europanel

installation guide
horizontally laid panel
standard details
europanel horizontally laid

A 1. Check all support steelwork


has been installed within C 4. Apply a continuous strip of the
95 x 10mm structural rear air
Continuous strip of
standard dimensional seal to the centre of the vertical 95 x 10mm structural
tolerances. support steelwork ensuring that rear air seal
Check that the width of it laps over the drip flashing
the steel bearing face is and butts tightly to the rear
consistent with any wind air seal at the base position.
loading calculations that 5. Check actual panel length
have been undertaken. on-site and mark set-out
Minimum 65mm bearing point for the panels taking into
per panel end. consideration the steelwork
and panel length tolerances.

• SET OUT PANELS

2. Fix the drip flashing and the


B EBS1 base section onto the
12 x 6 air seal
D 6. Lift panel from stack using your
chosen method of handling • CHECK PANEL LEVEL
base angle at 450mm centres and remove the protective film
with suitable austenitic stainless from the liner side of the panel.
steel tek screws. If lifting via vacuum, the
Ensure that both are level and Base Angle sealed protective film on the face of the
to floor slab
the correct set-out dimensions panel should also be removed. Rear female panel
have been used. 7. Lift the panel carefully and joint engaged onto
EBS1 Base Section
3. Apply a continuous strip of the lower into position onto the
12 x 6mm rear air seal above EBS1 Base Section EBS1 base section ensuring
the EBS1 base section. that the rear female joint of
the panel engages sufficiently.
Check panel is level before
proceeding.
Austenitic
stainless steel tek
screw fixings at
450mm centres If you would like further
information on the installation of
Drip Flashing europanel panels please contact
our technical team.
Call. +44 (0) 29 20 77 66 77
Fax. +44 (0) 29 20 36 91 61
Email. technical@eurobond.co.uk

www.eurobond.co.uk

2 3
standard details
europanel horizontally laid

13. Apply a continuous strip of


E 8. Before fixing, insert anti-
compression gauges into the
Continuous bead of
G 12 x 6mm rear air seal to the
Top panel cut to
panel end joint in the position silicone sealant
horizontal steel at the top of required height
shown. the elevation.
9. Fix the panels with a minimum of 14. Cut the top panel to the
Continuous strip
3 No. suitable austenitic stainless required height if necessary of 12 x 6mm rear
steel fixings per panel support*, lay and through fix into the steel air seal
of
remembering to use the ion at 450mm centres.
ect
spreader washers. The long Dir NOTE: To ensure the correct
end of the spreader washer is compression of fixings and
positioned on the opposite Austenitic stainless prevent distortion of the
end to your direction of lay. steel fixings panel face, depth gauges
NOTE: To ensure the correct must be used on fixing guns.
compression of fixings and
prevent distortion of the
panel face, depth gauges
must be used on fixing guns.
Fixing at 450mm
10. Once the panel is fixed, remove centres into support
the anti-compression gauges 3mm pre-punched
steelwork
from the joint before proceeding. Spreader washer
11. Run a bead of silicone sealant • ENSURE ANTI-
from the rear air seal over the COMPRESSION EHJ filler plug
rear male joint and insert the GAUGES ARE
EHJ filler plug to the ends of REMOVED
the external male joint. BEFORE Anti-compression
CONTINUING gauge
* The number of fixings is dependant on
wind loadings. Calculation to be undertaken.

12. Install further panels one bay


F at a time removing the film H 15. Repeat the method above to
install further bays of panels
from the panels as the along the elevation. To ensure
installation progresses. the vertical joint position does Ensure vertical gap is
NOTE: The use of seating not creep along the elevation 30mm, consistent
gauges is essential to ensure check that all panel lengths and within tolerances
a joint with a uniform width. and steelwork tolerances are along elevation
accounted for.
16. Ensure that the spreader
washers are positioned as
shown to create the fixing point
Spreader washer
for omega section cover strips.

Use seating gauge If you would like further


to ensure consistent
panel joint
information on the installation of
5mm panel joint
europanel panels please contact
our technical team. y
of la
Call. +44 (0) 29 20 77 66 77 tion
ec
Fax. +44 (0) 29 20 36 91 61 Dir
Email. technical@eurobond.co.uk

www.eurobond.co.uk

4 5
standard details
europanel horizontally laid

I 17. Insert the insulation infill


into the gap between panels
Stone wool
ensuring they are tightly insulation infill
butted.
18. Apply a continuous run of
9 x 3mm butyl mastic to the 2 continuous
rear of each flange on the runs of 9 x 3mm
omega section (total 2 runs butyl mastic seal
per omega) and mark positions
of panel spreader washers on
the centre face of the omega
Austenitic
section. stainless steel
19. Carefully position the omega tek screw fixings
section and press onto the
front of the panels. Fix through
the centre of the omega
section into the spreader
Omega section
washers behind with suitable Recessed Window Head Personnel Door Head
austenitic stainless steel tek
screws.
Omega insert
(push fit)

J 20. Continue to install panels around the building in


accordance with our standard details shown here.
Flashings to be sealed to panel using 9 x 3mm
butyl mastic and fixed with suitable austenitic
Full key details are available on request. stainless steel tek screws at 450mm centres.
All cut panels around doors and windows to * The number of fixings is dependant on wind
be fully trimmed out with support steel and loadings. Calculation to be undertaken.
through fixed at 450mm centres.
Recessed Window Jamb Personnel Door Jamb

External Corner Panel External Corner Recessed Window Cill Parapet

6 7
europanel