NBC Compliance Check list on Structural Analysis & Design for RCC
A General Information:
A.1 Owner’s Name: -
Address: Itahari 06
A.3 Type of Building: Mixed type(Residential & Commercial)
A.4 Structural Designed By:
Consultancy Firm: -
Designers’ Name: -
Nepal Engineering Council No: -
C Geological Investigation:
i) Geological Investigation Conducted yes
If Yes
C.1 Soil Investigation Report:
C.2 Soil Investigation Done By: Agni Boring and Soil Test Pvt Ltd
C.3 Allowable Bearing Capacity: 79.46 KN/m2
C.4 N- value: 13
C.5 Type of Soil: Type III (Soft Soil)
C.6 Water Table: 1.63m
C.7 Liquefaction Potential:
Itahari SubMetropolitan
Office of The Municipal Executive
Department of building Permit and Implementation of By laws
Itahari Sunsari
NBC Compliance Check list on Structural Analysis & Design for RCC
F Attachments:
H.1 Application form
H.2 Structural Design Report
H.3 Detailed Architectural Drawings
H.4 Detailed Structural Drawings
H.5 CD of Structural Analysis
I hearby Declare that the Above Data and Information are True and Are according To Nepal Building Code,Indian Code and
Prevailing International Codes.
…………………… ……………………..
Signature Signature
- -
Owner’s Name: Designer’s Name:
DECLARATION
Reference No: ________
All necessary calculations and documents are attached herewith for ready reference and record.
Yours faithfully,
-
-
Itahari 6
1.Introduction
1.1 About this Report
This report has been prepared for the purpose of Design Approval and submission
to Itahari Submetropolitan City This report deals about a Mixed Type Building at
itahari submetropolitan ward no 06 .This Report has been prepared by dedicated
team of our firm under the guidance of experiance Eengineer. This report deals
with methodology of the structural analysis and design of a Building and its
results. This report includes different parameters for the analysis and design of the
structure. The design results are shown in a very convenient tabular format in the
report.The results of calculation are presented in tabular form and sample
calculations are provided in details to reduce the bulkiness of the report. Sufficient
figure and sketches have been introduced to illustrate the theories. Reference to
the appropriate clauses of standard codes of practices has been made wherever
necessary. It is clear that for understanding the process physically and realizing
the structure behaviour, manual steps by steps procedure is necessary. However
due to the time constraint and to be familiar to the modern technology.
1.2.Objective
* To achieve a practical knowledge on structural analysis, design and detailing of
structural components using principles of Earthquake resistant design
SPECIFIC OBJECTIVES:
2. Loading
All loadings are derived bases on different parts of IS875. Earthquake load is
structure’s design life. The dead loads included in the design are:
With 40%
Full Load With 25% opening With 30% opening
opening
S.n Description
Load Load Load
Height Load Height Height Height
KN/m KN/m KN/m
1
Full Brick
2.68 14.18 2.75 10.90 2.75 10.20 2.75 8.75
Wall
2
1/2 Brick Wall 2.68 7.49 2.75 5.75 2.75 5.39 2.75 4.62
Marble
Bottom
Slab Only Screed Only Marble Only &
plaster
Sn Description screed
Load Load Thickne Load Load Load
Width Width
KN/m2 KN/m2 ss KN/m2 KN/m2 KN/m2
1
Slab 0.125 3.125 0.038 0.912 0.012 0.312 1.224 0.24
1
Staircase 0.15 3.75 0.038 0.912 0.012 0.312 1.224 0.24
Live loads for different rooms and roofs are calculated as per the functional
As per IS 1893-2002 Summary Report from Etabs calculation attached with this
Report
TABLE: Auto Seismic - IS 1893:2002
Direction = Multiple
Seismic Response
Sa
ZI
Seismic Coefficient, Ah [IS 6.4.2] g
Ah =
2R
Period Used W Vb
Direction
(sec) (kN) (kN)
X 0.684 10496.0572 922.5482
X + Ecc. Y 0.684 10496.0572 922.5482
X - Ecc. Y 0.684 10496.0572 922.5482
Figure Mass Source
Dead Dead 1
Live<3 Live 0
Live>3 Live 0
Roof Live Roof Live 0
Wall Superimposed Dead 0
Finish Superimposed Dead 0
Water Tank Other 0
Ex Seismic 0 IS1893 2002
Ey Seismic 0 IS1893 2002
loads and design strengths of the materials. These design loads and design
strengths are obtained by applying partial safety factors for characteristic loads
and strengths of the materials as concrete and steels.The limit state method of
design covers different criteria for design. The two major criteria are
a. Limit State of Collapse:
The limit state of collapse of the structure or part of the structure could be
assessed from rupture of one or more critical sections and from buckling due to
elastic or plastic instability (including effects of sway where appropriate) or
overturning. The resistance to bending, shear, torsion and axial loads at every
section shall not be less than the appropriate value at that section produced by
the probable most unfavourable combination of loads on the structure using the
appropriate partial safety factors.
b. Limit State of Serviceability:
It includes limit for deflection and cracking or local damage. Excessive deflection
and cracks adversely affects the finishes, efficiency and appearance of the
0.3mm in members where cracking is not harmful and does not have any serious
adverse effects upon the preservation of the reinforcing steel nor upon the
provided to be helpful tools in the analysis of frame for various loading condition.
In the project, the analysis, design and detailing of all require element of building
procedures, site study etc. Design and layout of the building services like pipeline,
electrical appliances, sanitary and sewage system were not covered in this project.
The environmental, social and economical condition of the locality was not taken
into consideration. The project work was only related with the Structural analysis
of building. Detail cost estimate of the project was not included in this report.
Finally we hope that efforts and coordination for the project work will prove much
useful in our career and project will be helpful in providing information on the
earthquake resistant design and its safe practice and we hope, this project will
help us in similar jobs that we might have in our hands in the future.
DRAWINGS &
ATTACHMENTS
Fig 1 Axial Force Diagram
M20
No of Tread=18 and No of Riser=20
Grade of Steel
Fe 500
Live load
4 KN/m2
Finish Load
2.08 m
2.00 KN/m2
Main Bar
12 mm Dia
Distribution Bar
8 mm Dia
0.00 m
A
A B
0.00 m 2.08 m 1.27 m
Design moments
Taking moments about A
Rb 41.27 KN Zero Sf 1.66 m
Ra 42.51 KN Max BM 35.32 KN-m
Depth
Ast = d: 93 mm Safe
Solving 4619 mm2
Mu=0.8 1072 mm2
Design Summary
Depth of slab 150.00 mm
Depth of Riser 160 mm
Width of Tread 280 mm
Main bar 12mm Dia @125mm Centre to Centre Spacing
distribution bar 8mm Dia @150mm Centre to Centre Spacing
R.C.C TWO WAY SLAB DESIGN
Case4
Two Adjacent Edges Discontinuous
Page 1 of 2
Mat foundation Nagar.fdb SAFE v12.3.2 - License #
11 March 2020
Page 2 of 2
Mat foundation Nagar.fdb SAFE v12.3.2 - License #
11 March 2020
Page 1 of 2
Mat foundation Nagar.fdb SAFE v12.3.2 - License #
11 March 2020
Page 2 of 2