Professional Documents
Culture Documents
TABLE OF CONTENTS
PAGE
S.NO DESCRIPTION
NO.
1 Introduction 3
1.1 About This Manual 3
1.2 Intended Use 3
1.3 Notice Of Claims 4
1.4 Copyright 4
2 Safety 4
2.1 Safety Devices 4
2.2 Basic safety instructions 5
3 Technical data 11
3.1 Control Boards 11
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 2 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
1. Introduction
This manual is part of the project documentation for a machine/plant supplied by ANDRITZ HYDRO. The
manual is particularly adapted and refers to the stipulated scope of supply solely.
The manual contains essential information about the correct, safe and purposeful operation of the ma-
chine/plant. The adherence to these instructions helps to avoid so far well-known dangerous situations, to
minimize repair- and standstill costs and to optimize the availability and life cycle of the plant.
But the manual cannot cover all precautions, safety instructions and operating instructions of hydro power
plants. It contains only the most important information (in compressed form), which have to be taken into ac-
count and cannot compensate technical competence and training of operating personnel.
The manual is exclusively addressed to the operator and his personnel, operating and maintaining the ma-
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Existing national instructions regarding health & safety and environmental protection have to be added to this
manual by the operator. Such instructions can regard e.g. handling with hazardous substances or availability /
wear of personal protective equipment, too.
Instructions, which consider the operational characteristics regarding labour organisation, operational se-
quences and employed personnel have to be added to this manual by the operator, too. This includes instruc-
tions regarding obligatory supervision and notification requirements.
The manual is to be kept always at place of installation within reach.
The machine/power plant must be operated in accordance with the specifications acc. contract solely. Any
operation exceeding the stipulated performance limits or contrary to the intended company regulations, is
considered as unintended and can lead to damages. ANDRITZ HYDRO does not assume liability for these
damages.
The intended use contains also the compliance with this manual as well as the adherence to operating and
maintenance conditions and the adherence to cleaning and maintenance instructions.
The correct and safe operation of the machine/plant requires proper transport and storage, installation and
assembly as well as careful operation and maintenance.
REGISTERED
Date 31.01.2014
Page 3 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Lacks and damages, detected by the customer or operating personnel, serious accidents or other detected de-
viations from the normal operating condition have to be announced immediately to ANDRTIZ HYDRO regard-
less of the occurrence during or after expiration of the warranty period.
This notification should contain in particular the following information:
Maintenance data
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
1.4 Copyright
This manual is the intellectual property of ANDRITZ HYDRO GmbH and must neither be copied nor handed
over to third parties without prior express agreement of ANDRITZ HYDRO GmbH. Violation will cause indem-
nities and can lead to prosecution. We reserve the right to make changes of technical details in relation to the
details stated in the manual.
2. Safety
The chapter Safety contains general safety instructions, which have to be considered when working on the
machine/plant.
Supplementary additional safety instructions to the individual activities are provided in the chapters of the
manual. These are set apart from the text by special warning notices.
Safety instructions for components, which were not made by ANDRITZ HYDRO, are included in the descrip-
tions of the component suppliers and have to be considered, too.
Non-adherence to the safety instructions can lead to personal injuries, environmental damages and/or materi-
al damages.
ANDRITZ HYDRO assumes that the operator guarantees the following:
2.1 Safety devices
REGISTERED
The access to all safety devices must be ensured at any time.
The machine/plant can be put from operation to a safe operating condition at any time by pressing the
EMERGENCY STOP BUTTON (possible designs see illustrations below).
Date 31.01.2014
Page 4 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The operating and maintaining personnel of the operator must be informed about the location and function
of the EMERGENCY STOP BUTTONS.
The location and number of EMERGENCY STOP BUTTONS is shown on the wiring diagrams.
Voltages and hydraulic pressures can still be present after pressing the EMERGENCY STOP
BUTTON.
(iv) Instruction
The operating and maintaining personnel of the operator must be introduced by qualified persons af-
ter completing the installation work.
The operator is obliged to introduce new operating and maintaining personnel in the same extent and
with the same care under consideration of all safety instructions.
Client VSH Prep. ST Contract Nº.
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH REGISTERED
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 5 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Persons, who are involved with the transport, assembly, commissioning, operation and maintenance
of the machine/plant must have read and understood this manual as well as the descriptions of the
component suppliers before commencing work.
Safety instructions for components, which were not made by ANDRITZ HYDRO, are included in the
descriptions of the component suppliers and have to be considered, too.
check regularly whether the safety instructions are kept in accordance with the manual when working
on the machine,
Train the operating and maintaining personnel regularly and to confirm their knowledge.
In order to avoid personnel injuries and material damages the following safety instructions apply to all per
sons, working on the machine/plant:
Observe the safety instructions mentioned in the manual and attached on the machine.
In case of safety-relevant malfunctions stop or secure the concerned part of the machine immediately.
Announce and repair the malfunctions immediately.
Any safety-precarious mode of operation is not allowed. REGISTERED
Use only the provided entries, routes and aisles.
Client VSH Prep. ST Contract Nº.
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 6 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Keep the machine/plant and work place clean and tidy. Do not put down tools and other items on the
machine.
Do not wear clothes or pieces of jewelry, which enable getting caught by mobile machine parts. Ties,
neckerchiefs, rings and chains belong thereto.
Do not wear long hair loose.
Inform the personnel about the function and malfunction of monitoring instruments before commenc-
ing work.
If necessary, place temporary barriers and limit the entrance when working on the machine/plant.
Entering of danger zones is only allowed after the power supply is safely disconnected and the me-
chanical safety devices are mounted. Protective equipment must not be blocked or bridged.
Avoid contact with switched-on circuits or rotating parts.
Use or take along the personal protective equipment in accordance
With the national instructions or instructions of the operator when working on the machine.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
High voltage can lead to heavy or fatal injuries. Therefore it is essential to observe the following:
Work on/in electrical systems must not be carried out unless a permit has been issued by the senior
authorized person.
Operation and maintenance of the machine/plant only by qualified personnel.
A second person must be present when working on live parts. In case of emergency this person can
press the EMERGENCY STOP BUTTON or the main switch with shunt trip. Demarcate the working
area with a red-white safety chain and a warning sign.
Use proper insulated tools, protection devices and personal protective equipment and check them be-
fore each use.
It is recommended to make oneself familiar with the safety standards, guidelines and electrical regula-
tions as well as the usual national and proven operating modes for plants (e.g. EN 50110, VDE0104
or IEC-standards). The following steps have to be met as minimum requirement before commencing
work on electrical machines/plants:
Disconnect completely
Secure against re-connecting
Verify that the installation is dead (de-energized).
