MCcB
FUNCTIONS AND FEATURES
SE Electronic Molded Case Circuit Breaker
Technical Parameters
Shunt release ů ů ů ů ů
Alarm contact ů ů ů ů ů
Auxiliary contacts ů ů ů ů ů
Extension terminal ů ů ů ů ů
AC Motor ů ů ů ů ů
Phase partition ů ů ů ů ů
(*)
: Available
42
MCcB
FUNCTIONS AND FEATURES
SE Electronic Molded Case Circuit Breaker
» Flexible setting: offer three section protection function, including long delay, short-time delay, instantaneous
protection, realize the action currents and action time adjustable, the user can set the trip module according
» Design patent: current transformer design, it can judge effectively even the current reaches a high value
» Instantaneous trip design: trip the large short circuit current, and also improve the action reliability
» Load monitoring: electronic tripping device configured load indicator lamp, can indicate the actual load
» Fault indication: when the hardware of electronic trip fault, the indication light; during the normal operation,
the indicator will flicker as a frequency of 50Hz, every 0.5 seconds for 1 bright
Isolation Function
SE series product has isloation protection function. The operation handle can indicate “OFF”
43
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker
List of accessories
7
1 2
9
8
6 10
11
5 4 3
6 Shunt release
44
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker
Electrical Accessories
Auxiliary contact:
An accessory connected in the auxiliary circuit of the switching device to indicate the circuit
Alarm contact:
An accessory used to indicate the circuit breaker status of ON or OFF or Trip. When the alarm
contact indicates that the circuit breaker is at Trip status, there are the following five possibilities:
Alarm B12
B11 B14 B11
B14
45
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker
Electrical Accessories
Shunt release
» The shunt release shall reliably trip the circuit breaker at the voltage between 70% and 110% of the rated
» The circuit breaker shall be reset on the spot after tripping through the shunt release.
Undervoltage release
» The undervoltage release shall reliably trip the circuit breaker at the voltage between 35% and 70% of
» The undervoltage release shall ensure that the circuit breaker can be switched on at the voltage between
» The undervoltage release shall prevent the circuit breaker from switching on when voltage is below 35%
Ue
Electric Motor
» Provide on-site and remote distance control circuit breaker to implement switch-on and switch-off
46
MCcB
ACCESSORIES
SE Electronic Molded Case Circuit Breaker
Mechanical Accessories
Interphase barriers
The interphase barriers can enhance the insulating performances of the conductors between the phases.
They can be installed from the front slot even after the switch is installed.
Extension terminals
» Residual earth-leakage fault. The circuit breaker cannot switch-on when the switch board door is open
» An extension shaft that can be adjusted to the distance between the back of circuit breaker and door, the
specific distance refers to the dimensions at the rear and the installation part
» The OFF-Position of the circuit breaker can hang 1-3 locks with the diameter of 5mm
47
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker
65
35.5
47
127
165
front connection
43
26.5
38.5
97.5
44
100
140 114
146
48
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker
M12*40
70
104.5
70.5
55.5
243
280
35.5
97.5
100
70 70
114
210
146
Safety Distance
Circuit Breaker A B B1 C
SE-100 60 60 30
Legnth of
SE-250 60 60 30
Exposed
SE-400 110 110 70
Conductor +B
SE-630 110 110 70
49
MCcB
INSTALLATION DIMENSIONS
SE Electronic Molded Case Circuit Breaker
Circuit Breaker C D E H K
Round
Square
SE-100/SE-250 SE-400/SE-630/
SE-800
50
MCcB
TRIPPING CURVES
SE Electronic Molded Case Circuit Breaker
Tripping characteristics
