Professional Documents
Culture Documents
This chapter presents the proposed layout of facilities, design considerations and design
standards and specifications. Preliminary viable design of the project is also presented together
with standards which are used to come up with it. All designs presented in this chapter are based
on the National Structural Code of the Philippines (NSCP), National Building Code of the
Academic facilities must be a priority of a school development plan since these facilities
will help on the educational growth of students which will lead them as qualified participants
of nation building. Academic laboratories, buildings and gymnasiums are one of these
facilities.
According to the population growth table of Calantas National High School as discussed
on chapter 1 under table., the school’s total population will boost up to 850 persons by year
2029. This implies that additional facilities must be built to accommodate the growth. Also,
since the school offers ABM, HUMSS and TechVoc (Agriculture) tracks, related laboratories
topography, direction of water flow, air circulation and natural lights. These facilities
include:
PLEASE INSERT the two four storey building pics. Include description
The four storey academic building is intended for the students’ classes. Also, the
building has faculty rooms for the staffs of each department and storage rooms for the
files or other important materials. Restrooms are also included in the building plan
divided into male, female and persons with disabilities (PWD) restrooms. Table shows
Table 6
Standard
NBC)
1.4 sq. m per
Classroom 7.00 x 9.00 63.00 45 students
occupant
14 faculty
Faculty Room 9.00 x 4.50 40.50 -
teachers
Comfort Room 4.50 x 3.50 15.75 4 cubicles -
(Male and Female)
PWD Comfort
2.75 x 2.70 7.425 1 person
Room
Storage Room 2.75 x 2.70 7.425 - -
Table 6
Standard
NBC)
1.4 sq. m per
Classroom 7.00 x 9.00 63.00 45 students
occupant
14 faculty
Faculty Room 9.00 x 4.50 40.50 -
teachers
Comfort Room
4.50 x 3.50 15.75 4 cubicles -
(Male and Female)
PWD Comfort
2.75 x 2.70 7.425 1 person -
Room
Storage Room 2.75 x 2.70 7.425 - -
The facilities for both of the four storey two-classroom buildings are the same.
For aesthetic purposes, their only difference is the placement of stairs and the building’s
finishing accessories. In this way, the visitors may easily distinguish whether the building
is for senior high school or junior high school. The stairs for senior high school academic
building is placed at the center of the building while for the junior high school academic
Every storey of both buildings has two academic classrooms with a total area of
63 square meters and a dimension of 7 meters x 9 meters. Each room will be well-spaced
classrooms will be constructed per building which can accommodate a total of 360
students. This is based on the total projection of the student population after 10 years
which is 800 students. Faculty rooms are located on the ends of the second and third
floor of the building with a dimension of 9 meters by 4.50 meters which can
accommodate a total of 56 faculties per building. Every room also has their own comfort
room of 3 square meter area. PWD restrooms are located at both ends of the ground floor
with a total area of 7.425 square meters. Male restrooms will be located at the left ends of
ground floor and third floor while the female restrooms will be located on the other ends.
Every restroom has a total area of 15.75 square meters that has 4 cubicles each. At fourth
floor, storage rooms are situated at both ends with area similar to the PWD restroom
Each classroom has 2 main doors, 4 –double panel sliding windows, and an extra
1 door at the back as fire exit. 3-double panel windows, 1 main door and 1 door and 1
awning window for CR are installed for every faculty rooms. Storage rooms, PWD
restrooms and male and female restrooms both have 1 awning window and 1 entrance
door.
Accessories for academic classrooms include armchairs, glass boards, and a
teacher’s table. Whereas for faculty rooms, office tables, chairs and cabinets are the main
accessories. For safety reasons, railings and handrails will be installed on every
building’s stairs and balconies. Also, handrails will be installed in the PWD restroom in
compliance with the NBCP. Ramps will also be constructed at the entrance for persons
with disabilities.
Actual works relating to the subjects the students are taking will be done in the laboratory.
