You are on page 1of 5

Generation Load V (p.u) Z at Buses(p.

u)
Bus P (MW) Q (Mvar) P (MW) Q (Mvar) V Delta, d (°) bus type R
1 0 0 0 0 1.06 0 1 0
2 232 0 21.7 12.7 1.045 0 2 0
3 0 0 94 19 1.01 0 2 0
4 0 0 47.8 10 1 0 3 0
5 0 0 7.6 1.6 1 0 3 0
6 0 0 11.2 7.5 1.07 0 2 0
7 0 0 0 0 1 0 3 0
8 0 0 0 0 1.09 0 2 0
9 0 0 29.5 16.6 1 0 3 0
10 0 0 9 5.8 1 0 3 0
11 0 0 3.5 1.8 1 0 3 0
12 0 0 6.1 1.6 1 0 3 0
13 0 0 13.5 5.8 1 0 3 0
14 0 0 14.9 5 1 0 3 0
Z at Buses(p.u) Y at buses (p.u) Q_Generation limits Bus V limits
X G B Q_Gmin Q_Gmax Vmin Vmax injected
0 0 0 -10 10 1.059 1.061 0
0 0 0 -40 50 1.044 1.046 0
0 0 0 0 40 1.009 1.011 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
0 0 0 -6 29 1.069 1.071 0
0 0 0 0 0 0.95 1.05 0
0 0 0 -6 37 1.089 1.091 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
0 0 0 0 0 0.95 1.05 0
Line bus to bus Series Z (pu) Half shunt(pu)
s_ Bus r_Bus No_of_Lines R X G B tap
1 2 1 0.01938 0.05917 0.0000 0.02640 1.0000
2 3 2 0.04699 0.19797 0.0000 0.02190 1.0000
2 4 3 0.05811 0.17632 0.0000 0.01870 1.0000
1 5 4 0.05403 0.22304 0.0000 0.02460 1.0000
2 5 5 0.05695 0.17388 0.0000 0.01700 1.0000
3 4 6 0.00000 0.17103 0.0000 0.01730 1.0000
4 5 7 0.00000 0.04211 0.0000 0.00640 1.0000
5 6 8 0.00000 0.25202 0.0000 0 0.9320
4 7 9 0.00000 0.20912 0.0000 0 0.9780
7 8 10 0.00000 0.17615 0.0000 0 1.0000
9 4 11 0.00000 0.55618 0.0000 0 0.9690
7 9 12 0.00000 0.11001 0.0000 0 1.0000
9 10 13 0.03181 0.08450 0.0000 0 1.0000
6 11 14 0.09498 0.19890 0.0000 0 1.0000
6 12 15 0.12291 0.25581 0.0000 0 1.0000
6 13 16 0.06615 0.13027 0.0000 0 1.0000
9 14 17 0.12711 0.27038 0.0000 0 1.0000
10 11 18 0.82050 0.19207 0.0000 0 1.0000
12 13 19 0.22092 0.19988 0.0000 0 1.0000
13 14 20 0.17093 0.34802 0.0000 0 1.0000
tap-controlled tap-min tap-max
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
1 0.9 1.2
1 0.9 1.2
0 1 1
1 0.9 1.2
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
0 1 1
Maxflow