERMINAL DETAILS:
Max. Operating Altitude 2000 m
Housing Flame retardant (UL 94-V0) 0.4 N.m (3.6 Lb.in)
Degree & Protection IP - 20 for Terminal, IP - 40 for Front Side, IP - 30 for Housing. 3.5...3.8 mm
Pollution Degree II 2
1 x 2.5 mm
Isolation ( I/P and O/P) 2 kV Solid / Stranded Wire
Isolation (Terminal and Casing ) 2.5 kV
AWG 1 x 24 to 12
Type of Insulation Reinforced
Certifications CE, RoHS Use Cu wire of 75°C only.
Initiate Time Max. 100 ms AWG Sq.mm. Max. Current (A)
Reset Time Max. 200 ms 12 2.5 16*
EMI / EMC: 14 2.0 15
Harmonic Current Emissions IEC 61000-3-2 Class A 16 1.5 10
ESD IEC 61000-4-2 Level II 18 1.0 7
Radiated Susceptibility IEC 61000-4-3 Level III 20 0.75 5
Electrical Fast Transient IEC 61000-4-4 Level IV 22 0.5 3
Surge IEC 61000-4-5 Level III 24 0.2 2
Conducted Susceptibility IEC 61000-4-6 Level III *This maximum rating has been decided
Voltage Dips & Interruptions (AC) IEC 61000-4-11 For < 24 VAC/DC, Performance Criteria B on basis of maximum current capacity of
the product.
Conducted Emission CISPR 14-1 Class A Note: Maximum current values are
Radiated Emission CISPR 14-1 Class A mentioned for resistive load. 1LL014_00
ELECTRONIC TIMER - SERIES MICON™ 175 san) Accumulative Delay On Signal 2) INTERVAL INSTALLATION:
MULTI-FUNCTION Select mode (iL) ON Impulse. If Switch (S) is closed
Time commences as supply is present and Switch (S) is between A1-B1 before making power supply ON and a. DIN-Rail Mounting:
open. Closing Switch (S) pauses timing. Timing resumes during execution of timing, it will work as Interval. The Timer should be mounted on 35 mm symmetrical
Series 175 1M MULTIFUNCTION Timer is manufactured
when Switch (S) opened again R energizes at the end of DIN Rail.
to a high degree of precision & accuracy. The time timing.
SENSOR CONNECTION DIAGRAM:
settings are stepless and can be set with the
NPN Proximity Sensor With &
knob. Without Open collector output
PNP Proximity Sensor
(With common power supply)
(With separate power supply)
Overall product dimensions and mounting details :
FUNCTION DIAGRAM : -+
24VDC (24VDC sensor
TIMER power supply)
(sensor TIMER
sbi
it
Mode
--
68.0
90.0
10m
10s
1m 1h
10h Operates with Transistor ON Operates with Transistor ON
1s
.5
T 100h
.7
.3
.9
.1 1 AC 2-Wire Proximity Sensor Switch/Relay NO Contact
xt
(With Separate Power Supply)
L/+ TIMER TIMER
iL) ON Impulse, Constant Supply + L/+
A1 A1
cnf) Cyclic On/Off: On start When switch (S) is closed and remains closed output relay
I/P R
Relay Coil R
energizes until timing is over. If Switch (S) is Opened B1 Supply B1
Initially the relay (R) is On for period Ts after the power is OVERALL DIMENSIONS
during period Ts, R resets.
applied. The relay (R) keeps on changing its status till 65.0X90.0X18.0
N/-
A2 A2
power is removed with On and period = Ts. - N/-
16A/240VAC
cfn) Cyclic Off/ On : Off start When Switch (S) is opened, R energizes and de-energizes B1
when timing is over. If Switch (S) is closed during period Ts
Initially the relay (R) is Off for period Ts after the power is R resets.
applied. The relay (R) keeps on changing its status till
power is removed with On and Off period = Ts.
Safety:
R energizes when Switch (S) is closed. Timing commences Single Fault IEC 61010-1
after Switch (S) is opened and then the relay de-
Insulation Resistance UL 508 > 50 k
energizes.
Leakage Current UL 508 < 3.5 mA
1) ON Delay Environmental:
1. Select mode signal On Delay (stn) and close Switch (S)
Cold Heat IEC 60068-2-1
sfn) Signal Off/On or short A1-B1 before power ON, it will work as ON Delay.
2. Select mode Accumulative On Delay (san) keeping Dry Heat IEC 60068-2-2
When Switch (S) is closed or opened for preset time Ts, signal open before power ON and during execution of
the relay changes its state after time duration Ts. Repetitive Shock IEC 60068-2-27, 40 g, 6 ms
time as well, it will work as ON Delay.
Non-Repetitive Shock IEC 60068-2-27, 30 g, 15 ms
1LL014_00
TECHNICAL SPECIFICATIONS: ELECTRONIC TIMER - SERIES MICON™175
Cat. No.: 1CJDT0 ASYMMETRIC ON OFF / OFF ON TIMER
SUPPLY CHARACTERISTICS:
Supply Voltage 12 - 240 VAC / DC Cat. No.: 1CJDT0
Supply Variation -15 % to +10 % of
Frequency 50 to 60 Hz, (± 3 Hz)
Power Consumption (Max.) 2 VA
RELAY O/P CHARACTERISTICS:
RoHS
Contact Arrangement 1 C/O Potential free contacts
Contact Rating (Resistive Load) 8A (Res.) @ 250 V AC, 5A at 24 VDC
Contact Material AgNi
Electrical Life 50000 Operations min.
