FUNCTIONS AND FEATURES
SE Electronic Molded Case Circuit Breaker

Technical Parameters

SE-100 SE-250 SE-400 SE-630 SE-800


Rated voltage Ue (V) 400 400 400 400 400
Rated insulation voltage Ui (V) 800 800 800 800 800
Rated impulse withstand voltageUimp (KV) 8 8 8 8 8
Rated current In (A) 100 250 400 630 800
Number of poles 3 3 3 3 3
C C D D D
Rated ultimate short circuit
50HZ AC 400V 35 35 50 50 50
breaking capacity Icu kA
Rated operating short circuit
50HZ AC 400V 75% 75% 75% 75% 75%
breaking capacity Ics kA
Mechanical life Mechanical without maintenance 8500 7000 4000 2500 2500
Electrical life AC 400V 1500 1000 1000 500 500
Tripping ways Electronic tripping ů ů ů ů ů

Installation mode Fixed front connection ů ů ů ů ů

Fixed rear connection ů ů ů ů ů

Product accessories Undervoltage release ů ů ů ů ů

Shunt release ů ů ů ů ů

Alarm contact ů ů ů ů ů

Auxiliary contacts ů ů ů ů ů

Extension terminal ů ů ů ů ů

AC Motor ů ů ů ů ů

Round extended handle ů ů ů ů ů

Square extended handle ů ů ů ů ů

Phase partition ů ů ů ů ů

Use class Class A Class A Class A Class A Class A


"DQSHƥB@SHNM TUV CE TUV CE TUV CE TUV CE TUV CE

(*)
: Available

42
MCcB
FUNCTIONS AND FEATURES
SE Electronic Molded Case Circuit Breaker

Trip unit function

» Flexible setting: offer three section protection function, including long delay, short-time delay, instantaneous

protection, realize the action currents and action time adjustable, the user can set the trip module according

to the load current requirements

» Design patent: current transformer design, it can judge effectively even the current reaches a high value

» Instantaneous trip design: trip the large short circuit current, and also improve the action reliability

» Load monitoring: electronic tripping device configured load indicator lamp, can indicate the actual load

status during operation accurately

» Fault indication: when the hardware of electronic trip fault, the indication light; during the normal operation,

the indicator will flicker as a frequency of 50Hz, every 0.5 seconds for 1 bright

SE Electronic Molded Case Circuit Breaker

Intelligent controller funtion

Rated Current (A) In Frame 100/250 Frame 400/630/800

Overload Protection (long delay)

Tripping Current(A) Ir=In x 0.4/0.5/0.6/0.7/0.8/0.9/0.95/1 0.4/0.5/0.6/0.7/0.75/0.8/0.85/0.9/0.95/1

Delay time (S) Tr 0.5/1/2/4+OFF 0.5/1/2/4/8/12/16+OFF

Short-Circuit Protection (short delay)

Tripping Current(A) Isd=Ir x 2/2.5/3/3.5/4/5/6/7/8/10 2/2.5/3/3.5/4/5/6/7/8/10

Delay time Tsd 0.1/0.2/0.3/0.4+0/0.1/0.2/0.3 0.1/0.2/0.3/0.4+0/0.1/0.2/0.3/0.4+OFF


/0.4+OFF

Short-Circuit Protection (instantaneous)

Tripping Current(A) Ii=In x 2/4/6/8/10In+OFF 2/4/6/8/10/12In+OFF

Isolation Function

SE series product has isloation protection function. The operation handle can indicate “OFF”

position only when the contact is really opened.

43
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker

List of accessories

7
1 2

9
8

6 10

11

5 4 3

1 Extension terminal 7 Under voltage release


2 Interphase barriers 8 Leakage alarm contact
3 Electric motor 9 Fixed Rear Connection

4 Round handle 10 Alarm contact

5 Square handle 11 Auxilary contact

6 Shunt release

44
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker

Electrical Accessories

Auxiliary contact and alarm contact

Auxiliary contact:

An accessory connected in the auxiliary circuit of the switching device to indicate the circuit

breaker status of ON or OFF or Trip.

Alarm contact:

An accessory used to indicate the circuit breaker status of ON or OFF or Trip. When the alarm

contact indicates that the circuit breaker is at Trip status, there are the following five possibilities:

» Overload or short circuit fault

» Residual current fault

» Manual test button trip

» Shunt release action

» Line fault and undervoltage release action

Electrical wiring diagram

Circuit Breaker ON OFF/Trip

Auxiliary F12 F12


F11 F11
F14 F14

Alarm B12
B11 B14 B11
B14

Electrical parameters of auxiliary alarm contact


Conventional Thermal Current 3A
Thermal Current Use class (IEC/EN 60947-2) AC 15 / DC 13
Working electricity 50Hz / AC 400V 0.3A
electricty 50HZ / DC 220V 0.15

45
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker

Electrical Accessories

Shunt release

» The shunt release shall reliably trip the circuit breaker at the voltage between 70% and 110% of the rated

control power voltage U

» The circuit breaker shall be reset on the spot after tripping through the shunt release.

Undervoltage release

» The undervoltage release shall reliably trip the circuit breaker at the voltage between 35% and 70% of

the rated operational voltage

» The undervoltage release shall ensure that the circuit breaker can be switched on at the voltage between

85% and 110% of the rated operational voltage

» The undervoltage release shall prevent the circuit breaker from switching on when voltage is below 35%

of the rated operational voltage

Undervoltage Release Wiring

Ue

Electric Motor

» Provide on-site and remote distance control circuit breaker to implement switch-on and switch-off

46
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker

Mechanical Accessories

Interphase barriers

The interphase barriers can enhance the insulating performances of the conductors between the phases.

They can be installed from the front slot even after the switch is installed.

