4 PEU02-02A,02B GENERAL ADMIN OFFICE 2F 2 9.9 7.7 823 100 0.28 CEILING MOUNTED DUCT FXMQ100PVE 27,4 / 22,2 11.6 6.5 382/448/531 50/100/200 0.215 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
5 PEU02-02C GUEST ROOM 2F 1 1.5 1 91 - 0.06 CEILING MOUNTED DUCT FXMQ20PVE 28,0 / 22,9 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
6 PEU02-02D HALL 2F 1 3.9 2.6 272 100 0.15 CEILING MOUNTED DUCT FXMQ32PVE 27,7 / 22,8 3.7 2.1 116/132/158 30/50/100 0.06 30/32/34 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
7 PEU02-02E LOCKER ROOM (F) 2F 1 2.4 1.5 150 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 28,0 / 23,3 2.3 1.3 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
8 PEU02-02F LOCKER ROOM (M) 2F 1 2.9 2 207 100 0.06 CEILING MOUNTED DUCT FXMQ25PVE 27,8 / 22,8 2.9 1.7 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
9 PEU02-02G MEETING ROOM 1 2F 1 11.7 5.3 477 100 0.28 CEILING MOUNTED DUCT FXMQ100PVE 28,8 / 23,9 11.9 6.1 382/448/531 50/100/200 0.215 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
10 PEU02-02H MEETING ROOM 2 2F 1 11.7 5.3 480 100 0.28 CEILING MOUNTED DUCT FXMQ100PVE 28,8 / 23,9 11.9 6.1 382/448/531 50/100/200 0.215 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
11 PEU02-02I PRAYING ROOM 2F 1 17.5 8.3 749 200 1.29 CEILING MOUNTED DUCT FXMQ140PVE 28,5 / 23,9 17 8.6 531/648/763 50/100/140 0.405 43/45/46 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
12 PEU02-02J MANAGER ROOM 2F 1 9.4 7.5 787 100 0.28 CEILING MOUNTED DUCT FXMQ80PVE 27,4 / 21,9 9.3 5.5 331/373/415 50/100/200 0.185 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
13 PCU02-02 -- ROOF 1 80.8 - - - 30 VRV OUTDOOR UNIT RXQ30TANY14 34,5 / -- 80.7 - - - 23.7 64 380/3/50 19.1 34.9 VRV OUTDOOR UNIT
14 PEU02-03A,03B,03C,03D GENERAL MEETING ROOM 3F 4 14 7.5 684 200 0.28 CEILING MOUNTED DUCT FXMQ125PVE 28,3 / 23,8 14.9 7.4 465/548/548/648 50/100/200 0.284 40/42/44 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
15 PEU02-03E HALL 3F 1 4.7 3.4 349 100 0.13 CEILING MOUNTED DUCT FXMQ40PVE 27,6 / 22,4 4.7 2.8 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
16 PEU02-03F RESTING PLACE (F) 3F 1 4.3 3.5 384 100 0.13 CEILING MOUNTED DUCT FXMQ40PVE 27,4 / 22,0 4.7 2.8 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
17 PEU02-03G RESTING PLACE (M) 3F 1 5 3.8 393 100 0.13 CEILING MOUNTED DUCT FXMQ50PVE 27,6 / 22,3 5.8 3.4 250/273/298 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
18 PEU02-03H ROOM 1 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
19 PEU02-03I ROOM 2 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
20 PEU02-03J ROOM 3 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
21 PEU02-03K ROOM 4 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
22 PEU02-03L ROOM 5 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
23 PEU02-03M ROOM 6 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
24 PEU02-03N ROOM 7 3F 1 1.8 1.6 176 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,3 / 22,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
25 PEU02-03O ROOM 8 3F 1 2.4 2.1 231 100 0.15 CEILING MOUNTED DUCT FXMQ20PVE 27,4 / 21,8 2.3 1.5 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
26 PEU02-03P ROOM 9 3F 1 2.4 2.1 231 100 0.16 CEILING MOUNTED DUCT FXMQ20PVE 27,4 / 21,8 2.3 1.5 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
27 PEU02-03Q ROOM 10 3F 1 2.4 2.1 231 100 0.17 CEILING MOUNTED DUCT FXMQ20PVE 27,4 / 21,8 2.3 1.5 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
