Point Assignment Display
NAME range = Not applicable
Tag Name |__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__| default = Blank

NODETYP An HPM point is being configured


Node Type HPM If a PM, APM, LM or SM point is being
configured, go to the appropriate
forms for those devices.

PNTFORM Full Point is fully displayed and alarmed


Point Form Componnt Pt. Is partially displayed but not alarmed

PTDESC range = Not applicable


Point Descriptor default = Blank
l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l
EUDESC range = Not applicable
Enginering UnitsD escriptor |__.__.__.__.__.__.__.__ | default = Blank

KEYWORD range = Not applicable


Keyword Descriptor |__.__.__.__.__.__.__.__ | default = Blank

ASSOCDSP range = Not applicable


Associated Display |__.__.__.__.__.__.__.__ | default = Blank

$CDETAIL (R620 and later) range = Not applicable


Point Custom Display |__.__.__.__.__.__.__.__ | default = Blank

UNIT range = Two Alphanumeric Characters


Process Unit Point Is Assigned To |__.__| default = Not applicable

NTWKNUM range = 1 to 20
NIM's UCN That This Point Is In |__.__| default = Not applicable

NODENUM range = 1 to 64
HPMM's Address On The UCN |__.__| default = Not applicable

SLOTNUM
Slot Number l__.__.__| 1-999 (but<= the value in NDCSLOT)

N/A if ALMOPT = None or if PNTFORM = Componnt. or if NODINPTS =0 or if FBTIME = 0.


PRIMMOD range = Not Applicable
Primary Module ID l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l default = Null
N/A if PNTFORM = Componnt

USER ID l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l range = Sixteen Character String


User ID Reservation default = Dashes
HP88-607
Page 2 of 7
09/08 HPM Digital Composite Point
Unit: Tagname: Engineer: Date:
Point Assignment Display
default = Not applicable
NOSTATES 2 2 digital switch states can be configured
Number Of Digital States 3 3 digital switch states can be configured

NODINPTS 0 0 digin connections can be configured


# Of Digital Input Connections 1 1 digin connections can be configured
2 2 digin connections can be configured

NODOPTS 0 0 digout connections can be configured


# Of Digital Output Connections 1 1 digout connections can be configured
2 2 digout connections can be configured
3 3 digout connections can be configured

State Configuration Display N/A if PNTFORM = Componnt.

PVTXTOPT Off range = Not applicable


PV Text Option On default = “Off”

STATETXT ( ) (1) l__.__.__.__.__.__.__.__l range = Not applicable


State - Descriptor Text default = “On”
(0) l__.__.__.__.__.__.__.__l default = “Off”
(2) l__.__.__.__.__.__.__.__l default = “State2”

BOXCLR (1) Red Green (Top box default) White Black


State 1 Box Color Cyan Yellow Blue Magenta

BOXCLR (0) Red Green White Black


State 0 Box Color Cyan Yellow (Middle box default) Blue Magenta

BOXCLR (2) Red (Lower box default) Green White Black


State 2 Box Color Cyan Yellow Blue Magenta

MOVPTXT range = Eight character string


Moving PV Text |__.__.__.__.__.__.__.__ | default = “MOVING”

BADPVTXT range = Eight character string


Bad PV Text |__.__.__.__.__.__.__.__ | default = “BAD”
HP88-607
HPM Digital Composite Point Page 3 of 7
09/08
Unit: Tagname: Engineer: Date:
State Configuration Display (Continued)
MOMSTATE (N/A if NODOPTS = 0) None No momentary output states
Momentary Output States Mom_0 State 0 is valid if (NOSTATES = 2)
Mom_1 State 1 is valid if (NOSTATES = 2 or 3)
Mom_2 State 2 is valid if (NOSTATES = 3)
Mom_1_2 State 1 or 2 is valid if (NOSTATES = 3)
LOGICSRC Logic Point driving the interlock
Logic Source l__.__.__.__.__.__.__.__ .__.__.__.__.__.__.__.__.__.__.__l to this Digital Composite Point

DISRC (Digital-Input-Connection Source)


Input # (N/A if NODINPTS = 0) DISRC (point.parameter) Destination

l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l D1
1

l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l D2
2

PV / Input ConfigurationDisplay -Only if NODINPTS = 1


D1_1 PVState0 Use & display contents of STATETXT0
D1_One PV State PVState1 Use & display contents of STATETXT1

