350 KTA LLDPE PLANT Vol. : 4
Project n° 61070F
Process Design Package
VOLUME 4
CHAPTER 3
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial
Services UK Limited, and the information and images it contains are strictly confidential and may not be altered or
amended, copied, used or disclosed without the express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
SPECIFICATION
Document revisions.
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and the information and
images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the express permission of INEOS Commercial
Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
CONTENTS
1. INTRODUCTION................................................................................................................................................................ 7
1.1 MISCELLANEOUS ................................................................................................................................................... 8
1.2 ABBREVIATIONS ..................................................................................................................................................... 8
1.3 REFERENCE DOCUMENTS .................................................................................................................................. 8
2. INTERLOCK TABLES .................................................................................................................................................... 10
2.1 SECTION 100 .......................................................................................................................................................... 10
I-1010-O: FLARE DRUM PUMPS ................................................................................................................................. 10
I-1012-O: FLARE KO DRUM OVERFILL ..................................................................................................................... 10
I-1013-O: BACK FLOW FROM OSBL TO FLARE ...................................................................................................... 10
I-1020-O: LP CONDENSATE RETURN PUMPS PROTECTION ............................................................................. 11
I-1508-O: POWDER RECEIVER DRUM EMPTYING ................................................................................................ 11
I-1601-O: POLYMER WATER EXPORT PUMP STOP / START BY LEVEL CONTROL ..................................... 11
I-1702-O: PHNP (HIGH PRIORITY HP NITROGEN) NITROGEN SUPPLY PRIORITY ...................................... 12
I-1730-S: BACKFLOW INTO PHNP NITROGEN FROM USERS ............................................................................ 12
I-1731-S: BACKFLOW INTO MN NITROGEN FROM MN AND LN USERS .......................................................... 12
I-1732-S: BACKFLOW INTO LP NITROGEN FROM MPN USERS ........................................................................ 13
I-1733-S: BACKFLOW INTO LP NITROGEN MAIN HEADER ................................................................................. 14
I-1744-S: BACKFLOW INTO HP NITROGEN FROM NITROGEN TREATERS .................................................... 14
I-1751-S: BACKFLOW INTO LP NITROGEN FROM LPN USERS ......................................................................... 14
2.2 SECTION 200 .......................................................................................................................................................... 16
I-2025-O: HIGH TEMPERATURE IN STEAM CONDENSATE HEADER FROM ETHYLENE REGENERATION
HEATER ............................................................................................................................................................................ 16
I-2302-S: ETHYLENE O2 AND CO REMOVAL TREATERS EXOTHERM ............................................................ 16
I-2303-S: LOW PRESSURE AT SUCTION OF ETHYLENE COMPRESSOR ....................................................... 18
I-2304-S: FPU ETHYLENE DEPRESSURISATION ................................................................................................... 18
I-2305-O: ETHYLENE RECYCLE COMPRESSOR AUTO-START ......................................................................... 19
I-2306-S: LOW TEMPERATURE IN ETHYLENE O2 AND CO TREATERS .......................................................... 19
I-2307-S: REGENERATION AIR TO FLARE............................................................................................................... 20
I-2308-O: ETHYLENE CO/O2 TREATERS EXOTHERM DUE TO EXCESS H2 INJECTION ............................ 20
I-2309-S: HC RELEASED TO ATM DURING ETHYLENE TREATERS REGENERATION ................................ 21
I-2310-O: ETHYLENE CO/O2 TREATERS EXOTHERM DUE TO EXCESS O2 INJECTION ............................ 21
I-2311-O: HIGH PRESSURE AT ETHYLENE COMPRESSOR ............................................................................... 22
I-2312-O: ETHYLENE FEED TO TREATERS HEATING CUT-OFF ....................................................................... 22
I-2314-O: BACKFLOW THROUGH ETHYLENE COMPRESSOR MINI FLOW LINE ........................................... 22
I-2323-S: BACKFLOW INTO REGENERATION INSTRUMENT AIR FROM ETHYLENE TREATERS ............. 23
I-2324-S: HC RELEASED TO ATM DURING COMONOMER OR PENTANE TREATERS REGENERATION 23
I-2327-S: LOW TEMPERATURE IN ETHYLENE ADSORBERS ............................................................................. 24
I-2328-O: BACKFLOW INTO H2 FROM CO/O2 ETHYLENE TREATER ............................................................... 24
I-2410-S: COMONOMER PREPARATION UNIT ISOLATION ................................................................................. 25
I-2411-O: COMONOMER PUMPS ................................................................................................................................ 25
I-2412-O: COMONOMER DRUM OVERFILLING ....................................................................................................... 26
I-2416-S: COMONOMERS SIMULTANEOUS FEED................................................................................................ 26
I-2417-O: COMONOMER INJECTION PUMPS .......................................................................................................... 27
I-2420-S: PENTANE PREPARATION UNIT ISOLATION.......................................................................................... 27
