0020-1 Battery Critical Batteries are 1. Check whether battery polarities are
connected not properly correctly installed by using a multimeter. If
reversely installed no, correct the installation.
2. Check whether the battery input
voltage of the UPS is normal. If yes, the
battery sampling circuit of the power
module is faulty. Replace the power
module.
Troubleshooting HUAWEI UPS
The power
module
Battery fuse is
blown.
0025-1 Battery Minor The configured 1. Check whether battery
overvoltage number of parameters are correctly set.
batteries is less 2. If they are correctly set, certain
than the actual batteries may be faulty.
number. 3. Check whether the battery
neutral wire is correctly
The battery connected.
neutral
wire is not
installed
properly.
0026-1 Low battery Minor Battery discharge 1.If the low battery voltage alarm is
voltage results in low generated in battery mode, check whether
battery voltage. the mains voltage recovers. If yes, charge
batteries immediately.
The battery 2. Check whether the battery neutral wire
neutral wire is is correctly connected.
not installed 3. If this alarm is generated in normal
properly. mode, check whether the battery switch is
ON. If yes, the charger may be faulty.
The charger is Replace the related power module.
faulty.
0530-1 Battery Critical The battery 1. Check whether the positive and
ground fault string is not negative terminals of the battery string
properly are grounded or have sufficient resistance
grounded. to the ground.
Troubleshooting HUAWEI UPS
The actual
number of
batteries does
not meet
requirements.
0036-2 Battery Warning The time for Maintain the batteries.
maintenance maintenance
reminder arrives.
0037-1 Battery U/V Critical The UPS has 1. Check whether the battery voltage is
worked in normal.
battery mode for 2. Check whether the output is
an extended overloaded.
amount of time. 3. Check whether any battery is damaged.
If yes, replace the battery.
The charger is 4. Check whether any battery charger
faulty. generates an alarm. If yes, replace the
faulty module.
0040-7 Rectifier Critical The fan for the 1. Check that the air channel for the
abnormal power module is module is free from blockage.
Not functioning 2. Check whether the fans are functioning
properly. properly. Replace the power module if the
fans are faulty.
The air channel
for the power
module is
obstructed
Troubleshooting HUAWEI UPS
The fan
monitoring cable
for the power
module is not
working
properly.
0043-2 The fan is Check the fan or replace the bypass
faulty. module.
0043-3 Fan abnormal Critical The fan is faulty 1. Replace the fan.
0043-4 2. Check the fan monitoring cable.
The fan
monitoring cable
is faulty
0047-1 Not ready Critical The ready Switch Close the ready switch.
is OFF
0060-4 Inverter Critical A load short- 1. Check load cable distributions.
abnormal circuit occurs. 2. If load cable distributions are normal,
replace the power module.
A short circuit
occurs inside the
Module. (This
fault
Seldom occurs.)
0061-2 Inverter Minor The I2C bus is not 1. Rectify the fault and check whether the
alarm normal. alarm is cleared.
2. If the alarm is generated again, replace
The E2PROM is the power module.
faulty.
0061-7 Inverter Minor The bypass If not all modules generate the
alarm waveform is not alarm, start the UPS, transfer it
normal. to normal mode, and replace the
faulty module.
If all modules generate the alarm, open
the bypass input circuit breaker. After the
inverter relay is closed, close the bypass
input circuit breaker
10 seconds later.
Troubleshooting HUAWEI UPS
The module is
damaged.
0565-1 Load impact Minor A large-power 1. Check the load.
transfer-to- RCD 2. If the load is normal, replace the power
bypass load is instantly module.
connected, or
the
output load
short-circuits.
The inverter
bridge
short-circuits.
The module is
damaged.
0570-4 BPM module Critical The bypass fan is 1. Check the bypass fan and air
abnormal not functioning channel. If the fan is faulty,
properly, or the replace it.
air 2. Check that the ambient
channel is temperature has not exceeded
blocked. 40°C.
3. Check that there is no overload.
The ambient
temperature
exceeds the
upper
threshold.
The load is
excessive.
Troubleshooting HUAWEI UPS
Only one
Rack works in a
Parallel system.
An ECM is faulty.
0583-4 The inter-rack Replace the inter-rack parallel cable.
Industrial
frequency
synchronization
cable is broken.
0583-5 The inter-rack
Carrier
synchronization
cable is broken.
0583-6 The intra-rack
INVBYP cable is
broken.The
parallel
CAN bus is
broken.
0584-2 Inter-rack Minor The inter-rack Replace the inter-rack parallel cable.
par. cable parallel cable is
alarm faulty.
0584-4 The inter-rack
Industrial
frequency
synchronization
cable is broken.
0085-1 EPO Critical The EPO button Restore the EPO button status. Start the
is UPS after the alarm is cleared.
pressed.
0086-1 Max. number Minor The system Check the load.
of frequently
BPM transfers transfers to
bypass mode due
to overload
timeout or load
impact.
Troubleshooting HUAWEI UPS
0101-1 BSC signal Minor The dual bus 1. Check the dual bus connector.
abnormal connector is 2. Check the parameter settings.
loose.
Parameters are
set incorrectly.
0102-1 Maint breaker Critical The user 1. Shut down the inverter and then close
Misoperation operation is the maintenance circuit breaker.
incorrect.
2. After maintenance, open the
maintenance circuit breaker and then
start the inverter.
0380 In self Check Warning The inverter is in Wait until the inverter self-check is
self-check. complete.