D2D1_00 PVState1 Use & display contents of STATETXT1


D2_D1 Zero_Zero PV State PVState0 Use & display contents of STATETXT0
D2 = OFF, D1 = OFF PVState2 Use & display contents of STATETXT2*
MovPV Use & display contents of MOVPVTXT
BadPV Use & display contents of BADPVTXT
D2D1_01 PVState1 Use & display contents of STATETXT1
D2D1 Zero_One PV State PVState0 Use & display contents of STATETXT0
D2 = OFF, D1 = ON PVState2 Use & display contents of STATETXT2*
MovPV Use & display contents of MOVPVTXT
BadPV Use & display contents of BADPVTXT
D2D1_10 PVState1 Use & display contents of STATETXT1
D2D1 One_Zero PV State PVState0 Use & display contents of STATETXT0
D2 = ON, D1 = OFF PVState2 Use & display contents of STATETXT2*
MovPV Use & display contents of MOVPVTXT
BadPV Use & display contents of BADPVTXT
D2D1_11 PVState1 Use & display contents of STATETXT1
D2D1 One_One PV State PVState0 Use & display contents of STATETXT0
D2 = ON, D1 = ON PVState2 Use & display contents of STATETXT2*
MovPV Use & display contents of MOVPVTXT
BadPV Use & display contents of BADPVTXT
*Only applies if NOSTATES = 3

PV / Input ConfigurationDisplay (Continued) - N/A if NODINPTS = 0


Only Auto PV Source selection is not available and
PVSRCOPT
Field wiring or memory fetch supplies PV.
PV Source Option
All Selection from PVSOURCE is available
& Operator/CL-program may supply PV.
Auto Field wiring /memory -fetch supplies PV
PVSOURCE Man PV is supplied by Operator or program
PV Source Sub A value is substituted by a CL program
Track PV tracks the output
HP88-607
Page 4 of 7 HPM Digital Composite Point
09/08
Unit: Tagname: Engineer: Date:
Output Configuration Display – N/A if NODOPTS = 0
NOSTATES NODOPTS

ST1_OP1 Off 2-3 1-3


State 1 - Output 1 On

ST1_OP2 Off 2-3 2-3


State 1 - Output 2 On

ST1_OP3 Off 2-3 3


State 1 - Output 3 On

ST0_OP1 Off 1-3 1-3


State 0 - Output 1 On

ST0_OP2 Off 1-3 2-3


State 0 - Output 2 On

ST0_OP3 Off 1-3 3


State 0 - Output3 On

ST2_OP1 Off 3 1-3


State 2 - Output 1 On

ST2_OP2 Off 3 2-3


State 2 - Output 2 On

ST2_OP3 Off 3 3
State 2 - Output 3 On

DODSTN (Digital Output Connection Destination)


Output# DODSTN (point.parameter) NODOPTS

1 l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__. 1
__.__.__l
2 l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__. 2
__.__.__l
3 l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__. 3
__.__.__l

PULSEWTH l__.__.__.__l range = 0.0 to 60.0


Pulse Width For DigComp Point Outputs default = 1.0

Applies if NOSTATES = 3, and MOMSTATE = None


STCHGOPT None range = Not Applicable
State Change Option State 0 default = None

PAUSETIM l__.__.__.__l range = 0 to 1000 seconds


State 0 Pause Time default = 0

SEALOPT None range = Not Applicable


Seal-in Circuit Option Sealin default = None
HP88-607
HPM Digital Composite Point Page 5 of 7
09/08
Unit: Tagname: Engineer: Date:
Maintenance Display
MAINTOPT Off range = Not Applicable
Maintenance Support On default = Off

Maintenance Statistics
Maximum Hours Maximum Number of
Allowed in Each State Transistions into State