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
ST
I-8249-O: 1 EXTRUDER FEED SCREW ................................................................................................................ 102
ND
I-8250-O: 2 EXTRUDER FEED SCREW ................................................................................................................ 102
I-8251-O: EXTRUDER STOPPED .............................................................................................................................. 103
I-8252-O: ADDITIVE ACCUMULATION WHEN POWDER FEED TO EXTRUDER IS STOPPED................... 103
I-8256-S: NITROGEN AND DUST EXPLOSURE FOR OPERATOR IN ADDITIVE FIBC UNLOADING
STATIONS ...................................................................................................................................................................... 104
I-8260-O: POLYMER VIBRATING SCREEN WASTE SKIP SYSTEM .................................................................. 106
I-8417-O: PELLET CONVEYING HOPPER OVERFILLING ................................................................................... 106
I-8418-O: EXTRUDER SHUTDOWN DUE TO PELLETISER PROBLEM ............................................................ 106
I-8419-O: EXTRUDER SHUTDOWN DUE TO PELLET DRYER/DEWATERING STOPPAGE ........................ 107
I-8420-O: PELLET DRYER/DEWATERING .............................................................................................................. 107
I-8470-S: PELLETIZER HOOD OPENING WHILE HOT WATER CIRCULATING .............................................. 108
I-8471-S: PELLET DRYER/DEWATERING DOORS OPENING WHILE HOT WATER DIRECTED TO PELLET
DRYER ............................................................................................................................................................................ 108
I-8801-O: PELLET CONVEYING LINE FROM FEED HOPPER BLOCKAGE ..................................................... 109
2.8 LIST OF PROCESS DATA SHEETS INCLUDING INEOS TECHNOLOGIES CONTROL SPECIFIC
REQUIREMENTS .............................................................................................................................................................. 110
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
1. INTRODUCTION
This chapter provides the narrative description of the DCS and SIS interlocks, which protect
the INEOS Technologies licensed process.
The DCS interlocks are noted I-xxxx-O and SIS I-xxxx-S and are shown on the PID drawings
with a diamond symbol as per:
I I
xxxx xxxx
S O
The implementation of interlocks in the DCS and the SIS must follow the requirements
described in the Instrument and Process Control Philosophy chapters “DCS hardware
implementation”, “SIS hardware implementation” and ”Interlock functionality”.
This document (Process Interlock Description) is a simplified description of the way that each
piece of logic should work. As such, all of the details are not explicitly described.
To improve reading of the document, the instrument and equipment tags do not include the
prefix 3200.
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
1.1 MISCELLANEOUS
The trip settings are not listed in this document. Values are gathered in the instrument
datasheets or instrument lists.
Trip on control valves: when an interlock is activated and trips a control valve, 2 types
of trip are required:
For a DCS interlock trip, the action on the valve is made via the DCS analogue output
to the valve positioner. The relevant action is noted FMC or FMO meaning that the
relevant controller is forced into manual mode and the output is forced to close or open
position. It will be noted ―FMC FIC-xxxxxx‖ or ―FMO FIC-xxxxxx‖ in the interlock
description.
For a SIS interlock trip, the action on the valve is made via a solenoid valve installed on
the control valve actuator and via the DCS analogue output to the valve positioner.
The relevant actions are noted ―Close FV-xxxxxx (SIS)‖ or ―Open FV-xxxxxx (SIS)‖ in
the interlock description.
When a DCS or a SIS interlock trips an on/off valve, if there is a corresponding control
valve, the DCS should force the control valve to manual and either open or close the
control valve, as appropriate. This will ensure that the control valve and controller are
in the correct state when the on/off valve is reset.
1.2 ABBREVIATIONS
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
PID
Sequence description
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
2. INTERLOCK TABLES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes: Auto-reset
Minimum SIL level: 0
Causes:
LT-10103 (SL) Polymer water pit PID:0108
Actions:
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
PT-20513 (LL) Nitrogen header PID:0215
Actions:
FMC PIC-10581 Nitrogen to low priority users PID:0102
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes:
Minimum SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Close XZV-20302 H2 to Ethylene CO/O2 treater PID:0202
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-20303 H2 to Ethylene CO/O2 treater PID:0202
AND
Open (note 1) XZV-20301 Bleed H2 line to Ethylene CO/O2 treater PID:0202
Causes:
[TZT- Ethylene CO/O2 treater A PID:0202
20120/20122/20123/20128/20129 ( >
120°C) (Voting 1oo5)] AND PZT-
20127 ( > SL = 9 barg)
OR
[TZT- Ethylene CO/O2 treater B PID:0202
20120/20122/20123/20128/20129 ( >
120°C) (Voting 1oo5)] AND PZT-
20137 ( > SL = 9 barg)
Actions:
AND
Stop H201 Regeneration Nitrogen heater PID:0212
AND
Close TZV-20316 (SIS) Regeneration Nitrogen steam heater PID:0212
AND
Close XZV-20120 (note 1) Regeneration H2 PID:0202
AND
Close XZV-20121 (note 1) Regeneration H2 PID:0202
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes: Note 1: Open bleed valve when both corresponding isolation valves are
detected closed. Opening of isolation valves possible only if
corresponding bleed valve is detected closed
Minimum SIL level: 1
AND
Close XZV-40066 (note 1) Ethylene from EPU to loop PID:0404
AND
Open XZV-20204 (note 1) FPU ethylene vent to HPF PID:0203
AND
Stop K-230 Ethylene compressor PID:0201
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-20303 H2 to ethylene O2 treater PID:0202
AND
Open (note 2) XZV-20301 Bleed H2 line to ethylene O2 treater PID:0202
Notes: Note 1: open depressurisation valves only when isolation valves are
closed
Note 2: open bleed valve when both corresponding isolation valves are
detected closed. Opening of isolation valves possible only if
corresponding bleed valve is detected closed.