Carry out earthing and short-circuiting REGISTERED
Provide protection against adjacent live parts
After finishing the work, carry out the above 5 steps in reverse order.
Date 31.01.2014
Page 7 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Only personnel with special knowledge and experience are entitled to work on hydraulic equipment.
Regular inspection of pipes, hoses and bolted connections for leakage and externally visible damages
(leaking-out oil can lead to injuries and fire). Damages have to be repaired immediately.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
System sections and pressure pipes (hydraulic, compressed air) have to be depressurised before
commencing repair work in accordance with the module descriptions.
Hydraulic and compressed-air pipes have to be laid professionally (connections must not be mistak-
en).
Armatures, length and quality of hose lines must correspond to the requirements.
The operating space of the actuators must not be blocked and the access to this space must be
properly secured. This applies in particular to closing weights, servo motors and the guide apparatus.
The notices, stated in the following, have to be kept when lifting and transporting components in order to
avoid injuries and material damages.
Do not stay or work below floating loads. Further it is not allowed to ride on floating loads.
Adhere to the general and also local safety instructions as well as specifications or manuals of the lift-
ing tool or load lifting attachment manufacturer.
The used lifting tool or transport vehicle must be suitable for the loads to be transported. If a mobile
crane is used, take additionally into ac-count that this crane is mounted in accordance with the manu-
facturer’s instructions.
Usage permission for the crane must be available. Operation of remote controlled cranes only by per-
sonnel with proper written driving license.
The results of the regular lifting tool inspection (inspection log book) must be available.
All used slinging means (ropes, chains, shackles, eyebolts, lifting eye nuts, S-hooks) must be used
only in accordance with the manufacturer's data.
Determine the required space in the power plant or on other provided (temporary) storage areas be-
fore commencing with lifting and transport operations. Further make sure that the floor loading is ade-
quate by granting access to the as-built drawings.
Client VSH Prep. ST Contract Nº. REGISTERED
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 8 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
During lifting observe the signs and other written instructions attached on the packing or components;
special customer requirements are to be considered, too.
A "test brake" of the lifting unit is necessary when lifting heavy loads. Lift the load approx. 10 cm and
lower it in small steps. After each switch-off, the brakes have to stop the lowering process.
Secure the machines/components with appropriate fixings against un-intended positional changes be-
fore or immediately after finishing the loading process.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Disconnect the machines/components from any external power supply; also in case of slight reloca-
tions.
Mount and fasten the parts, which were removed for transportation purposes, again before re-
commissioning.
Welding, burning and grinding operations on the machine/plant are only allowed if expressly ap-
proved.
Remove dust and inflammable materials from the machine/plant and its surrounding before welding,
burning and grinding operations. Further proper ventilation is to be ensured (danger of explosion)!
If necessary take available national instructions for work in close rooms into account.
2.2.8 Noise
Noise protection devices of the machine/plant must be in safe position during operation.
When required, use hearing protection.
REGISTERED
2.2.9 Operating supplies
Before operating supplies can be used, read the safety data sheets of the machine and the instructions of
the manufacturer. Based on these data sheets prepare a proper protection concept and observe it.
Apart from that take the following measures in order to avoid damages and injuries of the personnel:
Date 31.01.2014
Page 9 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Ignoring of these precautionary measures can lead to injuries by inhalation of poisonous steams or lead to
suffocation.
Be careful when dealing with hot operating supplies. Danger of burns and scalds!
Swarf of coatings, arising during repair work, must be disposed as hazardous waste.
The entire operating and maintenance personnel of the operator must be familiar with the operating mode
of the gas extinguishing system, when using such a system. Further it must also be familiar with the
resulting special safety precautions in case of emergency.
Ignoring of these safety precautions can lead to injuries or death of persons by inhalation or quenching
gas.
If the gas extinguishing system is part of the scope of supply of ANDRITZ HYDRO, the description of the
operating mode and special safety precautions is contained in the project documentation of ANDRITZ
HYDRO.
REGISTERED
Date 31.01.2014
Page 10 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
3. Technical data
This chapter defines the main technical data of the Control system components. Details about Technical da-
ta’s of Hardware will be found in document TKT-CM-01-DS-1034-I Datasheets – Control & Monitoring System
Each Control Board consists of one or more standard cubicles as specified below:
Date 31.01.2014
Page 11 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Mouse: Dell
Keyboard: English
3.4 Printers
Type HP Color Laser jet CP5225N
Print speed: 20 ppm black/color
Resolution: 600 x 600 dpi,
Tray: 1x 100 sheet input tray,
Processor, memory: 540 MHz processor, 192 MB memory,
Print language: PCL 5C, PCL 6 & PS-3 emulation,
Interface: Ethernet 10/100Base-TX, USB 2.0,
Dimension: w x d x h = 545 x 598 x 338 [mm], 40,9kg,
Date 31.01.2014
Page 12 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
For detailed technical data of modules pls. refer to document TKT-CM-01-DS-1034-I Datasheet Control
and Monitoring System Components.
Type CP-2016
Function Main processor of each AK 3 system
main function: administration of the whole controller (Automation Unit),
I/O hardware connection, serial/LAN communication and logic function
Type CP-2019
Function processor of AK 3 system
Main function: I/O hardware connection, serial/LAN communication and
logic function.
Type DI-6103
Function 16x2 110/220V DC
Type DO-6212
Function 8 x2 Relay 24-220V DC / 230V AC
Date 31.01.2014
Page 13 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Type AI-6300
Function 4 x2 ± 4-20mA / ±10V
Type AI-6310
Function 4 x2 PT100
Type AI-6303
Function 3 CT-inputs, 4 VT-inputs
Type PS-6632
Input 110…220V DC
Type PS-2632
Input 110…220V DC
Date 31.01.2014
Page 14 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Type CM -0843
Interface RJ-45 connector for the AX-Bus (I/O Bus) to the CPU USB-connector for
the AX-Bus (I/O Bus) from max. 4 Line Selectors (electrical RS485 star
coupler, proprietary protocol)
Type CM-0821
Interface 1x RJ 45 RS485, 3x Optical Fiber Multi Mode connector ST
Type CM-0822
Interface 4x Optical Fiber Multi Mode connector ST
Date 31.01.2014
Page 15 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Angle PHImax:
Maximum Permissible Residual 20 V
Voltage of a Dead System :
Maximum Adjustable CB Clos- 500 ms
ing Time:
4. Description
4.1 General
The detailed configuration of the Control & SCADA System is shown in DOC- TKT-CM-01-DM-1028-A
Design Memorandum Control and Monitoring System.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
4.2.3 Switchyard
1 (one) Switchyard Control Board (SCB)
Date 31.01.2014
Page 16 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
4.3 Communication
The communication between the components of Control & SCADA System is based on optic fibers.
