Professional Documents
Culture Documents
9PX 1000i
9PX 1500i
9PX 2200i
9PX 3000i
9PX EBM 48V
9PX EBM 72V
Installation
and user manual
The 9PX models that are covered in this manual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.
Please check section "6.1 Equipment care", page 31, for additional information.
Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
ENGLISH
Safety of persons
• The system has its own power source (the battery). Consequently, the power outlets may be ener-
gized even if the systems is disconnected from the AC power source. Dangerous voltage levels are
present within the system. It should be opened exclusively by qualified service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about bat-
teries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
• Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
Product safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided
with 20 or 30 amperes maximum branch circuit overcurrent protection in accordance with the
National Electric Code, ANSI/NFPA 70 (US installations only).
• Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -25ºC to +55ºC without batteries, 0ºC to +40ºC with
batteries.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75 (US installations only).
Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75
requirement.
Special precautions
• The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations.
• All handling operations will require at least two people (unpacking, lifting, installation in rack
system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS
must be energized for a period of 24 hours, at least once every 6 months (for a normal storage
temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. If there are any questions, don’t hesitate to contact your EATON
representative.
• All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the UPS.
• For potential safety issue on defective UPS : DISCONNECT INTERNAL BATTERY for storage and
transportation.
ENGLISH
1. Introduction..........................................................................................
1.1 Environmental protection................................................................................................6
2. Presentation.........................................................................................
2.1 Standard installations......................................................................................................8
2.2 Rear panels.....................................................................................................................9
2.3 Accessories.................................................................................................................. 10
2.4 Control panel................................................................................................................. 11
2.5 LCD description............................................................................................................ 12
2.6 Display functions.......................................................................................................... 13
2.7 User settings................................................................................................................ 13
3. Installation...........................................................................................
3.1 Inspecting the equipment ............................................................................................ 17
3.2 Checking the accessory kit........................................................................................... 17
3.3 Connecting the EBM(s) ................................................................................................ 18
3.4 Connecting other accessories ..................................................................................... 19
3.5 Tower installation..........................................................................................................20
3.6 Rack installation............................................................................................................21
3.7 UPS connection without HotSwap MBP module.........................................................22
3.8 Connection with a HotSwap MBP module (optional, standard on HotSwap versions)...... 23
4. Communication...................................................................................
4.1 Communication ports...................................................................................................24
4.2 UPS remote control functions......................................................................................25
4.3 Eaton Intelligent Power Software suite........................................................................27
5. Operation.............................................................................................
5.1 Start-up and Normal operation......................................................................................28
5.2 Starting the UPS on Battery..........................................................................................28
5.3 UPS Shutdown.............................................................................................................28
5.4 Operating modes..........................................................................................................28
5.5 Return of AC Input Power.............................................................................................29
5.6 Setting High Efficiency mode.......................................................................................29
5.7 Configuring Bypass settings.........................................................................................29
5.8 Configuring battery settings.........................................................................................30
5.9 Retrieving the Event log................................................................................................30
5.10 Retrieving the Fault log.................................................................................................30
6. UPS maintenance................................................................................
6.1 Equipment care.............................................................................................................31
6.2 Storing the equipment..................................................................................................31
6.3 When to replace batteries............................................................................................31
6.4 Replacing batteries.......................................................................................................32
6.5 Replacing the UPS equipped with a HotSwap MBP.....................................................34
6.6 Recycling the used equipment.....................................................................................34
7. Troubleshooting....................................................................................
7.1 Typical alarms and faults...............................................................................................35
7.2 Silencing the alarm.......................................................................................................36
7.3 Service and support......................................................................................................36
7.4 CE compliance contact.................................................................................................36
8. Specifications.......................................................................................
8.1 Model specifications.....................................................................................................37
9. Glossary............................................................................................ 40
Thank you for selecting an EATON product to protect your electrical equipment.
The 9PX range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing your 9PX, please read the booklet presenting the safety instructions.
Then follow the indications in this manual.