The proposed two storey laboratory building consists of TechVoc Laboratory, Science
Laboratory and Computer Laboratory. Male and female restrooms are also included in the
building together with Storage rooms. The dimensions of the facilities are summed up into
table
Table 6
(based from
NBC)
Technical
LAB)
Storage Room 9.00 x 4.50 40.50 - -
Comfort Room
4.50 x 3.50 15.75 4 cubicles -
(Male and Female)
2.1 sq. m per
Science Laboratory 7.00 x 18.00 126.00 60 students
person
PWD Comfort
2.75 x 2.70 7.425 1 person
Room
Computer
2 laboratory
Laboratory 2.75 x 2.70 7.425 -
technicians
Technician’s Office
located on the ground floor of the building. It is intended for the use of senior high school
students taking up the Agriculture Strand under TVL Track. The facility has a dimension
of 7 meters x 27 meters with a total area of 126 square meters. It can accommodate a total
of 60 students during their laboratory works regarding agriculture. It will also serve as
storage place for farming equipment. Also, if there is an upcoming event to be held in the
school, the TVL Laboratory may be used as function hall by removing its foldable
partitions.
Science Laboratory and Computer Laboratory is placed at the second floor of the
building. The Science laboratory will be used as a place where the junior high school
students will perform their experiments on Physics or Chemistry. Laboratory chairs and
tables and glass boards are the accessories of this laboratory. Meanwhile, storage rooms
for this laboratory are placed at both ends of the building’s second floor. Materials which
are fragile, and heavy will be stored on the storage room adjacent with the laboratory
together with the different chemicals. Lightweight materials and laboratory gowns will be
kept in the farther storage room. Storage rooms will be provided with cabinets and closets
for materials.
On the other hand, students taking up ABM Track will use the provided
Computer Laboratory for their computations as part of their subjects. The laboratory can
accommodate a total of 45 students with provided personal computer for every student.
Glass boards will also be installed for lectures about computer use.
PWD restrooms will be provided at the first floor of the building with a total area
of 7.425 square meters. Male and female restrooms is located on the second floor with a
total area of 15.75 square meters each that can accommodate a total of 4 persons at a
time.
All rooms will be properly ventilated by installing doors and windows. Air will
be circulated using ceiling fans. The Computer Laboratory will be air-conditioned for the
2 main doors and a fire exit. The same number and kind of doors and windows are also
installed at the Science Laboratory. 3-double panel windows, 1 main door and 1 door
are installed for every storage rooms. PWD restrooms and male and female restrooms
3. Proposed Gymnasium
incorporates the design of a gymnasium as part of the proposed project. The facility will
serve as a location for sport activities in the school such as intramurals and other special
that can accomodate 680 students. A stage will also be included within the gymnasium
with an elevation of 1 meter from the ground. Table shows the list of facilities included
Table
Proposed Gymnasium
Facilities Dimension (m) Area (m2) Capacity
Basketball Court 30.00 x 45.00 1,350 680 students
6 cubicles & 3
Comfort Room 3.00 x 4.00 31.50
urinals
Comfort rooms are also included on the gymnasium. Each comfort room will have its
own floor drains with the floor slightly sloping towards it.
4. Retaining Walls
Retaining walls will be built along the sloping areas where erosion is present and where
cutting of land will be done. Cantilever retaining walls will be constructed with a total
walls with a height of 3.2m while a total length of INSERT LENGTH NUNG RETAINING
WALLS NA 2.7METERS for walls with height of 3 meters. These walls will be designed to
prevent erosion and for aesthetic purposes, as division of the different land elevations on the
site.
5. Perimeter Fence
The overall perimeter and boundaries of the site will be laid out with perimeter
fence. The fence will be constructed of Concrete Hollow Blocks (CHB#5) for its walls
with 12mm diameter rebars for horizontal and vertical reinforcements, reinforced
concrete for columns with 4-16 mm and 2-12mm rebars, and tubular bars for entrance
gates and angular bars for perimeter grills. The column of the fence will have a
dimension of 300mm by 300mm. The total perimeter of the fence will be 416.69 meters.