STATE 1 MAXTIM1H |__.__.__.__.__.__.__.__| MAXTRAN1 l__.__.__.__.__.__.__.__|

STATE 0 MAXTIM0H |__.__.__.__.__.__.__.__| MAXTRAN0 l__.__.__.__.__.__.__.__|


STATE 2 MAXTIM2H |__.__.__.__.__.__.__.__| MAXTRAN2 l__.__.__.__.__.__.__.__|
range = N/A range = 0 (No Limit)
default = 0 default = 0.0
Mode ConfigurationDisplay - N/A if NODOPTS = 0
NMODATTR None Parameter NMODE sets “normal” mode
Normal Mode Attribute Operator Operator sets “normal” operating mode
Program Program sets “normal” operating mode
MODEPERM Permit Operator can change this point’s mode
Mode Permissive NotPerm Optr. cannot change this point’s mode
$MODESEL (R630 and later) Man Prog Man mode and Prog mode attribute are allowed
Mode Selection List for this data point.
OROPT Off Optr. cannot bypass this point’s interlocks
Interlock Bypass Option On Operator can bypass this point’s interlocks
If BYPASS = ON
BYPASS Off Outputs not allowed to ignore interlocks
Interlock Bypass State On Stores to OP & SO are allowed to ignore
the interlocks
Alarming Display - N/A if PNTFORM = Componnt or if NODINPTS = 0
range = Any configured LCN Unit ID
$AUXUNIT
l__.__l default = Null (- -)
Auxiliary Unit

$REALARM l__.__.__.__l range = 0 to 9999 minutes


Re-alarming Interval (R660 and default = 0 minutes
later)

PVNORMAL range = STATETXT(0) – STATETXT(2)


PV Value’s Normal State Text l__.__.__.__.__.__.__.__l default = None

FBTIME range = 1 to 1000


Feedback Time l__.__.__.__l default = 0
N/A if FBTIME = 0.
CMDFALTM l__.__.__.__l range = 0 to 1000 seconds
Command Failure Timeout default = 0
ALENBST Displayed Logged Reported to EIP
Alarm Enable Status Enable Yes Yes Yes
Disable No Yes Yes
Inhibit No No No
HP88-607
Page 6 of 7
09/08 HPM Digital Composite Point
Unit: Tagname: Engineer: Date:

Alarming Display- N/A if PNTFORM = Componnt. or if NODINPTS = 0


SI0ALOPT None No alarms are generated
Safety Override Alarm Auto_Rtn Alarms generated, return to normal when override clears
Cnfm_Rqd Alarms generated, confirmed before returning to normal
If override clears. SIOALPPR must NoAction or
Journal.

SI0DESC l__.__.__.__.__.__.__.__l range = 8 Alphanumeric Characters


SI0 Alarm Descriptor default = blank

OVRDALOP None No alarms are generated


Override Alarm Option Auto_Rtn Alarms generated, return to normal when override clears
Cnfm_Rqd Alarms generated, confirmed before returning to normal
If override clears. OVRDALPR must NoAction or
Journal.
I1DESC range = 8 Alphanumeric Characters
l__.__.__.__.__.__.__.__l
I1 Alarm Descriptor default = blank

I0DESC range = 8 Alphanumeric Characters


l__.__.__.__.__.__.__.__l
I0 Alarm Descriptor default = blank

I2DESC range = 8 Alphanumeric Characters


l__.__.__.__.__.__.__.__l
I2 Alarm Descriptor default = blank

BADPVPR NoAction Journal Low High Emergncy Printer JnlPrint


Bad PV Alarm Priority (R670 and
later)

N/A if FBTIME = 0.

CMDDISPR NoAction Journal Low High Emergncy Printer JnlPrint


Command Disagree Priority (R670 and
later)

OFFNRMPR NoAction Alarm not reported to the system and not annunciated
Offnormal Alarm Priority (R670 and
later) Alarm is historized, not reported to US, not annunciated
Journal Alarm is historized, reported to US, and annunciated
Low Alarm is historized, reported to US, and annunciated
High Alarm is historized, reported to US, and annunciated
Emergency Not historized, reported to the printer, not annunciated
Printer Alarm historized, reported to the printer, not annunciated
JnlPrint
$OFSELCT (R681 and later) Cutout range = Cutout, Allow
Off Normal Selective Cutout Allow default = Cutout
HP88-607
Page 7 of 7
09/08
HPM Digital Composite Point
Unit: Tagname: Engineer: Date:

N/A if SI0ALOPT = None.

SI0ALPR NoAction Journal Low High Emergncy Printer JnlPrint


Override SI0 Alarm Priority

N/A if OVRDALOP = None.

