Professional Documents
Culture Documents
Industrial Waste Water Auxiliary Treatment System
Industrial Waste Water Auxiliary Treatment System
carried out
Root’s Blower-A Suction Fan is Intact And its Mesh is Clean 10GNC11AA*** Check
Root Blower-B Suction Fan is Intact And its Mash is Clean 10GNC12AA*** Check
10GNC12*****
Root Blower-B Discharge Line Relief Valve is Intact and its root Valve Check Open
10GNC12AA***
10GNC12CP101
Root Blower-B Discharge pressure Indicator is Intact and its root Valve Check Open
10GNC12AA101
Root Blower-B Discharge Isolating Valve 10GNC12AA001 Close
Root Blower Common Header Vent SOV is Intact 10GNC10AA101 Check
Root Blower Common Header Vent SOV 10GNC10AA101 Close
Root Blower Air to Storage pond-1 SOV is Intact Check
Root Blower Air to Storage pond-1 SOV Open
Root Blower Air to Storage pond-2 SOV is Intact Check
Root Blower Air to Storage pond-2 SOV Close
Post
Maintenance
Checks For
Storage Pond
Waste Water From Unit Drainage Pond isolating valve Close
E. Pump and Motor Base plate Bolts are In place Motor
Post
Maintenance
Checks For pH
Regulator Tank
pH Regulator Tank Inlet Isolation Valve 10GNL20AA001 Open
pH Regulator Tank Drain Isolation Valve 10GND10AA401 Close
Acid Dosing valve at the inlet of pH regulation tank 10GND10AA601, Open
Caustic Dosing valve , at the inlet of pH regulation tank 10GND10AA602, Open
10GND10AM00
pH Regulator Tank Agitator Motor Check
1
A. Motor are Coupled and Coupling guard in place. Coupl
B. Motor Fan cover in place.
C. Motor Ground strip in place.
D. Motor Base plate Bolts are In place
pH Regulator Tank PH Indicator is Intact and its root Valve. 10GND10CQ001 Check Open
PRE-START
CHECK OF
FLOCCULATIO
N TANK
Flocculation Tank Drain Isolation Valve 10GND20AA401 Close
PAC Dosing valve , at the inlet of the Flocculation tank 10GND20AA602, Open
10GND20AM00
Flocculation Tank Agitator Motor Check
1
Wash Water for Sludge Line From Industrial Water isolating Valve 10GNS10AA401 Close
Clarified Sludge pump-2 Discharge Line Drain Isolating Valve 10GNS12AA401 Close
Final Neutralizer Pond Inlet from Inclined Plate Clarifier Inlet isolating Valve 10GND40AA001 Open
10GND50AM00
Final Neutralizer Pond Mixer Check
1
A. Motor are Coupled and Coupling guard in place. Coupl
B. Motor Fan cover in place.
C. Motor Ground strip in place.
D. Motor Base plate Bolts are In place
10GND50CQ101
Final Neutralizer Pond Level Transmitter is intact and its root Valve CheckOpen
10GND50AA101
Clarified Water Pond Pump-1 Discharge Pressure Indicator is Intact and its 10GND61CP501
CheckOpen
root Valve 10GND61AA501
Clarified Water Pond Pump-1 Discharge Isolating Valve 10GND61AA001 Open
Clarified Water Pond Pump-1 10GND61AP001 Check
A. Motor And Pump are Coupled and Coupling guard in place. Coupl
B. Motor Fan cover in place.
Clarified Water Pond Pumps Discharge NTU Transmitter is Intact and its root 10GND60CF101
Check Open
Valve 10GND60CA102
and Clarified Water Pond Pumps Discharge to Reuse Water Pond SOV is
10GND60AA101 Check Close
Intact
and Clarified Water Pond Pumps Discharge to Waste Water Storage Pond
10GND60AA102 Check Open
SOV is Intact