The water demand on site is approximated to be 45 cubic meters per day after 10 years.
This approximation is based on the total projected population which is 850 persons, from a
projected 5 cubic meters for the school farm’s irrigation and from an allowance of 10 cubic
meters in case of emergencies. The water tank will be positioned at the center of the existing
The concrete road will be designed based from the standards set by the Department of Public
Works and Highways (DPWH). The road width will be 3.5m. This concrete road will be used as
an access to the different buildings and facilities of Calantas National High School. The parking
on the other hand will be located in an area which it is more efficient, where vehicles can move
with ease. Signs or symbols will be slightly placed to guide or inform the drivers.
The proposed road section of the proposed project shows in Figure 6 . A seven (7) meters
wide and insert total length of roads meters long concrete paved road will be constructed to have
access from the outside to the proposed site development of Calantas National high School
Figure 5.
Based on Department of Public Works and Highways (DPWH) that shows in Figure 5, item
105 means subgrade material, item 200 is the aggregate subbase course and item 311 is the
This college building as art of the facilities will feature the common utility that includes:
1. Power Supply
The Batangas Electric Cooperative II Inc. (BATELEC II) supplies the electricity in the site
being the nearest source of electricity that can be accessed. Also, the proposed facilities are
The shallow well with electric pump and Municipality Water District supply the water in the
site. Other supplies are from barangays water works, deep well and shallow tube well. The water
from the water district is stored on tanks to supply the college school in case of water deficiency.
3. Drainage System
The drainage system in this project should follow all the provison implemented by the
municipal ordinances. The project also uses the drainage line present in the barangay road and
Calantas National High School will use different references and bases for the standard
designs of the buildings such as the National Building Code, Educational Facilities Manual 2010
Site Development Plan is a graphic presentation of the Site Development Program. Its
main function is to show the school site in its present status and the current program period.
Thus, preparing the site development plan is an exercise in the layout of infrastructure based on
The principle in the preparation of the Site Development Plan is that all physical structures
with similar functions shall be grouped together. The grouping of these structures is in
accordance with the most favorable option for grounds utilization which creates functional zones
School buildings shall be oriented in accordance with the sun path or the east-west course of
the sun during the day. Variations in the sun path on certain season of the year are negligible. To
prevent the direct entry of sunlight into the instructional spaces, buildings shall be laid out along
3. Arrangement of Buildings.
Buildings shall be arranged to facilitate cross ventilation by exposing the window sides to the
4. Site Limitations.
When there are site limitations, such as the unfavorable area and/or shape of the site, prevent
the proper solar orientation of buildings, economical alternatives shall be resorted to. For
example, trees near the building are effective for minimizing the direct entry of sunlight into
instructional spaces. Also, trees and shrubs between the buildings and street will serve as
acoustic barriers.
Layout
The layout of school building on the school site refers to the location and arrangement of
school buildings to achieve maximum functional efficiency and aesthetic effect. As a general
rule, the different school buildings shall be laid out according to functional grouping. The
suggested.
Greater distance than the minimum between school buildings is desirable. Wider
distance between buildings allows for adequate free space to be utilized for many
school-related activities.
e. The recommended minimum setback of a school from the street is five (5) meters to
f. The School Site Development Plan must be considered in the laying-out of school
buildings.
Table 9 shows the standards and requirements between the distances of each building and
setback as per Educational Facilities Manual. It includes the distances used by the proponents
in their designs together with setback used for the Calantas National High School.
Table
Setback of School
Minimum Setback Setback Used
5 meters 5 meters
Table shows the summarized standard minimum distances between buildings and the
distances used on each proposed building. Standard minimum setback and the setback used are
also included in the table. This shows that the following buildings have followed the standard
requirements prescribed.