SE-100/SE-250
10000
5000
I=
R 100~ 250 0.4~1.0 In
2000
1000
500
200
T=
R (0.5~4)s
100
50
20
10
t(s)
5
1.5
Isd=(2~10)Ir
I2tON
1
0.5 0.4s
0.3s
0.2 0.2s
0.1
I2tOFF 0.1s
0s
0.05
Ii=(2~10)ln
0.02
0.01
0.005
0.002
0.2 0.30 .4 0.60 .8 1 24 68 10 20 34 68 10 20 30
IR In
SE-400
10000
5000
I=
R 160~400= 0.4~1.0 In
2000
1000
500
200
100
T=
R (0.5~16) s
50
20
10
t(s)
5
1.5 2
Isd=(2~10)Ir I tON
1
0.5 0.4s
0.3s
0.2 2 0.2s
0.1
I tOFF 0.1s
0s
0.05
Ii=(2~12)ln
0.02
0.01
0.005
0.002
0.2 0.30 .4 0.60 .8 1 23 46 8 10 20 34 68 10 20 30
IR In
51
MCcB
TRIPPING CURVES
SE Electronic Molded Case Circuit Breaker
Tripping characteristics
SE-630/SE-800
10000
5000
I=
R 320~ 800= 0.4 ~1.0 In
2000
1000
500
200
100
T=R (0.5~16) s
50
20
10
(s)
t
5
1.5 2
Isd=(2~10)Ir It ON
1
0.5 0.4s
0.3s
0.2 0.2s
0.1
It2 OFF 0.1s
0s
0.05
Ii =(2~12)l n
0.02
0.01
0.005
0.002
0.2 0.30 .4 0.60 .8 1 23 46 8 10 20 34 68 10 20 30
IR In
SELECTION GUIDE
SE Molded Case Circuit Breaker
Ordering codes
52
MCcB
CERTIFICATIONS
SE 100
SE 630
SE 800
53
55
ACB
RANGE OF PRODUCTS
SA Air Circuit Breaker
ACB,, Frame
e 2000A,, Fixed ACB
B , F rame
e 3200A, Fixed
Technical Parameters
SA-2000 SA-3200
Rated voltage Ue (V) 400 400
Rated insulation voltage Ui (V) 800 800
Rated impulse withstand voltage Uimp (KV) 8 8
Rated current In (A) 1000--2000 2000--3200
Number of poles 3, 4 3, 4
T T
Rated ultimate short circuit
50/60HZ AC 400V 80 80
breaking capacity Icu kA
Rated operating short circuit
50/60HZ AC 400V 50 80
breaking capacity Ics kA
Rated Short-Time withstand
50/60HZ AC 400V 50 65
current lcw (kA/1s)
Mechanical life Mechanical with maintenance 10000 8000
Mechanical without maintenance 2500 2500
Electrical life Electrical with maintenance 1000 1000
Electrical without maintenance 500 500
54
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker
Function Information
ECW-L
Protection Use
Long time delay L Protect cable, prevent ageing
Earthing G /QDUDMSƥQD
Action current IR (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0) In+OFF
Action current Ii (10, 11, 12, 14, 16, 18, 20) In+OFF (Frame 2000A)
Earthing protection
Action current Ig (0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8) In+OFF
55
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker
Function Information
ECW-M
Protection Use
Earthing G /QDUDMSƥQD
Measure
Current measurement
Voltage measurement
Miscellaneous function
Pre-alarm Fault log
t=(1.5/N)2xtR
N=Fault current divided by the setting current I/IR
t=Delay Time of Failure Action
tR=Setting Value of Long-Delay Time
56
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker
Function Information
ECW-M
Protection Characteristics for Short-Delay Short Circuit
Action current Isd
](M
.%%2SDORDSSHMFJ ADKNVơ J @ANUDơ
SA-2000 SA-3200
Action current Ii 2.0In~50kA+OFF 2.0In~75kA+OFF
Measure
Action current Ig (0.2~1.0)In+OFF
57
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker
Function Information
ECW-H
Protection Use
Earthing G /QDUDMSƥQD
Measure
Current measurement Power measurement
Communication function
58
ACB
INTELLIGENT CONTROLLER
SA Air Circuit Breaker
Function Information
ECW-H
Protection Characteristics for Short Delay
Action Current of Inverse
Time Limit Is OFF+(0.4~15)In
SA-2000 SA-3200
Action current Ii 2.0In~50kA+OFF 2.0In~75kA+OFF
59
ACB
ACCESSORIES
SA Air Circuit Breaker
List of accessories
8
9
10
6
16
5 15
3 14
13
12
1
11
60
ACB
ACCESSORIES
SA Air Circuit Breaker
List of accessories
When the breaker is stored, under prescriptive voltage, through long-distance remote
Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.7-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <30ms
The undervoltage release automatically opens a circuit breaker when voltage drops
to a value ranging between 35% to 70% of the line voltage. after tripping,the