To ensure a high reliability of the communication between the Automation Units Hirschman Industrial
Ethernet Switches are used. These switches use the proprietary Hyper ring protocol which ensures a
quick switching (less than 500ms) if one of the fiber optic cable is damaged.
Communication Protocols:
Local Area Network (LAN): IEC 60870-5-104
Control System with Generator Protection: IEC 60870-5-103
Control System with Unit and line Protection: IEC 60870-5-103
Control System with Excitation: IEC 60870-5-104
Control System with Digital Turbine Controller: IEC 60870-5-104
Communication with Dispatch Centre:
For communication with a Dispatch Centre two serial communication ports are provided in Switchyard
Control Board. Communication will be based on RS232/V.28 interface with protocol IEC 60870-5-101.
Transmission media and facilities are not included in scope of Control & SCADA System.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
The time and date information usually is entered in the automation system at a central point by a GPS
time signal receiver and distributed by the Network Time Server to all other components, using the
Standardized Network Time Protocol.
This real-time concept facilitates time-tagging of process data throughout the system with a resolution of
10ms. This time tagging is carried out directly at the input peripheral or at the data source. In the SCADA-
System data (events, values, counter, commands, set point values etc.) are stored in logs or archives
chronologically according to their time tags.
Date 31.01.2014
Page 17 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
4.6.4.2 Clock
1 (one) GPS receiver with integrated NTP time Server for time synchronization of Control System via
LAN.
(Details pls. refer to item 3, Technical Data)
Controller function:-
Automatic unit control and sequencing
Mechanic Protection and alarm system
Communication
Date 31.01.2014
Page 18 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
For detailed software functions of Controller (mechanic protection and automatic control) please refer to
chapter 5, Operation.
Controller function:-
Control and supervision of LT and MV system
Control and supervision of common auxiliaries like LP Compressor, Drainage and dewatering, etc.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Controller function:-
Control and supervision of air supplying system
Control and supervision of air discharging system and their auxiliaries.
Controller function:-
Control and supervision of intake gates and other dam auxiliaries
Supervision of water level, pressure loss through track racks etc.
Date 31.01.2014
Page 19 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
5. Operation
Date 31.01.2014
Page 20 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
5.1.1.1 Toolbars
Icons Description
Open Report.
Open Curve.
Open Curve.
Refresh Key.
Screen Navigation.
Onscreen Keyboard
Date 31.01.2014
Page 21 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
A. Overview:
Date 31.01.2014
Page 22 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 23 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 24 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
(ii) Actual Status signals of Pumps and Valves used in OPU System.
Date 31.01.2014
Page 25 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
(ii) Feedbacks and Interlocks of Pumps and Valves used in MIV System.
Date 31.01.2014
Page 26 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
(iii) Interfacing of Main Cooling Water System with Auxiliary Cooling System.
Date 31.01.2014
Page 27 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 28 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
(ii) Other Generator Parameters along with Alarms & trip limits highlighted.
Date 31.01.2014
Page 29 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 30 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 31 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 32 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 33 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 34 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 35 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 36 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 37 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 38 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 39 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 40 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 41 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 42 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 43 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 44 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 45 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 46 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
C. Switchyard:
1. Internal Toolbar 2
Date 31.01.2014
Page 47 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 48 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 49 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
D. Common System:
1. Internal Toolbar 3
Date 31.01.2014
Page 50 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 51 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 52 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 53 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 54 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 55 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 56 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 57 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 58 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 59 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
E. Topology:
1. Internal Toolbar 4
Date 31.01.2014
Page 60 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 61 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 62 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
A. Lists
Lists are used exclusively for the logging of events from the process data stream on the monitor, whereby
a certain memory range is available for buffering, in which one can browse using the scrollbars. If this
buffer is full, for each new event, the oldest event is removed from the buffer each time. Such events are
however not lost, but can be retrieved from the archive by means of reports.
Lists basically contain the entire event-stream of loggable events. It is valid for all lists that for the selec
tion a filter must be chosen, that specifies which events in these lists are to be displayed. The choice of
filter can either take place via a form operation for the selection or the filter already exists directly behind
this selection point due to construction and parameterization.
The filter criterion can be changed at any time using the menu line of the list.
With the lists, one differentiates between four types. Due to its function, each list type has its own special
operating cases and not every type is suitable for every task of the momentary process management.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Types of lists:
CEL Chronological event list
AEL Acknowledgeable event list
ASL Acknowledgeable state list
PSD Plant state display
Depending on the type of the list, there is a particular purpose. Not every list is suitable for all tasks of the
process management. Therefore the correct list must be selected for the momentarily required activity.
Purpose
The CEL contains all loggable events. The default sorting criterion is the event time. Data sources can
thereby be current data and archives.
By including filters a process-related selection of the events can be carried out. As a result, clear, techno-
logically related lists are created.
This list is used for precise analysis of chronological developments and sequences for the error analysis.
Date 31.01.2014
Page 63 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Purpose
The AEL contains all acknowledgeable events in the chronological order of their occurrence.
The default sorting criterion is the event time.
By including filters a process-related selection of the events can be carried out. As a result, clear, techno-
logically related lists are created.
This list can therefore be used for the display and acknowledgement of alarms.
Purpose
The ASL contains all acknowledgement-obligated events as well as all events that are in an alarm state,
as long as this state remains. An automatic sorting is made that allows all unacknowledged events to ap-
pear at the beginning of the list.
By including filters a process-related selection of the events can be carried out. As a result, clear, techno-
logically related lists are created.
This list is therefore used to alarm and inform the operator about the current alarm state in his process.
Date 31.01.2014
Page 64 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Purpose
The plant state list represents the momentary state of process variables, regardless of whether it is alarm
states or not.
By including filters a process-related selection of the events can be carried out. As a result, clear, techno-
logically related lists are created.
Consequently, this list is used for quickly creating an overview of the state of plant components that is not
available in this list in the form of plant displays.
The new functions for "Printing from Lists" and "Data export from Lists" have been realized with a Look &
Feel common with modern software products. The aforesaid functionality is available universally with all
lists (PSD, CEL, AEL and ASL).