Minimum SIL level: 1 for cause “I-2302-S part 2 is initiated” and all actions
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Close XZV-20312 Regeneration N2 make-up PID:0212
Notes:
Minimum SIL level: 1
AND
Close FZV-20122 (SIS) Air to ethylene CO/O2 treaters PID:0202
Notes: Note 1: Open bleed valve when both corresponding isolation valves are
detected closed. Opening of isolation valves possible only if
corresponding bleed valve is detected closed
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-20560 Hexene-1 from OSBL PID:0205
AND
Close XZV-20570 Octene-1 from OSBL PID:0205
AND
Close XZV-40902 Comonomer to Main loop separator PID:0403
AND
Close XZV-40905 Comonomer to Reactor PID:0404
AND
Close XZV-20602 Comonomer buffer drum Bottom PID:0207
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Stop P-241B Comonomer injection pump PID:0207
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
HS-20502 = Octene-1 Comonomer selector PID:0206
Actions:
Close XZV-20550 Butene-1 from OSBL PID:0205
AND
Close XZV-20560 Hexene-1 from OSBL PID:0205
Notes:
Minimum SIL level: 1
Actions:
Stop P-241A/B Comonomer injection pumps PID:
0207
Notes: T1-2417: timer = 20s. Time for pump to establish flow and avoid trip on
low flow at start-up.
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-40909 Pentane start-up PID:0403
AND
Close XZV-20242 Pentane feed to Pentane treaters PID:0208
AND
Close XZV-20205 Pentane feed to users PID:0209
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Close XZV-40062 Hydrogen to PU PID:0040
4
AND
Close XZV-40067 Hydrogen to catalyst stingers PID:0404
AND
Close XZV-20401 Regeneration Hydrogen to N2 treaters PID:0214
AND
Close XZV-20403 Regeneration Hydrogen to N2 treaters PID:0214
AND
Open (note 1) XZV-20402 Regeneration bleed H2 line (N2 treaters) PID:0214
AND
Close XZV-20302 H2 to Ethylene treaters PID:0202
AND
Close XZV-20303 H2 to Ethylene treaters PID:0202
AND
Open (note 1) XZV-20301 Bleed H2 line to Ethylene treaters PID:0202
AND
Close XZV-20101/20102 H2 from OSBL PID:0210
AND
Open (Note 1)XZV-20103 Bleed H2 from OSBL PID:0210
AND
Close XZV-20120 Regeneration H2 PID:0202
AND
Close XZV-20121 Regeneration H2 PID:0202
AND
Open XZV-20122 (Note 1) Bleed regeneration H2 PID:0202
Notes: H2 compressor kept running to ensure mini flow for cata. bed
protection.
Note 1: Open bleed valve when both corresponding isolation valves
are detected closed. Opening of isolation valves possible only if
corresponding bleed valve is detected closed
SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Stop K-271A Hydrogen compressor A PID:0210
Notes:
SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Stop K-271B Hydrogen compressor B PID:0210
Notes:
SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
FZT-20311 (L4) (note 2) Nitrogen to Regeneration nitrogen heater PID:0212
Actions:
Close XZV-20411 Regeneration air to nitrogen CO/O2 PID:0214
treaters
Notes: Note 1: Risk of O2 ingress into flare system to be reviewed by detailed
engineering.
Note 2: interlock to be overriden during last step of oxidation when only
air is used. Interlock implementation to be developed by detailed
engineering.
As a guidance, the override could be set after a timer = time necessary
for the sequence to reach regeneration with pure air. Timer is launched
when the air feed isolation valve is detected open. The duration of the
override setting = regeneration time with pure air. After that time the
override is automatically removed.
