SHORT CIRCUIT ANALYSIS‐REFERENCE DIAGRAM
33kV MAIN HT PANEL BUS‐I 33kV MAIN HT PANEL BUS‐II
33kV, U.G Cable 33kV, U.G Cable 33kV, U.G Cable 33kV, U.G Cable
Cable Conductor Cable Conductor Cable Conductor Cable Conductor
properties: Length properties: Length properties: Length properties: Length
= 1km Z=0.160 = 1km Z=0.160 = 1km Z=0.160 = 1km Z=0.160
Ohm/km Ohm/km Ohm/km Ohm/km
33kV, U.G Cable 33kV, U.G Cable 33kV, U.G Cable 33kV, U.G Cable 33kV, U.G Cable
33kV, U.G Cable Cable
Cable Conductor Cable Conductor Cable Conductor Cable Conductor Cable Conductor
Conductor properties:
properties: Length properties: Length properties: Length properties: Length properties: Length
Length = 1km
= 1km Z=0.160 = 1km = 1km Z=0.160 = 1km Z=0.160 = 1km Z=0.160
Z=0.160 Ohm/km
Ohm/km Z=0.160Ohm/km Ohm/km Ohm/km Ohm/km
Power Trafo - 1, Power Trafo - 3, Power Trafo - 5, Power Trafo - 6, Power Trafo - 8, Power Trafo - 10,
7.5MVA, 33/0.6 kV, 7.5MVA, 33/0.6 kV, 5MVA, 33/0.6 kV, 5MVA, 33/0.6 kV, 7.5MVA, 33/0.6 kV, 7.5MVA, 33/0.6 kV,
Z=8.35% Z=8.35% Z=7.15% Z=7.15% Z=8.35% Z=8.35%
Max HT Fault current: Max HT Fault Max HT Fault current: Max HT Fault current: Max HT Fault current: Max HT Fault current:
1.57kA current: 1.57kA 1.22kA 1.22kA 1.57kA 1.57kA
Inverter Block - 01 Inverter Block - 03 Inverter Block - 05 Inverter Block - 06 Inverter Block - 08 Inverter Block - 10
132kV Fault Level Calculation
Route length of conductor Section 2 ( Transformer 13,14 - Bus Bar ) 500 Mtrs As per pooling scheme in sheet 1
Per Unit impedence of Conductor Section 1 with base kVA 0.0007 p.u (Base kVA*Impedance)/10*(Base kV)²
Per Unit impedence of Conductor Section 2 with base kVA 0.01396 p.u
Total Per Unit impedance of transformer 11,12 and associated conductor 0.063 p.u
Total Per Unit impedance of transformer 13,14 and associated conductor 0.056 p.u
Total Per Unit impedance of transformer 11-14 and associated conductor 0.030 p.u