Standard offer 2pcs (3P)

Extension terminals

Easy to install and connect the products in the Rear Connection

Handle operating mechanism

Extended Rotary Handle

» Function: indication of the three positions of switch-on, switch-off and trip

» Residual earth-leakage fault. The circuit breaker cannot switch-on when the switch board door is open

» The door cannot be opened if the circuit breaker is ON

» An extension shaft that can be adjusted to the distance between the back of circuit breaker and door, the

specific distance refers to the dimensions at the rear and the installation part

» The OFF-Position of the circuit breaker can hang 1-3 locks with the diameter of 5mm

47
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker

100/250AF Installation Dimension


M8*16

65

35.5
47
127
165

Chart of fixed front connection


installation hole 23.5
Remark: X-X, Y-Y is the center of
3-pole circuit breaker
48.5
35
400AF Installation Dimension 107
85.5
89.5
97
M10*45 112
Installation dimension of fixed 114.5
54.5 54.5
105

front connection
43
26.5

Chart of fixed front connection


installation hole
Remark: X-X, Y-Y is the center of
3-pole circuit breaker
257
215

38.5
97.5
44
100
140 114
146

48
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker

630/800AF Installation Dimension

M12*40

70

104.5
70.5
55.5
243
280

Remark: X-X, Y-Y is the center of


3-pole circuit breaker

35.5

97.5
100
70 70
114
210
146

Safety Distance
Circuit Breaker A B B1 C

SE-100 60 60 30
Legnth of
SE-250 60 60 30
Exposed
SE-400 110 110 70
Conductor +B
SE-630 110 110 70

SE-800 110 110 70


Remark: no matter whether the products have the accessories,
the distance between the products must meet the requirements
of C distance.

49
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker

Extension Rotary Handle Base Dimension


*

Circuit Breaker C D E H K

SE-100 35 71.5 71.5 56 20

SE-250 35 71.5 71.5 56 20

SE-400 44 107.5 107.5 76 20

SE-630 70 121.5 121.5 76 20

SE-800 70 121.5 121.5 76 20


Remark: the shortest distance of G connecting rod is 50mm and
ex-factory standard configuration is 150mm, please contact the
factory if the special customization is required

Round

Square

SE-100/SE-250 SE-400/SE-630/
SE-800

50
MCcB
TRIPPING CURVES
SE Electronic Molded Case Circuit Breaker

Tripping characteristics

SE-100/SE-250
10000

5000
I=
R 100~ 250 0.4~1.0 In
2000

1000

500

200
T=
R (0.5~4)s
100

50

20
10
t(s)
5

1.5
Isd=(2~10)Ir
I2tON
1
0.5 0.4s
0.3s
0.2 0.2s
0.1
I2tOFF 0.1s
0s
0.05
Ii=(2~10)ln
0.02
0.01
0.005

0.002
0.2 0.30 .4 0.60 .8 1 24 68 10 20 34 68 10 20 30

IR In

SE-400
10000

5000
I=
R 160~400= 0.4~1.0 In
2000

1000

500

200
100
T=
R (0.5~16) s

50

20
10
t(s)
5

1.5 2
Isd=(2~10)Ir I tON
1
0.5 0.4s
0.3s
0.2 2 0.2s
0.1
I tOFF 0.1s
0s
0.05
Ii=(2~12)ln
0.02
0.01
0.005

0.002
0.2 0.30 .4 0.60 .8 1 23 46 8 10 20 34 68 10 20 30

IR In

51
MCcB
TRIPPING CURVES
SE Electronic Molded Case Circuit Breaker

Tripping characteristics

SE-630/SE-800
10000

5000
I=
R 320~ 800= 0.4 ~1.0 In
2000

1000

500

200
100
T=R (0.5~16) s
50

20
10
(s)
t
5

1.5 2
Isd=(2~10)Ir It ON
1
0.5 0.4s
0.3s
0.2 0.2s
0.1
It2 OFF 0.1s
0s
0.05
Ii =(2~12)l n
0.02
0.01
0.005

0.002
0.2 0.30 .4 0.60 .8 1 23 46 8 10 20 34 68 10 20 30

IR In

SELECTION GUIDE
SE Molded Case Circuit Breaker

Ordering codes

Frame Rated Current Ordering Codes


35KA 50KA
Frame 100A 100 A SE100C1003FF -

Frame 250A 250 A SE250C2503FF -

Frame 400A 400 A - SE400D4003FF

Frame 630A 630 A - SE630D6303FF

Frame 800A 800 A SE800D8003FF

52
MCcB
CERTIFICATIONS
SE 100

SE 630

SE 800

53
55
ACB
RANGE OF PRODUCTS
SA Air Circuit Breaker

ACB,, Frame
e 2000A,, Fixed ACB
B , F rame
e 3200A, Fixed

FUNCTIONS AND FEATURES


SA Air Circuit Breaker

Technical Parameters

SA-2000 SA-3200
Rated voltage Ue (V) 400 400
Rated insulation voltage Ui (V) 800 800
Rated impulse withstand voltage Uimp (KV) 8 8
Rated current In (A) 1000--2000 2000--3200
Number of poles 3, 4 3, 4
T T
Rated ultimate short circuit
50/60HZ AC 400V 80 80
breaking capacity Icu kA
Rated operating short circuit
50/60HZ AC 400V 50 80
breaking capacity Ics kA
Rated Short-Time withstand
50/60HZ AC 400V 50 65
current lcw (kA/1s)
Mechanical life Mechanical with maintenance 10000 8000
Mechanical without maintenance 2500 2500
Electrical life Electrical with maintenance 1000 1000
Electrical without maintenance 500 500

54
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker

Function Information

ECW-L

Protection Use
Long time delay L Protect cable, prevent ageing

Short time delay S Protect equipment, prevent impedance short circuit

Instantaneous I Protect equipment, prevent metallicity short circuit

Earthing G /QDUDMSƥQD

Protection Characteristics Setting range

Protection Characteristics for Overload Delay

Action current IR (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0) In+OFF

Delay time tL 30s, 60s, 120s, 240s

Protection Characteristics for Short-Delay Short Circuit

Action current Isd (3, 4, 5, 6, 7, 8, 10) In+OFF

Delay time ts 0.2s, 0.4s

Protection Characteristics for Instantaneous Short Circuit

Action current Ii (10, 11, 12, 14, 16, 18, 20) In+OFF (Frame 2000A)

(7, 8, 9, 10, 11, 12, 14) In+OFF (Frame 3200A)

Earthing protection

Action current Ig (0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8) In+OFF