circuit breaker cannot be re-closed again when the voltage lowers than 35% or until
returns to 85% of line voltage. Undervoltage relay release lets the breaker break in
1s-5s(adjustable)
Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.7-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <30ms
When the breaker is stored, under prescriptive voltage, through long-distance remote
Accessory parameter
Rated operational voltage V 230VAC 400VAC 220VDC
Operation voltage (0.85-1.1)Us
Consumption 300VA(AC) 40W(DC)
Breaking time <70ms
61
ACB
ACCESSORIES
SA Air Circuit Breaker
List of accessories
Motor mechanism
When the breaker is under breaking and power supply, motor mechanism is automatic
stored. So under shunt release, undervoltage and closing release, let the breaker break
and close
Accessory parameter
Rated control voltage V 230VAC 400VAC 220VDC
Action voltage (0.85-1.1)Us
Consumption 192VA(AC) 192W(DC)
Energy storage time <5s
Auxiliary contact
It is used for keeping watch on the breaker’s status, connecting position signal light
Accessory parameter
Utilization category AC-15 DC13
Auxiliary contact default type 5NO 5NC (4NO 4NC for 1000AF)
Conventional thermal current Ith 6A
Auxiliary contact’s energized Equal to circuit breaker operation
operational performance performance
Making & Under I/Ie making 10 1
breaking normal I/Ie breaking 1 1
capacity conditions U/Ue 1 1
cosø or T0.95 0.3 6Pe*
62
ACB
ACCESSORIES
SA Air Circuit Breaker
List of accessories
Keylock
It is divided into three types: one lock and one key, two locks and one key, three
*Note: Only for Vertical intallation, and the Max installation distance is 0.9M
Phase Barrier
Install in the middle of the breaker busbar, increase creepage distance, prevent to
63
ACB
WIRING DIAGRAM
SA Air Circuit Breaker
UV SO SC
Energy
storage
Pin function:
» #1 and #2: auxiliary supply input terminal (#1 for positive terminal when being DC)
» #3, #4 and #5: contact output of tripping fault (#4 refers to shared terminal);
contact capacity: 16A @380VAC
» #6, #7, #8 and #9: two groups of auxiliary terminals with circuit breaker status;
contact capacity: 16A @380VAC
» #20 PE wire, protection earthing wire
» #25, #26: output for circumscribed transformer
Remarks
» #27 and #28 of undervoltage release UV connect to main circuit.
» UV, SO, SC and Motor can be connected with different control voltage, Auxiliary contact is 5a5b, Shunt
open and close have been tandem connected with NO & NC auxiliary contact in the factory.
» #35 can be connected to the power supply directly (automatic pre-storing energy), also to the power
supply after adopting tandem connection with normal open button (manual pre-storing energy).
» #6 & #7 can output normal close contacts, if the users put forward.
» Power module 1 is DC Power module, and there is no such module when the power AC power supply. The
input & output terminals cannot be connected reversely.
» The auxiliary contact is 5 open and 5 close, #25 & #26 are circumscribed transformer, applied for (3P+N)
T type earthing failure protection.
Components:
UV: undervoltage, SO: Shunt open, SC: Shunt closes, AUX: auxiliary contact, M: Motor,
SB1: Make button, SB2: Shunt button
64
ACB
INSTALLATION DIMENSIONS
SA Air Circuit Breaker
65
ACB
INSTALLATION DIMENSIONS
SA Air Circuit Breaker
66
ACB
SELECTION GUIDE
S Molded Case Circuit Breaker
Ordering codes
1250 A 80 KA SA02KT12K3FH
1600 A 80 KA SA02KT16K3FH
2000 A 80 KA SA02KT02K3FH
2250 A 80 KA SA32KT25K3FH
3200 A 80 KA SA32KT32K3FH
67
ACB
CERTIFICATIONS
ACB SA
68
Contactors
PRODUCT DETAILS
SC 9A~95A Contactor
IEC 60947-4-1
With the new generation of technical platform and automated production and testing equipment, the brand new SC9~95
LNSNQBNMSQNK@MCOQNSDBSHNMOQNCTBSRDƤDBSHUDKXƥSSGD@BST@KBTRSNLDQ@OOKHB@SHNMMDDCRADBNLHMFOQNCTBSRVHSG
convenient use and international leading quality.