To discover the entire range of EATON products and the options available for the 9PX range, we invite you
to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identification symbol 01
PET
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
ENGLISH
The Eaton® 9PX uninterruptible power system (UPS) protects your sensitive electronic equipment from the
most common power problems, including power failures, power sags, power surges, brownouts, line noise,
high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware - causing
hours of lost productivity and expensive repairs.
With the Eaton 9PX, you can safely eliminate the effects of power disturbances and guard the integrity
of your equipment. Providing outstanding performance and reliability, the Eaton 9PX’s unique benefits
include:
• True online double-conversion technology with high power density, utility frequency independence, and
generator compatibility.
• ABM® technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life.
• Selectable High Efficiency mode of operation.
• Standard communication options: one RS-232 communication port, one USB communication port, and
relay output contacts.
• Optional connectivity cards with enhanced communication capabilities.
• Extended runtime with up to four Extended Battery Modules (EBMs) per UPS.
• Remote On/Off control through Remote On/Off (ROO) and Remote Power Off (RPO) ports.
• Backed by worldwide agency approvals.
Tower installation
Rack installation
ENGLISH
2.2 Rear panels
9PX 1000IRT & 9PX 1500IRT
1 2 3 4 5 1 Socket for connection to AC power
source
2 Slot for optional communication card
3 Relay output contact
4 Connector for additional battery
module
5 Primary group: outlets for
11 10 9 8 6 7
connection of critical equipment
6 Group 1: programmable
outlets for connection of equipment
7 Group 2: programmable
9PX 2200IRT & 9PX 3000IRT (2U)
outlets for connection of equipment
1 2 3 8 4 5 8 Connector for automatic recognition
of an additional battery module
9 RS232 communication port
10 USB communication port
11 Connector for ROO (Remote On/Off)
control and RPO (Remote Power Off)
9 11 10 6 7
4 9 11 10 6 7
12 12
12 12
9PX 1-3 KVA EU_EN Page 9
2. Presentation
12 12
2.3 Accessories
Part number Description
9PXEBM48RT2U
9PXEBM72RT2U Extended battery module
9PXEBM72RT3U
ENGLISH
2.4 Control panel
The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status,
events, measurements and settings.
Online mode
100% 100%
2.7k W 19min
3.0kVA 1EBM
Efficiency: 94 %
The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Operation status
Online mode
100% 100%
Load/equipment status
2.7kW 19min Battery status
3.0kVA 1EBM
Efficiency: 94%
The following table describes the status information provided by the UPS
Note: If other indicator appears, see troubleshooting on page 35 for additional information.
Online mode The UPS is operating normally. The UPS is powering and protecting
the equipment.
Battery mode A utility failure has occured and The UPS is powering the equipment
the UPS is on Battery mode. with the battery power.
Prepare your equipment for shut-
down.
Bypass mode An overload or a fault has occurred, Equipment is powered but not
or a command has been received, protected by the UPS.
and the UPS is on Bypass mode.
ENGLISH
2.6 Display functions
Press the Enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter ( ) button to select an option. Press the button to cancel
or return to the previous menu.
Main menu Submenu Display information or Menu function
Measurements [Load] W VA A pf / [Input/Output] V Hz / [Efficiency] % /
[Battery] % min V n° EBM / [Battery remaining life] months /
[Average power usage] Wh / [Cumulated power] Wh
Control Go to Bypass Transfers the UPS on Bypass mode
Load segments On/Off Commands the load segments
Start battery test Starts a manual battery test
Connectivity test Tests dry contact relay outputs and relay card contacts.
Simulates line failure and battery low
Function reset Clears active fault, power usage, battery remaining life, reset
NMC, Restore factory settings.
Settings Local settings Sets product general parameters
In/Out settings Sets Input and Output parameters
On/Off settings Sets On/Off conditions
Battery settings Sets battery configuration
Com settings Sets communication parameters
Event log Event filter Selects faults, alarms and/or events to display
Event list Displays the events stored
Reset event list Clears events
Fault log Fault list Displays the faults stored
Reset fault list Clears faults
Identification [Product type/model] / [Part/Serial number] / [UPS/NMC
firmware] / [Com card IPv4], [Com card IPv6], [Com card MAC]
Registration Links to Eaton registration website
ENGLISH
Submenu Available settings Default settings
Automatic battery In ABM cycling mode :
test [No test] [Every ABM cycle] [Every ABM cycle]
In constant charge mode:
[No test] [Every day] [Every week] [Every week]
[Every month]
Low battery [Capacity] [0%] … [100%] [0%]
warning [Runtime] [0min] … [60min] [3min]
The alarm triggers when the set
percentage of battery capacity or
remaining back-up time is reached.
