The latest range of advanced process controllers from Eurotherm provide • 2 PID loops
precision control of temperature and a host of other process variables • 50 Programs
together with an abundance of advanced options making it the most
• Precision PV input
adaptable product in its class.
• Carbon potential
The emphasis is on flexibility yet the 3500 controllers still maintain ease of • Maths/logic/timers
use. A simple ‘Quick Start’ process is used to configure all the basic • Custom user interface
functions essential to controlling your process. This includes input sensor • Recipes
type, measurement range, control options and alarms making ‘Out the Box’ • Digital communications
operation truly achievable. More advanced features are configured using a
– Modbus RTU Master and
PC based graphical configuration tool enabling users to pick function blocks
from a library then connect them together using soft wiring. – Slave
– Ethernet Modbus TCP
The large 5-digit display provides a clear and unambiguous indication of the – Profibus DP network
process value. A four-line message centre provides custom or standard – DeviceNet® network
views of important information to the user while vertical and horizontal
• OEM Security
bargraphs provide at a glance visual indication of the process. OEM Security
• Multi-language support (English, French,
enables a user to protect their intellectual property by preventing
German, Spanish and Italian)
unauthorised cloning of the configuration.
Input/output flexibility
A range of plug-in I/O modules caters for
individual application requirements minimising
stock and spares holding. A total of sixteen
module types, including relay, logic, triac and
analogue, are available to fit into either three slots
on 3508 or six slots on 3504.
IO Expander
Extra IO can be provided by the IO Expander. Options are
available for 10in 10out and 20in 20out.
Live Module 1
Rectification
264V ac
Installation Power
Supply
Double
3508 3504 Neutral Circuits
48mm 96mm Module 2
Functional Earth
264V ac 264V ac
Double Double
96mm Communications
(H Comms) Module 3
µP &
264V ac system 264V ac
Double circuits Double
Communications
159mm Module 4
(J Comms)
148mm
264V ac
Double
PSU mounted
Logic I/O & Module 5
Common
264V ac
Double
PSU mounted
Module 6
3508 Panel cut-out 92mm (–0.0 +0.8) x 45mm (–0.0 +0.6) PV Input
3504 Panel cut-out 92mm (–0.0 +0.8) x 92mm (–0.0 +0.8)
14 15 16 17 18 19 20 21
Basic Product 1 Function
Note 2
6 Recipes
X No recipes
1 1 Recipe
4 4 Recipes
8 8 Recipes
Notes
1. Only available with the Profibus
Controller
2. I/O slots 4, 5 and 6 are only
available on the 3504
3. Provides Valve Position option in
Heat/Cool applications. Single
channel VP included as standard
4. If standard config is selected an
instrument without configuration will
be supplied.
5. If C or F units are selected they
must be the same for both loops. If
C or F are not selected for Loop 1
they cannot be selected for Loop 2.
3500 Accessories 6. CH1 = Heat, CH2 = Cool.
HA027987 User guide
HA027988 Engineering manual Table 1
SUB35/ACCESS/249R.1 2.49R Precision resistor
A 4-20mA Linear
iTools/None/3000IR Configuration IR clip
Y 0-20mA Linear
iTools/None/3000CK Configuration clip W 0-5V dc Linear
2000IO/VL/10LR/XXXX 10IN, 10OUT Expander G 1-5V dc Linear
2000IO/VL/20LR/20LR 20IN, 20OUT Expander V 0-10V dc Linear
14 15 16 17 18 19 20 21 22 23 24
Basic Product 1 Function
Note 2 Note 2 Note 2
1 Configuration 7 Loop 2 Units 16-17 Logic LA and Logic LB 19-24 ... continued
STD Standard config. (Note 4) C Centigrade (Note 5) XX Unconfigured CCX Ch2 O/P for loops 1 and 2