Mechanical Life 10000000 Operations min.
FEATURE CHARACTERISTICS:
Timing Ranges 0.1 s; 1 s; 10 s; 1 min.; 10 min.; 1 h; 10h; 100h
Setting Accuracy +/- 5% of full scale Supply
Repeat Accuracy +/- 1% Indication LED
Mode Adjustment Flush (Refer “Functions diagram”)
Supply Indication on front panel Green LED for power Amber LED for Relay. Relay
Mounting Din-Rail Status LED
Dimensions ( W X H X D ) 18 x 60 x 85 ( in mm)
Detent pots for
Weight (Unpacked) 72 gms. Time Selection
Humidity 95% Rh Non Condensing
Operating Temperature -10° C to + 60° C
Storage Temperature -15° C to + 70° C Smooth pots
Housing Color Dark Gray for Range
Selection
Max. Operating Altitude 2000 m
Housing Flame retardant (UL 94-V0)
Degree & Protection IP - 20 for Terminal, IP - 40 for Housing.
Pollution Degree II
Isolation ( I/P and O/P) 2 kV
Isolation (Terminal and Casing ) 4 kV TERMINAL DETAILS:
Type of Insulation Reinforced
Certifications CE, RoHS
Torque 0.6 N.m (6 Lb.in)
Initiate Time Max. 100 ms
Terminal screw - M3
Reset Time 3.5...4.0 mm
Max. 200 ms
EMI / EMC: 2
1 x 4.0 mm
Harmonic Current Emissions IEC 61000-3-2 Class A Solid / Stranded Wire
ESD IEC 61000-4-2 Level II
AWG 1 x 20 to 10
Radiated Susceptibility IEC 61000-4-3 Level III
Electrical Fast Transient IEC 61000-4-4 Level IV Use Cu wire of 75°C only.
Surge IEC 61000-4-5 Level III AWG CURRENT (A)
Conducted Susceptibility IEC 61000-4-6 Level III 10 5.00
Voltage Dips & Interruptions (AC) IEC 61000-4-11 For < 24 VAC/DC, 12 5.00
14 3.33
Performance Criteria B
16 1.67
Conducted Emission CISPR 14-1 Class B
18 1.00
Radiated Emission CISPR 14-1 Class A 20 1.00
1LL009_02
ELECTRONIC TIMER - SERIES MICON™ 175 MODE SELECTION: CAUTION:
ASYMMETRIC ON OFF / OFF ON TIMER
MODE SELECTION 1. Always follow the instructions stated in this product
leaflet.
ASYMMETRIC OFF - ON Do not connect Link 2. Before installation, check to ensure that the
Series 175 Asymmetric On Off / Off On Timer is
between A1 & B1 specifications agree with the intended application.
manufactured to a high degree of precision & accuracy.
ASYMMETRIC ON - OFF Connect Link between 3. Installation to be done by skilled electrician.
The time settings are stepless and can be set with the A1 & B1 4. Automation & Control devices must be properly
knob. installed so that they are protected against any risk of
involuntary actuations.
Overall product dimensions and mounting details :
5. Suitable dampers should be provided in case of
Feature:
excessive vibrations.
Asymmetric On-Off / Off-On Timer: 6. Use of 250 mA fuse in series with product supply is
17.5mm wide recommended, for protection.
Time setting from:0.1 s; 1 s; 10 s; 1 min; 10 min; 7. The timers shall be placed in an enclosure that is
1 h; 10 h; 100 h. minimum 200% of the size of the timer in the
LED status indicators: Power On (Green) and Relay end use application.
status (Amber). 8. Setting of all potentiometers must be done in the
Cadmium free contact material. clockwise direction only.
9. At power on to detect the proper mode, 100 ms
FUNCTION DIAGRAM : (minimum) stable signal input should be present.
10.Keep at least 1 cm clearance from both side while
A) ASYMMETRIC OFF - ON : using this product.
If the link is not connected at A1-B1 and Supply is turned
ON. Timing starts and Output Relay remains OFF for set
NOTE:
Time. After set OFF Time has elapsed, Output Relay turns
ON and remains ON till the set ON time has elapsed and OVERALL DIMENSIONS Product innovation being a continuous process, we
the cycle repeats. 65.0X85.0X18.0 reserve the right to alter specifications without any
INSTALLATION: prior notice.
B) ASYMMETRIC ON - OFF :
If the link is connected at A1-B1 and supply is turned ON,
Output Relay turns On and Timing starts. Output Relay a. DIN-Rail Mounting:
turns OFF after the Set ON time has elapsed and remains The Timer should be mounted on 35 mm symmetrical
OFF till the Set OFF time has elapsed and the cycle DIN Rail.
repeats.
Safety:
Test Voltage between I/P and O/P IEC 60947-5-1 2 kv
Test Voltage between all terminals and enclosure IEC 60947-5-1 4 kv
Impulse Voltage between I/P and o/p IEC 60947-5-1 Level IV
Single Fault IEC 61010-1
NOTE: Insulation Resistance UL 508 > 50 k
1. T1 and T2 are detent pots for Time selection
Leakage Current UL 508 < 3.5 mA
2. t1 and t2 are smooth pots for Range Selection
Product IEC 61812-1
Environmental:
Connection Diagram:
Cold Heat IEC 60068-2-1
Dry Heat IEC 60068-2-2
Repetitive Shock IEC 60068-2-27, 40 g, 6 ms
Non-Repetitive Shock IEC 60068-2-27 ., 30 g, 15 ms
1LL009_02