Design Requirements
The following pertinent requirements prescribed in the National Building Code of the
a. Windows.
Window openings shall be equal to or at least ten (10) percent of the floor area of the
room, provided that such opening shall be not less than one square meter, except those in
toilets and baths which shall be not less than one-twentieth of the floor area of such rooms, or
b. Ceiling Height.
The ceiling height of rooms with natural ventilation shall be not less than 2.70 meters
measured from the floor to the ceiling; rooms provided with artificial ventilation shall have
All floors shall be so framed and secured into the framework and supporting walls so as to
form an integral part of the whole building; the type of floor construction used shall
provide means to keep the beam and girders from lateral buckling.
d. Roof Construction.
All roofs shall be so framed and tied into the framework and supporting walls so as to
form an integral part of the whole building; dark stops, roof drains, flushing, etc., shall be
provided. Purlins can be made up of angle bars instead of the conventional C-purlins where
text screws easily loosen resulting in detachment of roofs. The thickness of the angle bar
serves as a knot, holding text screws firmly. Purlins are securely welded to steel trusses
e. Exit Doors.
At least two (2) exit doors are required where the number of room occupants is over 50 in
the case of classrooms, conference rooms, exhibit rooms, gymnasium, school shops,
vocational institutions, laboratories, and auditorium; a door shall not be less than 2.10 meters
f. Corridors.
Corridors are required at ground level if appropriate direct access to enclosed spaces is
provided. Every corridor shall not be less than 1.10 meters wide and shall be unobstructed.
Above ground level, the minimum clear width is 2.00 meters provided that the provisions of
the National Building and Fire Codes of the Philippines and other relevant rules and
Stairways serving an occupant load of 50 or less must be 1.10 meters wide; those servings
more than 50 shall not be less than 1.50 meters. The rise of every step shall not exceed 200
millimeters and the tread shall not be less than 250 millimeters. Handrails shall be provided
Table 19
Design Requirements
Table shows the summarized standard design requirements considered on the design and the
measurements used on the design. This shows that it has followed the standard requirements
Science Laboratory
In designing/constructing a Science Laboratory, the building must have the following features
1. The science laboratory should be designed as a wide space to allow mobility inside the
room.
2. There should be at least two (2) entry/exit doors for easy access and egress. The doors
3. The science laboratory should have provisions for laboratory counter, control room and
storage room.
storage/stockroom. The storage room and control room should be equipped with built-in
cabinets not higher than 1.90 meters. Bolt storage cabinets to the wall and install strong
latches so that doors will remain closed as contents of cabinets can shift during an
earthquake.
5. Stock/storage room should be provided with security grills on the windows to ensure the
6. Science laboratory buildings should provide with neutralization tank/drain pit for proper
7. The working tables inside the science laboratory should be fixed on the floor. It should be
made of reinforced concrete with mosaic tiles topping and should be acid resistant. Each
9. Laboratory working areas should be well lighted and have a bilateral fenestration for
11. Every Science Laboratory room should have a notice/reminder posted on conspicuous
side of the room for students’ awareness and shall be provided with a First Aid Kit.
12. Single storey, science laboratory building should be located far from academic
classrooms.
13. In case of multi-storey building, the science laboratory should be located on the highest
Computer Laboratory
The Computer Laboratory is a special instructional space necessary to meet the current
and future demand of modern technology. The room shall provide at least a minimum space
of 1.40 square meter per place and shall accommodate at least ten (10) networked Personal
C. Preliminary Design
Architectural Plan
The Department of Education Facilities Manual and Building Code of the Philippines
were considered in the design of the proposed structures to make sure that all requirements and
standards are met in terms of its quality and appearance. See Appendix A for the detailed plans
2. Perspectives
3. Floor Plans
4. Elevations
a. Front Elevation
b. Rear Elevation
5. Sections
a. Longitudinal Section
b. Transverse Section
Structural Design
Structural analysis of the proposed buildings will be done as per National Structural Code
of the Philippines 2015. All the geotechnical data to be used will be acquired from the
At the same time, all materials chosen for the construction will conform to the standards
of Department of Education and complying with the National Building Code of the Philippines
Electrical Design
The electrical design of the proposed project should be observed for the safety of the
users. Thus, the electrical design and analysis should obey the Philippine Electrical Code (PEC).
