0% found this document useful (0 votes)
1K views8 pages

AC Calculation

This document contains calculations to determine the appropriate air conditioning unit for three rooms. It provides the room name, size, temperature conditions, ventilation requirements, and breakdown of sensible and latent heat loads from people, equipment, lighting and fresh air. Total cooling capacities ranging from 1.6 kW to 30.1 kW are calculated. Load per unit area is also reported, ranging from 167-464 W/m2.

Uploaded by

Fauzi Rahman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views8 pages

AC Calculation

This document contains calculations to determine the appropriate air conditioning unit for three rooms. It provides the room name, size, temperature conditions, ventilation requirements, and breakdown of sensible and latent heat loads from people, equipment, lighting and fresh air. Total cooling capacities ranging from 1.6 kW to 30.1 kW are calculated. Load per unit area is also reported, ranging from 167-464 W/m2.

Uploaded by

Fauzi Rahman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
  • Air Conditioner Calculation - Utility Room Telecom: Provides a detailed calculation of air conditioning requirements for the Utility Room Telecom, including room size, ventilation, and load breakdowns.
  • Air Conditioner Calculation - New Panel Room: Calculates air conditioning needs for the New Panel Room on the 1st Floor, with specifications on room temperature, size, and equipment load.
  • Air Conditioner Calculation - New Server Room: Details air conditioning calculations for the New Server Room on the 2nd Floor, covering room temperature, load distribution, and cooling capacity.
  • Air Conditioner Calculation - Multifunction Room: Contains air conditioner load calculations for the Multifunction Room in the East Jakarta Japanese School, including a breakdown of various load factors.

AIR CONDITIONER CALCULATION

DEPOT REMAINING BUILDING


INFRASTRUCTURE MAINTENANCE OFFICE

Room name :  UTILITY ROOM TELECOM


Room temperature
conditions :  27℃ / RH 60%

Outside air condition :  40℃ / RH 60%

Room size :  3m x 4.1 m x 4.3

Ventilation volume :  52.89 m3 x 3 ACH = 158.67


45.00

1) Room load (sensible heat)


:  60 w x 2 Person = 120
People load
Lighting load  :  20 w x 12 m2 = 246
Building load :  60 w x 12 m2 = 738

:  1500 w x 60 % = 1,050
Equipment load

2) Room load (latent heat)


People load :  80 w x 2 Person = 160

3) Fresh air load


Sensible heat  :  0.33 w x 158.67 CMH x 13
Latent heat :  833 w x 158.67 CMH x 0.0069

Subtotal  2,314 w x 1.1 (SF 10%) = 2545.4


= 2.5

Load per unit area = 207

1
Room area : 12 m2

Room
mH 52.89 m3
volume :
CMH
L/S

W
W
W
W

℃ = W
kg/kg (DA) = W
# Fresh Air by Natural Grille

W
kW (Total Cooling Capacity)

W/m2

2
AIR CONDITIONER CALCULATION
DEPOT REMAINING BUILDING
WORKSHOP OFFICE

Room name :  NEW PANEL ROOM (SERVICE ROOM) - 1st Floor


Room temperature
conditions :  27℃ / RH 60%

Outside air condition :  40℃ / RH 60%

Room size :  1.4 m x 3.8 m x 4.3

Ventilation volume :  22.88 m3 x 3 ACH = 68.63


20.00

1) Room load (sensible heat)


:  60 w x 2 Person = 120
People load
Lighting load  :  20 w x 5 m2 = 106
Building load :  60 w x 5 m2 = 319

:  850 w x 100 % = 850


Equipment load

2) Room load (latent heat)


People load :  80 w x 2 Person = 160

3) Fresh air load


Sensible heat  :  0.33 w x 68.63 CMH x 13
Latent heat :  833 w x 68.63 CMH x 0.0069

Subtotal  2,244 w x 1.1 (SF 10%) = 2468.9


= 2.5

Load per unit area = 464

3
Room area : 5 m2

Room
mH 22.88 m3
volume :
CMH
L/S

W
W
W
W

℃ = 294 W
kg/kg (DA) = 394 W
# Fresh Air by Intake Fan

W
kW (Total Cooling Capacity)

W/m2

4
AIR CONDITIONER CALCULATION

Room name :  NEW SERVER ROOM - 2nd Floor


Room temperature
conditions :  27℃ / RH 60%

Outside air condition :  40℃ / RH 60%

Room size :  1.8 m x 3.7 m x 2.6

Ventilation volume :  17.32 m3 x 3 ACH = 51.95


= 15.00

1) Room load (sensible heat)


:  60 w x 2 Person = 120
People load
Lighting load  :  20 w x 7 m2 = 133
Building load :  60 w x 7 m2 = 400

:  = 160
Equipment load

2) Room load (latent heat)


People load :  80 w x 2 Person = 160

3) Fresh air load


Sensible heat  :  0.33 w x 51.95 CMH x 13
Latent heat :  833 w x 51.95 CMH x 0.0069

Subtotal  1,494 w x 1.1 (SF 10%) = 1643.7


= 1.6

Load per unit area = 247

5
Room area : 7 m2

Room
mH 17.32 m3
volume :
CMH
L/S

W
W
W
W

℃ = 223 W
kg/kg (DA) = 299 W

W
kW (Total Cooling Capacity)

W/m2

6
AIR CONDITIONER CALCULATION
EAST JAKARTA JAPANESE SCHOOL

Room name :  MULTIFUNCTION ROOM


Room temperature
conditions :  24℃ / RH 60%

Outside air condition :  35℃ / RH 60%

Room size :  9m x 20 m x 3

Ventilation volume :  540 m3 x 2 ACH = 1080


300.00

1) Room load (sensible heat)


:  60 w x 20 Person = 1,200
People load
Lighting load  :  20 w x 180 m2 = 3,600
Building load :  60 w x 180 m2 = 10,800

:  w x % = 0
Equipment load

2) Room load (latent heat)


People load :  80 w x 20 Person = 1,600

3) Fresh air load


Sensible heat  :  0.33 w x 1,080.00 CMH x 11
Latent heat :  833 w x 1,080.00 CMH x 0.0069

Subtotal  27,328 w x 1.1 (SF 10%) = 30060.7


= 30.1

Load per unit area = 167


= 570
= 600

7
Room area : 180 m2

Room
mH 540 m3
volume :
CMH
L/S

W
W
W
W

℃ = 3,920 W
kg/kg (DA) = 6,208 W
# Fresh Air by Natural Grille

W
kW (Total Cooling Capacity)

W/m2
BTUH/m2
BTUH/m2 (Rounded)