The series include three major categories, namely SC9~95 contactor, SO-93 thermal overload relay and their accessories.
SC contactor: 9-95A SCHPCs transparent dust cover, AXF top auxiliary contact, AXS side CB,CE, SEMKO
NORMAL INST
TALLA
ATION AND
D OPERATION CONDITIONS
Installation position:
Ş3GDHMRS@KK@SHNMRHSDRG@KKADUDQSHB@KVHSGHMBKHM@SHNM@S@KKCHQDBSHNMRMNSDWBDDCHMFo
Ť
2.NEMNFQD@SDQSG@MŤHMRS@KK@SHNM"K@RR(KK
• Pollution class: Class 3
Ambient temperature:
• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC
Ş2SNQ@FDSDLODQ@STQDŤ"
Ť"TOSN
x"VHSGHM@RGNQSSHLDG
Altitude:
• Altitude at normal installation position does not exceed 2000m
Humidity:
Ş3GD@SLNROGDQHBQDK@SHUDGTLHCHSXCNDRMNSDWBDDCVGDMSGDGHFGDRS@LAHDMSSDLODQ@STQDHR
Ť"
(SHR@KKNVDC
SNG@UD@QDK@SHUDGHFGDQGTLHCHSXTMCDQKNVDQSDLODQ@STQDD
F
TOSN@S
Ť"
69
Contactors
Contactor Model SC09 SC12 SC18 SC25 SC32 SC38 SC40 SC50 SC65 SC80 SC95
Main Circuit Characteristics
Number of Poles 3
Rated Insulation Voltage (Ui) V 690
Rated Operational Voltage (Ue) V 690
Conventional Thermal Current 20 20 25 32 40 40 50 60 80 110 110
AC-3, 380/400V A 9 12 18 25 32 38 40 50 65 80 95
Conventional
Operational AC-3, 660/690V A 6.6 8.9 12.0 18.0 22.0 22.0 34.0 39.0 42.0 49.0 49.0
Current (Ie) AC-4, 380/400V A 3.5 5.0 7.7 8.5 12.0 14.0 18.5 24.0 28.0 37.0 44.0
AC-4, 660/690V A 1.5 2.0 3.8 4.4 7.5 8.9 9.0 12.0 14.0 17.3 21.3
AC-3, 380/400V KW 4.0 5.5 7.5 11.0 15.0 18.5 18.5 22.0 30.0 37.0 45.0
Conventional
Operating AC-3, 660/690V KW 5.5 7.5 10.0 15.0 18.5 18.5 30.0 33.0 37.0 45.0 45.0
Power (Pe) AC-4, 380/400V KW 2.2 3.0 4.0 5.5 7.5 7.5 7.5 11.0 15.0 18.5 22.0
AC-4, 660/690V KW 1.1 1.5 3.7 4.0 5.5 7.5 7.5 11.0 11.0 15.0 18.5
Mechanical Durabilities 10,000 times 1200 1000 900 650
Electrical AC-3 10,000 times 110 90 65
Durabilities AC-4 22 22 17 11
10,000 times
Operation AC-3 Time/Hour 1200 600
Frequency AC-4 Time/Hour 300 300
Coil
Rated control 50 Hz V 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440
circuit voltage (Us) 50/60 Hz V 24, 36, 48, 110, 127, 220/230, 240, 380/400, 415, 440
70
Contactors
SC09 ~SC95
SC09 ~ SC38
SC40 ~ SC95
71
Contactors
SC09~SC38
72
Contactors
SELECTION GUIDE
SC Contactors
4 KW 9A 1 0 SC009M5310
0 1 SC009M5301
5.5 KW 12 A 1 0 SC012M5310
0 1 SC012M5301
7.5 KW 18 A 1 0 SC018M5310
0 1 SC018M5301
11 KW 25A 1 0 SC025M5310
0 1 SC025M5301
15 KW 32 A 1 0 SC032M5310
0 1 SC032M5301
18.5 KW 38 A 1 0 SC038M5310
18.5 KW 40 A 1 1 SC040M5311
22 KW 50 A 1 1 SC050M5311
30 KW 65 A 1 1 SC065M5311
37 KW 80 A 1 1 SC080M5311
45 KW 95 A 1 1 SC095M5311
Product Name Rated Current Coil Voltage Coil Frequency Poles Auxiliary Contacts
SC 09 M 5 3 10
09 : 09 A B : 24 V 5 : 50 Hz 3 10 : 1NO+0NC
... ... ... 01 : 0NO+1NC
95 : 95 A M : 220V/230V 7: 50/60 Hz 11 : 1NO+1NC
...