CFG Factory configured F Fahrenheit (Note 5) 1_ Loop 1 SBR Sensor Break both loops
% Percent 2_ Loop 2 Dual Triac (TT)
H %RH _B Sensor Break _HC Ch1 O/P and Ch2
2 Loop 1 Units P PSI _M Manual Select _VH VP Ch1
B Bar _H Control Ch1 O/P _VR VP Ch2
C Centigrade M mBar _C Control Ch2 O/P P12 Prog Ch1 Event 1 and 2
F Fahrenheit X None _R Remote SP P34 Prog Ch1 Event 3 and 4
% Percent
_S Setpoint 2 Enable P56 Prog Ch1 Event 5 and 6
H %RH
A_ Alarm P78 Prog Ch1 Event 7 and 8
P PSI 8 Loop 2 Function
_A Acknowledge all Alarms A12 Alarm 1 and 2 O/P
B Bar XX Single Loop Only A34 Alarm 3 and 4 O/P
_1 Alarm 1 O/P
M mBar PX Single Channel PID HHX Ch1 O/P for loops 1 and 2
_2 Alarm 2 O/P
X None FX Single Ch Valve with feedback P_ Programmer CCX Ch2 O/P for loops 1 and 2
VX Single Ch Valve w/out feedback _R Run DC Control (D4)
3 Loop 1 Function NX Single Ch On/Off _H Hold For range select third digit from Table 1
PP Dual Channel PID _A Reset _H_ Ch1 O/P
PX Single Channel PID PN Dual Ch PID/OnOff _C_ Ch2 O/P
_1 Prog Ch1 Event 1
FX Single Ch Valve with feedback FF Dual Ch Valve with feedback DC Retransmission (D6)
_2 Prog Ch1 Event 2
VX Single Ch Valve w/out feedback VV Dual Ch Valve w/out feedback For range select third digit from Table 1
NX Single Ch On/Off PF Dual Ch PID/Valve with feedback _T_ PV Retransmission
PP Dual Channel PID PV Dual Ch PID/Valve w/o feedback _S_ SP Retransmission
PN Dual Ch PID/OnOff 18 Relay AA Analogue Input (AM)
FF Dual Ch Valve with feedback 9 Loop 2 PV For range select third digit from Table 1
VV Dual Ch Valve w/out feedback XX Unconfigured
2PV Loop 2 PV
PF Dual Ch PID/Valve with feedback X Unconfigured 1_ Loop 1
_R_ Remote SP
PV Dual Ch PID/Valve w/o feedback J J Thermocouple 2_ Loop 2
Analogue Input (AM)
K K Thermocouple _H Control Ch1 O/P
For range select third digit from Table 1
T T Thermocouple _C Control Ch2 O/P
2PV Loop 2 PV
4 Loop 1 PV (from Main PV) L L Thermocouple _B Sensor Break
_R_ Remote SP
N N Thermocouple SB Setpoint Break (any loop)
J J Thermocouple Potentiometer Input (VU)
R R Thermocouple A_ Alarm
K K Thermocouple _RS Remote SP
S S Thermocouple _A Any Alarm Active
T T Thermocouple B B Thermocouple _VF Valve Feedback Ch1
_N New Alarm Active
L L Thermocouple P Platinell II _VG Valve Feedback Ch2
_1 Alarm 1 O/P
N N Thermocouple C C Thermocouple Dual 4-20mA O/P/TxPSU
_2 Alarm 2 O/P
R R Thermocouple Z Pt 100 _HC Ch1 O/P and Ch2 O/P
P_ Programmer
S S Thermocouple A 4-20mA Linear _HT Ch1 O/P loops1, TxPSU
_1 Prog Ch 1 Event 1
B B Thermocouple Y 0-20mA Linear HHX Ch O/P for loops 1 and 2
_2 Prog Ch 1 Event 2
P Platinell II W 0-5V dc Linear TTX Both channels TxPSU
C C Thermocouple G 1-5V dc Linear Triple Logic IP (TL) or (TK)
Z Pt 100 V 0-10V dc Linear ___ Select function below for each ch
A 4-20mA Linear D D Thermocouple 19-24 Slot Functions 1-6 (Note 2) X Unconfigured
Y 0-20mA Linear E E Thermocouple M Loop 1 Manual
W 0-5V dc Linear 1 Ni/Ni 18% MO XXX Unconfigured N Loop 2 Manual
G 1-5V dc Linear 2 Pt20%Rh/Pt40%Rh 1__ Loop 1 Q Loop 1 Remote SP
V 0-10V dc Linear 3 W/W26%Re (Englehard) 2__ Loop 2 V Loop 2 Remote SP
D D Thermocouple 4 W/W26%Re (Hoskins) Changeover Relay (R4) S Loop 1 Setpoint 2 enable
E E Thermocouple 5 W5%Re/W26%Re (Englehard) _ HX Control Ch1 O/P T Loop 2 Setpoint 2 enable
1 Ni/Ni 18% MO 6 W5%Re/W26%Re (Bucose) _CX Control Ch2 O/P E Acknowledge all Alarms
2 Pt20%Rh/Pt40%Rh 7 Pt10%Rh/Pt40%Rh _BX Sensor Break P Program Run
3 W/W26%Re (Englehard) Q Custom Curve 2-Pin Relay (R2) R Program Reset