Mechanical Design
All buildings will follow the standard ventilation and air-conditioning principles
The proponents will base their design from Uniform Plumbing Code 2013 Edition and
Plumbing Design regarding the standard specifications and requirements of proper sanitation,
The basis of the structural analysis of the proposed project is the National Structural Code
1. Dead Loads
Dead load is a constant load in a structure that is due to the weight of the
members, the supported structure, and the permanent attachments or accessories. The
dead loads are calculated from the member sizes and estimated material densities. The
minimum design dead loads are determined from Table 204-2 of Section 204 of the
NSCP 2015.
2. Live Loads
Live loads refers to loads that do, or can, change over time, such as people
maximum loads expected by the intended use or occupancy but in case shall be less than
the loads required. Minimum uniform and concentrated live loads that will be used will
refer to the Table 205 of this code. For the Roof Live Load, Table 205-3 of section 205.4
of the NSCP 2015 presents the minimum roof live loads. (Note: Design tables from
NSCP and other reference used in the design are shown in Appendix B.)
3. Wind load
Wind load is the force in the structure arising from the impact of wind on it. All
vertical structures must be designed and constructed to resist wind loads. The general
requirements use to determine the basic parameters for determining wind loads on main
wind force resisting system and components and cladding basis is in accordance to
section 207A of National Structural Code of the Philippines 2015. The basic parameters
includes: Basic Wind Speed, V on figure 207A.5 -1A, B or C, Wind directionality factor,
section 207A.10 and Internal pressure coefficient, GCpi on section 207A-1. The
directionality factor shall only be included in determining wind loads when the load
combinations specified in Section 2.3 and 3.4 of the National Structural Code of the
Philippines 2015 are used for the design. For the Internal pressure coefficients, GC pi, it
shall be determined from Table 207A.11-1 based on the building enclosure classifications
determined from Section 201A.10 of National Structural Code of the Philippines 2015.
4. Earthquake Load
portions thereof shall, as a minimum, be designed and constructed to resist the effects of
seismic ground motions as provided in the section 208 of NSCP 2015. The general
section 208.4 of National Structural Code of the Philippines 2015. These basic
Table 208-3, Seismic Zone on section 208.4.4, Fig. 208-1 Seismic Zone Factor on Table
208-3, Seismic Source Types on Table 208-4, Near Source Factors, N A and Nv on Table
208-5 and Table 208-6, Seismic Response Coefficients, C A and Cv on Table 208-7 and
Ultimate Strength Design will be used in the computation of structural analysis of the
proposed buildings. The following are the design criteria that will be used from NSCP 2015:
1. Procedure in Determining Wind Loads for enclosed, partially enclosed and open
buildings of all heights under Table 207B.2-1 of National Structural Code of the
b) Determine the basic wind speed, V, for the applicable risk category.
Exposure Category
Enclosure Classification
d) Determine the velocity pressure exposure coefficient, Kh.