Action current tG 0.1s, 0.2s, 0.3s, 0.4s

55
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker

Function Information

ECW-M
Protection Use

Long time delay L Protect cable, prevent ageing

Short time delay S Protect equipment, prevent impedance short circuit

Instantaneous I Protect equipment, prevent metallicity short circuit

Earthing G /QDUDMSƥQD

Measure
Current measurement

Voltage measurement
Miscellaneous function
Pre-alarm Fault log

Self-diagnosis function Test function

Protection Characteristics Setting range

Protection Characteristics for Overload Delay


Action current IR (0.4~1.0) In + OFF (>>100A)

Delay time tL Fault current Delay time


tR 15 30 60 120 240 480
1.5xIR 15 30 60 120 240 480
2xIR 8.4 16.9 33.8 67.5 135 270
7.2xIR 0.65 1.3 2.6 5.2 10.4 20.8

t=(1.5/N)2xtR
N=Fault current divided by the setting current I/IR
t=Delay Time of Failure Action
tR=Setting Value of Long-Delay Time

56
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker

Function Information

ECW-M
Protection Characteristics for Short-Delay Short Circuit
Action current Isd  ](M
.%%2SDORDSSHMFJ ADKNVơ J @ANUDơ

Action time tS Inverse time Limit I2T


Fault current Delay time
ts(s) 60 120 240 480
2
I T: OFF Min.delay(ms) 60 120 240 480
Max.delay 33.8 67.5 135 270
2
I T: ON Min.delay 2.6 5.2 10.4 20.8
I>8IR Max.delay 140 240 345 460
2
I T: ON Inverse time limit delay t=(8IR)2/I2×ts
(ơ(R

Protection Characteristics for Instantaneous Short Circuit

SA-2000 SA-3200
Action current Ii 2.0In~50kA+OFF 2.0In~75kA+OFF

Measure
Action current Ig (0.2~1.0)In+OFF

Action current tG 0.1s, 0.2s, 0.3s, 0.4s, OFF

57
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker

Function Information

ECW-H
Protection Use

Long time delay L Protect cable, prevent ageing

Short time delay S Protect equipment, prevent impedance short circuit

Instantaneous I Protect equipment, prevent metallicity short circuit

Earthing G /QDUDMSƥQD

Measure
Current measurement Power measurement

Voltage measurement Harmonic wave measurement


Miscellaneous function
Pre-alarm Fault log

Self-diagnosis function Test function

Communication function

Protection Characteristics Setting range

Protection Characteristics for Overload long time delay


Action current IR OFF+0.4~1.0In

Protection curve SI: Standard inverse time limit

Type selection VI: Rapid inverse time limit

EI(G): Express inverse time limit (distribution)

EI(M): Express inverse time limit (electromotor)

HV: High-Pressure Welding Fuse Compatibility

I2t: Universal inverse time limit protection

Setting delay time C01~C16

58
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker

Function Information

ECW-H
Protection Characteristics for Short Delay
Action Current of Inverse
Time Limit Is OFF+(0.4~15)In

Action Current of Fixed Time


OFF+(0.4~15)In
Limit Isd

Delay Time of Fixed Time


Limit tsd (0.1~0.4s)

Instantaneous protection Characteristics

SA-2000 SA-3200
Action current Ii 2.0In~50kA+OFF 2.0In~75kA+OFF

Earthing protection Characteristics


Action current Ig (0.2~1.0)In+OFF

Inverse time limit 1.5~6, +OFF


VKHDULQJFRHƫFLHQW&U

Delay time tg (0.1~0.4)s

59
ACB
ACCESSORIES
SA Air Circuit Breaker

List of accessories

8
9

10
6

16

5 15

3 14

13

12

1
11

1 Veil 6 DC power supply module 11 Undervoltage delayrelease

2 Door frame 7 N-phased transformer 12 Auxiliary contact

3 Key lock 8 Cable mechanical interlock 13 Motor mechanism

4 Power supply module 9 Mechanical interlock rod 14 Undervoltage release

5 Relay module 10 Phase barrier 15 Shunt close release

16 Shunt open release

60
ACB
ACCESSORIES
SA Air Circuit Breaker

List of accessories

Shunt open release

When the breaker is stored, under prescriptive voltage, through long-distance remote

control operation, let the breaker break

Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.7-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <30ms

Undervoltage release and undervoltage delay release

The undervoltage release automatically opens a circuit breaker when voltage drops

to a value ranging between 35% to 70% of the line voltage. after tripping,the

circuit breaker cannot be re-closed again when the voltage lowers than 35% or until

returns to 85% of line voltage. Undervoltage relay release lets the breaker break in

1s-5s(adjustable)

Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.7-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <30ms

Shunt close release

When the breaker is stored, under prescriptive voltage, through long-distance remote

control operation, let the breaker close

Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.85-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <70ms

61
ACB
ACCESSORIES
SA Air Circuit Breaker

List of accessories

Motor mechanism

When the breaker is under breaking and power supply, motor mechanism is automatic

stored. So under shunt release, undervoltage and closing release, let the breaker break

and close

Accessory parameter
Rated control voltage V 230VAC 400VAC 220VDC
Action voltage (0.85-1.1)Us
Consumption 192VA(AC) 192W(DC)
Energy storage time <5s

Auxiliary contact

It is used for keeping watch on the breaker’s status, connecting position signal light

and breaking indicator light

Accessory parameter
Utilization category AC-15 DC13
Auxiliary contact default type 5NO 5NC (4NO 4NC for 1000AF)
Conventional thermal current Ith 6A
Auxiliary contact’s energized Equal to circuit breaker operation
operational performance performance
Making & Under I/Ie making 10 1
breaking normal I/Ie breaking 1 1
capacity conditions U/Ue 1 1
cosø or T0.95 0.3 6Pe*

Under U/Ue 10 1.1


abnormal I/Ie 1 1.1
conditions cosø or T0.95 1 1
Operation cycles 10 10

62
ACB
ACCESSORIES
SA Air Circuit Breaker

List of accessories

Keylock

When the breaker is breaking, it could be lock in.