Restart bat. level [0%] ... [100%] [0%]
If set, automatic restart will occur only
Battery settings when percentage of battery charge is
reached.
Battery charge [ABM cycling] [Constant charge] [ABM cycling]
mode
External battery [Auto detection] [Manual EBM set.] [Auto detection]
[Manual battery set.] Using standard EBM, UPS
detects automatically the
number of EBM connected
Deep Disch. [Yes] [No] [Yes]
protect. If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
Input signals [ROO] [RPO] [DB9-4]
Sets Input signals parameters
(function, delay, operation) through
external contact connectors or RS232
port.
ROO port:
- [Function]: [No] [ROO] [RPO] [No]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s] [0s]
- [Active]: [Open] [Closed] [Closed]
Com settings
RPO port:
- [Function]: [No] [ROO] [RPO] [No]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s] [0s]
- [Active]: [Open] [Closed] [Open]
DB9-4 port:
- [Function]: [No] [ROO] [RPO] [No]
[Building alarm] [Forced bypass] [On
generator] [Remote shutdown]
- [Delay]: [0s] … [999s] [0s]
- [Active]: [High] [Low]: [High]
[DB9-1]: [On bat] [Low bat] [Bat fault] [DB9-1] [Low bat]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-7]: [On bat] [Low bat] [Bat fault] [DB9-7] [UPS OK]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-8]: [On bat] [Low bat] [Bat fault] [DB9-8] [On bat]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
Remote command [Enabled] [Disabled] [Enabled]
If Enabled, shutdown or restart
Com settings commands from software are
authorized.
Shutdown [Send CMD] [Output OFF] [OFF delay]
commands [restart]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Send CMD]: [Yes] [No] Send CMD: [No]
[Output OFF]: [No] [UPS] [Group 1] Output OFF: [No]
[Group 2] [Group 1 + Group 2]
[OFF delay]: [0s] …[999s] OFF delay: [0s]
[Restart]: [Yes] [No] Restart: [Yes]
On battery notice [0s] ... [99s] [0s]
delay Sets delay before noticing on battery
information to software.
ENGLISH
3.1 Inspecting the equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials
for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage:
1. File with the carrier within 15 days of receipt of the equipment;
2. Send a copy of the damage claim within 15 days to your service representative.
Check the battery recharge date on the shipping carton label. If the date has passed and the batte-
ries were never recharged, do not use the UPS. Contact your service representative.
15
16
14
17
21 22 23
24
19
20 18
25
27 28
26
• Verify that the following additional items are included with the UPS:
• If you ordered an optional Extended Battery Module (EBM), verify that the following additional items are
included with the EBM:
2 3
Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time.
Use the UPS user’s guide to install both the UPS and the EBM.
contents.
1. Plug the EBM power cable(s) into the battery connector(s). Up to 4 EBMs may be connected
to the UPS.
2. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
3. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
9PXEBM48RT2U
ENGLISH
9PXEBM72RT2U
9PXEBM72RT3U
If you ordered other UPS accessories, refer to user manuals to check the connection
to the UPS.
If you ordered other UPS accessories, refer to specific user manuals to check the tower installation
with the UPS.
ENGLISH
3.6 Rack installation
• Rack mounting of UPS, EBM, and accessory modules.
2 3
4
The rails and necessary hardware are supplied by EATON.
Note. The UPS charges the battery as soon as it is connected to the AC-power source, even if button
is not pressed.
Once the UPS is connected to the AC-power source, eight hours of charging are required before the
battery can supply the rated backup time.
ENGLISH
3.8 Connection with a HotSwap MBP module (optional, standard on HotSwap versions)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected
loads (HotSwap function).