qh = 0.613KzKztKdV2 ; (V in m/s)
2. Seismic Load Analysis According to NSCP 2015 and Uniform Building Code
a. Determine Seismic factors from Tables 208-1 to 208-8 of the NSCP 2015
Importance Factor, I
Seismic Coefficient, Ca
Seismic Coefficient, Cv
Structural System Factor, R
TA = Ct(hn) ¾
Where:
0.0731 for reinforced concrete moment resisting frames and eccentrically based
frames,
6.1
p=2−
rmax √ Ab
Loads are transferred into slabs as one way or two way. For each type of slab, the design
b. Determine the minimum slab thickness (h) using the following tables from the code:
Slabs
Table 408.3.1.1 – Minimum thickness Of Solid Non Prestressed Two-Way
h. Compute the required main bar spacing with the minimum result obtained from this
conditions:
3h
450mm
i. Calculate the required steel ratio of temperature bars (pt) and its spacing based on
The design of beam will be done in compliance with the National Structural Code
of the Philippines 2015. Under this code, specific sections for minimum beam depth,
The following are the specific steps in designing a reinforced rectangular beam for
flexure.
a. Calculate the loadings in terms of dead loads and live loads which will be carried by
the beam.
b. Assume the minimum overall depth, h of the beam by adhering to the minimum depth
c. Compute the beam weight by estimating the width as equal to ½ of assumed value of h
and multiplying it with h/144 times the concrete weight per foot.
f. Try a value of steel ratio ρ from 0.5 ρb , but not less than ρmin
ρmin = 1.4/fy
reasonable dimension. Check also the minimum thickness of the beam required by the
All loads coming from slabs and beams are transferred into columns. Columns
support compressive loads with or without bending. The design of columns used in the
proposed structures will adhere the requirements and standards of National Structural Code
For a column subjected purely to an axial load, the nominal load is computed by
the equation:
In case of eccentricity effects, the factor of 0.80 is multiplied to Pn for tied columns whereas
0.85 to spiral columns. The ultimate axial load capacity or Pu is computed by using these
reduction factors:
Based on NSCP 2015, all columns with an average fpe<1.6MPa, area of longitudinal
reinforcement shall be at least 0.01Ag but shall not exceed 0.08Ag. Also, minimum of for
The total load of a building is transmitted to the underlying soils by the footing.
Its large area reduces the bearing and compressive stress cause by the large value of loadings
The footings to be used in the proposed structures shall be proportioned to resist the
factored loads and induced reactions, in compliance with the requirements of NSCP 2015.
Steel structures will be designed based on the design standards and specifications stated
on the Chapter 5 National Structural Code of the Philippines 2015. The Load Resistance and
a. Load Combinations
The load combinations according to the LRFD to be used on the design will be:
1. 1.4(D + F)
Slenderness
Tensile Yielding
Tensile Rupture
1. General Form:
Slenderness
Flexural buckling
kL E
If ≤ 4.71 √ ,then: 𝐹𝑐𝑟 = 0.658QF𝑦/𝐹𝑒 (Q𝐹𝑦)
r Fy
kL E
If > 4.71 √ ,then: 𝐹𝑐𝑟 = 0.877Fe
r Fy
KL=¿effective length
1. GeneralForm:
0.90
Flexural yielding
Lateral-Torsional Buckling
W here :
All geotechnical standards and requirements to be constructed will conform with the
Chapter 3 of National Structural Code of the Philippines. Cutting and Filling of Slopes will be
done according to the Sections 301 and 302 of NSCP. Specifically, Erosion Control will be done
according to Section 302.6 of the code which is entitled “Erosion Control”. Meanwhile, the
design of fotings and foundations will be done based on the code’s Section 303, Section 304 and
Section 305.
BIBLIOGRAPHY
A. Books
Association of Structural Engineers of the Philippines, 2015. National Structural Code of the
Philippines, 2015. Seventh ed. Quezon City: The Association of Structural Engineers of
the Philippines Inc.
Department of Education, 2010. DepEd Educational Facilities Manual 2010. Revised Edition of
2007 ed. Pasig City: Physical Facilities and School’s Engineering Division Office of
Planning Service.
B.Online References
World Bank 2017. Assessing Basic Education Service Delivery in the Philippines: Public
Education Expenditure Tracking and Quantitative Service Delivery Study from
http://www.worldbank.org/en/country/philippines/public-education-expenditure-tracking-
and-quantitative-service-delivery-study