Q : 380V/400V
73
Contactors
INSTALLATION DIMENSION
Model a b c d e f
SC 09, 12, 18 35 50/60 - - - -
SC 25, 32, 38 40 50/60 - - - -
SC 40, 50, 65 - - 105 40 100/110 59
SC 80, 95 - - 105 40 100/110 67
74
Contactors
Contactor Model SC115 SC150 SC185 SC225 SC265 SC330 SC400 SC500 SC630
Main Circuit Characteristics
Number of Poles 3
Rated Insulation Voltage (Ui) V 1000
Rated Operational Voltage (Ue) V 690
AC-3, 380/400V A 115 150 185 225 265 330 400 500 360
Conventional
Operational AC-4, 380/400V A 52 60 79 85 105 117 138 147 188
Current (Ie) AC-1, 380/400V A 200 250 275 315 350 400 500 630 800
75
Contactors
WIRING DIAGRAM
SC 115A~630A Contactor
76
Contactors
SC 115A-630A Contactor
77
Contactors
SC 115A-630A Contactor
Auxiliary Contact
Installation Position Poles Composition Contact Point Layout Ordering Codes
NO NC
2 0 2 AXF6 02
1 1 AXF6 11
2 0 AXF6 20
Top 4 0 4 AXF6 04
1 3 AXF6 13
2 2 AXF6 22
3 1 AXF6 31
4 0 AXF6 40
2 0 2 AXF6 02
Side 1 1 AXF6 11
2 0 AXF6 20
0.1-3s TD6 20
Making
0.1-30s TD6 22
type delay
10-180s TD6 24
Top
10-180s TD6 34
78
Contactors
SC 115A-630A Contactor
Mechanical Interlock
Interlock Type Contactor Type Ordering Codes
SC-115~150 L6 FFH
SC-185~225 L6 GGH
Mechanical Interlock
SC-265~330 L6 HHH
Without electrical interlock
SC-400~500 L6 KKH
SC-630 L6 LL H
* Note: For vertical interlock contact supplier
Coils
Contactor Type Coil Voltage Ordering Codes
79
Contactors
INSTALLATION DIMENSION
SC 115A~630A Contactor
Overall dimensions
SC-115~SC330
SC-400~SC500
SC-630
SC-400 213 206 220 48 25 M10 146 181 158 145 15 20 80 170~180
SC-500 223 233 233 55 30 M10 150 208 172 146 15 20 80 170~180
SC-630 309 304 256 80 40 M12 181 264 202 155 20 30 180 180~190
* Note: 'f' reserved space to ensure draw-out coil can take out easily
80
OVERLOAD RELAY
NC 5 5 5
SO-25 SO25J
SO-36 SO36J
SO-93 SO93J
81
OVERLOAD RELAY
Trip Characteristics
Trip Characteristics for current balance
Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
1.05 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.2 Tripping within 2h Tripping within 2h After No.1 Test
1.5 <2 min <4 min After No.1 Test
7.2 R3OơR R3OơR Without Previous load +20Ƴ"
82
OVERLOAD RELAY
WIRING DIAGRAM
SO Thermal Overloads Relays
Fu-fuse.
KM-Contactor.
Fr-Thermal overload relay.
SB1-Stop button.
SB2-Start button.
83
OVERLOAD RELAY
SELECTION GUIDE
SO Thermal Overloads Relays
80-93 95 SO093095T095
84
OVERLOAD RELAY
INSTALLATION DIMENSION
SO Thermal Overloads Relays
Overall dimensions
SO-25
SO-36
SO-93
85
OVERLOAD RELAY
SELECTION GUIDE
SO Thetrmal Overloads Relays
86
OVERLOAD RELAY
Trip Characteristics
Trip Characteristics
Multiples of Tripping Time Initial Condition Ambient Temp.