OVRDALPR NoAction Journal Low High Emergncy Printer JnlPrint


Override Alarm Priority (R670 and
later)

None No Reporting
EVTOPT Eip Digital PV changes invoke Event-Initiated
Event Reporting Option Processing
l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l range = Not applicable
EIPPCODE default = Null
Event Init Proc Destination
HP88-602
HPM Analog Input Point Page 1 of 8
09/08
Unit: Tagname: Engineer: Date:

Point Assignment Display


range = Not applicable
NAME default = Blank
Tag Name |.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__|
NODETYP An HPM Point Is Being Configured
Node Type HPM If a PM, APM, LM or SM is being
configured, go to the appropriate
PM, APM, forms for those devices.
LM or SM
PNTFORM FuLL Point is fully displayed and alarmed
Point Form Componnt Pt. is partially displayed but not alarmed

PTDESC range = Not applicable


Point Descriptor default = Blank
l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l
EUDESC range = Not applicable
Engineering Units Descriptor |__.__.__.__.__.__.__.__ | default = Blank

KEYWORD range = Not applicable


Keyword Descriptor |__.__.__.__.__.__.__.__ | default = Blank

ASSOCDSP range = Not applicable


|__.__.__.__.__.__.__.__ |
Associated Display default = Blank
$CDETAIL (R620 and later) range = Not applicable
|__.__.__.__.__.__.__.__ |
Point Custom Display default = Blank
UNIT range =Two Alphanumeric Characters
|__.__|
Process Unit Point Is Assigned To default = Not applicable

NTWKNUM range = 1 to 20
|__.__|
NIM's UCN That This Point Is In default = Not applicable
NODENUM range = 1 to 64
|__.__|
HPMM's Address On The UCN default = Not applicable

MODNUM range = 1 to 40
|__.__|
I/O Module Number default =Not applicable
SLOTNUM 1-16 (For HLAI or STIM module)
|__.__|
Slot Number 1-8 (For LLAI or PI module)
1-32 (For LLMUX and RHMUX modules)

N/A if PNTFORM = Componnt.


PRIMMOD range = Not Applicable
l__.__.__.__.__.__.__.__.__.__.__.__.__.__.__.__l
Primary Module ID default = Null

PNTMODTY HLAI -> pg 2-A High Level Analog Input


Point’s IO Module Type STIM -> pg 3-B Smart Transmitter Intf. Module
PI -> pg 5-C Pulse Input Module
LLMUX -> pg 2-D Low Level Multiplexer; also applies to
-> RHMUX, except that RHMUX does not
LLAI pg 4-E apply to SENSRTYP of RTD
Low Level Analog Input
HP88-602
Page 2 of 8
09/08 HPM Analog Input Point
Unit: Tagname: Engineer: Date:

A HLAI Only PV Configuration Display


SENSRTYP 1_5_V +1 to +5 volts
Sensor Type P4_2_V .4 to 2 volts
0_5_V 0 to 5 volts
Slidwire Slidewire Resistance Device

PVCHAR Linear Linear


PV Characterization SqrRoot Squareroot

Btherm Etherm Jtherm Ktherm Thermocouple Type:


Rtherm Rptherm Stherm Ttherm B, E, J, K, R, RP, S, or T

DinRtd JisRtd NicklRtd CopprRtd Resistance Temperature Device


Type:
Din,Jis,Nickel, or Copper

PVTEMP DegreesC DegreesF C = Celcius; F = Farenheit


Thermal EUS For PV DegreesR DegreesK R = Rankin; K = Kelvin

SLWSRCID range = 1 – 16
Slidwire Voltage Slot ID (number) l__.__l default = 1

D LLMUX Only PV Configuration Display (continued)


NOTE: PV configuration display for LLMUX also applies to RHMUX IOP,
except that RTD is not supported by RHMUX IOP.

SENSRTYP Thermcpl Thermocouple


Sensor Type RTD Resistance Temp.Device
0_100_MV 0 to 100 millivolts

PVCHAR Linear Linear


PV
Characterization
Btherm Etherm Jtherm Ktherm Thermocouple Type:
Rtherm RPtherm Stherm Ttherm B, E, J, K, R, RP, S, or T

DinRtd JisRtd NicklRtd CopprRtd Resistance Temperature Device Type:


Din, Jis, Nickel, or Copper

PIUOTDCF Off Open Thermocouple Detection


Open T/C Detect Enable Option On (LLMUX-Thermcpl only)

PVTEMP DegreesC DegreesF C = Celcius; F = Farenheit


Thermal EUS For PV DegreesR DegreesK R = Rankin; K = Kelvin

TCRNGOPT Normal Use PVEXEULO’s normal range table


Thermocouple Range Option Extended Use PVEXEULO’s extended range table
HP88-602
Page 3 of 8
09/08
HPM Analog Input Point
Unit: Tagname: Engineer: Date:

B This page - STIM Only PV Configuration Display


STITAG l__.__.__.__.__.__.__.__l Device name stored in the Smart Xmtr.
Transmitter Tag ID default = Blank
SENSRTYP SPT_DP Differential Pressure Xmtr.
Smart Transmitter SPT_GP Gauge Pressure Xmtr.
Sensor Type SPT_AP Absolute Pressure Xmtr.
SFM Magnetic Flow Xmtr.
STT Temperature Xmtr.
PVCHAR Linear Linear
PV Characterization Option SqrRoot Squareroot

Btherm B type thermocouple NicklRtd Nickel type Res. Temp. Device


Etherm E type thermocouple PT200Rtd Point 200 Resistance Temp. Dev
Jtherm J type thermocouple PT500Rtd Point 500 Resistance Temp. Dev.
Ktherm D type thermocouple CU10Rtd Copper 10 Resistance Temp. Dev.
Rtherm R type thermocouple CU25Rtd Copper 25 Resistance Temp. Dev.
Stherm S type thermocouple RTD_OHMS Ohms Resistance Temp. Dev.
Ttherm T type thermocouple RHRAD RH Radiomatic
Ntherm N type thermocouple W5W26TC C type thermocouple
DinRtd Din type Res. Temp. Device W3W25TC D type thermocouple
JisRtd Jis type Res. Temp. Device NINIMOTC Nickle/nickle/Mol. thermocouple

STI_EU
Applies if – SENSRTYP = SFM SENSRTYP = STT AND
STI Engineering Units

SENSRTYP = SPT_DP/GP/AP CM_HR BRL_DAY CLUB_M PV CHAR =


GAL_HR CM_SEC LITRES MV
INH20 MBAR
MMHG BAR
LIT_HR PRCNT MLITRES x Linear V
CC_HR BLANK FL_OZ
PSI G_SQCM
CM_MIN LBS FEET
KPA KG_SQCM
MPA MMH20
GAL_MIN KG METERS x RTD_OHMS- OHMS
LIT_MIN TONS MM
INHG
CC_MIN GRAMS INCHES DEG_C
CM_DAY OZ KG_CUM x All Other DEG_F
GAL_DAY GAL G_CUM DEG_K
KGAL_DAY BRL LBS_CUFT DEG_R
LBS_CUIN

DECONF PV Broadcast PV 3.6 time/sec.


DE Configuration Mode PV_SV Broadcast PV 3.2 times/sec., SV .46 X/Sec.
PV_DB Broadcast PV 2.7 times/sec. Plus data base
PV_SV_DB B/cast PV 2.4 X/Sec., SV .34 X/Sec+ d/base
URL range = See Parameter Ref.Guide
Upper Range Limit l__.__.__.__.__.__.__.__l default = NaN
URV range = See Parameter Ref.Guide
Upper Range Value l__.__.__.__.__.__.__.__l default = NaN
LRV range = See Parameter Ref.Guide
Lower Range Value l__.__.__.__.__.__.__.__l default = NaN
DAMPING SPT=0-32, STT=0-102.3,SFM=0-100
Xmtr Filter Lag Time l__.__.__.__.__.__.__.__l (discrete increments); default = 0.0
HP88-602
Page 4 of 8
09/08 HPM Analog Input Point
Unit: Tagname: Engineer: Date:

Applies if SENSRTP=STT
PIUOTDCF Off Thermocouple fault detection
Open TC Detection Enable Option On range = Off or On.
CJTACT On On = Internal cold Jct.compensation active
Int. Cold Jct. Compensation Off Off = External cold Jct.compensation active

PV Configuration Display (continued) – Applies To All Point Types Except As Noted


E
LLAI Only PV Configuration Display

SENSRTYP 1_5_V +1 to +5 volts


Sensor Type 0_5_V .0 to 5 volts
RTD Resistance Temp. Device
Thermcpl Thermocouple
0_100_MV 0 to 100 millivolts

PVCHAR Linear Linear


PV Characterization SqrRoot Squareroot

Btherm Etherm Jtherm Ktherm Thermocouple Type:


Rtherm Rptherm Stherm Ttherm B, E, J, K, R, RP, S, or T

DinRtd JisRtd NicklRtd CopprRtd Resistance Temperature Device Type:


Din, Jis, Nickel, or Copper

PVTEMP DegreesC DegreesF C = Celcius; F = Farenheit


Thermal EUS For PV DegreesR DegreesK R = Rankin; K = Kelvin

TCRNGOPT Normal Use PVEXEULO’s normal range table


Thermocouple Range Option Extended Use PVEXEULO’s extended range table

Applies if SENSRTYP = Slidewire or 0-100mV


0 to 100 mv Slidewire
PVRAWHI l__.__.__.__.__l range = 0 – 100 0.0 - 1
PV Raw High Limit default = 1.0 1.0
units = millivolts Ratio

PVRAWLO 0 to 100 mv Slidewire


PV Raw Low Limit l__.__.__.__.__l range = 0 – 100 0.0 - 1
default = 0 0
units = millivolts Ratio
Applies if PVCHAR = LINEAR or SQRROOT
INPTDIR Direct PVCALC increases as PVRAW increases
Analog Input Direction Reverse PVCALC decreases as PVRAW increases
HP88-602
Page 5 of 8
HPM Analog Input Point 09/08
Unit: Tagname: Engineer: Date:

PVEUHI range = PVEULO to PVEXEUHI


PV High Range In EUs |__.__.__.__.__.__.__.__l default = 100.0
PVEULO range = PVEXEULO to PVEUHI
PV Low Range In EUs |__.__.__.__.__.__.__.__l default = 0.0

PVFORMAT DO D2 D0 = 9999. D2 = 99.99


PV Decimal Point Format D1 D3 D1 = 999.9 D3 = 9.999

N/A if SENSRTYP = Thermcpl or RTD.


PVEXEUHI range = >=PVEUHI
PV Extended Hi Range in EUs |__.__.__.__.__.__.__.__l default = 102.9
PVEXEULO range = <=PVEULO
PV Extended Lo Range in EUs |__.__.__.__.__.__.__.__l default = -2.9

PV Configuration Display (continued) – Applies To All Point Types Except As Noted


PVCLAMP NoClamp No clamping of the PV value
PV Clamping Option Clamp Clamp PV value at range extension limit

N/A if SENSRTYP = THERMCPL or RTD

LOCUTOFF l__.__.__.__.__.__.__.__l range = PVEULO – PVEUHI and NaN


Low Signal CO For Flow Inputs default = NaN

C PI Only
C1 range = Real Number t0.0
Scaling Constant 1 l__.__.__.__.__.__.__.__l default = 1.0
C2 range = Real Number t0.0
Scaling Constant 2 l__.__.__.__.__.__.__.__l default = 1.0
TIMEBASE Seconds Minutes Hours PV & Setpoint Eng. Units per
Input Time Base Second, Minute, or Hour

N/A if PNTFORM = Componnt.


PVSRCOPT Only Auto PV Source selection is not available and
PV Source Option Field wiring or memory fetch supplies PV.
All Selection from PVSOURCE is available
& Operator/CL-program may supply PV.
PVSOURCE
PV Source Auto Field wiring/memory fetch supplies PV
Man PV is supplied by Operator or program
Sub A value is substituted by a CL program

TF range = 0.0 to 60.0 (minutes)


PV Filter Lag Time in Minutes |__.__.__.__l default = 0.0 (PV will not be delayed)

N/A if PNTFORM = Compnnt.


PVTV range = PVEXEULO-PVEXEUHI, & NaN
|__.__.__.__.__.__.__.__l
PV Target Value in EUs default = NaN
OVERVAL range = 0 to 100
Overview Display Value l __.__.__l default = 25
HP88-602
Page 6 of 8 HPM Analog Input Point
09/08
Unit: Tagname: Engineer: Date:

Alarming Display – N/A if PNTFORM = Componnt


As you enter alarm trip points and alarm priorities in the next section please refer to the following alarm
Priority definitions and the note.
NoAction Alarm is not reported to the system and not annunciated (R670 & later)
Journal Alarm is historized, not reported to US, not annunciated
Low Alarm is historized, reported to US, and annunciated
High Alarm is historized, reported to US, and annunciated
Emergency Alarm is historized, reported to US, and annunciated
Printer Not historized, reported to the printer, not annunciated
JnlPrint Alarm historized, reported to the printer, not annunciated
Note: If you do not enter a trip point value for a given pair of trip-points and alarm-priorities, do not
Circle an alarm priority option for that pair (i.e., no trip point, no alarm priority).