5 9PX 2200IRT / 9PX 3000IRT:
1. Connect the input socket 36 on
the HotSwap MBP module to the
AC-power source using the cable
15 supplied.
3. C
onnect the UPS outlet 5 to the
“UPS Output” 34 on the HotSwap
HotSwap MBP
MBP module, using the cable 28
supplied.
These cables and the connectors
are marked in red.
4. C
onnect the equipment to the
29 30 31 32 33 34 35 36 outlets 29 and 30 on the HotSwap
MBP module. These outlets differ,
depending on the version of the
HotSwap MBP module.
15
LOAD Caution. Do not use UPS outlets
to supply equipment because use
of switch 33 on the HotSwap MBP
module would cut supply to the
equipment.
2. C
onnect the other end of the
17
communication cable 17 or
18 to the USB 10 or RS232 9
communication port on
the UPS.
10
1. R
emove the slot cover 2
secured by screws.
2. Insert the communication
card in the slot.
3. S ecure the card cover with
the 2 screws.
ENGLISH
4.2 UPS remote control functions
Function Description
No No function, please choose a function if you want to use input signal
RPO Remote Power off (RPO) is used to shutdown the UPS remotely
ROO Remote On/Off allows remote action of button to switch On/Off the UPS.
(Cold start is prohibited while using the ROO function)
Forced bypass If feeding the load the unit goes to bypass operation and stays there regardless of
the bypass state until the input is inactivated
Building Active input generates an alarm “building alarm”
alarm
On generator Active input disables synchronization and transfers to bypass
Remote Active input turns UPS output (or outlet groups) off after a user defined shutdown
shutdown delay but keeps on charging batteries according to a selected charging scheme,
inactive input does not abort shutdown countdown. Depending on the “Restart”
parameter (see Settings > Com Settings > Shutdown commands on page 16) the
unit may startup automatically.
Warning Signal inputs have no function by default please choose a function through the LCD
(Settings > Com settings > Input signals on page 15).
See below 2 examples of configuration with RPO terminal used as RPO function and ROO terminal use as
ROO function:
RPO connections:
RPO Comments
Connector type Terminal, 14 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max
ROO
11
RPO
ROO connections:
ROO Comments
Connector type Terminal, 14 AWG Maximum wires
External breaker specification 60 V DC/30 V AC 20 mA max
ROO
11
RPO
Normally closed
4. Plug the RPO connector into the back of the UPS and fix the screws.
5. Connect and restart the UPS according to the previously described procedures.
6. Activate the external remote shut down contact to test the function.
Always test the RPO function before applying your critical load to avoid accidental load loss.
Normally Closed
1
Normally Open
3 2
Common
3
ENGLISH
Connectivity Cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with dif-
ferent types of devices. The 9PX models have one available communication bay for the following
connectivity cards:
• Network-MS card - has SNMP and HTTP capabilities as well as monitoring through a Web browser inter-
face; connects to Ethernet network. In addition, a Environmental Monitoring Probe can be attached to
obtain humidity, temperature, smoke alarm, and security information.
• Modbus-MS card - has connection to Modbus protocol in addition to network management.
• Relay-MS card - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery
low, UPS alarm/OK, or on Bypass.
100M 10M UPS data Reset 100M 10M UPS data Reset
1. Press the button on the UPS front panel until the UPS front panel display illuminates and shows
a status of "UPS starting...".
The UPS transfers from Standby mode to Battery mode. The indicator illuminates solid.
The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms or notices besides the "Battery mode" notice
and notices that indicate missing utility power. Resolve any active alarms before continuing.
See "Troubleshooting" on page 35.
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart
if necessary.
Online mode
During Online mode, the indicator illuminates solid and the UPS is powered from the utility.
The UPS monitors and charges the batteries as needed and provides filtered power protection to your
equipment. Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack
environment. See user settings on page 13.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the
indicator illuminates solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Online mode operation while the battery recharges.
If battery capacity becomes low while on Battery mode, the audible alarm beeps once every 3 seconds.
