Flow Rate Table [m³/h] Series AQUADA

All flow rates are valid for the recommended water temperatures of 5 – 25°C!

UV Dose: 400 J/m² at the end of lamp lifetime*


UV T
80.0 82.0 84.0 86.0 88.0 90.0 92.0 94.0 96.0 98.0
(1 cm) in %
UV T
10.7 13.7 17.5 22.1 27.9 34.9 43.4 53.9 66.5 81.7
(10 cm) in %
Unit Flow rate in m³/h

AQUADA 1 0.60 0.62 0.63 0.64 0.66 0.67 0.69 0.70 0.72 0.73

AQUADA 2 1.52 1.55 1.59 1.63 1.66 1.70 1.74 1.77 1.81 1.85

AQUADA 4 2.30 2.39 2.49 2.58 2.69 2.79 2.90 3.01 3.12 3.24

AQUADA 7 4.8 5.0 5.2 5.4 5.6 5.8 6.0 6.2 6.5 6.7

AQUADA 10 6.1 6.5 6.8 7.2 7.6 8.1 8.5 9.0 9.5 10.1

Dose calculation is based on average intensities according to the “point source summation” method

* 400 J/m² = 40 mJ/cm² = 40,000 µWs/cm²

UV Dose: 300 J/m² at the end of lamp lifetime*


UV T
80.0 82.0 84.0 86.0 88.0 90.0 92.0 94.0 96.0 98.0
(1 cm) in %
UV T
10.7 13.7 17.5 22.1 27.9 34.9 43.4 53.9 66.5 81.7
(10 cm) in %
Unit Flow rate in m³/h

AQUADA 1 0.80 0.82 0.84 0.86 0.88 0.90 0.92 0.94 0.96 0.98

AQUADA 2 2.02 2.07 2.12 2.17 2.22 2.27 2.32 2.37 2.42 2.47

AQUADA 4 3.06 3.19 3.31 3.45 3.58 3.72 3.86 4.01 4.16 4.32

AQUADA 7 6.4 6.6 6.9 7.2 7.4 7.7 8.0 8.3 8.6 9.0

AQUADA 10 8.2 8.6 9.1 9.6 10.2 10.7 11.4 12.0 12.7 13.4

Dose calculation is based on average intensities according to the “point source summation” method

* 300J/m² = 30 mJ/cm² = 30,000 µWs/cm²


1 m³/h = 4.4033 GPM = 0.00634 MGD

AQUADA-Flow.doc -Vol. VII -


Rev.2
Subject to change without notice. 1/2
Flow Rate Table [m³/h] Series AQUADA

All flow rates are valid for the recommended water temperatures of 5 - 25°C!

UV Dose: 400 J/m² at the end of lamp lifetime*


UV T
80.0 82.0 84.0 86.0 88.0 90.0 92.0 94.0 96.0 98.0
(1 cm) in %
UV T
10.7 13.7 17.5 22.1 27.9 34.9 43.4 53.9 66.5 81.7
(10 cm) in %
Unit Flow rate in GPM

AQUADA 1 2.6 2.7 2.8 2.8 2.9 3.0 3.0 3.1 3.2 3.2

AQUADA 2 6.7 6.8 7.0 7.2 7.3 7.5 7.7 7.8 8.0 8.1

AQUADA 4 10.1 10.5 11.0 11.4 11.8 11.4 11.8 12.3 12.8 13.3

AQUADA 7 21.1 22.0 22.9 23.8 24.7 25.5 26.4 27.3 28.6 29.5

AQUADA 10 26.9 28.6 29.9 31.7 33.5 35.7 37.4 39.6 41.8 44.5

Dose calculation is based on average intensities according to the “point source summation” method

* 400 J/m² = 40 mJ/cm² = 40,000 µWs/cm²

UV Dose: 300 J/m² at the end of lamp lifetime*


UV T
80.0 82.0 84.0 86.0 88.0 90.0 92.0 94.0 96.0 98.0
(1 cm) in %
UV T
10.7 13.7 17.5 22.1 27.9 34.9 43.4 53.9 66.5 81.7
(10 cm) in %
Unit Flow rate in GPM

AQUADA 1 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.1 4.2 4.3

AQUADA 2 8.9 9.1 9.3 9.6 9.8 10.0 10.2 10.4 10.7 10.9

AQUADA 4 13.5 14.0 14.6 15.2 15.8 16.4 17.0 17.7 18.3 19.0

AQUADA 7 28.2 29.1 30.4 31.7 32.6 33.9 35.2 36.5 37.9 39.6

AQUADA 10 36.1 37.9 40.1 42.3 44.9 47.1 50.2 52.8 55.9 59.0

Dose calculation is based on average intensities according to the “point source summation” method

* 300J/m² = 30 mJ/cm² = 30,000 µWs/cm²


-3
1 GPM = 1.44*10 MGD = 0.227 m³/h

AQUADA-Flow.doc -Vol. VII -