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes:
Minimum SIL NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
level:
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XV-30076 Nitrogen to holding volume PID:0301
AND
Close XV-30075 Stock pipe transfer valve PID:0301
AND
Close XV-30078 Stock pipe transfer valve PID:0301
Notes: Autoreset
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
I-3077-S: ZIEGLER CATALYST (SDX) STOCK LINES BACK FLOW FROM REACTOR
Hazard: Backflow from reactor leading to stock line plugging and major outage
Causes:
PZDI-30073 (LL) (note 1) Reactor and catalyst stock line PID:0301
/ 0401
Actions:
Stop X-380A/B (DCS) Catalyst rotary valves PID:0303
AND
Close after T1-3077 XZV- Catalyst conveying line isolation valves PID:0303
30010/30110
Notes: Note 1: PZDI-30073 = PZT-30073 – PZT-40008
T1-3077: Timer = 30s.
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
XZV-30010 Not closed for more than Catalyst conveying line isolation valve PID:0303
T1-3078
Actions:
Close XZV-30010 Catalyst conveying line isolation valve PID:0303
Causes:
FT-30010 (LL) Motive Nitrogen of catalyst injection line PID:0303
Actions:
Stop X-380A Catalyst rotary valve PID:0303
Notes: T1-3078: timer = 30s
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
T1-3080
Actions:
Close XZV-30210 Catalyst conveying line isolation valve PID:0305
Causes:
FT-30210 (LL) Motive Nitrogen of catalyst injection line PID:0305
Actions:
Stop X-386A Catalyst rotary valve PID:0305
Notes: T1-3080: Timer = 30s
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
XV-30179 Not closed Stock pipe depressurisation valve PID:0302
Actions:
Close XV-30172 Nitrogen to holding volume PID:0302
AND
Close XV-30173 Nitrogen to holding volume PID:0302
AND
Close XV-30176 Nitrogen to holding volume PID:0302
AND
Close XV-30175 Stock pipe transfer valve PID:0302
AND
Close XV-30178 Stock pipe transfer valve PID:0302
Notes: Autoreset
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
I-3177-S: ZIEGLER CATALYST (NCT) STOCK LINES BACK FLOW FROM REACTOR
Hazard: Backflow from reactor leading to stock line plugging and major outage
Causes:
PZDI-30173 (LL) (note 1) Reactor and catalyst stock line PID:0302/
0401
Actions:
Stop X-380A/B (DCS) Ziegler catalyst rotary valves PID:0303
AND
Close after T1-3177 XZV- Catalyst conveying line isolation valves PID:0303
30010/30110
Notes: Note 1: PZDI-30173 = PZT-30173 – PZT-40008
T1-3177: Timer = 30s.
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XV-30276 Nitrogen to holding volume PID:0304
AND
Close XV-30275 Stock pipe transfer valve PID:0304
AND
Close XV-30278 Stock pipe transfer valve PID:0304
Notes: Autoreset
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-20560 Hexene-1 BL PID:0205
AND
Close XZV-20570 Octene-1 BL PID:0205
AND
Close XZV-20242 Pentane BL PID:0208
AND
Close XZV-20101 (Note1) H2 to FPU from OSBL PID:0210
AND
Close XZV-20102 (Note1) H2 to FPU from OSBL PID:0210
AND
Open XZV-20103 (Note 1) H2 bleed PID:0210
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
I-4013-O: BACK FLOW INTO COMONOMER FEEDING FROM MAIN LOOP SEPARATOR
Hazard: Backflow leading to comonomer headers contamination.
Causes:
PDT-40910 (LL) Comonomer to Main loop separator PID:0403
Actions:
Close XZV-40902 Comonomer to Main loop separator PID:0403
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes:
Minimum SIL level: 0
I-4014-O: BACK FLOW INTO COMONOMER FEEDING FROM GAS LOOP (K400
DISCHARGE)
Hazard: Backflow leading to comonomer headers contamination.
Causes:
PDT-40915 (LL) Comonomer to loop gas PID:0404
Actions:
Close XZV-40905 Comonomer to loop gas PID:0404
Notes:
Minimum SIL level: 0
I-4016-S: BACK FLOW INTO VRU MAIN SEPARATOR FROM GAS LOOP
Hazard: Backflow of loop gas into VRU up to degasser. Powder degassing issue and explosion in
degasser downstream equipment.
Causes:
PZDT-40904 (LL) VRU condensate to loop PID:0403
Actions:
Close XZV-40904 VRU condensate to loop PID:0403
Notes:
Minimum SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
I-4017-O: BACK FLOW INTO VRU COMPRESSOR SUCTION DRUM FROM GAS LOOP
Hazard: Backflow of loop gas into VRU up to degasser. Powder degassing issue and explosion in
degasser downstream equipment.