This warning is approximate, and the actual time to shutdown may vary significantly.
Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Page 28 9PX 1-3 KVA EU_EN
5. Operation
ENGLISH
Low-battery warning
• The indicator illuminates solid.
• The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment because
automatic UPS shutdown is imminent.
Bypass mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power.
Battery mode is not available and your equipment is not protected; however, the utility power continues
to be passively filtered by the UPS. The indicator illuminates.
Depending on overload conditions, the UPS remains in Bypass mode for at least 5 seconds and will stay
in this mode if three transfers to Bypass occur within 20 minutes.
The UPS transfers to Bypass mode when:
• the user activates Bypass mode through the front panel.
• the UPS detects an internal failure.
• the UPS has an overtemperature condition.
• the UPS has an overload condition listed in table 6 on page 38.
The UPS shuts down after a specified delay for overload conditions listed in table 6 on page 38.
The UPS remains on to alarm the fault.
Synchronization Window
The UPS tries to synchronize with Bypass when the Bypass frequency is less than the value set for the
“Synchronization Window” setting. When the Bypass frequency is more than the set value, the UPS goes to
nominal frequency.
Unsynchronized Transfers
When Qualify Bypass is set to “Always” or “Always on Fault” you can select the interruption time when
transferring to bypass, default setting is “Half Cycle” but can be changed to “Full cycle”.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
The battery test may be postponed due to bad conditions, or failed if battery is not ok.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes
or less than the setting capacity threshold (0 % by default).
This threshold can be modified.
ENGLISH
6.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free.
If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off.
The batteries are rated for a 3-5 year service life. The length of service life varies, depending
on the frequency of usage and ambient temperature (life divided by 2 each 10°C above 25°C).
Batteries used beyond expected service life will often have severely reduced runtimes. Replace
batteries at least every 4 years to keep units running at peak efficiency. Batteries runtime will be
reduced at low temperature (below 10°C).
Load not
Battery powered
replacement
4-% 100%
years battery
!
Replacement
-kW is
100min
recommended
-kVA 1 EBM
OK
Batteries can be replaced easily without turning off the UPS or disconnecting the load.
If you prefer to remove input power to change the batteries, see "UPS Shutdown" on page 28.
3
1
5
6
7
To replace the battery pack:
1. Remove the center cover of the front panel.
2. Push left cover toward to right direction.
3. Open the battery door.
ENGLISH
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
4. Remove the two screws of the metal protection cover of the battery and push it to the right.
5. Pull out the metal protection cover of the battery.
6. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable
surface. Use two hands to support the battery pack. See "Recycling the used equipment"
on page 34 for proper disposal.
7. Verify that the replacement batteries have the same rating as the batteries being replaced.
8 Put the new battery pack into the UPS. Push the battery pack firmly to ensure a proper connection.
9. Screw back the metal protection cover and the front panel, then clip the center cover.
10. Continue to “Testing new batteries” on page 33.
11. Reset the 4 years Life Cycling Monitoring (LCM): Control > Reset battery life.
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will
not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
3. Plug the EBM cable(s) into the battery connector(s). Up to four EBMs may be connected to the UPS.
4. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for
each cable.
5. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
Maintenance
1. Set switch 33 to Bypass position.
The red LED on the HotSwap MBP
1 6 7 module goes ON, indicating that the
load is supplied directly with AC input
28 source power.
2. S top the UPS by pressing the
button on the UPS control panel.
LED 31 "UPS ON - OK to switch"
HotSwap MBP goes OFF, the UPS can now be
disconnected and replaced.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste center.
ENGLISH
The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential ope-
rating problems may occur. Usually the alarms shown by the control panel do not mean that the output
power is affected. Instead, they are preventive alarms intended to alert the user.
• Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
• Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds. Example = "Battery low".
• Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on
the LCD with a specific message box. Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
No battery The batteries are disconnected. Verify that all batteries are properly
connected.
If the condition persists, contact your
service representative.
LED is On.
Beep continuous.
Battery fault The battery test is failed due to Verify that all batteries are properly
bad or disconnected batteries, connected. Start a new battery test:
or the battery minimum voltage is if the condition persists, contact your
reached in ABM cycling mode. service representative.