It is divided into three types: one lock and one key, two locks and one key, three

locks and two keys

Cable Mechanical Interlock

It could connect two or three breakers to be linkage.

*Note: The Max Horizonal installation distance is 2M.

Mechanical interlock rod

It could connect two breakers to be linkage,one of the breakers is closing,

the other is breaking

*Note: Only for Vertical intallation, and the Max installation distance is 0.9M

Phase Barrier

Install in the middle of the breaker busbar, increase creepage distance, prevent to

engender electric arc

63
ACB
WIRING DIAGRAM
SA Air Circuit Breaker

L - Type and M - Type intelligent controller

UV SO SC

Energy
storage

Main Auxiliary Shunt Shunt Energy


current Intelligent controller contact
Undervoltage
open close stored
indication
Motor Auxiliary contact

Pin function:
» #1 and #2: auxiliary supply input terminal (#1 for positive terminal when being DC)
» #3, #4 and #5: contact output of tripping fault (#4 refers to shared terminal);
contact capacity: 16A @380VAC
» #6, #7, #8 and #9: two groups of auxiliary terminals with circuit breaker status;
contact capacity: 16A @380VAC
» #20 PE wire, protection earthing wire
» #25, #26: output for circumscribed transformer

Remarks
» #27 and #28 of undervoltage release UV connect to main circuit.
» UV, SO, SC and Motor can be connected with different control voltage, Auxiliary contact is 5a5b, Shunt
open and close have been tandem connected with NO & NC auxiliary contact in the factory.
» #35 can be connected to the power supply directly (automatic pre-storing energy), also to the power
supply after adopting tandem connection with normal open button (manual pre-storing energy).
» #6 & #7 can output normal close contacts, if the users put forward.
» Power module 1 is DC Power module, and there is no such module when the power AC power supply. The
input & output terminals cannot be connected reversely.
» The auxiliary contact is 5 open and 5 close, #25 & #26 are circumscribed transformer, applied for (3P+N)
T type earthing failure protection.

Components:
UV: undervoltage, SO: Shunt open, SC: Shunt closes, AUX: auxiliary contact, M: Motor,
SB1: Make button, SB2: Shunt button

64
ACB
INSTALLATION DIMENSIONS
SA Air Circuit Breaker

2000AF Overall dimensions

65
ACB
INSTALLATION DIMENSIONS
SA Air Circuit Breaker

3200AF Overall dimensions

66
ACB
SELECTION GUIDE
S Molded Case Circuit Breaker

Ordering codes

Frame Rated Current Icu Ordering Codes


Frame 2000 1000 A 80 KA SA02KT10K3FH

1250 A 80 KA SA02KT12K3FH

1600 A 80 KA SA02KT16K3FH

2000 A 80 KA SA02KT02K3FH

Frame 3200 2000 A 80 KA SA32KT02K3FH

2250 A 80 KA SA32KT25K3FH

3200 A 80 KA SA32KT32K3FH

67
ACB
CERTIFICATIONS
ACB SA

68
Contactors

PRODUCT DETAILS
SC 9A~95A Contactor

IEC 60947-4-1

With the new generation of technical platform and automated production and testing equipment, the brand new SC9~95
LNSNQBNMSQNK@MCOQNSDBSHNMOQNCTBSRDƤDBSHUDKXƥSSGD@BST@KBTRSNLDQ@OOKHB@SHNMMDDCR ADBNLHMFOQNCTBSRVHSG
convenient use and international leading quality.
The series include three major categories, namely SC9~95 contactor, SO-93 thermal overload relay and their accessories.

SC contactor: 9-95A SCHPCs transparent dust cover, AXF top auxiliary contact, AXS side CB,CE, SEMKO

auxiliary contact, TD6 air delayed head and L4 mechanical in

SO thermal overload relay independent mounting base CB,CE, SEMKO

NORMAL INST
TALLA
ATION AND
D OPERATION CONDITIONS

Installation position:
Ş3GDHMRS@KK@SHNMRHSDRG@KKADUDQSHB@K VHSGHMBKHM@SHNM@S@KKCHQDBSHNMRMNSDWBDDCHMFo Ť
2.NEMNFQD@SDQSG@MŤHMRS@KK@SHNM"K@RR(KK
• Pollution class: Class 3

Ambient temperature:
• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC
Ş2SNQ@FDSDLODQ@STQD Ť"
Ť" TOSN
x"VHSGHM@RGNQSSHLDG

Altitude:
• Altitude at normal installation position does not exceed 2000m

Humidity:
Ş3GD@SLNROGDQHBQDK@SHUDGTLHCHSXCNDRMNSDWBDDCVGDMSGDGHFGDRS@LAHDMSSDLODQ@STQDHR
Ť" (SHR@KKNVDC
SNG@UD@QDK@SHUDGHFGDQGTLHCHSXTMCDQKNVDQSDLODQ@STQD D F TOSN@S
Ť"

Product protection grade: IP20

69
Contactors

FUNCTIONS AND FEATURES


SC 9A-95A Contactor

Main Technical Parameters of SC

Contactor Model SC09 SC12 SC18 SC25 SC32 SC38 SC40 SC50 SC65 SC80 SC95
Main Circuit Characteristics
Number of Poles 3
Rated Insulation Voltage (Ui) V 690
Rated Operational Voltage (Ue) V 690
Conventional Thermal Current 20 20 25 32 40 40 50 60 80 110 110
AC-3, 380/400V A 9 12 18 25 32 38 40 50 65 80 95
Conventional
Operational AC-3, 660/690V A 6.6 8.9 12.0 18.0 22.0 22.0 34.0 39.0 42.0 49.0 49.0
Current (Ie) AC-4, 380/400V A 3.5 5.0 7.7 8.5 12.0 14.0 18.5 24.0 28.0 37.0 44.0
AC-4, 660/690V A 1.5 2.0 3.8 4.4 7.5 8.9 9.0 12.0 14.0 17.3 21.3
AC-3, 380/400V KW 4.0 5.5 7.5 11.0 15.0 18.5 18.5 22.0 30.0 37.0 45.0
Conventional
Operating AC-3, 660/690V KW 5.5 7.5 10.0 15.0 18.5 18.5 30.0 33.0 37.0 45.0 45.0
Power (Pe) AC-4, 380/400V KW 2.2 3.0 4.0 5.5 7.5 7.5 7.5 11.0 15.0 18.5 22.0
AC-4, 660/690V KW 1.1 1.5 3.7 4.0 5.5 7.5 7.5 11.0 11.0 15.0 18.5
Mechanical Durabilities 10,000 times 1200 1000 900 650
Electrical AC-3 10,000 times 110 90 65
Durabilities AC-4 22 22 17 11
10,000 times
Operation AC-3 Time/Hour 1200 600
Frequency AC-4 Time/Hour 300 300
Coil
Rated control 50 Hz V 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440
circuit voltage (Us) 50/60 Hz V 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440

