Solution to Problem 1:
From Table A4, the 60-Hz resistance of one ACSR 900 kcmil 54/3 conductor at 25°C:
(1 mile = 1.609 km)
R = 0.104 Ω/mile = 0.0646 Ω/km
The per-phase resistance of this transmission line (with two conductors per phase):
𝑅 0.0646
R total = = = 0.0323 Ω/𝑘𝑚 (per phase)
2 2
Solution to Problem 2:
Distance between wires at phases a, b, c for this equal spacing 3-phase line:
D = 5 ft
Apply Equation (4.5.9) for equal-spacing 3-phase line with solid cylindrical conductors, the positive-
sequence inductance in H/m is:
𝐷 5
La = 2 × 10−7 ln (𝑟 ′ ) = 2 × 10−7 × ln (0.0260) = 1.0518 × 10−6 𝐻/𝑚
Solution to Problem 3:
Distance between wires at phases a, b, c for this un-equal spacing 3-phase line:
D12 = 10 m, D23 = 10 𝑚, D31 = (10 + 10) = 20 𝑚
From Table A4, for one ACSR 954 kcmil conductor, the GMR value (1 ft = 0.3048 m):
GMR = 0.0403 ft = 0.01228 m
Solution to Problem 4:
Bundle spacing = d = 0.5m.
From Table A4, GMR of a 1113 kcmil ACSR conductor (1 m = 3.28 ft):
0.0435
GMR = 0.0435 ft = m = 0.01326m.
3.28
DS = 𝐺𝑀𝑅 = 0.01326 𝑚.
The horizontal phase spacings between bundle centers are 7m, 7m, and 14m:
D12 = 7𝑚, 𝐷23 = 7𝑚, 𝐷31 = 14𝑚
Apply Equation (4.6.22), the phase-a inductance per unit length is:
𝐷𝑒𝑞 8.8194
La = 2 × 10−7 × ln 𝐷 = 2 × 10−7 × ln 0.1491 = 8.1602 × 10−7 𝐻/𝑚
𝑆𝐿