Causes:
PDT-40919 (LL) VRU condensate to loop PID:0403
Actions:
Close XZV-40919 VRU condensate to loop PID:0403
Notes:
Minimum SIL level: 0
AND
Close XZV-40522 TEAL injection pumps discharge PID:0410
AND
Close XZV-40207 (note 1) Liquid additive (B1) feed to reactor PID:0408
AND
Stop X-380A Ziegler catalyst rotary valve PID:0303
AND
Stop X-380B Ziegler catalyst rotary valve PID:0303
AND
Close XZV-40902 Comonomer to Main loop separator PID:0403
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-40903 Pentane make-up to Main loop separator PID:0403
AND
Close XZV-40909 Pentane start-up to Main loop separator PID:0403
AND
Close XZV-40904 VRU second interchanger condensate to PID:0403
Main loop separator
AND
Close XZV-40919 VRU compressor suction drum PID:0403
condensate to loop separator
AND
Close XZV-40920 VRU C8 compressor suction drum PID:0403
condensate to loop separator
AND
Set XZV-40065 to N2 Direction Ethylene/Nitrogen to purge gas system PID:0404
AND
Close XZV-40062 Hydrogen to loop PID:0404
AND
Close XZV-40063 Ethylene to loop PID:0404
AND
Close FZV-061 (SIS) HN to loop PID:0404
AND
Close XZV-40209 Liquid additive S1 to catalyst injection PID:0411
AND
Stop X-386A Metallocene catalyst rotary valve PID:0305
AND
Stop X-386B Metallocene catalyst rotary valve PID:0305
AND
Stop X-386C Metallocene catalyst rotary valve PID:0305
AND
Close XZV-40901 HC condensate to Liquid injection nozzles PID:0403
AND
Close XZV-40067 H2 to Metallocene catalyst injection PID:0404
nozzles
Notes: Note 1: This interlock also prevents B1 and TEAL additives
entering in direct contact by isolating the respective feeds when
Main loop compressor is stopped (see I-4021-S). There is a
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
I-4019-O: BACK FLOW INTO PURGE COLUMN FROM REACTOR VIA START-UP POWDER
LINE
Hazard: Lifting relief valve / blockage
Causes:
PZT-40008 (H1) (note 1) Loop gas PID:0401
Actions:
Close XV-60081 Start-up powder to Reactor PID:0608
Notes: Note 1: Trip activated during normal operation.
Minimum SIL NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
level:
AND
Close XZV-40521 TEAL injection pumps discharge PID:0410
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-40951 TEAL to nozzles PID:0405
AND
Close XZV-40101 TEAL container isolation PID:0409
AND
Close XZV-40111 TEAL container isolation PID:0409
AND
Close XZV-40103 TEAL container nitrogen purging PID:0409
AND
Close XZV-40113 TEAL container nitrogen purging PID:0409
AND
Open XZV-40102 TEAL container venting PID:0409
AND
Open XZV-40112 TEAL container venting PID:0409
AND
Close XZV-20205 Pentane flush from Pentane storage drum PID:0209
Notes: Note 1: Number of pressure transmitters to be determined by detailed
Engineering
Minimum SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
I-4023-S: BACK FLOW INTO VRU C8 COMPRESSOR SUCTION DRUM FROM GAS LOOP
Hazard: Backflow of loop gas into VRU compressor suction drum. Powder degassing issue and
explosion in degasser downstream equipment.
Causes:
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Close XZV-40920 VRU C8 condensate to loop PID:0403
Notes:
Minimum SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
I-4032-O: BACK FLOW INTO PENTANE FEED OR INTO 1ST STAGE K.O. DRUM OF
RECYCLE GAS COMPRESSOR
Hazard: Production loss and flaring.
Causes:
PDT-40903 (LL) Pentane make-up to Main loop separator PID:0403
Actions:
Close XZV-40903 Pentane make-up to Main loop separator PID:0403
Causes:
PDT-40909 (LL) Pentane start-up to Main loop separator PID:0403
Actions:
Close XZV-40909 Pentane start-up to Main loop separator PID:0403
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
The low and high stripping gas flow settings for the degassers and purge column are variable depending on
the groups of product. The different groups of product are identified by the reactor conditions which may
include catalyst, comonomer and temperature.
All these interlocks are implemented within the SIS system.
These conditions are then used to determine the trip settings for various interlocks.
I-4041-S: Poor degassing: Reactor Low Temperature
I-4042-S: Stop catalyst feeders: degassing capacity limit
I-6330-S: Poor degassing in Degasser: high stripping gas flow
I-6340-S: Poor degassing in Degasser: low stripping gas flow
I-6830-S: Poor degassing in C8 Degasser: high stripping gas flow
I-6840-S: Poor degassing in C8 Degasser: low stripping gas flow
I-6442-S: Poor degassing in purge column: low stripping gas flow
I-6445-S: Poor degassing in purge column: high stripping flow or high pressure
Each valve position should be based on three signals: SIS command status to the valve, closed limit switch
and open limit switch, in order to achieve the necessary interlock integrity. All three signals should be
consistent before the position of the valve is determined; if they are not consistent then the valve is faulty.