Allowable Control Operation V 85% ~ 110% Us


circuit voltage (Us) Drop out 20% ~ 75% Us
V
Coil Power Inrush VA 60 70 200
Sealed VA 6~9.5 6~9.5 15~20
Heat Dissipation W 1~3 1~3 6~10
Main circuit terminal wiring capability
Flexible wire 1 Wire mmƵ 1...4 1.5...6 2.5...25 4...50
without terminal 2 Wire mmƵ 1...4 1.5...6 2.5...16 4...25
Flexible wire 1 Wire mmƵ 1...4 1...6 2.5...25 4...50
with terminal 2 Wire mmƵ 1...2.5 1...4 2.5...10 4...16

Fixed wire 1 Wire mmƵ 1...4 1.5...6 1.5...10 2.5...25 4...50


without terminal 2 Wire mmƵ 1...4 1.5...6 1.5...6 2.5...10 4...25

Certificates CB, CE, SEMKO

70
Contactors

FUNCTIONS AND FEATURES


Wiring Diagram

SC09 ~SC95

SC09 ~ SC38

SC40 ~ SC95

Wiring digram for star-delta starter

71
Contactors

FUNCTIONS AND FEATURES


SC Schematic diagram of accessories

SC09~SC38

72
Contactors

SELECTION GUIDE
SC Contactors

Ratings & References

Motor Power Pe Rated Current Auxiliary Contacts Ordering Codes


KW, AC-3, 380V Ie (A) NO NC

4 KW 9A 1 0 SC009M5310

0 1 SC009M5301

5.5 KW 12 A 1 0 SC012M5310

0 1 SC012M5301

7.5 KW 18 A 1 0 SC018M5310

0 1 SC018M5301

11 KW 25A 1 0 SC025M5310

0 1 SC025M5301

15 KW 32 A 1 0 SC032M5310

0 1 SC032M5301

18.5 KW 38 A 1 0 SC038M5310

18.5 KW 40 A 1 1 SC040M5311

22 KW 50 A 1 1 SC050M5311

30 KW 65 A 1 1 SC065M5311

37 KW 80 A 1 1 SC080M5311

45 KW 95 A 1 1 SC095M5311

Note: Only 3 Poles are available

Product Name Rated Current Coil Voltage Coil Frequency Poles Auxiliary Contacts
SC 09 M 5 3 10

09 : 09 A B : 24 V 5 : 50 Hz 3 10 : 1NO+0NC
... ... ... 01 : 0NO+1NC
95 : 95 A M : 220V/230V 7: 50/60 Hz 11 : 1NO+1NC
...
Q : 380V/400V

73
Contactors

INSTALLATION DIMENSION

Model Amax Bmax B1max B2max Cmax C1max C2max


SC 09, 12, 18 74.5 45.5 58 71 82.5 114.5 139.5
SC 25, 32, 38 83 56.5 69 82 97 129 154
SC 40, 50, 65 127.5 74.5 88 101 117 148.5 173.5
SC 80, 95 127.5 85.5 99 112 125.5 157 182

Model a b c d e f
SC 09, 12, 18 35 50/60 - - - -
SC 25, 32, 38 40 50/60 - - - -
SC 40, 50, 65 - - 105 40 100/110 59
SC 80, 95 - - 105 40 100/110 67

74
Contactors

FUNCTIONS AND FEATURES


SC 115A~630A Contactor

Main Technical Parameters of SC

Contactor Model SC115 SC150 SC185 SC225 SC265 SC330 SC400 SC500 SC630
Main Circuit Characteristics
Number of Poles 3
Rated Insulation Voltage (Ui) V 1000
Rated Operational Voltage (Ue) V 690
AC-3, 380/400V A 115 150 185 225 265 330 400 500 360
Conventional
Operational AC-4, 380/400V A 52 60 79 85 105 117 138 147 188
Current (Ie) AC-1, 380/400V A 200 250 275 315 350 400 500 630 800

Conventional AC-3, 220/240V KW 30 40 55 63 75 100 110 147 200


Operating AC-3, 380/400V KW 55 75 90 110 132 160 200 250 335
Power (Pe) AC-4, 415/440V KW 59 80 100 110 140 180 220 280 375
AC-4, 660/690V KW 80 100 110 129 160 220 280 335 450
Mechanical Durabilities 10,000 times 1000 1000 600 600 600 600 600 600 600
Electrical Durabilities 10,000 times 120 120 100 100 80 80 80 80 80
Operation Frequency Time/Hour 600 600 600 600 600 600 300 300 300
Coil
Rated control 50 Hz 110V, 127V, 220V, 230V, 240V, 380V, 400V, 440V
circuit voltage (Us) 50/60 Hz 110V, 220V, 380V (115-225 AF)

Allowable Control Operation 85%~110% Us


circuit voltage (Us) Drop out 20%~75% Us
Coil Power Inrush VA 550 800 1200 1200 1250 1650
Sealed VA 45 55 13 20 24 22
Heat Dissipation W 16 24 12 14 18 20
Main circuit terminal wiring capability
Flexible wire 1 pc section mmƵ 95 120 150 185 240 240 - - -
without terminal 2 pc section mmƵ - - - - - - 150 240 -
Copper Bar 2 pc section mmƵ 20*3 25*3 25*3 32*4 32*3 30*5 30*5 40*5 60*5