For the paper printout and the data export the same selection properties as in the currently visualized
monitor list are the starting point for the printing- and data export time. In this context, the most important
output parameters adopted from the monitor list are:
_ Data source (RAM/Data Stream Archive)
_ List filter
_ TA-Filter
_ Time-range specification based on present representation period
_ Column labeling (incl. user-defined columns)
_ List coloring
_ Font
_ Sorting order of the columns
Date 31.01.2014
Page 65 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 66 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
AUTOSCALE (REDUCING
FONTSIZES) Depending on requirements, by reducing the list fonts attempts
to also get the last visible list column onto paper. Reduction
takes place down to a font size of 4. Not clicked, the preset font
does not change; i.e. the list line is if necessary curtailed on
reaching the right print margin.
Margins
Design possibility for text spacing. Specified in millimeters.
Common buttons
PRINT... This button enables printing; however the user must first select the printer in a Windows
standard dialog.
EXPORT... After actuating, a window is opened for selecting a folder. In this selected folder the file
is stored.
CANCEL Exit from this dialog without printing or exporting
This drawing/document is the INTELLECTUAL PROPERTY of
Date 31.01.2014
Page 67 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 68 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
B. Curve Display
SAT 250 SCALA curve objects are used for the graphical representation of value characteristics over
thtime axis, whereby any number of curve objects is possible on one workplace.
A curve object can represent up to 12 process variables (values or states). The selection of the values to
be represented can be carried out via parameter transfer or by means of Drag & Drop.
2. Group selection
Here, a group now to be displayed can be selected from the predefined PV-groups.
3. Time-Scrollbar
Enables the scrolling (paging) along the time axis, to make curve sections visible that are located
outside the currently represented time range.
4. Timescale
Time specification for the here represented time range.
The timescale also consists of a colored marking, whether the data represented above it come
from the temporary storage or the archive. If archive data are represented, then the timescale has
a colored background in this range.
5. Percentage scale
Shows the value as a percentage. The actual values for 0% and 100% are determined
for each PV by means of parameterization.
Date 31.01.2014
Page 69 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
6. Curves
That area in which the curve characteristics are represented.
8. Unit
Displays the physical unit in the curves legend of the currently selected curve.
9. Value scale
The value scale in the curves legend is displayed for the currently selected curve in its
technological unit.
10. Value-Scrollbar
Enables scrolling (paging) in the vertical direction, if parts of the represented curves
are located outside the represented value range (e.g. caused by higher zoom level).
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
12. Start/Stop-Buttons
Are used to switch between operator guide mode and pause.
The curve representation displays the current process data, whereby the values are continuously updat-
ed and the oldest values - similar to the paper on a typewriter - are slowly shifted in the direction of the
left window border.
SAT 250 SCALA manages a transient memory that contains all changes to all process variables in the
last 30 minutes. With this, not a fixed grid is used for recording, but rather all changes received by the au-
tomation units (Transitions) are stored.
With that it is ensured, that with each curve activation at least a 30 minute time range is available for the
representation that provides a very accurate resolution.
By scrolling the time axis towards the past, possibly available archive data are seamlessly displayed. This
range is specially identified by a colored background of the scale. From here, the data are naturally pro-
duced in the cycle available in the archive.
Date 31.01.2014
Page 70 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
C. Archiving Functions
Export and Import of Archives
The archives exist in the form of files, whereby a file is created for each archive and for each day.
Archives are only kept for a particular - determined through configuration - time period on the hard disk.
This means, that with day change those files that fall out of this time period are always deleted.
In order to safeguard these archives for a longer period and be able to restore them back to the system,
there are two functions available.
1. Export of archives
With this function archives can be exported and thus secured against deletion.
2. Import of archives
With this function previously exported archives can be loaded back in the system.
So that an analysis by means of SAT 250 SCALA is again possible.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
During export, the archives are copied to a drive/directory to be specified by the user; during
import, they are read again from this directory.
Exporting of Archives
After the start of the CAE Client you will find the export function on the left side in the folder Arch
ives (Import/Export).
Date 31.01.2014
Page 71 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
If a connection to the SCADA Server has not yet been established, then an information form appears that
a connection does not yet exist.
Confirm this here with the button YES. If you select the button NO, no data will be imported.
After the connection to the SCADA Server has been established or if a connection exists, all marked ar-
chives are imported to the SCADA Server.
During the import procedure a status indicator is displayed.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
The archives to be exported are first marked (Multiselects possible). In the context menu the entry EX-
PORT is then selected.
Date 31.01.2014
Page 72 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
If the export directory has not yet been defined or if it is invalid, the specification of an export directory is
requested.
The selected archives are now exported to the specified or already defined directory.
During the export process a progress indicator is displayed.
Date 31.01.2014
Page 73 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Export process
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Once the progress indicator disappears, the selected archives are created in the export directory. These
can now be exported by the system with other tools (e.g. provision of a CRRW for long-term backup).
Importing of Archives
After starting the CAE Client, the import function is located at the left side in the folder Archives
(Import/Export).
Date 31.01.2014
Page 74 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
If you wish to restore archives from an external data-carrier to SAT 250 SCALA, then first copy the re-
quired archives to the specified export directory.
Select the entry Exported Archives File.
All archives existing in the export directory are now displayed.
Date 31.01.2014
Page 75 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The archives to be imported are first marked (Multi selects possible). In the context menu the entry IM-
PORT is then selected.
Date 31.01.2014
Page 76 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
If a connection to the SCADA Server has not yet been established, then an information form appears that
no connection has yet been established.
Confirm this here with the button YES. If you select the button NO, no data will be imported.
After the connection to the SCADA Server has been established or if a connection exists, all marked ar-
chives are imported to the SCADA Server.
Date 31.01.2014
Page 77 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Import procedure
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
After the status indicator disappears, the selected archives are again available in SAT 250 SCALA.
These can now be analyzed again with the representations of SAT 250 SCALA (curves, reports etc.).
Date 31.01.2014
Page 78 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
D. Archive Editor
The archive editor is used for editing data in the cyclic archives of SAT 250 SCALA.
The selection of the archive editor is carried out from the interface of the SCADA Client.
Following this an Excel-Window opens, in which the function of the archive editor is available.
The selection of the PV's can take place using two possibilities.
Date 31.01.2014
Page 79 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Here, PV's from other representations can be entered by means of Drag & Drop. You only need to select
the required PV's and drag them into the white field with Drag & Drop.
If all selections have been actuated, the entry into the Excel-worksheet is carried out by actuating the but-
tons APPLY.
Variant 2: Archive
If you know the PV's or would like to edit a particular archive, then this is carried out with the possibilities
of the archive-tab. With this you can reduce the number of PV's offered with the selection of a particular
archive, if you know it.
