1. A thermometer having a time constant of 0.2 min is placed in a temperature bath, and after
the thermometer comes to equilibrium with the bath, the temperature of the bath is increased
linearly with time at a rate of 1°/min. What is the difference between the indicated
temperature and the bath temperature (a) 0.1 min, (b) 1.0 min after the change in temperature
begins?
(c) What is the maximum deviation between indicated temperature and bath temperature, and
when does it occur?
(d) Plot the forcing function and response on the same graph. After a long enough time, by
how many minutes does the response lag the input?
hD C p
k = 0.1914 Re0.618 Pr1/3 (Note: Pr = k )
Data:
Water: Cp = 1.0 Btu/lboF, k = 0.36 Btu/fthroF, = 0.72 cp = 0.72×2.42 lb/ fthr
Mercury: Cp = 0.33 Btu/lboF, specific gravity = 13.6
Solution
Solution
Solution
Solution
y = 50 + 34.94 = 84.94oC
6.1 The level in a tank responds as a first order system with changes in the inlet flow. Given
the following level vs. time data that was gathered after the inlet flow was increased quickly
from 1.5 gal/min to 4.8 gal/min, determine the transfer function that relates the height in the
tank to the inlet flow. Be sure to use deviation variables and include units on the steady state
gain and the time constant.
Time (min) Level (ft) Time (min) Level (ft) Time (min) Level (ft)
0 4.8 1.2423 8.9354 2.4847 11.4513
0.138 5.3673 1.3804 9.2805 2.6227 11.6612
0.2761 5.9041 1.5184 9.6071 2.7607 11.8599
0.4141 6.412 1.6564 9.9161 ………….. …………..
0.5521 6.8927 1.7945 10.2085 14.3558 15.3261
0.6902 7.3475 1.9325 10.4853 14.4938 15.328
0.8282 7.7779 2.0705 10.7471 14.6319 15.3297
0.9663 8.1852 2.2086 10.9949 14.7699 15.3313
1.1043 8.5706 2.3466 11.2294
Kp = 3.19 ft/gpm
In this equation: H(s) = h(s) 4.8 ft and Q(s) = q-1.5 . H(s) and Q(s) are deviation variables.
7. The bypass cooling system shown is designed so that the total flow of 200 gpm of a liquid
with heat capacity of 0.8 Btu/lboF is split under the normal conditions, 20 % going around
the bypass and 80 % going through the cooler. Process inlet and outlet temperature under
these conditions are 250 and 150oF. Inlet and outlet water temperatures are 80 and 120oF.
Process side pressure drop the exchanger is 10 psi. The control valves have linear trim and
are designed to be half open at design rates with a 15 psi drop over the bypass valve and 10
psi drop over the cooler valve. Liquid density is constant at 62.3 lb/ft3.
What will the valve positions be if the total process flow is reduced to 25 percent of design
and the process outlet temperature is held at 150oF?
S e t p o in t ( S P )
TC
P ro c e s s b y p a s s
TT
W a te r
T i( t ) T (t)
P ro c e s s C o o le d s t r e a m
s tre a m
Solution ------------------------------------------------------------------------------------------
Solution
4 4
3( s 1) 4.5
4 4
1 1
C(s)/R(s) = 3( s 1) = 4.5 = 0.47059
12. Consider the following control system with all instrumentation in electronic (4 to 20 mA)
Hot oil
o
90 F
Refrigerant
FT
o
50 F Heat
Cooler exchanger
Cooled oil
o
70 F
TT TC
a) If the temperature transmitter has a range of 50-100oF, determine the value from the
temperature transmitter.
b) If the range of the orifice-differential pressure flow transmitter on the water line is 0-2000
gpm, determine the value from the flow transmitter for a water flow rate of 900 gpm.
Solution
a) If the temperature transmitter has a range of 50-100oF, determine the value from the
temperature transmitter.
70 50
4 + 16 100 50 = 10.4 mA
b) If the range of the orifice-differential pressure flow transmitter on the water line is 0-2000
gpm, determine the value from the flow transmitter for a water flow rate of 900 gpm.
2
900
4 + 16 2000 = 7.24 mA