Certificates CB, CE, SEMKO

75
Contactors

WIRING DIAGRAM
SC 115A~630A Contactor

Wiring Diagram for Star-Delta Starter

76
Contactors

FUNCTIONS AND FEATURES


SC Schematic diagram of accessories

SC 115A-630A Contactor

77
Contactors

FUNCTIONS AND FEATURES


SC accessories

SC 115A-630A Contactor
Auxiliary Contact
Installation Position Poles Composition Contact Point Layout Ordering Codes
NO NC

2 0 2 AXF6 02

1 1 AXF6 11

2 0 AXF6 20

Top 4 0 4 AXF6 04

1 3 AXF6 13

2 2 AXF6 22

3 1 AXF6 31

4 0 AXF6 40

2 0 2 AXF6 02

Side 1 1 AXF6 11

2 0 AXF6 20

TD6 Air Delayed Head


Installation Position Dealy Type Wiring Diagram Delay Range Ordering Codes

0.1-3s TD6 20
Making
0.1-30s TD6 22
type delay
10-180s TD6 24
Top

Breaking 0.1-3s TD6 30

type delay 0.1-30s TD6 32

10-180s TD6 34

78
Contactors

FUNCTIONS AND FEATURES


SC accessories

SC 115A-630A Contactor
Mechanical Interlock
Interlock Type Contactor Type Ordering Codes

SC-115~150 L6 FFH
SC-185~225 L6 GGH
Mechanical Interlock
SC-265~330 L6 HHH
Without electrical interlock
SC-400~500 L6 KKH
SC-630 L6 LL H
* Note: For vertical interlock contact supplier

Coils
Contactor Type Coil Voltage Ordering Codes

SC-115~150 220V X6 150 M


380V X6 150 Q
SC-185~225 220V X6 250 M
380V X6 250 Q
SC-265~330 220V X6 330 M
380V X6 330 Q
SC-400 220V X6 400 M
380V X6 400 Q
SC-500 220V X6 500 M
380V X6 500 Q
SC-630 220V X6 630 M
380V X6 630 Q

79
Contactors

INSTALLATION DIMENSION
SC 115A~630A Contactor

Overall dimensions

SC-115~SC330

Model Amax Bmax Cmax P S Ø f M H L X1 X1 Ga Ha


(200-550V) (200-550V)

SC-115 167 163 172 37 20 M6 131 147 124 107 10 15 80 110~120


SC-150 167 171 172 40 20 M8 131 150 124 107 10 15 80 110~120
SC-185 171 174 183 40 20 M8 131 154 127 113.5 10 15 80 110~120
SC-225 171 197 183 48 25 M10 131 172 127 113.5 10 15 80 110~120
SC-265 202 203 215 48 25 M10 147 178 147 141 10 15 96 110~120
SC-330 213 206 220 48 25 M10 147 181 158 145 10 15 96 110~120

SC-400~SC500

SC-630

Model Amax Bmax Cmax P S Ø f M H L X1 X1 Ga Ha


(200-550V) (200-550V)

SC-400 213 206 220 48 25 M10 146 181 158 145 15 20 80 170~180
SC-500 223 233 233 55 30 M10 150 208 172 146 15 20 80 170~180
SC-630 309 304 256 80 40 M12 181 264 202 155 20 30 180 180~190
* Note: 'f' reserved space to ensure draw-out coil can take out easily

80
OVERLOAD RELAY

FUNCTIONS AND FEATURES


SO Thermal Overloads Relays

Main technical parameters

Temperature compensation -5Ƴ C ~ +40Ƴ C


Trip level 10A SO-25, SO-36
10 SO-93
Rated insulation voltage (Ui) V 660V
Product features

Overload protection YES


Phase failure protection YES
Manual reset YES
Automatic reset YES
Stop button YES
Test button YES
Trip indication YES
Tolerance on slope in any direction ±5Ƴ
Auxiliary circuit

Utilization category AC-15 DC-13


Rated frequency Hz 50 50
Rated insulation voltage (Ui) V 500 500 500
Rated operational voltage (Ue) V 230 230 230
Rated operational current (Ie) A 1.57 0.90 0.14
Conventional thermal current (Ith) A NO 5 5 5

NC 5 5 5

Product certification CB, CE, SEMKO

Base Name Reference

SO-25 SO25J

SO-36 SO36J

SO-93 SO93J

81
OVERLOAD RELAY

FUNCTIONS AND FEATURES


SO Thermal Overloads Relays

Trip Characteristics
Trip Characteristics for current balance
Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
1.05 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.2 Tripping within 2h Tripping within 2h After No.1 Test
1.5 <2 min <4 min After No.1 Test
7.2 R3OơR R3OơR Without Previous load +20Ƴ"

Trip Characteristics for current imbalance


Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
1.0 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.15 Tripping within 2h Tripping within 2h After No.1 Test

Trip Characteristics for Average Value (Environment temperature 20ƳC)

82
OVERLOAD RELAY

WIRING DIAGRAM
SO Thermal Overloads Relays

Installation wiring diagram

Fu-fuse.
KM-Contactor.
Fr-Thermal overload relay.
SB1-Stop button.
SB2-Start button.