LED is On.
Beep continuous.
The UPS does not The batteries need charging or Apply utility power for 48 hours to
provide the expected service. charge the batteries. If the condition
backup time. persists, contact your service
representative.
Bypass mode An overload or a fault has Equipment is powered but not
occurred, or a command has been protected by the UPS.
received and the UPS is in Bypass Check for one of the following alarms:
mode overtemperature, overload or UPS
LED is on.
failure.
Power overload Power requirements exceed the Remove some of the equipment from
UPS capacity (greater than the UPS.
100% of nominal; see in table 6 The UPS continues to operate, but
on page 38 for specific output may switch to Bypass mode or shut
LED is On. overload ranges). down if the load increases.
Beep continuous. The alarm resets when the condition
becomes inactive.
UPS overtemperature The UPS internal temperature is If the UPS transferred to Bypass
too high or a fan has failed. mode, the UPS will return to normal
At the warning level, the UPS operation when the temperature drops
generates the alarm but remains 5°C below the warning level.
LED is On. in the current operating state. If the condition persists, shut down
1 beep every 3 seconds. If the temperature rises another the UPS.
10°C, the UPS transfers to Bypass Clear vents and remove any heat
mode or shuts down if Bypass is sources. Allow the UPS to cool.
unusable. Ensure the airflow around the UPS is
not restricted. Restart the UPS.
If the condition continues to persist,
contact your service representative.
The UPS does not start. The input source is not connected Check the input connections.
correctly.
The Remote Power Off (RPO) If the UPS Status menu displays the
switch is active or the RPO "Remote Power Off" notice, inactivate
connector is missing. the RPO input.
Load not powered
After 4 years of operation, See "6.3 When to replace batteries"
Battery replacement
4-% 100%
years battery
the UPS will provide a battery
Replacement
-kW is
100min replacement notification
!
recommended
-kVA 1 EBM reminding you that your batteries
OK
are nearing the end of their useful
life.
For critical applications, immediate replacement may be available. Call the Help Desk for the
dealer or distributor nearest you.
ENGLISH
8.1 Model specifications
Bypass
DC/DC
Charger Battery
ENGLISH
Table 7. Electrical output connections
Model Output connection Output cables
9PX1000IRT2U (4) IEC10A (2) IEC10A
9PX1500IRT2U (2) IEC10A group 1
(2) IEC10A group 2
9PX1500IRTM
Table 9. Battery
Internal batteries EBM
Rack / Tower 1000VA: 48Vdc - 4 x 12V, 7Ah 9PXEBM48RT: 48Vdc - 2 x 4 x 12V, 9Ah
configuration 1500VA: 48Vdc - 4 x 12V, 9Ah 9PXEBM72RT: 72Vdc - 2 x 6 x 12V, 9Ah
2200VA: 72Vdc - 6 x 12V, 7Ah
3000VA: 72Vdc - 6 x 12V, 9Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 25°C (77°F).
Monitoring Advanced monitoring for earlier failure detection and warning
EBM battery cable 350 mm / 13.78 in
length
Bypass AC source Source supplying the bypass line. The equipment can be transferred to the by-
pass line if an overload occurs on the UPS output, for maintenance or in
the event of a malfunction.
Frequency converter Operating mode used to convert the AC-power frequency between the UPS input
and output (50Hz -> 60Hz or 60Hz -> 50Hz).
Low-battery warning This is a battery-voltage level indicating that battery power is low and that
the user must take action to prevent the imminent break in the supply of power
to the load.
Backup time ime during which the load can be supplied by the UPS operating on battery
T
power.
HE mode Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user. This mode reduces the consumption
of electrical power
Manual bypass Rotary switch controlled by the user, used to connect the loads directly to the
AC source. Transfer of the load to the manual bypass enables UPS maintenance
without interrupting the supply of power to the connected loads.
Normal (double The normal UPS operating mode in which the AC source supplies the UPS which
conversion) mode in turn supplies the connected loads (after electronic double conversion).
Relay contacts Contacts supplying information to the user in the form of signals.