You are on page 1of 3

niled s.a.e. ND 523-11.

8
Especificación Técnica 19-10-2018

mod. MET
Mechanical connectors

1. Description
The "MET" bolted connectors are made of high mechanical and corrosion perfor-
mance tin plated aluminum alloy.
The connection is carried out by hexagonal share head bolts with (TAS)* torque con-
trol system.
(*) The system assures the same contact force for all the conductor cross section range.

Note: see Table models in annex.

2. Use
Connections on LV and MV underground power networks with Al./Cu. conductors. (IEC 60228- Class 1/2)

3. Characteristics
The main characteristics and type tests are in correspondence with the Standard IEC 61238-1 (Class A).

4. Marking
Legible and indelible inscription of the following marks:
• Trademark: NILED / Product reference: MET / Conductor cross sections / Lot number

5. Packing
Presentation in plastic bags set in boxes packaging.

6. Installation
It is recommended to follow, as possible, the following steps for the connector installation:
⇒ Choose the connector type according to the cable cross sections to be connected.
⇒ Remove the insulation in the necessary length (L/2) and brush the conductor.
⇒ Fit the conductor into the sleeve and fasten screws steadily by hand.
⇒ Screw on alternating and slowly until the head shares off.

Recommended tooling:

CM-45 CL-200

Ref. ND523-11_Manguitos MET (en).docx


3 1
niled s.a.e. ND 523-11.8
Especificación Técnica 19-10-2018

ANNEX – A

Table A1– Standard models

Reference Cable cross sections Dimensions (mm) SH Bolts TORQUE


NILED (mm²) AWG ØA ØB L N HEX (Nm)

MET – 50 6 – 50 #10 – #1 9,0 18 40 10 10/12 ±1,0


MET – 95 25 – 95 #3 – 3/0 12,5 24 60 2 13 20/22 ±2,0
MET – 150 50 – 150 1/0 – 250 15,5 28 75 30/33 ±3,0
MET – 185 50 – 185 1/0 – 350 17,0 105 17 35/38 ±3,5
35
MET – 240 95 – 240 4/0 – 400 19,5 130 40/44 ±4,0
MET – 300 150 – 300 250 – 600 23,5 38 150 4 45/49 ±4,5
MET – 400 240 – 400 400 – 750 26,0 42 160 22 50/55 ±5,0
MET – 500 300 – 500 600 – 800 29,0 48 170 60/66 ±6,0
MET – 630 400 – 630 800 – 1000 32,5 55 70/77 ±7,0
210 6
MET – 800 630 – 800 1250 – 1500 37,5 60 24
80/88 ±8,0
MET – 1000 800 – 1000 1750 – 2000 42,0 65 230 8

Table A2 – Extended cross sections

Reference Cable cross sections Dimensions (mm) SH Bolts TORQUE


NILED (mm²) AWG ØA ØB L N HEX (Nm)

MET – 95H 16 – 95 #4 – 3/0 12,5 24 60 13 20/22 ±2,0


2
MET – 150H 35 – 150 #2 – 250 15,5 28 75 30/33 ±3,0
17
MET – 240H 70 – 240 2/0 – 400 19,5 35 130 40/44 ±4,0
MET – 300H 95 – 300 4/0 – 600 23,5 150 45/49 ±4,5
42 4
MET – 400H 185 – 400 350 – 750 26,0 160 22 50/55 ±5,0
MET – 500H 240 – 500 400 – 800 29,0 55 170 60/66 ±6,0

NOTA: Available models with center rings (Add ‘AC’ to the reference)

Ref. ND523-11_Manguitos MET (en).docx


3 2
niled s.a.e. ND 523-11.8
Especificación Técnica 19-10-2018

ANEXO – B

Table B – Reduced cross sections

Reference Sections (mm²) Dimensions (mm) SH Bolts


NILED S1 S2 Ø A1 Ø A2 ØB L1 L2 L N HEX
MET– 95/50 25 – 95 12,5 24 30 20 55
6 – 50 9,0 13
MET– 150/50 25 65 2
50 – 150 15,5 28 35
MET– 150/95 70
16 – 95 12,5 30
MET– 240/95 100
95 – 240 19,5 35 65 3 17
MET– 240/150 35 – 150 15,5 40 105
MET– 300/185 150 – 300 50 – 185 23,5 17,0 38 75 50 130
MET– 400/240 240 – 400 70 – 240 26,0 19,5 42 65 150 4
80
MET– 500/300 300 – 500 95 – 300 29,0 23,5 48 75 160 22
MET– 630/240 70 – 240 19,5 65 175
400 – 630 32,5 55
MET– 630/400 5
185 – 400 26,0 80 190
MET– 800/400
630 – 800 37,5 60
MET– 800/630 400 – 630 32,5 105 210 6
105
MET–1000/400 185 – 400 26,0 80 190 5 24
MET–1000/630 800 – 1000 400 – 630 42,0 32,5 65
MET–1000/800 105 210 6
630 – 800 37,5
MET–1200/800 1000 – 1200 45,0 70

NOTA: Available models with center rings (Add ‘AC’ to the reference)

Ref. ND523-11_Manguitos MET (en).docx