83
OVERLOAD RELAY

SELECTION GUIDE
SO Thermal Overloads Relays

Ratings & References

Frame Rating Setting Current Suitable Contactor Ordering Codes


(A) (A) SC

25 0. 1-0.16 09-38 SOD16009T032

0.16-0.25 09-38 SOD25009T032

0.25-0.4 09-38 SO0D4009T032

0.4-0.63 09-38 SOD63009T032

0.63-1 09-38 SO001009T032

1-63-1 09-38 SO1D6009T032

1.6-2.5 09-38 SO2D5009T032

2.5-4 09-38 SO004009T032

4-6 09-38 SO006009T032

5.5-8 09-38 SO008009T032

7-10 09-38 SO010009T032

9-13 12-38 SO013012T032

12-18 18-38 SO018018T032

17-25 25-38 SO025025T032

36 23-32 25-32 SO032025T032

30-40 32-38 SO040032T032

93 23-32 40-95 SO032040T095

30-40 40-95 SO040040T095

37-50 50-95 SO050050T095

48-65 50-95 SO065050T095

55-70 65-95 SO070065T095

63-80 80-95 SO080080T095

80-93 95 SO093095T095

84
OVERLOAD RELAY

INSTALLATION DIMENSION
SO Thermal Overloads Relays

Overall dimensions

SO-25

SO-36

SO-93

85
OVERLOAD RELAY

SELECTION GUIDE
SO Thetrmal Overloads Relays

Ratings & References

Frame Rating Setting Current Suitable Contactor Ordering Codes


(A) (A) SC

65 48-65 SC 115~185 SO 065115T185

70 55-70 SC 115~185 SO 070115T185

80 63-80 SC 115~185 SO 080115T185

95 75-95 SC 115~185 SO 095115T185

115 90-115 SC 115~185 SO 115115T185

135 105-135 SC 115~185 SO 135115T185

150 120-150 SC 115~185 SO 150115T185

160 130-160 SC 115~185 SO 160115T185

185 150-185 SC 115~185 SO 185115T185

200 145-200 SC 225~630 SO 200115T630

250 180-250 SC 225~630 SO 250115T630

320 230-320 SC 225~630 SO 320115T630

400 290-400 SC 225~630 SO 400115T630

480 350-480 SC 225~630 SO 480115T630

630 460-630 SC 225~630 SO 630115T630

86
OVERLOAD RELAY

FUNCTIONS AND FEATURES


SO Thermal Overloads Relays

Trip Characteristics

Temperature Compensation -10 ƳC~+55 ƳC


Trip Class 10A SO 630/F
10 SO185
Frame Current SO185 48~185A
SO630/F 145~630A
Rates impulse withstand voltage (Uimp) 6kV
Overload Protection
Phase Failure Protection
Manual and Automatic Reset
Tripping Indication
Stop Button
Test Button
Installation Method Assembly/Independent: SO185
Independent: SO630/F

Trip Characteristics
Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
1.05 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.2 Tripping within 2h Tripping within 2h After No.1 Test
1.5 < 2 min < 4 min After No.1 Test
7.2 R3OơR R3OơR Without previous load +20ƳC

Trip Characteristics for Current Imbalance


Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
any 2 phase 3rd phase

1.0 0.9 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.15 0 Tripping within 2h Tripping within 2h After No.1 Test

87
OVERLOAD RELAY

FUNCTIONS AND FEATURES


SO Thermal Overloads Relays

Trip Characteristics

Trip Characteristics for Average Value (Environment temperature 20ƳC)

88
OVERLOAD RELAY

INSTALLATION DIMENSION
SO Thermal Overloads Relays

Overall Dimensions

Model A B C
SC-115 248 167 172
SC-150 253 167 172
SC-185 257 171 183

89
CAPACITOR CONTACTOR

SELECTION GUIDE
SK Capacitor Switching Contactor

Standard: IEC 60947-4-1 IEC 60947-5-1

Function: SK capacitor switching contactor provide:


ʑSwitch three-phase unipolar or multipolar capacitor group,to improve their power factor
ʑReduce the current closing of the impact of capacitor

Rate Conventional Thermal Current Auxiliary Contact Ordering Codes


(A) NO NC

25 1 1 SK12M 25300

2 0 SK12M 25300

0 2 SK12M 25300

32 1 1 SK18M 32300

2 0 SK18M 32300

0 2 SK18M 32300

43 1 1 SK20M 43300

2 0 SK20M 43300

0 2 SK20M 43300

63 1 2 SK30M 63300

2 1 SK30M 63300

95 1 2 SK45M 95300

2 1 SK45M 95300

90
CAPACITOR CONTACTOR

FUNCTION AND FEATURES


SK Capacitor Contactors

Main technical parameters

Contactor Model SK12M-25 SK18M-32 SK20M-43 SK30M-63 SK45M-95


Main Circuit Characteristics
Number of Poles 3
Rated Insulation Voltage (Ui) V 500
Rated Operational Voltage (Ue) V 400
AC-6b, 400V A 17 23 29 43 63
Controlled
capacitor rate AC-6b, 230V Kvar 6 9 10 15 22.5
capacity AC-6b, 400V Kvar 12 18 20 30 45
Rate Conventional thermal current A 25 32 43 63 95
Control inrush current capacity ơ(M ơ(M ơ(M ơ(M ơ(M
Mechanical Life 10,000 times 100 100 100 100 100
Electrical Life AC-6b, 400V 10,000 times 10 10 10 10 10
Operation Frequency Operations/h 300 300 300 300 120
Cable connection cross section mmƵ 4 4 4 4 4
of copper conductor

Coil
Coil Voltage V AC36, 110V, 127V, 220V, 380V, 400V
Operational Voltage V 85%~110% Us
Drop-out Voltage V 20%~75% Us
Auxiliary Contact
Rated conventional thermal current A 10

Minimum load can be connected 6V x 10mA

91
CAPACITOR CONTACTOR

WORKING CO
O N DII TIONS

Ambient temperature:
• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC
Ş2SNQ@FDSDLODQ@STQD Ť"
Ť" TOSN
x"VHSGHM@RGNQSSHLDG

Altitude: ơ2000m

Humidity:
Ş3GD@SLNROGDQHBQDK@SHUDGTLHCHSXCNDRMNSDWBDDCVGDMSGDGHFGDRS@LAHDMSSDLODQ@STQDHR
Ť" (SHR@KKNVDC
SNG@UD@QDK@SHUDGHFGDQGTLHCHSXTMCDQKNVDQSDLODQ@STQD D F TOSN@S
Ť"

• Pollution class: Class 3


• Installation type: III
• ,QVWDOODWLRQSRVLWLRQVKRXOGEHLQVWDOOHGLQWKHDEVHQFHRIDVLJQLƩFDQWVKDNHDQGVKRFNDQGYLEUDWLRQSODFH

92
MANUAL MOTOR STARTER

FUNCTION AND FEATURES


SS Motor Starter

Introduction for Functions

93
MANUAL MOTOR STARTER

FUNCTION AND FEATURES


SS Motor Starter

Main technical parameters

Operation mode Button operated


Frame current 32A
Rated impulse withstand voltage 6000 V
Rated operational voltage 690 V
Rated isolation voltage 690 V
Rated operational frequency 50/60 Hz
Trip class 10 A
Fastening torque 1.7 N.m
Mechanical durabilities 100000
Electrical durabilities AC-3 400V 100000
Overload protection category Phase failure, thermal overload
Short circuit protection Yes
Isolation function Yes
Temperature compensation function Yes