28 PCU02-03 -- ROOF 1 89.8 - - - 41.7 VRV OUTDOOR UNIT RXQ34TANY14 34,5 / -- 89.9 - - - 24.5 63 380/3/50 19.1 34.9 VRV OUTDOOR UNIT
INFRASTRUCTURE MAINTENANCE OFFICE
29 PEU03-01A WORK STATION (SIGNAL & TEL 1F 1 6.8 5.8 604 50 0.22 CEILING MOUNTED DUCT FXMQ63PVE 27,1 / 21,5 7.4 4.4 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
30 PEU03-01B WORK STATION (ELECTRIC CATE 1F 1 6.5 5.5 572 50 0.22 CEILING MOUNTED DUCT FXMQ63PVE 27,2 / 21,6 7.4 4.4 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
31 PEU03-01C WORK STATION (TRACK/CIVIL) 1F 1 6.8 5.8 616 50 0.22 CEILING MOUNTED DUCT FXMQ63PVE 27,4 / 21,8 7.4 4.4 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
32 PEU03-01D WORK STATION (MACHINERY/BU 1F 1 4.8 3.9 413 50 0.19 CEILING MOUNTED DUCT FXMQ40PVE 27,3 / 21,8 4.7 2.9 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
33 PEU03-01E LOCKER ROOM (MALE) 1F 1 4.4 2.6 259 50 0.15 CEILING MOUNTED DUCT FXMQ40PVE 28,0 / 23,3 4.8 2.7 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
34 PEU03-01F LOCKER ROOM (FEMALE) 1F 1 2.7 1.4 139 50 0.06 CEILING MOUNTED DUCT FXMQ25PVE 28,0 / 23,3 3 1.6 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
35 PEU03-01G SECURITY ROOM 1F 1 2.9 2.2 227 50 0.15 CEILING MOUNTED DUCT FXMQ25PVE 27,5 / 22,0 2.9 1.7 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
36 PEU03-01H ENTRANCE HALL & CORRIDOR 1F 1 7.3 5.5 600 50 0.22 CEILING MOUNTED DUCT FXMQ63PVE 27,6 / 22,4 7.4 4.2 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
37 PCU03-01 -- ROOF 1 42.2 - - - 16.1 VRV OUTDOOR UNIT RXQ16TAY14 34,5 / -- 42.8 - - - 13 61 380/3/50 12.7 28.6 VRV OUTDOOR UNIT
38 PEU03-02A ADMINISTRATIVE OFFICE 2F 1 4.6 3.4 360 50 0.14 CEILING MOUNTED DUCT FXMQ40PVE 27,5 / 22,3 4.7 2.8 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
39 PEU03-02B SIGNAL TELECOMMUNICATION O 2F 1 6.5 4.8 507 50 0.19 CEILING MOUNTED DUCT FXMQ63PVE 27,4 / 22,3 7.4 4.2 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
40 PEU03-02C ELECTRICAL CATENARY OFFICE 2F 1 7.2 5.5 572 50 0.22 CEILING MOUNTED DUCT FXMQ63PVE 27,3 / 22,0 7.4 4.3 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
41 PEU03-02D TRACK/CIVIL OFFICE 2F 1 6.4 4.6 479 50 0.19 CEILING MOUNTED DUCT FXMQ63PVE 27,5 / 22,4 7.4 4.2 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
42 PEU03-02E MACHINERY BUILDING OFFICE 2F 1 5 3.8 400 50 0.14 CEILING MOUNTED DUCT FXMQ50PVE 27,3 / 22,0 5.8 3.5 250/273/298 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
43 PEU03-02F SUB MANAGER ROOM 2F 1 5.5 4.3 451 50 0.19 CEILING MOUNTED DUCT FXMQ50PVE 27,3 / 22,1 5.8 3.4 250/273/298 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
44 PEU03-02G GUEST ROOM 2F 1 1.1 0.6 57 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 28,6 / 24.1 2.3 1.3 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
45 PEU03-02H MEETING ROOM 2F 1 8.8 4.1 367 50 0.22 CEILING MOUNTED DUCT FXMQ80PVE 28,7 / 24.8 9.5 5.1 331/373/415 50/100/200 0.185 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
46 PEU03-02I LOCKER ROOM (MALE) 2F 1 2.5 1.4 132 50 0.06 CEILING MOUNTED DUCT FXMQ25PVE 28,3 / 23.9 3 1.6 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
47 PEU03-02J LOCKER ROOM (FEMALE) 2F 1 2.9 1.7 171 50 0.06 CEILING MOUNTED DUCT FXMQ25PVE 28,0 / 23,4 3 1.6 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
48 PEU03-02K ENTRANCE HALL / CORRIDOR 2F 1 8.2 6.4 687 50 0.28 CEILING MOUNTED DUCT FXMQ80PVE 27,5 / 22,2 9.3 5.4 331/373/415 50/100/200 0.185 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
49 PCU03-02 -- ROOF 1 58.7 - - - 23.9 VRV OUTDOOR UNIT RXQ22TANY14 34,5 / -- 58.9 - - - 15.9 61 380/3/50 15.9 28.6 VRV OUTDOOR UNIT