Setting current Trip class 10A Trip class 10
1.05 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.2 Tripping within 2h Tripping within 2h After No.1 Test
1.5 < 2 min < 4 min After No.1 Test
7.2 R3OơR R3OơR Without previous load +20ƳC
1.0 0.9 Non-tripping within 2h Non-tripping within 2h Without previous load +20ƳC
1.15 0 Tripping within 2h Tripping within 2h After No.1 Test
87
OVERLOAD RELAY
Trip Characteristics
88
OVERLOAD RELAY
INSTALLATION DIMENSION
SO Thermal Overloads Relays
Overall Dimensions
Model A B C
SC-115 248 167 172
SC-150 253 167 172
SC-185 257 171 183
89
CAPACITOR CONTACTOR
SELECTION GUIDE
SK Capacitor Switching Contactor
25 1 1 SK12M 25300
2 0 SK12M 25300
0 2 SK12M 25300
32 1 1 SK18M 32300
2 0 SK18M 32300
0 2 SK18M 32300
43 1 1 SK20M 43300
2 0 SK20M 43300
0 2 SK20M 43300
63 1 2 SK30M 63300
2 1 SK30M 63300
95 1 2 SK45M 95300
2 1 SK45M 95300
90
CAPACITOR CONTACTOR
Coil
Coil Voltage V AC36, 110V, 127V, 220V, 380V, 400V
Operational Voltage V 85%~110% Us
Drop-out Voltage V 20%~75% Us
Auxiliary Contact
Rated conventional thermal current A 10
91
CAPACITOR CONTACTOR
WORKING CO
O N DII TIONS
Ambient temperature:
• In normal operation, the ambient temperature ranges between -5 ºC and +40 ºC
Ş2SNQ@FDSDLODQ@STQDŤ"
Ť"TOSN
x"VHSGHM@RGNQSSHLDG
Altitude: ơ2000m
Humidity:
Ş3GD@SLNROGDQHBQDK@SHUDGTLHCHSXCNDRMNSDWBDDCVGDMSGDGHFGDRS@LAHDMSSDLODQ@STQDHR
Ť"
(SHR@KKNVDC
SNG@UD@QDK@SHUDGHFGDQGTLHCHSXTMCDQKNVDQSDLODQ@STQDD
F
TOSN@S
Ť"
92
MANUAL MOTOR STARTER
93
MANUAL MOTOR STARTER
Setting Current Ue: 230/240 V Ue: 400/415 V Ue: 440 V Ue: 500 V Ue: 690 V
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
0.1 - 0.16 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
0.16 - 0.25 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
0.25 - 0.4 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
0.4 - 0.63 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
0.63 - 1 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
1 - 1.6 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA
1.6 - 2.5 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 3kA 2.25kA
2.5 - 4 A 100kA 100kA 100kA 100kA 100kA 100kA 100kA 100kA 3kA 2.25kA
4 - 6.3 A 100kA 100kA 100kA 100kA 50kA 50kA 50kA 50kA 3kA 2.25kA
6 - 10 A 100kA 100kA 100kA 100kA 15kA 15kA 10kA 10kA 3kA 2.25kA
9 - 14 A 100kA 100kA 15kA 7.5kA 8kA 4kA 6kA 4.5kA 3kA 2.25kA
13 - 18 A 100kA 100kA 15kA 7.5kA 8kA 4kA 6kA 4.5kA 3kA 2.25kA
17 - 23 A 50kA 50kA 15kA 6kA 6kA 3kA 4kA 3kA 3kA 2.25kA
20 - 25 A 50kA 50kA 15kA 6kA 6kA 3kA 4kA 3kA 3kA 2.25kA
24 - 32 A 50kA 50kA 10kA 5kA 6kA 3kA 4kA 3kA 3kA 2.25kA
94
MANUAL MOTOR STARTER
95
MANUAL MOTOR STARTER
Wiring diagram
96
MANUAL MOTOR STARTER
SELECTION GUIDE
SS Motor Starter
Thermal Release Magnetic Release Rated Operating Power Recommended Ordering Codes
Setting Current Current Id (A) (KW) Contactor
97
MANUAL MOTOR STARTER
SELECTION GUIDE
SS Motor Starter
Accessories
/TSSGDƦ@SRTQE@BDNESGDSNO@TWHKH@QX
contact close to the circuit breaker
98
MANUAL MOTOR STARTER
CERTIFICATIONS