Setting Current Ue: 230/240 V Ue: 400/415 V Ue: 440 V Ue: 500 V Ue: 690 V
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

0.1 - 0.16 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

0.16 - 0.25 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

0.25 - 0.4 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

0.4 - 0.63 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

0.63 - 1 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

1 - 1.6 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA

1.6 - 2.5 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 3kA 2.25kA

2.5 - 4 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 3kA 2.25kA

4 - 6.3 A 100kA 100kA 100kA 100kA 50kA 50kA 50kA 50kA 3kA 2.25kA

6 - 10 A 100kA 100kA 100kA 100kA 15kA 15kA 10kA 10kA 3kA 2.25kA

9 - 14 A 100kA 100kA 15kA 7.5kA 8kA 4kA 6kA 4.5kA 3kA 2.25kA

13 - 18 A 100kA 100kA 15kA 7.5kA 8kA 4kA 6kA 4.5kA 3kA 2.25kA

17 - 23 A 50kA 50kA 15kA 6kA 6kA 3kA 4kA 3kA 3kA 2.25kA

20 - 25 A 50kA 50kA 15kA 6kA 6kA 3kA 4kA 3kA 3kA 2.25kA

24 - 32 A 50kA 50kA 10kA 5kA 6kA 3kA 4kA 3kA 3kA 2.25kA

94
MANUAL MOTOR STARTER

FUNCTION AND FEATURES


SS Motor Starter

Main technical parameters

3 Phase motor rated power, 50/60 Hz, AC-3


Setting Current Ue: 230/240 V Ue: 400/415 V Ue: 690 V
0.1 - 0.16 A - - -
0.16 - 0.25 A - 0.06kW -
0.25 - 0.4 A - 0.09kW -
0.4 - 0.63 A - 0.12kW 0.37kW
0.63 - 1 A - 0.25kW 0.55kW
1 - 1.6 A - 0.37kW 1.1kW
1.6 - 2.5 A 0.37kW 0.75kW 1.5kW
2.5 - 4 A 0.75kW 1.5kW 3kW
4 - 6.3 A 1.1kW 2.2kW 4kW
6 - 10 A 2.2kW 4kW 7.5kW
9 - 14 A 3kW 5.5kW 9kW
13 - 18 A 4kW 7.5kW 11kW
17 - 23 A 5.5kW 9kW 15kW
20 - 25 A 5.5kW 11kW 18.5kW
24 - 32 A 7.5kW 15kW 22kW

Multiples of Setting current Tripping Time Initial Condition Ambient Temp.


Trip Characteristics for phase load balance
1.05 Non-tripping within 2h Without previous load +20ƳC
1.2 Tripping within 2h Immediately after No.1 Test +20ƳC
1.5 < 2 min Immediately after No.1 Test +20ƳC
7.2 R3OơR Without previous load +20ƳC
Trip Characteristics for phase load unbalance (Phase failure)
any 2 phase 3rd phase

1.0 0.9 Non-tripping within 2h Without previous load +20ƳC


1.15 0 Tripping within 2h Immediately after No.1 Test +20ƳC

The temperature compensation performance


1.0 Non-tripping within 2h Without previous load +40ƳC
1.2 Tripping within 2h Immediately after No.1 Test +40ƳC
1.05 Non-tripping within 2h Without previous load -5ƳC
1.3 Tripping within 2h Immediately after No.3 Test -5ƳC

95
MANUAL MOTOR STARTER

FUNCTION AND FEATURES


SS Motor Starter

Main technical parameters

Wiring diagram

96
MANUAL MOTOR STARTER

SELECTION GUIDE
SS Motor Starter

Standard: IEC 60947-1 IEC 60947-2 IEC 60947-4-1

Thermal Release Magnetic Release Rated Operating Power Recommended Ordering Codes
Setting Current Current Id (A) (KW) Contactor

0.1 - 0.16 1.5 - SC-0911 SSD16100K

0.16 - 0.25 2.4 0.06 SC-0911 SSD25100K

0.25 - 0.4 5 0.09 SC-0911 SS0D4100K

0.4 - 0.63 8 0.12 SC-0911 SSD63100K

0.63 - 1 13 0.25 SC-0911 SS001100K

1 - 1.6 22.5 0.37 SC-0911 SS1D6100K

1.6 - 2.5 33.5 0.75 SC-0911 SS2D5100K

2.5 - 4 51 1.5 SC-0911 SS004100K

4 - 6.3 78 2.2 SC-0911 SS6D3100K

6 - 10 138 4 SC-0911 SS010100K

9 - 14 170 5.5 SC-1211 SS014015K

13 - 18 223 7.5 SC-1811 SS018015K

17 - 23 327 9 SC-2511 SS023015K

20 - 25 327 11 SC-2511 SS025015K

24 - 32 416 15 SC-3211 SS032010K

97
MANUAL MOTOR STARTER

SELECTION GUIDE
SS Motor Starter

Accessories

Name Type Specs Ordering Codes


Undervoltage Release HUV 110~127V SS-HAU110
220~240V SS-HAU220
380~400V SS-HAU380
415V SS-HAU415
Shunt Release HAS 110~127V SS-HAS110
220~240V SS-HAS220
380~400V SS-HAS380
415V SS-HAS415
Auxiliary Contact Top AE 2NO SS-HAE20
1NC+1NO SS-HAE11
Side AN 2NO SS-HAN20
1NC+1NO SS-HAN11
Waterproof Cover MC IP55 SS-HDP632MC

Installation of SS-HAE11 or SS-HAE20

1- Pry the top auxiliary protective cover up;

 /TSSGDƦ@SRTQE@BDNESGDSNO@TWHKH@QX
contact close to the circuit breaker

3- Align the installation position and insert it

98
MANUAL MOTOR STARTER

CERTIFICATIONS
Control Products

Extra High Voltage Research Center

99