With the buttons ADD -> or <- REMOVE select the required PV's for subsequent manipulation.
Client VSH Prep. ST Contract Nº.
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 80 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Further on there is the possibility to reduce the amount of PV's by using wildcards. If all selections have
been actuated, the entry into the Excel-worksheet is carried out by actuating the button APPLY.
In the time range tab carry out the selection of the start- and end time for the display of the values.
Similarly, the cycle in which you wish to have the values displayed is set.
If all selections have been actuated, the entry into the Excel-worksheet is carried out by actuating the but-
ton APPLY or OK.
Date 31.01.2014
Page 81 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This is how the completed data selection appears. Now the values can be fetched from the archive.
Date 31.01.2014
Page 82 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The table completed with text addresses and time range can now be filled with values from the archives.
By selecting the button DATA _ from the toolbar and the menu item READ the table is filled with data.
Depending on the quantity of selected data the filling of the table takes more or less time.
Date 31.01.2014
Page 83 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The updating of the diagram must be carried out by selecting the button DATA from the toolbar and the
menu item DIAGRAM CREATE.
Following this the selected PV's can be viewed in the diagram. By selecting the worksheet
Diagram, the diagram is displayed.
Date 31.01.2014
Page 84 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
E. Excel Reports
Excel reports are the customized way of data logging in a Tabular format using Excel application. This
will be finalized during detailed engineering and commissioning.
Date 31.01.2014
Page 85 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The Unit Control Board (UCB) contains all equipment, necessary for fully automatic as well as manual con
trol and supervision of the entire unit:
LCU (Local Control Unit or Controller) with LAN connection. For detailed configuration please refer to
Touch Panel and LAN connection
Auxiliary devices, such as miniature circuit breakers, control switches, relays, terminals etc.
Date 31.01.2014
Page 86 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This panel provides manual and automatic control and sequencing as well as supervision of operation con
ditions of the unit, manual and automatic synchronization of the unit.
Date 31.01.2014
Page 87 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The controller is connected to the station LAN (Local Area Network) for communication to control room.
The Station LAN is an Ethernet LAN (TCP/IP) with protocol IEC 60870-5-104.
The sequencing covers the complete automatic control under normal conditions and provides fully
automatic and step by step control of the unit set. It includes control of all auxiliary equipment of the
turbine/generator set.
This mode can be selected on the touch panel when +#CJA01-S05 is in position "Local" or is
active when +#CJA01-S05 is in position "Remote"
It is provided for maintenance and service works only and should only be performed by well
trained staff.
In this mode the unit can be controlled from the local Touch Panel or from the Operator station in
the control room by means of auxiliary control windows and feedbacks. Each individual auxiliary
pump or valve has to be initiated by a command, given by the operator.
In this mode the time monitoring of the sequencing is inactive – that means that the unit can stay
at any condition for unlimited time.
This mode can be selected on the touch panel when +#CJA02-S05 is in position "Local" or is
active when +#CJA02-S05 is in position "Remote"
It is provided for maintenance and service works only and should only be performed by well
trained staff.
In this mode the unit can be controlled from the local Touch Panel or from the Operator station
In the control room by means of detailed sequence and step displays. Each step of a sequence
has to be initiated by a command, given by the operator.
Client VSH Prep. ST Contract Nº.
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 88 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
In this mode the time monitoring of the sequencing is inactive – that means that the unit can stay
at any condition for unlimited time.
c) Automatic mode
This mode can be selected on the touch panel when +#CJA02-S05 is in position "Local" or is
active when +#CJA02-S05 is in position "Remote"
In this mode the unit can be controlled from the local Touch Panel or from the Operator station
in the control room in fully automatic mode by selecting the required state of operation of the
unit by the corresponding buttons in the unit displays.
Place of control in this mode – local Touch Panel or Operator Station – is determined by posi
tion of +#CJA02-05 Control from both places at same time is not possible!
The LAN is using Ethernet (TCP/IP) with standardised protocol IEC 60870-5-104.
Conditions, determining the states of operation are displayed on the Touch Panel and the Op
erator stations in the Control Room and are defined in detail in document. All other operating
conditions can only occur during transitions between these states of operation and during
abnormal conditions.
The states of operation are displayed and can be selected on Touch Panel and the Operator
Stations in the Control Room.
Date 31.01.2014
Page 89 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 90 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 91 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
(IV) Synchronizing
Independent of the Control Mode (Step by Step, Auto) the synchronising of the Unit can be done in
Automatic or Manual mode.
Synchronizing is effected with 220 kV breakers
Mode of synchronizing is selected with switch +#CJA02-S06 with three positions:
manual
automatic
For fully automatic start of the unit the selector switch must be in the "Automatic" position.
Manual synchronizing
Position of +#CJA2-S06: Manual
Unit can be synchronized manually in this position:
Pushbuttons Voltage raise/lower and Seed raise/lower (+#CJA02-S09 & S08) allow adjusting the
synchronizing parameters before closing of circuit breaker with +#CJA02-S10.
The Synchronoscope +#CJA12-P03 shows the phase difference between the Generator and grid by LED.
When the phase angle is zero, the green LED at the top in the form of an arrow is lit. This position
indicates that the Generator and the network are synchronous.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
The Synchronoscope has an interlocking contact which is closed only when the phase angle is within
preset limits (synchrocheck function). The circuit breaker close command from +#CJA02-S10 is
interlocked with this contact to prevent closing of breaker at wrong time.
Automatic synchronizing
Position of +#CJA2-S06: Auto
Synchronizing is done automatically by the SYN3000, when position of switch +#CJA2-S07 Syn
Start/Stop is in the start condition.
As long as the synchronising is ongoing, the Manual Synchronizing Instrument +#CJA02-P05 is activated
and allow supervision of the process.
Where technically required, analogue measuring values, connected to the controller either as mA signals or
as Pt100 temperature values, are supervised for limit values. Normally two limits are preset:
Alarms
All external and internally created signals (e.g. temperature exceeded) which are giving evidence of an ab-
normal condition in the plant, are treated principally as alarms, independent if the signal causes a trip of the
unit or not.
Every alarm is time tagged with a resolution of 1 msec. The SCADA system uses this time stamp for re-
ports, lists and archives. Please refer also to chapter “Operations”
Every alarm signal causes an acoustic alarm and is displayed on the Touch Panel and the Operator Sta-
tions in the Control Room in the alarm list (please refer also to chapter “Operations”)
Date 31.01.2014
Page 92 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Both tripping relays require a manual reset action by the operator - without a reset the unit cannot be
started because the starting conditions require both relays to be in operation position!