4 W/W26%Re (Hoskins) _HX Control Ch1 O/P H Program Hold
5 W5%Re/W26%Re (Englehard) 10 Loop 2 Range Low _CX Control Ch2 O/P Triple Logic OP (TP)
6 W5%Re/W26%Re (Bucose) _BX Sensor Break ___ Select function below for each ch
7 Pt10%Rh/Pt40%Rh XXXXX Enter value with decimal point Single Logic (LO) X Unconfigured
Q Custom Curve _HX Control Ch1 O/P F Loop 1 Control Ch1 O/P
_CX Control Ch2 O/P G Loop 1 Control Ch2 O/P
11 Loop 2 Range High Single Triac (T2) K Loop 2 Control Ch1 O/P
5 Loop 1 Range Low _HX Control Ch1 O/P L Loop 2 Control Ch2 O/P
XXXXX Enter value with decimal point _CX Control Ch2 O/P A Alarm 1 O/P
XXXXX Enter value with decimal point Dual Relay (RR) B Alarm 2 O/P
_HC Ch1 O/P and Ch2 C Alarm 3 O/P
12-15 Alarms 1-4
_VT VP Ch1 D Alarm 4 O/P
6 Loop 1 Range High
XXX Unconfigured _VR VP Ch2 1 Program Event 1
1_ _ Loop 1 P12 Prog Event 1 and 2 2 Program Event 2
XXXXX Enter value with decimal point
2_ _ Loop 2 P34 Prog Event 3 and 4 3 Program Event 3
_FH Full scale high P56 Prog Event 5 and 6 4 Program Event 4
_FL Full scale low P78 Prog Event 7 and 8 5 Program Event 5
_DH Deviation high A12 Alarm 1 and 2 O/P 6 Program Event 6
_DL Deviation low A34 Alarm 3 and 4 O/P 7 Program Event 7
_DB Deviation band HHX Ch1 O/P for loops 1 and 2 8 Program Event 8
Line Line
4A
1A
1A
HA
HA
L
L
85 to 264V ac 85 to 264V ac
IO Module 1
Module 4
Module 1
Comms Channel 1
4B
1B
1B
HB
HB
Neutral Neutral
N
N
Comms Channel 1
4C
1C
1C
HC
HC
Earth Earth
4D
Logic IO A Logic IO A
1D
1D
HD
HD
D8
D8
Logic IO B
HE
Logic IO B
HE
LB
LB
2A
5A
2A
IO Module 2
HF
Common
HF
Common
LC
LC
Module 5
Module 2
2B
5B
2B
2C
5C
2C
NO
AA
NO
AA
JA
JA
2D
Comms channel 2
5D
2D
AB
AB
JB
JB
C C
Comms Channel 2
AC
AC
JC
JC
3A
6A
NC
3A
NC
IO Module 3
Module 6
Module 3
JD
JD
VI
VI
3B
6B
3B
RTD RTD
V+
V+
JE
JE
3C
6C
3C
mV mA mV mA
3D
6D
V–
3D
V–
JF
JF
NO + +
Potentiometer Input
A A A A + A A A
Triple Logic Output
Transmitter PSU
DC Transmitter
Not in slots 2 or 5
+ +
Dual Triac
B B B B B B B
Relay
C Out B – In B 0V
NO + +
C C C C C C C
Out C In C
– +
D D D D D D D
Comm Comm
NO + + +
Isolated Logic Output
Potentiometer Input
A A A A + A A A
Out A In A EXC
Transducer PSU
–
DC Output
+
Dual Relay
B B B B B B B
Triac
+0.5V C – In B EXC
NO + +
C C C C C C C
Wiper In C CAL
– + –
D D D D D D D
0V C Comm Comm CAL
NO
A + A
Change Over Relay
DC Output
B B
C –
NO
C + C
D D
–
Eurotherm Limited Eurotherm by Schneider Electric, the Eurotherm logo, Chessell, EurothermSuite,
Mini8, Eycon, Eyris, EPower, EPack, nanodac, piccolo, versadac, optivis, Foxboro
Faraday Close, Durrington, and Wonderware are trademarks of Schneider Electric, its subsidiaries and affiliates.
All other brands may be trademarks of their respective owners.
Worthing, West Sussex, BN13 3PL
All rights are strictly reserved. No part of this document may be reproduced, modified,
Phone: +44 (01903) 268500 or transmitted in any form by any means, nor may it be stored in a retrieval system
Fax: +44 (01903) 265982 other than for the purpose to act as an aid in operating the equipment to which the
document relates, without the prior written permission of Eurotherm Limited.
www.eurotherm.com/worldwide
Scan for local Eurotherm Limited pursues a policy of continuous development and product
improvement. The specifications in this document may therefore be changed without
contacts notice. The information in this document is given in good faith, but is intended for
guidance only.
Eurotherm Limited will accept no responsibility for any losses arising from errors in
this document.
Document Number HA029045 Issue 8 March 2016