Group identification
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
The group number is used to determine the trip matrix outputs (see below)
The SIS sends the group number to the DCS. This information is compared with group number defined in
GROWL for each grade. An alarm in DCS will be issued in case of discrepancy. This alarm may happen at
the start-up of the transition when operator will change of grade setting via the GROWL but has not yet
fulfilled the conditions to determine the group number. In steady state the group in SIS and DCS are
normally identical.
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
When the transition is completed the high or low trip value as appropriate is changed to increase to
the operating trip window for the new reactor conditions.
After transition the DCS operator sets the set point for the degassing flow controller in the DCS to
the required value independently of the changes in trip settings (refer to operating manual).
Degasser
Matrix Outputs MH ML
Matrix Inputs Group Number (I-6330-S: FZT-60514/60515 (I-6340-S: FZT-60514/60515
(HH) setting) (LL) setting)
3 3
1 3210 m /h 1550 m /h
3 3
2 3210 m /h 2130 m /h
3 3
3 3210 m /h 2370 m /h
3 3
4 2850 m /h 2130 m /h
3 3
5 2850 m /h 2130 m /h
3 3
6 3210 m /h 2370 m /h
Degasser C8
Matrix OutputsMH ML
(I-6830-S: FZT- (I-6840-S: FZT-
Matrix Inputs-Group 60814/60815 (HH) 60814/60815 (LL)
Number setting) (Note 2) setting) (Note 2)
1 High flow = 29500 kg/h Low FZT range
(note 3) kg/h
2 High flow = 29500 kg/h Low FZT range
(note 3) kg/h
3 High flow = 29500 kg/h Low FZT range
(note 3) kg/h
4 29160 kg/h 21550 kg/h
5 25860 kg/h 8910 kg/h
6 29160 kg/h 19760 kg/h
Note 2: the values given for non-C8 products are set into the matrix to distinguish C8 operation from C4/C6
operation. It is used in some interlocks only acting in C8 operation.
Note 3: High flow for C4/C6 groups only to prevent fluidization issue in the C8 degasser
Purge Column
Matrix Outputs MH ML
(I-6445-S: FZT- (I-6442-S: FZT-
Matrix Inputs-Group 60006A/B (HH) 60006A/B (LL)
Number setting) setting)
1 1760 kg/h 660 kg/h
2 1760 kg/h 1280 kg/h
3 1760 kg/h 1280 kg/h
4 1760 kg/h 1280 kg/h
5 1760 kg/h 1280 kg/h
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Transition:
If DT < DT_T Then hold timer t {Hold timer if reaction stops}
If DT ≥ DT_T Then restart timer t {Restart timer if reaction restarts}
if timer t> R Then TL = ML {If timer complete change FZALL and FZAHH trip settings to
TH = MH matrix values}
Goto Steady
If MLo≠ML or MHo≠MH Then {If matrix outputs change during transition, indicating a
Reset and restart timer t change in reactor conditions, then extend transition period
and change transition values}
TL = Max( TL, ML)
TH = Min (TH, MH)
If TL > TH Then set DCS alarm message ―POWDER CANNOT BE WITHDRAWN
FROM DEGASSER DURING THIS GRADE TRANSITION‖.
Goto transition
Where:
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
R 11.4 h for Time required before final change of FZAHH and FZALL
degasser
19.4 h for C8-
degasser
19.9 h for purge
column
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
FZT-40068 (HH) for T1-4042 (Note Ethylene feed to reactor PID:0404
1)
OR
FZT-40069 (HH) for T1-4042 (Note Ethylene feed to reactor PID:0404
1)
Actions:
Stop X-380A/B Ziegler rotary valves PID:0303
AND
Stop X-386A/B/C Metallocene rotary valves PID:0305
AND
Close XZV- Lock hoppers isolation valves PID:0601
60003/60005/60053/60055/60303/6 /0602/06
0305/60313/60315/60323/60325 03
Notes: Note 1: the trip setting is grade dependent. Refer below.
T1-4042: 15 min to increase availability.
Minimum SIL level: 2
Refer to section on Degassing Variable Trip Settings for how these values are determined.
The trip setting for FZT-40068 (HH) and FZT-40069 (HH) should be set according to the following matrix.
Group number
1 46 t/h
2 46 t/h
3 46 t/h
4 34 t/h
5 46 t/h
6 46 t/h
On Error 34 t/h
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-40522 TEAL pumps P-455A/B discharge PID:0410
AND
Close XZV-40207 Liquid additive (B1) feed to reactor PID:0408
Causes:
XZV-40521 not closed TEAL pumps P-455A/B discharge PID:0410
OR
XZV-40522 not closed TEAL pumps P-455A/B discharge PID:0410
Actions:
Close XZV-40209 Liquid additive S1 to injection PID:0411
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close XZV-40522 (Note 1) TEAL injection pumps discharge PID:0410
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR
PZT-40523B (HH) TEAL injection pump (B) suction PID:0410
Actions:
Close XZV-40521 TEAL pumps discharge PID:0410
AND
Close XZV-40522 TEAL pumps discharge PID:0410
Notes:
Minimum SIL level: 2
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Note 4: a pneumatic interlock between take-off and bottom lock hoppers valves
should not allow air supply to both valves. The pneumatick interlock must be
SIL 1. Refer to the valves datasheet for pneumatic interlock scheme.