Reset of 86M and 86E is possible by means of the corresponding pushbutton on unit control board in
local mode or from SCADA in remote mode.
A reset of ESD and QSD relay is only possible after all activating trip conditions are inactive again!
Tripping circuits
The tripping relays only operate the following tripping circuits:
Generator circuit breaker - two tripping coils, not energized in operation
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
In case of any trip – mechanic trip as well as electric - a normal shutdown sequence of the unit by the
Controller is initiated. This ensures that the state of operation “Standstill” is reached and all auxiliaries are
Operated correctly
There are two types of tripping circuits:
Circuits energized during normal operation conditions e.g. shut down valves
Circuit which have to be energized for activation e.g. tripping coils for circuit breakers
Circuit breaker can be closed only when the field breaker is closed
Opening of field breaker is only possible when the circuit breaker is open
Date 31.01.2014
Page 93 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The Common Control Board contains equipment, necessary for common auxiliary control and the Joint
Control system of the two units
Date 31.01.2014
Page 94 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 95 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The Intake Gate Control Board contains all equipment, necessary for control and supervision of the
Intakes.
Date 31.01.2014
Page 96 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
6. Maintenance
Necessary equipment
Oil free compressed air spray (if there is oil inside the compressed air the dust will start gluing on the
devices!)
Small flat screw driver (3.5mm)
Vacuum cleaner
Anti-static arm-band
AK-3-board "extraction tool" (should be at the AK-3 frame!)
*** It is important that all devices (Circuit breakers, pumps etc.) are switched to local control in order to
prevent false orders by unintentional operating relays during cleaning procedure!
Date 31.01.2014
Page 97 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Check status of LED's of all electronic devices inside the cubicle: All RY-LED's should be on, no red
LED should be on! If one or more red LED's are on, please note the modules with activated red LED's
and report to responsible service staff
Select on the Touch panel Shutdown Operation System (Windows XP Start Menu Item “Shutdown”)
and wait until the system confirms that it is ready for power off.
De-energize all devices inside the cubicle by switching off all MCB in the cubicle. No device should be
energized (no LED’s, ventilation’s …).
Clean Devices (cable channel, relays, …) carefully with compressed air. If the cubicle is strongly dusty,
use first the vacuum cleaner to prevent that dust is distributed in the surrounding area and afterwards
continue with compressed air.
Remove the AK-3 front-panel with screwdriver (4 screws) - AK-3 boards are accessible.
Put on anti-static arm-band
Pull out each board with the "Extraction tool" fixed to the ACP frame
Clean each board carefully with compressed air (both sides)
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
*** Do not mix up the boards! Take care on the peripheral board address (PBA). If you are not sure which
the original slot was, please have a look in the configuration documentation.
The Ready (RY)-LED's of all boards should be on and no red LED (at the AK-3) should be on.
Protection System and Touch Panel should start-up also.
Ask the operator if there are no errors displayed at the SCADA system.
Create a backup
Necessary equipment
Backup medium of Toolbox II data (file, CD-ROM, tape, etc...)
Procedure
Date 31.01.2014
Page 98 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Select with the mouse the root entry in the left window
Hold the CTRL key and drag the selected root entry in the right window.
*** If the CTRL key is not held during drag and drop all selected parameters will be exported and kept
As read only in the database. In this case it will not be possible to modify them anymore.
Date 31.01.2014
Page 99 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Procedure
Start Toolbox II "Data Distribution Center"
Open "Import"-folder
Specify backup file
Check if the "Data Distribution Center" is able to read the backup file
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Procedure
Start Toolbox II
Connect Toolbox II PC to the Network
Start any Toolbox Tool (e.g. Diagnosis)
Client VSH Prep. ST Contract Nº.
Plant TKT HPP (2X110 MW) Chk. TD 817/2012/HD-VSH-AH
Project Nº C.388/C.389 / V-0322 Appr. HJ = +
Index R1 DOC Nº TKT-CM-01-OM-1060-I
HIB
Date 31.01.2014
Page 100 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
In a window a feedback about the established remote connection should appear. Leave this window
open!
Now start the normal diagnosis of this station.
When the diagnosis is working without any problems, the remote-connection is ok!
Date 31.01.2014
Page 101 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Procedure
Start Toolbox II
Start Toolbox II Presets
Click Database | Reorganisation
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Hint:
This function can also be performed automatically by the Windows scheduler. A description can be found
in the Toolbox O7nline Help!
*** Reorganisation of database can take several minutes!
The hardware of ACP 1703 is developed according the latest available technology on the market. By
Using low power electronic modules, Flash Prom's, motionless elements etc. there are only a few
Maintenance activities recommended.
People, handling electronic components or modules have to be electrically grounded (with arm bands or
ESD shoes). This also applies when handling processing signal connectors (plugs, terminals, etc.) on
equipped boards.
Electronic components or boards may be transported only in electrically conductive containers or packag-
ing.
Regular checking of all grounding devices and ESD workplaces to ensure their effectiveness.
6.2.3
*** The activities described in this chapter presume that the grounding connection between Control
System and cabinet or rack has been properly carried out and that these are earthed.
Date 31.01.2014
Page 102 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
6.2.3.1 Preparations
The grounding strap can be connected directly to the mounting rack. The connection point i located
on the left side panel of the mounting rack: see in below picture:
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Open the knurled screws* which connect the front panel with the mounting rack CM-2844:
Take hold of the front panel at the knurled screws and remove it.
Date 31.01.2014
Page 103 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
6.2.3.1 Removal
This is included in the scope of supply of every mounting rack and must be inserted in the bracket,
provided on the mounting rack during installation.
Connect/put on grounding strap and remove front panel
Position the extracting tool between module and profile rail.
Loosen the plug-in connector by pushing the unlocking clip upwards, or downwards.
Grasp the module at the unlocking blocks and withdraw it from the mounting rack.
Date 31.01.2014
Page 104 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Installation of a Serial Interface Module (SIM) on master control element (CP-2016) or on processing-
and communication element (CP-2019)
Fitting of the connection boards on Patch Plugs
Installation of the connection boards on master control element or on processing- and communication
element
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 105 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
SIM and module are connected by means of 3 connectors and 2 retainer clips. The connectors serve the
mechanical and electrical connection of both components. The clips provide an additional mechanical
hold:
For type of Patch Plug please refer to the relevant plant documents.