WORKSHOP
50 PEU-04-04A RESTING ROOM 1 1F 1 5.9 4.4 383 50 0.14 CEILING MOUNTED DUCT FXMQ50PVE 27,3 / 21,3 7.3 4.6 266/290/323 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
51 PEU-04-04B RESTING ROOM 2 1F 1 4 2.7 252 50 0.15 CEILING MOUNTED DUCT FXMQ40PVE 27,4 / 22,0 4.7 2.8 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
52 PEU-04-04C PRAY ROOM 1F 1 7.1 3 235 50 0.19 CEILING MOUNTED DUCT FXMQ63PVE 29,0 / 23,9 7.5 4.1 266/290/323 50/100/200 0.139 38/40/42 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
53 PEU-04-04D CORRIDOR 1 1F 1 5 3.9 356 50 0.13 CEILING MOUNTED DUCT FXMQ50PVE 27,4 / 21,3 5.8 3.8 250/273/298 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
54 PEU-04-04E LOCKER ROOM (M) 1F 1 10 4.9 389 50 0.22 CEILING MOUNTED DUCT FXMQ100PVE 28,7 / 23,9 11.9 6.1 382/448/531 50/100/200 0.215 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
55 PEU-04-04F LOCKER ROOM (F) 1F 1 4.3 1.8 130 50 0.15 CEILING MOUNTED DUCT FXMQ40PVE 29,4 / 23,9 4.8 2.9 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
56 PCU04-04 -- 1F 1 36.3 - - - 10.9 VRV OUTDOOR UNIT RXQ14TAY14 34,5 / -- 38 - - - 10.7 60 380/3/50 12.7 28.6 VRV OUTDOOR UNIT
INSPECTION SHED
57 PEU05-01A RESTING ROOM 1 1F 1 4.3 2.7 257 50 0.15 CEILING MOUNTED DUCT FXMQ40PVE 27,6 / 21,9 4.7 2.9 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
58 PEU05-01B LOCKER ROOM 01 (F) 1F 1 2.1 1 97 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 28,2 / 23,3 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
59 PEU05-01C LOCKER ROOM 01 (M) 1F 1 2.3 1.2 113 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 28,1 / 23,0 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
60 PEU05-01D RESTING ROOM 2 1F 1 3.6 2.1 194 50 0.06 CEILING MOUNTED DUCT FXMQ32PVE 27,8 / 22,2 3.7 2.2 116/132/158 30/50/100 0.06 30/32/34 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
61 PEU05-01E INSPECTION ROOM 01 1F 1 3.8 2.2 210 50 0.151 CEILING MOUNTED DUCT FXMQ32PVE 27,8 / 22,1 3.7 2.3 116/132/158 30/50/100 0.06 30/32/34 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
62 PCU05-01 -- 1F 1 16.1 - - - 5.21 VRV OUTDOOR UNIT RXQ8TAY14 34,5 / -- 19.4 - - - 5.18 56 380/3/50 9.5 19.1 VRV OUTDOOR UNIT
63 PEU05-02A INSPECTION ROOM 02 1F 1 9.8 7.1 670 50 0.22 CEILING MOUNTED DUCT FXMQ100PVE 27,3 / 21,3 11.5 7.1 382/448/531 50/100/200 0.215 39/41/43 220/1/50 9.5 15.9 CEILING MOUNTED DUCT
64 PEU05-02B PRAYROOM 1F 1 5.4 2 188 50 0.13 CEILING MOUNTED DUCT FXMQ50PVE 29,0 / 23,9 5.9 2.9 250/273/298 50/100/200 0.128 37/39/40 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
65 PEU05-02C LOCKER ROOM 02 (F) 1F 1 2.2 1.3 119 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,7 / 22,8 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
66 PEU05-02D LOCKER ROOM 02 (M) 1F 1 2.2 1.3 119 50 0.06 CEILING MOUNTED DUCT FXMQ20PVE 27,7 / 22,8 2.3 1.4 108/125/150 30/50/100 0.056 29/31/33 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
67 PEU05-02E RESTING ROOM (CLEANING WOR 1F 1 4.5 3.2 304 50 0.15 CEILING MOUNTED DUCT FXMQ40PVE 27,3 / 21,5 4.7 3 182/218/264 30/50/160 0.151 35/37/39 220/1/50 6.4 12.7 CEILING MOUNTED DUCT
68 PCU05-02 -- 1F 1 24.1 - - - 7.29 VRV OUTDOOR UNIT RXQ10TAY14 34,5 / -- 24.5 - - - 6.88 57 380/3/50 9.5 22.2 VRV OUTDOOR UNIT
TOKYU WIKA JOINT OPERATION LIST OF EQUPMENT
Construction of Jakarta Mass Rapid
Transit
Surface Section CP101
SPLIT AIR CONDITIONING SYSTEM
MRT - DEPOT REMAINING BUILDING
F1,F2
PCU02-03 RXQ34TANY14 VRV Unit
F1,F2
PCU04-03 RNQ36MY14 Split Unit
F1,F2
PCU03-01 RXQ16TAY14 VRV Unit