Minimum SIL level: SIL 2: On high pressure, close upflow and downflow lock hoppers isolation
valves
SIL 1: interlocking of lock-hopper take-off and filling valves
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR
LSHH-60111 (HH) Conveying filter PID:0606
OR
LSHH-60072 (HH) Start-up powder silo PID:0608
AND XDX-60642 set to start-up silo
OR
X-641 detected stopped Conveying filter outlet rotary valve PID:0606
OR
SAL-60101 (L) Conveying filter outlet rotary valve PID:0606
OR
K-660A detected stopped Gas conveying blowers PID:0607
OR
PT-60021 (HH) ] Powder conveying line A PID:0607
AND
XDX-60639A/B routed to purge Diverters PID:0605
column
Actions:
Stop X-660 Powder conveying feed rotary valve PID:0605
AND
Stop X-661 Powder conveying feed rotary valve PID:0613
Causes:
[ LSHH-60024 (HH) Purge column PID:0606
AND XDX-60642 set to Purge
column
OR
LSHH-60111 (HH) Conveying filter PID:0606
OR
LSHH-60072 (HH) Start-up powder silo PID:0608
AND XDX-60642 set to start-up silo
OR
X-641 detected stopped Conveying filter outlet rotary valve PID:0606
OR
SAL-60101 (L) Conveying filter outlet rotary valve PID:0606
OR
K-660B detected stopped Gas conveying blowers PID:0607
OR
PT-60039 (HH) ] Powder conveying line B PID:0607
AND
XZDX-60639A routed to C8 Diverter PID:0605
degasser
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Stop X-661 Powder conveying feed rotary valve PID:0613
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
OR
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
LZT-60501A/B/C (HH) (2oo3) VRU main separator PID:0612
Actions:
Close FZV-60602 Stripping gas to Degasser PID:0611
AND
Initiate Interlock I-6750-O Poor degassing in degasser: Nitrogen
back-up
AND
AND
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
st
Close LV-60001B (DCS) Condensate from recycle compressor 1 PID:0610
stage KO drum
Notes:
Minimum SIL level: 2
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Close XZV-60060 Purge column off gas to snuffing system PID:0618
AND
When XZV-60060 Confirmed closed. Steam to snuffing system PID:0618
then wait T2-6408 and close XZV-
60061
Notes: Autoreset interlock
T1-6408 timer = 15s
T2-6408 timer = 60s
Minimum SIL level: SIL 1 for steam opening part of the interlock
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR PID:0606
XV-60014 Not open Purge column recyling line
OR PID:0606
XDX-60604 Not set to recycling ] Purge column recycle diverter valve
AND
[ LZT-60021 (LL) OR LZT-60022 Purge column PID:0606
(LL)
OR LZT-60023 (LL) (1oo3)]
Actions:
Stop X-660 Powder conveying feed rotary valve PID:0605
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
AND
Close XZV-60011 Purge column to extrusion isolation PID:0606
Notes: T1-6442: timer = 5 Seconds.
Note 1: the trip setting is grade dependent. Refer to section
on Degassing Variable Trip Settings for how trip settings are
determined.
Minimum SIL level: 2
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
AND
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes:
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
XV-60081 Detected not open Start-up powder to reactor PID:0608
OR
PT-60081 (HH) Start-up powder conveying nitrogen PID:0608
OR
FT-60081 (LL) Start-up powder conveying nitrogen PID:0608
Actions:
Stop X-667 Start-up powder rotary valve PID:0608
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Close LZV-60001C (SIS) Condensate from VRU condensate PID:0610
pumps
Causes:
K-675 detected stopped Recycle gas compressor PID:0610
Actions:
Close XZV-60009 Cooling liquid to recycle gas compressor PID:0610
suction
AND
Close XZV-60010 Cooling liquid to recycle gas compressor PID:0610
st
1 stage
Notes: To be finalised with compressor vendor
Note 1: Liquid build-up when machine stops. Risks and protection to be
provided by detailed engineering in accordance to machine and system
low points.
Minimum SIL level: To be assessed by DE
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Hazard: Inject back-up nitrogen into degasser in case of VRU shutdown. The back-up nitogen flow is
ramped to prevent N2 network over draw.
Causes:
I-6341-S Activated High HC content on stripping gas to
degasser protection
Actions:
Open XV-60603 Back-up N2 for stripping gas from VRU PID:0611
AND
Set to Auto mode and ramp set point Back-up N2 for stripping gas from VRU PID:0611
of FIC-60603 T1-6750 (Note 1)
Notes: Note 1: T1-6750: timer = 5 min corresponding to a ramp rate
= 500 kg/hr/min
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Actions:
Stop P-672A/B Recycle gas compressor condensate PID:
pumps 0610
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes: T1-6778: timer = 20s Time for pump to establish flow and avoid trip on
low flow at start-up.