The fitting is carried out by engaging the connection board in the red seating frame and subsequent
screwing with the fastening bracket on the underside of the mounting rack:
Date 31.01.2014
Page 106 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Insert the connection board into the mounting rack from below, until the point of the grip flap lies between
profile rail and seating frame . (Wall bracket and cover plate support this activity with the help of an inte-
grated guide plate.)
Swing the lower part of the connection board forward . Ensure that the hook of the grip flap is guided
through the unlocking lever.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Push the connection board upward until grip flap and seating frame are finally fixed together.
Finally the front panel of the connection board is screwed with the fastening bracket on the underside of
the mounting rack .
Configuration Notes
Depending on the type of used connection board and the communication module (SIM) different interface
ports for connection of cables are available:
Date 31.01.2014
Page 107 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
For mounting the locking clips on the top side of the module are pressed together, the module coupled
with the neighboring module by means of the guides at the corners of the housing and positioned on the
rail.
Date 31.01.2014
Page 108 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Modules that are adjacent to each other are mechanically connected with each other by means of the guides
at the corners of the housing.
For the removal, the locking clips are pressed together and the module is withdrawn with clips pressed
together
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
`
Guideline For The Replacement Of Modules
By means of the modular design of AK-3 the replacement of a faulty module is achievable in an easy
manner:
• The peripheral cables can be detached without tools.
• The modules are detached from the rack with the unlock tool TA2-105 (scope of delivery).
• Serial interface modules and connection boards can be detached without tool.
• The user data (parameters and application program) are stored non-volatile on the flashcard.
Date 31.01.2014
Page 109 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
• The flash card can be withdrawn from the removed master control module.
• For the commissioning of a new module the TOOLBOX II is not required.
*** For the replacement of system elements a shutoff of the power supply is not required. By means of
that, the function of the subsystems which are not affected by the replacement is maintained.
*** For peripheral elements that operate with voltages > 60 V (e.g. DI-2111) care must be taken that mani
pulation on the peripheral connectors may only be carried out in a de-energized state.
parameterization). After the loading of the changed configuration into the target system, a startup of the
system must be performed.
Date 31.01.2014
Page 110 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
*** For replacement of CPU boards no parameter loading procedure with Toolbox is required, as long
as no parameters have to be modified and the Flash Card/SIM Card is not exchanged!
All required parameters; Firmware as well as plant parameters are stored on the Flash Card / SIM Card.
For changing and loading of changed parameters the Toolbox PC has to be connected to the concerned
AK 1703 automation unit (controller) and a Flash Card must be inserted in the slot of the master control
element (CP-2016). For the MIC the SIM card must be inserted please refer to Chapter
6.3.1.1 Physical Connection between Toolbox PC und AK-3
Following types of connections between TOLLBOX and AK -3 controllers are possible:
direct local via toolbox cable
Ethernet (TCP/IP, TELNET)
Date 31.01.2014
Page 111 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 112 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
• Messages with system information are either processed directly (e.g. station interrogation) or distributed
further based on their destination address (CASDU) (e.g. messages for remote maintenance)
Date 31.01.2014
Page 113 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 114 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 115 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 116 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 117 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 118 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
The reset signal of the master control element affects the entire automation unit, this means
also the:
• Processing and communication elements
• Protocol elements
• Peripheral elements
The reset signal of a processing and communication element affects its belonging subordinate
• Protocol elements
• Peripheral elements
Date 31.01.2014
Page 119 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
During startup of the AK 1703 ACP system, checks of the hardware and the software are performed by
the individual system elements.
If an error is detected, this leads
• To a signaling via the LED-displays (an overview can be found below)
• Depending on the seriousness of the error, possibly to an abortion of the startup
After error-free startup of a system element, further checks are performed.
Date 31.01.2014
Page 120 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Date 31.01.2014
Page 121 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 122 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Protocol Elements
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 123 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Peripheral Elements
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 124 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
6.3.5 Diagnosis
General
The following listing explains the different error categories and how the error messages are logged.
• Hardware errors
Monitoring of the individual system elements, communication and time synchronization by the firmware
of the target system in operation. Error information takes place by
─ Logging via diagnostic function (online)
─ Activation of the red error-LED on the master control element
• Software errors
─ Parameter setting
The input of the parameters with the help of the TOOLBOX II tools is subjected to – as far as logically
recordable - parameter-specific conventions or plausibility checks. Faulty inputs are notified or directly
prevented with the entry.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
If a - in principle permitted - parameter setting, that however does not match the physically present
system elements, is loaded into the target system, the method of procedure is as with hardware errors.
─ Programming
Monitoring by the CAEx plus compiler and logging in an error information list during compiling of the
application program code.
• Operator errors
Are largely excluded due to plausibility checks or queries by the TOOLBOX II. Naturally, all operator
inputs, such as for example the loading of parameters or the online testing of application programs, are
subject to the responsibility of the user.
System Diagnosis
AK 1703 ACP contains extensive diagnostic functions for monitoring the system. Since the firmware
automatically executes the appropriate error monitoring routines, for this no settings of any kind by the
user are necessary.
Date 31.01.2014
Page 125 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
With the tool "Diagnostic", system states and errors can be read out and displayed in plain
text and printed out if required (online).
• AU overview diagnostic
The error messages of all automation units in the network are output in a report window with the function
AU OVERVIEW DIAGNOSTIC (sum information for each system element able to report).
• History
The history of error messages is output in a report window with the function HISTORY DIAGNOSTIC.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
• Automatic diagnostic
An overview of the error messages of all automation units in a network as well as their system elements is
output in a report window with the function AUTOMATIC DIAGNOSTIC. The outputs are structured hierar-
chically in
─ Network overview diagnostic
─ AU overview diagnostic
─ AU single diagnostic
─ History (if preset)
Date 31.01.2014
Page 126 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 127 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
System Performance
Information about the system performance of a selected automation unit can be interrogated
(Online) with the tool "Service Function Online":
• Display equipped system elements
• Read serial numbers
• Display/delete data flow routing
• Shut down selected system elements
• Shut down selected automation unit
• Startup selected system elements
• Startup automation unit
• Display time
• Memory check
• Data processing capacity
• Control- and bus runtime
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
With the tool "CAEx plus" the following status information can be displayed for each task with the function
ONLINE-TEST:
• Parameterized cycle time
• Current runtime
• Minimum/maximum runtime
• Number of runtime time-outs
• Bus runtime
Further Information can be found in the manual AK-3 Common Functions System and
Basic System Elements, chapter "Automation", section "Open-/Closed-loop Control Function", section
"Display Status Information".
