Site Lighting Power Density Calculation

Fixture Power Total Fixtures Total Fixture LPD


Site Lighting Fixture (Watts) (QTY) Power (Watts) Site Location Site Area (SF) (W/SF)
Pole Fixture 1 250 14 3500 Parking 1 32,000 0.11
Pole Fixture 1 250 8 2000 Parking 2 18,000 0.11
Pole Fixture 2 115 1 115 Walkways 1 875 0.13
Bollard Fixture 1 40 4 160 Walkways 1 875 0.18
Bollard Fixture 1 40 6 240 Courtyard 1 1,500 0.16
Wall Washer 1 50 5 250 Building Façade N 2,500 0.10

Site Areas
ASHRAE
90.1.2007 Actual LPD (From
Allowable LPD Site Lighting
Identification Area (SF) (W/SF) Table) Complies (Y/N)
Parking 1 32,000 0.25 0.11 Yes
Parking 2 18,000 0.15 0.11 Yes
Walkways 1 (10' wide) 1,500 0.2 0.16 Yes
Courtyard 1 1,500 0.2 0.16 Yes
Building Façade N 2,500 0.2 0.1 Yes

Lamp Lumen Calculation


Luminaire Type Quantity of Initial Fixture Total Fixture Initial Fixture Total Fixture Pecent
Installed Lumens per Lumens (column Lumens from Lumens above 90 Lumens
Luminaires Luminaire 2 x column 3) Luminaire above Degrees (column above 90
90 Degrees from 2 x column 5) Degrees
Nadir from
Nadir
A 10 4600 46,000 100 1000 2%
B 20 11,900 238,000 0 0 0%
C 5 2,000 10,000 2000 10000 100%
Total 294,000 11,000 4%
Site Lighting Power Density Calculation
Fixture Power Total Fixture Power
Site Lighting Fixture (Watts) Total Fixtures (QTY) (Watts)
Hanging Fixture 1 60 3 180
Walkway Path Fixture 1 13 17 221

Site Areas
ASHRAE 90.1.2004 Actual LPD (From Site
Identification Area (SF) Allowable LPD (W/SF) Lighting Table)
Parking 1 6,160 0.25 0.03
Walkways 1 (10' wide) 1,454 0.2 0.15

Lamp Lumen Calculation


Luminaire Type Quantity of Initial Fixture Lumens per Total Fixture Lumens
Installed Luminaire (column 2 x column 3)
Luminaires

A 3 5800 17,400
B 17 890 15,130
Total 32,530

FS Comments
1 Change the ASHRAE code to 90.1-2007.
2 No % reduction in LPD is required in LEED 2009
3 Remove these columns
Site Location Site Area (SF) LPD (W/SF)
Parking 1 6,160 0.03
Walkways 1 1,454 0.15

Acutal LPD Required LPD Complies


Reduction (%) Reduction (%) (Y/N)
88% 20% YES
24% 20% YES

Initial Fixture Total Fixture Pecent


Lumens from Lumens above Lumens
Luminaire above 90 Degrees above 90
90 Degrees from (column 2 x Degrees
Nadir column 5) from Nadir

0 0 0%
0 0 0%
0 0%