Minimum SIL level: NO SIL REQUIREMENT BY INEOS TECHNOLOGIES
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR
Causes:
[ (X-661 Stopped OR SSL-60861 C8 Powder conveying feed rotary valve PID:0613
(L))
AND XDX-60801 Set to X-661] C8 Degasser Recycle diverter valve PID:0613
OR
[ (X-662 Stopped OR SSL-60871 C8 Degasser Recycle rotary valve PID:0613
(L))
AND XDX-60801 Set to Recycle] C8 Degasser Recycle diverter valve PID:0613
Actions:
Stop X-638 C8 Degasser outlet rotary valve PID:0613
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes:
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
OR
LZSLL-60815 (LL)]
AND
HZS-60801 In Normal mode NORMAL / EMPTY C8 Degasser PID:0613
Actions:
Stop X-661 Powder conveying feed rotary valve PID:0613
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Causes:
LZT-60871A/B/C (HH) (2oo3) C8 VRU main separator PID:0617
Actions:
Close FZV-60865 (SIS) Gas flow from C8 VRU PID:0616
AND
AND
Notes:
Minimum SIL level: 2
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
explosion.
Causes:
[TZDI-60811A (HH) (Note 1) Temperature difference between reactor PID:0613
and C8 degasser
OR
TZDI-60811B (HH) (Note 1)] Temperature difference between reactor PID:0613
and C8 degasser
AND
C8 operation (Note 2)
Actions:
Close XZV-60003/60053 Upflow lock hoppers top isolation valves PID:0601
AND
Close XZV-60303/60313/60323 Downflow lock hoppers top isolation PID:0602
valves /0603
AND
Stop X-661 if HZS-60801 In Normal Powder conveying feed rotary valve PID:0613
mode
AND
Stop X-660 Powder conveying feed rotary valve PID:0605
Notes: Note 1:TZDI-60811y = Mo3 of (TZT-40044A/B/C) – TZT-60811y
Note 2: The interlock is active only in C8 operation. C8 operation is
determined with the value of the degassing trips for high and low
degassing flow in C8 operation.
C8 operation when (TH not equal to High flow and TL not equal to low
flow range).
Refer to section on Degassing Variable Trip Settings for how trip settings
are determined.
Minimum SIL level: 2
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
flow range).
Refer to section on Degassing Variable Trip Settings for how trip settings
are determined.
Minimum SIL level: 1
OR
LZSLL-60818 (LL) C8 Degasser pipe outlet PID:0613
Actions:
Close XZV-20570 Octene-1 from OSBL PID:0205
Interlock Reset:
Causes:
LZSLL-60814 (NOT LL) C8 Degasser PID:0613
AND
Actions:
Permissive to open XZV-20570 Octene-1 from OSBL PID:0205
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
AND
Stop W-835D/E/F (Note 1) Additive feeders PID:0803
AND
Stop (pulse command) X-855 after Rerun pellet rotary valve PID:0807
T1-8252 (Note 1, 2)
Causes:
M-820 is detected stopped for more than First extruder feed screw PID:0801
T2-8252
OR
SSL-80041 for more than T2-8252 First extruder feed screw PID:0801
Actions:
Stop W-835D/E/F (Note 1) Additive feeders PID:0803
AND
Stop (pulse command) X855 after T2- Rerun pellet rotary valve PID:0807
8252 (Note 1, 2)
Notes: Note 1: Detailed engineering to ensure that feeders can be started for
pellet purge at extruder start-up.
Note 2 : and if pellets are routed to the extruder hopper
T1-8252: Residence time for the powder conveyor (20 seconds)
T2-8252: Residence time for the 2nd powder conveyor (Hold seconds)
This interlock must be reset automatically at extruder start-up
Minimum SIL level: 0
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
Notes: Note 1: Detect valve is moving from open to close position. It must be
possible to start extruder with valve XZV-80802 closed
Interlock to be developed by detailed engineering and extruder vendor.
Minimum SIL level: No SIL requirement by INEOS Technologies
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
should also prevent equipment starting until the doors are closed.
Minimum SIL level: 1
© INEOS Commercial Services UK Limited. All rights reserved. This document is the property of INEOS Commercial Services UK Limited, and
the information and images it contains are strictly confidential and may not be altered or amended, copied, used or disclosed without the
express permission of INEOS Commercial Services UK Limited.
OWNER REFERENCE
Project Package Originator Discipline Doc. Type Unit n° Serial n°
This paragraph lists all the process data sheets where specific INEOS Technologies control
requirement are described.
This list will help the DE to have an overall view to design properly the safety and control
systems.