Errors that can occur with the creation of the function diagram (for example the linking of a binary signal to
an analog input of a function) are displayed in a separate report window ("POU error check"):
• Automatically with the incorrect input
• Manually with the function EARLY ERROR DETECTION (Pop-up menu in the function diagram).
All editing errors can be displayed at any time.
In AK -3, new system elements or new revisions of system elements can be integrated, if required. The
updating of the system takes place in steps:
Date 31.01.2014
Page 128 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
The firmware revisions of all configured system elements (basic system element, peripheral element, pro-
tocol elements) can be displayed on the screen and printed out for a selected automation unit with the
tool "Revision Interrogation".
Further details about the tool can be found in the TOOLBOX II User Manual, chapter "Revision Interroga-
tion".
Date 31.01.2014
Page 129 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
SAT SCALA CD
License Sheet with activation codes
SCALA Parameter Backup
updates. To keep the computer time synchronized the Software Tardis needs to be installed. This
Software will be found on the SCADA software CD.
Start the installation and follow the instruction.
Date 31.01.2014
Page 130 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Default already three time sources are defined. This time sources should be deleted with the button "Clear All",
confirm the warning with "YES".
Date 31.01.2014
Page 131 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Protocol needs to be SNTP/NTP, Address and Name is the IP Address from the NTP Server. Enter the IP ad-
dress according the attached Network List.
To optimize automatic time adjustment following settings are recommended:
Date 31.01.2014
Page 132 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 133 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Procedure
Insert SAT SCALA CD into CD-ROM drive. If the Computer is configured for automatic installation the
setup screen is displayed. For Manual start of the Setup select the Windows Explorer, open the CD
drive folder, sub directory SATSCALA and select the Program Setup.
The installation Program will ask for the preferred language. Available is English and German. Select
the preferred language and follow the instruction of the installation program.
Select Custom Installation to activate these software parts which are indicated on the license sheet. It
is not possible to install software, not listed on the license sheet.
Choose the Software parts, which should be installed:
Date 31.01.2014
Page 134 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
The below table informs about the necessary part which should be installed:
Date 31.01.2014
Page 135 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 136 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Enter the destination drive for the SCALA (the normally proposed destination is in most cases correct) and
follow the instruction of the installation program.
After successful installation of SCALA the setting screen will pop up. Keep the default settings and confirm
the Screen with OK.
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Last step is to restore the Plant parameter. In this case you should not interrupt the restore procedure you
should continue.
Restart the computer, after this procedure the SCADA system should work.
6.4.5 Cleaning
Computers
Cleaning of PC's should be done one a year or when the machines are polluted heavy due to abnormal
conditions
Necessary equipment
Oil free compressed air spray
Small screw driver (Phillips screwdriver)
Anti-static arm-band
brush
vacuum cleaner
Procedure
Inform operator that Operator station will be out of operation for about 30 minutes.
Date 31.01.2014
Page 137 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Shutdown Operation System (Windows Start Menu Item “Shutdown”) and wait until the system confirms
that it is ready for power off.
Switch off the PC and disconnect PC from 230 V AC-power supply
Open PC according to manufacturer’s manual
Clean PC inside with compressed air. If the PC is extremely dusty it is recommended to clean first with the
vacuum cleaner and afterwards with compressed air to prevent that the dust is distributed.
*** Do not touch the sensible electronic components with the pipe - it is recommended to have a
brush on top of the vacuum pipe!
Monitor
Necessary equipment
- Appropriate cleaner
- Soft cleaning cloth
Procedure
Careful cleaning of screen and housing of monitor
Printers
Necessary equipment
Appropriate cleaner
Soft cleaning cloth
Compressed air spray or vacuum cleaner
Procedure
Open the flap of the printer (please follow printer manual)
Use compressed air spray or vacuum cleaner to clean the printers inside.
Close the flap of the printer
Use cleaning cloth and cleaner to clean printers housing.
Use printer handbook to execute further maintenance like exchange of cartridge(s)
Check if sufficient printer paper is available
Check if sufficient spare cartridges are still available
Mouse
Necessary equipment
Appropriate cleaner
Soft cleaning cloth
Date 31.01.2014
Page 138 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Procedure
Clean mouse body with cleaner and cloth
Clean mouse bottom with cleaner and cloth
Procedure
Open My computer Icon on the Desktop
Select Hard disk Drive C press the right mouse button and select properties
Open folder Tools and select Defragment Now
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Date 31.01.2014
Page 139 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
After finishing the defragmentation select the next drive in the defragmentation tool and start the
defragmentation again. Continue this step until all drives are defragmented.
After any change in SAT 250 SCALA at least one backup has to be performed.
The backup file should be copied to a safe media like CD Rom or save drive on a Server.
Create backup!
Necessary equipment
Backup medium of SCALA 250 software (file, CD-ROM, tape, etc...)
Procedure
Start "Start | Programs | SAT 250 SCALA | Data Storage Client"
Select "Backup"
Date 31.01.2014
Page 140 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Next
Select path of backup
Next
Select the check boxes for "SCADA client", "CAE Server", "User Data", "Scada Server"
Select Finish
Date 31.01.2014
Page 141 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Procedure
Start "Start | Programs | SAT 250 SCALA | Data Storage Client"
Select "Restore"
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Next
Select source path
Check if "data storage info" are plausible
Date 31.01.2014
Page 142 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
*** The last step of this procedure defines if a restore process is started or if the process is
cancelled!
Cancel ends the check of backup files
Finish will start the restore process
REGISTERED
Date 31.01.2014
Page 143 of page 144 Internal Nº 2801060
O&M Manual –Control & Monitoring system
Quanti-
Sr.No. Description Unit Remark
ty
1 CPU-2016 No. 2 #
2 Process Input/ Output card
1. DI-card 6103 110/220V DC, Siemens No. 2 #
3 Push Button Set 1 #
4 Selector Switch Set 1 #
5 Indicating Lamp Set 1 #
This drawing/document is the INTELLECTUAL PROPERTY of
ANDRITZ HYDRO GmbH, Vienna, Austria
Sr. Quanti-
Description Unit Remark
No. ty
1 Process Input/ Output card
1. DO-card 6212, 24-220V DC/230V AC, Siemens No. 2 #
2. AI-card 6300, (4to20mA), Siemens No. 2 #
2 Ethernet Interface Module No. 1 #
3 Touch Panel 19” No. 1 #
4 Electric Measuring Equipment Set 1 @
5 Synchronizer No. 1 *
REGISTERED
Date 31.01.2014
Page 144 of page 144 Internal Nº 2801060