Alarming Display – N/A if PNTFORM = Componnt.


$AUXUNIT range = Any configured LCN Unit ID
Auxiliary Unit l__.__l default = Null (--)
$ALDLOPT (R620 and later) None
Alarm Delay Option OffDlyLo Off Delay Lo
OffDlyHi Off Delay Hi
OffDlyEm Off Delay Emergency
OnDlyLo On Delay Lo
OnDlyHi On Delay Hi
OnDlyEm On Delay Emergency

$DLBADAL (R681 and later) None range = Offdelay, None


Delay for BADPV Offdelay default = None

DLYTIME (R620 and later) l__.__.__.__l range = 0 to 9999 seconds


Delay Time default = 0 seconds

$REALARM (R660 and later) l__.__.__.__l range = 0 to 9999 minutes


Re-alarming Interval in minutes default = 0 minutes

PVALDB
PV Alarm Deadband In % Half One Two Three Four Five EU

PVALDBEU range >= 0.0


PV Alarm Deadband in EU |__.__.__.__.__.__.__.__l default = 1.0

PVHITP range = PVLOTP - PVHHTP, & NaN


PV High Alarm Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVHIPR NoAction Journal Low High Emergency Printer JnlPrint


PV High Alarm Priority (R670 and
later)
$HISELCT (R681 and later) Cutout range = Cutout, Allow
PV High Selective Cutout Allow default = Cutout
HP88-602
HPM Analog Input Point Page 7 of 8
09/08

Unit: Tagname: Engineer: Date:

PVLOTP range = PVLLTP - PVHITP, & NaN


PV Low Alarm Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVLOPR NoAction Journal Low High Emergency Printer JnlPrint


PV Low Alarm Priority (R670 and
later)
$LOSELCT (R681 and later) Cutout range = Cutout, Allow
PV Low Selective Cutout Allow default = Cutout

PVHHTP range = PVHITP to PVEXEUHI, & NaN


PV Hi Hi Alarm Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVHHPR NoAction Journal Low High Emergency Printer JnlPrint


PV High High Alarm Priority (R670 and
later)
$HHSELCT (R681 and later) Cutout range = Cutout, Allow
PV High High Selective Cutout Allow default = Cutout

PVLLTP range =PVEXEULO – PVLOTP, & NaN


PV Low Low Alarm Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVLLPR NoAction Journal Low High Emergency Printer JnlPrint


PV Low Low Alarm Priority (R670 and
later)
$LLSELCT (R681 and later) Cutout range = Cutout, Allow
PV Low Low Selective Cutout Allow default = Cutout
PVROCPTP range = >=0.0, andNaN
PV Pos Rate Of Chg Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVROCPPR NoAction Journal Low High Emergency Printer JnlPrint


PV Pos Rate Of Chg Alarm (R670 and
Priority later)
HP88-602
Page 8 of 8
HPM Analog Input Point
09/08
Unit: Tagname: Engineer: Date:

$RPSELCT (R681 and later) Cutout range = Cutout, Allow


PV Positive Rate of Change Allow default = Cutout
Selective Cutout

PVROCNTP range = >=0.0, andNaN


PV Neg Rate Of Chg Trip Point |__.__.__.__.__.__.__.__l default = NaN

PVROCNPR NoAction Journal Low High Emergency Printer JnlPrint


PV Neg Rate Of Chg Alarm Priority (R670 and
later)
$RNSELCT (R681 and later) Cutout range = Cutout, Allow
PV Negative Rate of Change Allow default = Cutout
Selective Cutout

BADPVPR NoAction Journal Low High Emergency Printer JnlPrint


Bad-PV Alarm Priority (R670 and
later)
ALENBST Displayed Logged Reported to EIP
Point Alarm Enable Status Enable Yes Yes Yes
Disable No Yes Yes
Inhibit No No No

Applies if PNTMODTY = LLAI or LLMUX and if the SENSRTYP = THERMCPL or RTD

$OLDEVDS
Open-Line Detect Event Disable Enable Allows BADPV alarms when open line
detected.

Disable Disables BADPV alarms when open line


detected.

Applies if PNTMODTY = HLAI, STIM, PI, or if SENSRTYP not THERMCPL or if SENSRTYP not RTD

$OLDEVDS
Open-Line Detect Event Disable NOOTDETC Value must be selected. Point operation is
not affected by this function.